MULTIPLE OF LONG-TIME PICKUP

100

100
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
1000 1000
900 900
800 800
700 700
600 600
500 500

400 Short Time Time (Sec.) 400


Band (60Hz) Commit Clear
300 1 0.025 0.080 300
2 0.033 0.088
200 3 0.042 0.097
200
Sensors Max ST Pickup 4 0.058 0.113
Envelope 1 400-2000A 12X 5 0.092 0.147
6 0.117 0.172
Envelope 2 400-3200A 12X
7 0.158 0.213
100 Envelope 3 3000-6000A 10X 100
90 8 0.183 0.238 90
80 80
9 0.217 0.272
70 70
10 0.350 0.405
60 60
11 0.417 0.472
TIME IN SECONDS

TIME IN SECONDS
50 50
ST Pickup is a multiple of the nominal
40 (RPXPU) LT PI 40

30
Curve represents a tolerance of -9% 30
and 11% around the actual value of
current, + operating time.
20 FE time current curves include all 20
required trip unit tolerance and CB
operational variance
Bottom/left of curve band is the
“commit” time. The top/right is
10 the “maximum” clear time. 10
9 9
8 8
7 7
6 6
5 5

4 4

3 3

2 2

Max.
1 1
.9 .9
.8 .8
Int.
.7 .7
DES-092B

DES-092B
.6 .6
.5 .5
11
.4 .4
Min. 10
.3 .3

9
.2 8 .2
7
6
5
.1 .1
.09 .09
.08 4 .08
.07 .07
3
.06 10X STPU Maximum .06
.05 Slope Calculation 2 .05

.04 1 .04

.03 .03

.02 .02
Transition to Instantaneous, Transition to Instantaneous,
Override or Application Override or Application
Determines End of Curve Determines End of Curve
.01 .01
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100

100

MULTIPLE OF LONG-TIME PICKUP

Low-Voltage Circuit Breakers DES-092B


Frames 800-5000A UL1066
Frames 800-6000A UL489
EntelliGUard TU Trip Unit Pickup Range

Sensors 400-6000A for EntelliGuard G and R (Retrofill) 1.5X-12X Long-Time Pickup


Circuit Breakers
UL489 and UL1066 Stored Energy
Mechanism Circuit Breakers
All Voltages: 600 Vac and below
Short-Time Pickup and Delay Bands
Curves apply at 60 Hertz
and from -20°C to 55°C circuit breaker ambient temperature.

12.14