MULTIPLES OF CURRENT RATING

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

100

200

300

400

500
600
Temp. 0 25 40 50 60C .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

100

200

300
Shift index for
long-time delay only.
1000 1000
900 900
800 For other than 40ºC 800
700 ambient, Shift unity 700
600 index for long-time delay 600
(thermal) portion of curve
500 500
to desired ambient.
400 400

300 300

200 200

100 Maximum Total 100


90 Clearing Time 90
80 80
70 Minimum Total 70
60 Clearing Time 60
TIME IN SECONDS

TIME IN SECONDS
50 50

40 40

30 30

20 20

10 10
9 125 Amp 9
8 8
7 7
6 6
5 5

4 250 Amp 4
150 Amp 400 Amp
3 3

2 2

175 Amp 300 Amp


1 1
.9 .9
.8 .8
.7 .7
GES-6105

GES-6105
.6 .6
.5 .5
200 Amp
.4 350 Amp .4

.3 .3

.2 .2
225 Amp

.1 .1
.09 HI Magnetic .09
.08 LO Magnetic .08
Setting
.07 Setting .07
.06 .06
.05 .05

.04 Application determines .04


end of curve
.03 .03

.02 .02

.01 .01
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100

200

300

400

500
600

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100

200

300

MULTIPLES OF CURRENT RATING

Molded Case Circuit Breaker


GE Consumer & Industrial -
Electrical Distribution K 1000 LINE GES-6105
Current Ratings Types TKM & THKM (125–400 Amperes) Adjustments
125, 150, 175, 200, 225, 250, 300, 350,
and 400 Amperes
Long-time Delay and Instantaneous Long-time delay thermal trip: not adjustable.
Time-current Curves Instantaneous magnetic trip, five settings, factory
set on HI. Blocks show trip range at each setting.
Voltage Ratings Curves show circuit breaker in open air, 40ºC ambient,
600 Vac, 250 Vdc wired with conductors of corresponding rating, no
prior load. For all other ambients, use rating shift
Frequency Ratings index at top of sheet.
Dc or 60 cycles

2.62 3M