1756 ControlLogix I/O Modules Specifications

1756-OB32, 1756-OB32K

ControlLogix DC (10…31.2V) output module

Simplified Schematic 1756-OB32, 1756-OB32K


Display Optoisolation Gate Drive
OUT-1 2 1 OUT-0
DC-0(+) Group 0 OUT-3 4 3 OUT-2
OUT-5 6 5 OUT-4
OUT-7 8 7 OUT-6
Daisy Chain
OUT-9 10 9 OUT-8
OUT-0 to Other
OUT-11 12 11 OUT-10 Group 0
RTBs
OUT-13 14 13 OUT-12
ControlLogix Backplane RTN OUT-0 OUT-15 16 15 OUT-14
DC-0(+) 18 17 RTN OUT-0
OUT-17 20 19 OUT-16
OUT-19 22 21 OUT-18
Surge Current Chart
OUT-21 24 23 OUT-20
OUT-23 26 25 OUT-22
Surge
1A Group 1 OUT-25 28 27 OUT-24 Group 1
OUT-27 30 29 OUT-26
Continuous @ 60 °C (140 °F)
Current

0.5 A OUT-29 32 31 OUT-28


OUT-31 34 33 OUT-30
DC-1(+) 36 35 RTN OUT-1
0 10 ms
Time + _

DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7
1 11 11 1 O
ST 8 9 0 12 3 4 5
K
1 1 1 12 22 2
ST 6 7 8 90 1 2 3
2 2 2 22 23 3
ST 4 5 6 78 9 0 1

Technical Specifications - 1756-OB32, 1756-OB32K


Attribute 1756-OB32, 1756-OB32K
Outputs 32 (16 points/group)
Voltage category 12/24V DC source
Operating voltage range 10…31.2V DC
Output delay time
Off to On 60 s nom/1 ms max
On to Off 200 s nom/1 ms max
Current draw @ 5.1V 300 mA
Current draw @ 24V 2 mA
Total backplane power 1.58 W
Power dissipation, max 4.8 W @ 60 °C (140 °F)
Thermal dissipation 16.37 BTU/hr
Off-state leakage current per point, max 0.5 mA per point
On-state voltage drop, max 200 mV DC @ 0.5 A
0.5 A @ 50 °C (122 °F) linear derating
Current per point, max 0.35 A @ 60 °C (140 °F)
16 A @ 50 °C (122 °F) linear derating
Current per module, max 10 A @ 60 °C (140 °F)
Surge current per point, max 1 A for 10 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min 3 mA per point

166 Rockwell Automation Publication 1756-TD002N-EN-E - November 2021


1756 ControlLogix I/O Modules Specifications

Technical Specifications - 1756-OB32, 1756-OB32K


Attribute 1756-OB32, 1756-OB32K
Scheduled outputs Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point Hold last state, On or Off (Off is default)
States in Program mode per point Hold last state, On or Off (Off is default)
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
Isolation voltage No isolation between individual group outputs
Module keying Electronic, software configurable
Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the
ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-
Fusing TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix
system that uses other wiring termination methods can require application-specific approval by the
certifying agency.
1756-TBCH
Removable terminal block 1756-TBS6H
RTB keying User-defined mechanical
Slot width 1
Wire category 1(1)
Enclosure type None (open-style)
North American temperature code T3C
IEC temperature code T3
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1.

Environmental Specifications - 1756-OB32, 1756-OB32K


Attribute 1756-OB32, 1756-OB32K
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat), 0…60 °C (32…140 °F)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), -40…+85 °C (-40…+185 °F)
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock)
Relative humidity
IEC 60068-2-30 (Test dB, Unpackaged Damp Heat) 5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10…500 Hz
Shock, operating 30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g
Emissions IEC 61000-6-4
ESD immunity 6 kV contact discharges
IEC 61000-4-2 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
IEC 61000-4-3 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4 ±4 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5 ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
IEC 61000-4-6

Rockwell Automation Publication 1756-TD002N-EN-E - November 2021 167


1756 ControlLogix I/O Modules Specifications

Certifications - 1756-OB32
Certification (when product is marked)(1) 1756-OB32, 1756-OB32K
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
CE • EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
Australian Radiocommunications Act, compliant with:
RCM EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
Ex • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EAC Russian Customs Union TR CU 004/2011 LV Technical Regulation
(1) See the Product Certification link at rok.auto/certifications for Declarations of Conformity, Certificates, and other certification details.

168 Rockwell Automation Publication 1756-TD002N-EN-E - November 2021