ED 40 - 017B

Packaged Air Conditioners


Duct Connection Type
(Middle Static Pressure Application)

FD(Y)M-FA Series
— Cooling Only —
— Heat Pump —
ED40-017B

Part 1 Indoor Unit FD(Y)M03~06FA................................................ 1


1. External Appearance and Features ........................................................2
2. Power Supply ..........................................................................................3
2.1 Cooling Only.............................................................................................3
2.2 Heat Pump ...............................................................................................4
3. Specification............................................................................................5
3.1 Cooling Only.............................................................................................5
3.2 Heat Pump .............................................................................................11
4. Optional Accessories ............................................................................16
4.1 Option List ..............................................................................................16
5. Dimensions ...........................................................................................17
6. Remote Controller .................................................................................19
6.1 Dimensions.............................................................................................19
6.2 Operation................................................................................................20
7. Wiring Diagrams....................................................................................22
8. Sound Level ..........................................................................................24
8.1 Overall Sound Level ...............................................................................24
8.2 Octave Band Level .................................................................................25
9. Fan Performance ..................................................................................26
10.Installation .............................................................................................28

Part 2 Outdoor Unit LU Series ..................................................... 37


1. External Appearance.............................................................................38
2. Power Supply ........................................................................................39
2.1 Cooling Only...........................................................................................39
2.2 Heat Pump .............................................................................................39
3. Specification..........................................................................................40
4. Dimensions and Service Space ............................................................41
4.1 Dimensions.............................................................................................41
4.2 Installation Service Space ......................................................................43
5. Piping Diagrams....................................................................................45
5.1 Cooling Only...........................................................................................45
5.2 Heat Pump .............................................................................................47
6. Wiring Diagrams....................................................................................49
6.1 Cooling Only...........................................................................................49
6.2 Heat Pump .............................................................................................52
7. Capacity Table ......................................................................................55
7.1 Cooling Only...........................................................................................55
7.2 Heat Pump .............................................................................................60
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ............63
8. Operation Limits ....................................................................................64
8.1 Cooling Only...........................................................................................64
8.2 Heat Pump .............................................................................................64
9. Sound Level ..........................................................................................65
9.1 Overall Sound Level ...............................................................................65
9.2 Octave Band Level .................................................................................66

Table of Contents i
ED40-017B

10.Electric Characteristics..........................................................................68
10.1 Cooling Only...........................................................................................68
10.2 Heat Pump .............................................................................................69
11.Field Piping and Wiring .........................................................................70
11.1 Field Piping.............................................................................................70
11.2 Field Wiring ............................................................................................72

Part 3 Outdoor Unit KU Series ..................................................... 75


1. External Appearance.............................................................................76
2. Power Supply ........................................................................................77
2.1 Cooling Only...........................................................................................77
2.2 Heat Pump .............................................................................................77
3. Specification..........................................................................................78
4. Dimensions and Service Space ............................................................79
4.1 Dimensions.............................................................................................79
4.2 Installation Service Space for R(Y)140KU .............................................81
4.3 Installation Service Space for R(Y)200 · 250KU ....................................83
5. Piping Diagrams....................................................................................84
5.1 Cooling Only...........................................................................................84
5.2 Heat Pump .............................................................................................85
6. Wiring Diagrams....................................................................................89
6.1 Cooling Only...........................................................................................89
6.2 Heat Pump .............................................................................................91
7. Capacity Table ......................................................................................94
7.1 Cooling Only...........................................................................................94
7.2 Heat Pump .............................................................................................96
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ............99
8. Operation Limits ..................................................................................100
8.1 Cooling Only.........................................................................................100
8.2 Heat Pump ...........................................................................................101
9. Sound Level ........................................................................................102
9.1 Overall Sound Level .............................................................................102
9.2 Octave Band Level ...............................................................................103
10.Electric Characteristics........................................................................105
10.1 Cooling Only.........................................................................................105
10.2 Heat Pump ...........................................................................................106
11.Field Piping and Wiring .......................................................................107
11.1 Field Piping (R(Y)140KU).....................................................................107
11.2 Field Piping (R(Y)200 · 250KU)............................................................109
11.3 Field Wiring ..........................................................................................112

Part 4 Outdoor Unit FU Series ................................................... 115


1. External Appearance...........................................................................116
2. Power Supply ......................................................................................117
2.1 Power Supply .......................................................................................117
3. Specification........................................................................................118
4. Dimensions and Service Space ..........................................................119
4.1 Dimensions...........................................................................................119
4.2 Installation Service Space ....................................................................120

ii Table of Contents
ED40-017B

5. Piping Diagrams..................................................................................122
5.1 Cooling Only.........................................................................................122
5.2 Heat Pump ...........................................................................................123
6. Wiring Diagrams..................................................................................124
6.1 Cooling Only.........................................................................................124
6.2 Heat Pump ...........................................................................................127
7. Capacity Table ....................................................................................129
7.1 Cooling Only.........................................................................................129
7.2 Heat Pump ...........................................................................................132
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ..........134
8. Operation Limit....................................................................................135
8.1 Cooling Only.........................................................................................135
8.2 Heat Pump ...........................................................................................136
9. Sound Level ........................................................................................137
9.1 Overall Sound Level .............................................................................137
9.2 Octave Band Level ...............................................................................138
10.Electric Characteristics........................................................................140
10.1 Cooling Only.........................................................................................140
10.2 Heat Pump ...........................................................................................141
11.Field Piping and Wiring .......................................................................142
11.1 Field Piping...........................................................................................142
11.2 Field Wiring ..........................................................................................144

Table of Contents iii


ED40-017B

iv Table of Contents
ED40-017B

Part 1 1
Indoor Unit
FD(Y)M03~06FA
1. External Appearance and Features ........................................................2
2. Power Supply ..........................................................................................3
2.1 Cooling Only.............................................................................................3
2.2 Heat Pump ...............................................................................................4
3. Specification............................................................................................5
3.1 Cooling Only.............................................................................................5
3.2 Heat Pump .............................................................................................11
4. Optional Accessories ............................................................................16
4.1 Option List ..............................................................................................16
5. Dimensions ...........................................................................................17
6. Remote Controller .................................................................................19
6.1 Dimensions.............................................................................................19
6.2 Operation................................................................................................20
7. Wiring Diagrams....................................................................................22
8. Sound Level ..........................................................................................24
8.1 Overall Sound Level ...............................................................................24
8.2 Octave Band Level .................................................................................25
9. Fan Performance ..................................................................................26
10.Installation .............................................................................................28

Indoor Unit FD(Y)M03~06FA 1


External Appearance and Features ED40-017B

1. External Appearance and Features


Indoor Unit

FDM04FA
FDM05FA
FDM03FA FDYM04FA
FDYM03FA
FDYM05FA
FDYM06FA

Remote Controller

Signal Receiving Unit


Wired Type Wireless Remote Controller (Separate Type)

Features
„ Compact in size
„ Fits to the small ceiling spaces
„ Low operating sound: Top in the industry
„ Central control and group control are available
(by adopting the optional accessories)

Functions

Type Middle Static Pressure Type


Cooling Only Heat Pump
Functions FDM FDYM

Static Pressure Change Over { {


Field Setting by Remote Controller Field Setting by Remote Controller
Dehumidifying Operation { {
Hot Start — {
30m (LU · KU Type Outdoor Units) 30m (LU · KU Type Outdoor Units)
Chargeless Length 5m (R200 · 250KU) 5m (RY200 · 250KU)
5m (FU Type Outdoor Units) 5m (FU Type Outdoor Units)
Power Failure Compensation
{ {
Operation
Auto Mode (Cooling / Heating)
Operation — {

Control by 2 Remote Controllers { {


Group Control by 1 Remote Controller { {
Remote Control by Group { {
Central Control { {
Interlock with HRV
(Heat Reclaim Ventilation) { {

2 Indoor Unit FD(Y)M03~06FA


ED40-017B Power Supply

2. Power Supply
1
2.1 Cooling Only
2.1.1 50Hz
Series Indoor Unit Cooling Only Power Supply
FDYM03FAV1 R71LUV1 ∗
1 phase 220–240V
FDYM04FAV1 R100LUV1 ∗

FDYM03FAV1 R71LUY1 ∗
R–LU
FDYM04FAV1 R100LUY1 ∗

FDYM05FAV1 R125LUY1 ∗

FDYM06FAV1 R140LUY1 ∗ 3 phase 380–415V (4 wires)

FDYM04FAV1×2 R200KUY1

R–KU FDYM03FAV1×3 R200KUY1

FDYM05FAV1×2 R250KUY1

FDM03FAV1 R71FUV1
1 phase 220–240V
FDM04FAV1 R100FUV1

R–FU FDM03FAV1 R71FUY1

FDM04FAV1 R100FUY1 3 phase 380–415V (4 wires)

FDM05FAV1 R125FUY1

2.1.2 60Hz
Series Indoor Unit Cooling Only Power Supply
FDYM03FAVAL R71LUVAL ∗
1 phase 220V
FDYM04FAVAL R100LUVAL ∗

FDYM05FAVAL R125LUTAL ∗
R–LU 3 phase 220V
FDYM06FAVAL R140LUTAL ∗

FDYM05FAVAL R125LUYAL ∗
3 phase 380V (4 wires)
FDYM06FAVAL R140LUYAL ∗

FDYM06FAVAL R140KUTALK

FDYM04FAVAL×2 R200KUTAL
3 phase 220V
FDYM03FAVAL×3 R200KUTAL

FDYM05FAVAL×2 R250KUTAL
R–KU
FDYM06FAVAL R140KUYALK

FDYM04FAVAL×2 R200KUYAL
3 phase 380V (4 wires)
FDYM03FAVAL×3 R200KUYAL

FDYM05FAVAL×2 R250KUYAL

FDM03FAVAL R71FUVAL
1 phase 220V
R–FU FDM04FAVAL R100FUVAL

FDM05FAVAL R125FUTAL 3 phase 220V

Note: 1. * : New Model or Changed Model


2. Power Supply Intake : Outdoor Unit

Indoor Unit FD(Y)M03~06FA 3


Power Supply ED40-017B

2.2 Heat Pump


2.2.1 50Hz
Series Indoor Unit Heat Pump Power Supply
FDYM03FAV1 RY71LUV1 ∗
1 phase 220–240V
FDYM04FAV1 RY100LUV1 ∗

FDYM03FAV1 RY71LUY1 ∗
RY–LU
FDYM04FAV1 RY100LUY1 ∗

FDYM05FAV1 RY125LUY1 ∗

FDYM06FAV1 RY140LUY1 ∗ 3 phase 380–415V (4 wires)

FDYM04FAV1×2 RY200KUY1

RY–KU FDYM03FAV1×3 RY200KUY1

FDYM05FAV1×2 RY250KUY1

2.2.2 60Hz
Series Indoor Unit Heat Pump Power Supply
FDYM06FAVAL RY140LUTAL ∗ 3 phase 220V
RY–LU
FDYM06FAVAL RY140LUYAL ∗ 3 phase 380V (4 wires)

FDYM06FAVAL RY140KUTALK

FDYM04FAVAL×2 RY200KUTAL
3 phase 220V
FDYM03FAVAL×3 RY200KUTAL

FDYM05FAVAL×2 RY250KUTAL
RY–KU
FDYM06FAVAL RY140KUYALK

FDYM04FAVAL×2 RY200KUYAL
3 phase 380V (4 wires)
FDYM03FAVAL×3 RY200KUYAL

FDYM05FAVAL×2 RY250KUYAL

FDYM03FAVAL RY71FUVAL
1 phase 220V
RY–FU FDYM04FAVAL RY100FUVAL

FDYM05FAVAL RY125FUTAL 3 phase 220V

Note: 1. * : New Model or Changed Model


2. Power Supply Intake : Outdoor Unit

4 Indoor Unit FD(Y)M03~06FA


ED40-017B Specification

3. Specification
1
3.1 Cooling Only
3.1.1 50Hz

FDYM–FA + R–LU
Indoor Unit FDYM03FAV1 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1
Model V1 R71LUV1 R100LUV1 — —
Outdoor Unit
Y1 R71LUY1 R100LUY1 R125LUY1 R140LUY1
kW 7.8/7.7/7.7 10.6/10.5/10.5 13.0/12.8/12.8 14.5/14.2/14.2
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 26,600/26,200/26,200 36,100/35,700/35,700 44,500/43,600/43,600 49,400/48,400/48,400
kcal/h 6,700/6,600/6,600 9,100/9,000/9,000 11,200/11,000/11,000 12,500/12,200/12,200
Indoor Unit FDYM03FAV1 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225 290
Air Flow Rate ∗2 m³/min (H) 20–22 (H) 26–28 (H) 35–40.5 (H) 37–42
External Static Pressure Pa 98 98 98 98
Sound Pressure Level ∗2 dB(A) (H) 39–41 (H) 39–41 (H) 44–46 (H) 46–48
Machine Weight kg 42 56 57 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C64
V1 R71LUV1 R100LUV1 — —
Outdoor Unit
Y1 R71LUY1 R100LUY1 R125LUY1 R140LUY1
Color Ivory
Dimensions H×W×D mm 770×900×320 1,170×900×320 1,170×900×320 1,345×900×320
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 2×52×2.0 2×60×2.0
Face Area m² 0.634 0.983 0.983 1.134
V1 ZR36K3–PFJ ZR48K3–PFJ — —
Model
Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE JT170BC–YE
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 2.24 3.00 3.75 4.50
Model P47L11S P47L11S P47L11S×2 P47L11S×2
Type Propeller
Fan
Motor Output W 65 90 65+85 65+90
Air Flow Rate ∗2 m³/min 48–51 59–62 92–100 97–109
V1 72 87 — —
Weight kg
Y1 71 84 98 109
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure
Safety Devices Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.2 1.2 1.5 1.6
Drawing No. 4D041138 4D041137

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB 50Hz, 220–240V cfm=m³/min×35.3
(1) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380–415V)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 50Hz, 220–240V
(2) 7.5m JIS B8616
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380–415V)

(3) Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 50Hz, 240V


Outdoor : 35°C(95°F)DB, 24°C(75°F)WB 7.5m (415V) AS 1861
2. ∗2 AFR (Air flow rafe) and sound pressure level are shown at 220V (380V)–240V (415V).
3. Capacities are net, including a deduction for cooling for indoor fan motor heat.
4. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
5. Wire for remote controller : Field supplied.

Indoor Unit FD(Y)M03~06FA 5


Specification ED40-017B

FDYM–FA + R–KU
Indoor Unit FDYM03FAV1×3 FDYM04FAV1×2 FDYM05FAV1×2
Model
Outdoor Unit R200KUY1 R200KUY1 R250KUY1
kW 22.5/22.2/22.0 22.5/22.2/22.0 27.1/26.6/26.3
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 76,800/75,800/75,100 76,800/75,800/75,100 92,500/90,800/89,800
kcal/h 19,400/19,100/18,900 19,400/19,100/18,900 23,300/22,900/22,600
Indoor Unit ∗3 FDYM03FAV1×3 FDYM04FAV1×2 FDYM05FAV1×2
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate ∗2 m³/min (H) 20–22 (H) 26–28 (H) 35–40.5
External Static Pressure Pa 98 98 98
Sound Pressure Level ∗2 dB(A) (H) 39–41 (H) 39–41 (H) 44–46
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C64
Outdoor Unit R200KUY1 R200KUY1 R250KUY1
Color Ivory
Dimensions H×W×D mm 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×40×2.0 2×40×2.0 2×50×2.0
Face Area m² 1.57 1.57 1.97
Model JT236D–P1YE JT236D–P1YE JT335D–P1YE
Comp. Type Hermetically Sealed Scroll Type
Motor Output kW 5.5 5.5 9.0
Model P52H11SM P52H11SM P52H11SM
Type Propeller
Fan
Motor Output W 230+190 230+190 230+190
Air Flow Rate ∗2 m³/min 150–154 150–154 175–179
Machine Weight kg 178 178 202
Liquid mm φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare)
Piping Connections Gas mm φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange)
Drain mm — — —
Safety Devices Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure
Switch. Over Current Relay (Compressor). Reverse Phase Protector. Fuse.
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 5.3 (Charged for 5m) 5.3 (Charged for 5m) 5.7 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 3.0 3.0 3.0
Drawing No. C : 4D029967 C : 4D029969

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB cfm=m³/min×35.3
(1) 5m 50Hz, 380–415V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB
(2) 5m 50Hz, 380–415V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB
(3) 7.5m 50Hz, 415V AS 1861
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
2. ∗2 AFR (Air flow rafe) and sound pressure level are shown at 380V–415V.
3. Capacities are net, including a deduction for cooling for indoor fan motor heat.
4. ∗3 Each value for indoor unit shows the specifications per one unit.
5. Wire for remote controller : Field supplied.

6 Indoor Unit FD(Y)M03~06FA


ED40-017B Specification

FDM–FA + R–FU 1
Indoor Unit FDM03FAV1 FDM04FAV1 FDM05FAV1
Model V1 R71FUV1 R100FUV1 —
Outdoor Unit
Y1 R71FUY1 R100FUY1 R125FUY1
kW 7.8/7.7/6.3 10.6/10.5/8.0 13.0/12.8/11.2
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 26,600/26,200/21,500 36,100/35,700/27,300 44,500/43,600/38,200
kcal/h 6,700/6,600/5,400 9,100/9,000/6,900 11,200/11,000/9,600
Indoor Unit FDM03FAV1 FDM04FAV1 FDM05FAV1
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate m³/min (H) 20 (H) 26 (H) 35
External Static Pressure Pa 98 98 98
Sound Pressure Level dB(A) (H) 39 (H) 39 (H) 44
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C64
V1 R71FUV1 R100FUV1 —
Outdoor Unit
Y1 R71FUY1 R100FUY1 R125FUY1
Color Ivory
Dimensions H×W×D mm 816×880×370 1,215×880×370 1,215×880×370
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×36×2.0 2×54×2.0 2×54×2.0
Face Area m² 0.653 0.979 0.979
V1 H23A35QABKA H23A46QABKA —
Model
Y1 H23A35QDBEA H23A46QDBEA H23A56QDBEA
Comp. Type Hermetically Sealed Type
No. of Cylinders 2 2 2
Motor Output kW 2.2 3.0 3.75
Model P45J11SM P45J11SM×2 P45J11SM×2
Type Propeller
Fan
Motor Output W 50 75+35 75+60
Air Flow Rate m³/min 46 80 87
V1 87 117 —
Machine Weight kg
Y1 84 109 110
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan motor and Indoor Fan Motor. Internal Pressure Relief Valve (Compressor).
Safety Devices
Motor Protector (Compressor).
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.1 (Charged for 5m) 2.4 (Charged for 5m) 2.8 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.48 1.63 1.63
Drawing No. C : 4D021049

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB 50Hz, 220–240V cfm=m³/min×35.3
(1) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380–415V)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 50Hz, 220–240V
(2) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380–415V)

(3) Indoor : 29°C(84°F)DB, 19.0°C(66°F)WB 50Hz, 240V


7.5m SSA 385/386
Outdoor : 46°C(115°F)DB, 24°C(75°F)WB (415V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.

Indoor Unit FD(Y)M03~06FA 7


Specification ED40-017B

3.1.2 60Hz

FDYM–FA + R–LU
Indoor Unit FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL FDYM06FAVAL
VAL R71LUVAL R100LUVAL — —
Model
Outdoor Unit TAL — — R125LUTAL R140LUTAL
YAL — — R125LUYAL R140LUYAL
kW 8.3/8.1 11.6/11.4 14.5/14.3 16.1/15.8
∗1 Cooling Capacity (1)/(2) Btu/h 28,200/27,800 39,700/38,900 49,600/48,800 55,000/53,900
kcal/h 7,100/7,000 10,000/9,800 12,500/12,300 13,800/13,500
Indoor Unit FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL FDYM06FAVAL
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1 3D18H2AF1
Type Sirocco Fan
Fan Motor Output W 125 135 225 290
Air Flow Rate m³/min (H) 22 (H) 28 (H) 38 (H) 40
External Static Pressure Pa 118 118 118 118
Sound Pressure Level dB(A) (H) 42 (H) 42 (H) 47 (H) 49
Machine Weight kg 42 56 57 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C64
VAL R71LUVAL R100LUVAL — —
Outdoor Unit TAL — — R125LUTAL R140LUTAL
YAL — — R125LUYAL R140LUYAL
Color Ivory
Dimensions H×W×D mm 770×900×320 1,170×900×320 1,170×900×320 1,345×900×320
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 2×52×2.0 2×60×2.0
Face Area m² 0.634 0.983 0.983 1.134
VAL ZR36K3–PFV ZR47K3–PFV — —
Model TAL — — JT160BC JT170BC
Comp. YAL — — JT160BC–YH JT170BC–YE
Type Hermetically Sealed Scroll Type
Motor Output kW 2.24 2.92 3.75 4.50
Model P47L11S P47L11S P47L11S×2 P47L11S×2
Type Propeller
Fan
Motor Output W 75 100 95+75 65+90
Air Flow Rate m³/min 49 59 94 97–109
Weight kg 75 92 98 109
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure
Safety Devices
Switch. Over Current Decive. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.2 1.2 1.5 1.6
Drawing No. 4D040215 4D040216

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB 60Hz, 220V cfm=m³/min×35.3
(1) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 60Hz 220V
(2) 7.5m JIS B8616
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.

8 Indoor Unit FD(Y)M03~06FA


ED40-017B Specification

FDYM–FA + R–KU 1
Indoor Unit FDYM06FAVAL FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2
Model TAL R140KUTALK R200KUTAL R200KUTAL R250KUTAL
Outdoor Unit
YAL R140KUYALK R200KUYAL R200KUYAL R250KUYAL
kW 16.1/15.8/14.0 22.5/22.2/20.0 22.5/22.2/20.0 27.1/26.6/24.1
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 55,000/53,900/47,800 76,800/75,800/68,300 76,800/75,800/68,300 92,500/90,800/82,300
kcal/h 13,800/13,500/12,000 19,400/19,100/17,200 19,400/19,100/17,200 23,300/22,900/20,700
Indoor Unit ∗2 FDYM06FAVAL FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2
Dimensions H×W×D mm 295×1,500×680 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.338 0.221 0.338 0.338
Model 3D18H2AF1 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 290 125 135 225
Air Flow Rate m³/min (H) 40 (H) 22 (H) 28 (H) 38
External Static Pressure Pa 118 118 118 118
Sound Pressure Level dB(A) (H) 49 (H) 42 (H) 42 (H) 47
Machine Weight kg 57 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ19.1 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C64
TAL R140KUTALK R200KUTAL R200KUTAL R250KUTAL
Outdoor Unit
YAL R140KUYALK R200KUYAL R200KUYAL R250KUYAL
Color Ivory
Dimensions H×W×D mm 1,345×880×370 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690
Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×40×2.0 2×50×2.0
Face Area m² 1.088 1.57 1.57 1.97
TAL JT170BC JT212D–P1 JT212D–P1 JT300D–P1
Model
YAL JT170BC–YH JT212D–P1YH JT212D–P1YH JT300D–P1YH
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 4.5 5.5 5.5 7.5
Model P45J11SM P52H11SM P52H11SM P52H11SM
Type Propeller
Fan
Motor Output W 120+100 230+190 230+190 230+190
Air Flow Rate m³/min 103 160 160 190
Weight kg 109 177 177 200
Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare)
Piping Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange)
Drain mm φ26.0 (Hole) — — —
Thermal Protector for Compressor (for R200 · 250KU), Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch.
Safety Devices
Low Pressure Switch. Over Current Relay (Compressor). Reverse Phase Protector. Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.7 (Charged for 5m) 5.3 (Charged for 5m) 5.3 (Charged for 5m) 5.7 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.6 3.0 3.0 3.0
Drawing No. C : 4D028027A C : 4D029968 C : 4D029970

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB 60Hz, 220V cfm=m³/min×35.3
(1) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 60Hz, 220V
(2) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor : 29°C(84°F)DB, 19.0°C(66°F)WB 60Hz, 220V
(3) 7.5m SSA 385/386
Outdoor : 46°C(115°F)DB, 24°C(75°F)WB (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. ∗2 Each value for indoor unit shows the specifications per one unit.
4. In case of drain piping for outdoor unit, drain piping kit (option) is needed. (for R140KUTALK · YALK)
5. Wire for remote controller : Field supplied.

Indoor Unit FD(Y)M03~06FA 9


Specification ED40-017B

FDM–FA + R–FU
Indoor Unit FDM03FAVAL FDM04FAVAL FDM05FAVAL
Model VAL R71FUVAL R100FUVAL —
Outdoor Unit
TAL — — R125FUTAL
kW 8.3/8.1/6.7 11.6/11.4/9.0 14.5/14.3/12.5
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 28,200/27,800/22,900 39,700/38,900/30,700 49,600/48,800/42,700
kcal/h 7,100/7,000/5,800 10,000/9,800/7,700 12,500/12,300/10,800
Indoor Unit FDM03FAVAL FDM04FAVAL FDM05FAVAL
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate m³/min (H) 22 (H) 28 (H) 38
External Static Pressure Pa 118 118 118
Sound Pressure Level dB(A) (H) 42 (H) 42 (H) 47
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C64
VAL R71FUVAL R100FUVAL —
Outdoor Unit
TAL — — R125FUTAL
Color Ivory
Dimensions H×W×D mm 816×880×370 1,215×880×370 1,215×880×370
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×36×2.0 2×54×2.0 2×54×2.0
Face Area m² 0.653 0.979 0.979
VAL H23A35QABCA H23A46QABCA —
Model
TAL — — H23A62QDBLA
Comp. Type Hermetically Sealed Type
No. of Cylinders 2 2 2
Motor Output kW 2.2 3.0 3.75
Model P45J11SM P45J11SM×2 P45J11SM×2
Type Propeller
Fan
Motor Output W 80 90+60 90+80
Air Flow Rate m³/min 55 92 98
Machine Weight kg 87 117 110
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Iindoor Fan Motor. Internal Pressure Relief Valve (Compressor).
Safety Devices
Motor Protector (Compressor).
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.2 (Charged for 5m) 2.9 (Charged for 5m) 3.1 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.48 1.63 1.63
Drawing No. C : 4D020831A

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB cfm=m³/min×35.3
(1) Outdoor : 35°C(95°F)DB, 24°C(75°F)WB 5m 60Hz, 220V —

Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB


(2) 5m 60Hz, 220V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
Indoor : 29°C(84°F)DB, 19.0°C(66°F)WB
(3) 7.5m 60Hz, 220V SSA 385/386
Outdoor : 46°C(115°F)DB, 24°C(75°F)WB
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.

10 Indoor Unit FD(Y)M03~06FA


ED40-017B Specification

3.2 Heat Pump


3.2.1 50Hz 1
FDYM–FA + RY–LU
Indoor Unit FDYM03FAV1 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1
Model V1 RY71LUV1 RY100LUV1 — —
Outdoor Unit
Y1 RY71LUY1 RY100LUY1 RY125LUY1 RY140LUY1
kW 7.8/7.7/7.7 10.5/10.4/10.4 13.0/12.8/12.8 14.5/14.2/14.2
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 26,600/26,200/26,200 35,700/35,300/35,300 44,500/43,600/43,600 49,400/48,400/48,400
kcal/h 6,700/6,600/6,600 9,000/8,900/8,900 11,200/11,000/11,000 12,500/12,200/12,200
kW 7.9/7.9/7.9 11.2/11.2/11.2 14.2/14.2/14.2 16.3/16.3/16.3
∗1 Heating Capacity (1)/(2)/(3) Btu/h 27,000/27,000/27,000 38,100/38,100/38,100 48,400/48,400/48,400 56,000/56,000/56,000
kcal/h 6,800/6,800/6,800 9,600/9,600/9,600 12,200/12,200/12,200 14,000/14,000/14,000
Indoor Unit FDYM03FAV1 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225 290
Air Flow Rate ∗2 m³/min (H) 20–22 (H) 26–28 (H) 35–40.5 (H) 37–42
External Static Pressure Pa 98 98 98 98
Sound Pressure Level ∗2 dB(A) (H) 39–41 (H) 39–41 (H) 44–46 (H) 46–48
Machine Weight kg 42 56 57 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C62
V1 RY71LUV1 RY100LUV1 — —
Outdoor Unit
Y1 RY71LUY1 RY100LUY1 RY125LUY1 RY140LUY1
Color Ivory
Dimensions H×W×D mm 770×900×320 1,170×900×320 1,170×900×320 1,345×900×320
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 2×52×2.0 2×60×2.0
Face Area m² 0.634 0.983 0.983 1.134
V1 ZR36K3–PFJ ZR48K3–PFJ — —
Model
Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE JT170BC–YE
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 2.24 3.00 3.75 4.50
Model P47L11S P47L11S P47L11S×2 P47L11S×2
Type Propeller
Fan
Motor Output W 65 90 65+85 65+90
Air Flow Rate (C/H) ∗2 m³/min 48–51 59–62 92–100 97–109
V1 73 89 — —
Weight kg
Y1 72 86 101 112
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <RY125·140>. Low Pressure
Safety Devices
Switch. Over Current Device. Motor Protector (Compressor) <RY71·100>. Reverse Phase Protector (Y1). Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.2 1.2 1.5 1.6
Drawing No. 4D041136 4D041137

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
(1) Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB 5m 50Hz, 220–240V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380–415V)

(2) Indoor
: 27°C(81°F)DB, 19.0°C(66°F)WB Indoor : 20°C(68°F)DB 50Hz, 220–240V
7.5m JIS B8616
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380–415V)

(3) Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB Indoor : 21°C(70°F)DB


7.5m
50Hz, 240V
AS 1861
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (415V)
2. ∗2 AFR (Air flow rafe) and sound pressure level are shown at 220V (380V)–240V (415V).
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
5. Wire for remote controller : Field supplied.

Indoor Unit FD(Y)M03~06FA 11


Specification ED40-017B

FDYM–FA + RY–KU
Indoor Unit FDYM03FAV1×3 FDYM04FAV1×2 FDYM05FAV1×2
Model
Outdoor Unit RY200KUY1 RY200KUY1 RY250KUY1
kW 22.5/22.2/22.0 22.5/22.2/22.0 27.1/26.6/26.3
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 76,800/75,800/75,100 76,800/75,800/75,100 92,500/90,800/89,800
kcal/h 19,400/19,100/18,900 19,400/19,100/18,900 23,300/22,900/22,600
kW 22.6/22.7/22.4 22.6/22.7/22.4 28.3/28.4/28.0
∗1 Heating Capacity (1)/(2)/(3) Btu/h 77,200/77,500/76,500 77,200/77,500/76,500 96,600/97,000/95,600
kcal/h 19,400/19,500/19,300 19,400/19,500/19,300 24,300/24,400/24,100
Indoor Unit ∗3 FDYM03FAV1×3 FDYM04FAV1×2 FDYM05FAV1×2
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate ∗2 m³/min (H) 20–22 (H) 26–28 (H) 35–40.5
External Static Pressure Pa 98 98 98
Sound Pressure Level ∗2 dB(A) (H) 39–41 (H) 39–41 (H) 44–46
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C62
Outdoor Unit RY200KUY1 RY200KUY1 RY250KUY1
Color Ivory
Dimensions H×W×D mm 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×40×2.0 2×40×2.0 2×50×2.0
Face Area m² 1.57 1.57 1.97
Model JT236D–P1YE JT236D–P1YE JT335D–P1YE
Comp. Type Hermetically Sealed Scroll Type
Motor Output kW 5.5 5.5 9.0
Model P52H11SM P52H11SM P52H11SM
Type Propeller
Fan
Motor Output W 230+190 230+190 230+190
Air Flow Rate (C/H) ∗2 m³/min 150/138–154/142 150/138–154/142 175/161–179/165
Machine Weight kg 180 180 206
Liquid mm φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare)
Piping Connections Gas mm φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange)
Drain mm — — —
Safety Devices Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure
Switch. Over Current Relay (Compressor). Reverse Phase Protector. Fuse.
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 4.0 (Charged for 5m) 4.0 (Charged for 5m) 5.5 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 3.0 3.0 3.0
Drawing No. C : 4D029816 C : 4D029818

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
(1) Indoor
: 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB
5m 50Hz, 380V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB

(2) Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB


Indoor : 20°C(68°F)DB
5m 50Hz, 380V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB

(3) Indoor
: 27°C(81°F)DB, 19.0°C(66°F)WB Indoor : 21°C(70°F)DB
7.5m 50Hz, 415V AS 1861
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB
2. ∗2 AFR (Air flow rafe) and sound pressure level are shown at 380V–415V.
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. ∗3 Each value for indoor unit shows the specifications per one unit.
5. Wire for remote controller : Field supplied.

12 Indoor Unit FD(Y)M03~06FA


ED40-017B Specification

3.2.2 60Hz
1
FDYM–FA + RY–LU
Indoor Unit FDYM06FAVAL
Model TAL RY140LUTAL
Outdoor Unit
YAL RY140LUYAL
kW 16.1/15.8
∗1 Cooling Capacity (1)/(2) Btu/h 55,000/53,900
kcal/h 13,800/13,500
kW 18.1/18.1
∗1 Heating Capacity (1)/(2) Btu/h 61,900/61,900
kcal/h 15,600/15,600
Indoor Unit FDYM06FAVAL
Dimensions H×W×D mm 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75
Face Area m² 0.338
Model 3D18H2AF1
Type Sirocco Fan
Fan Motor Output W 290
Air Flow Rate m³/min (H) 40
External Static Pressure Pa 118
Sound Pressure Level dB(A) (H) 49
Machine Weight kg 57
Liquid mm φ9.5 (Flare)
Piping Connections Gas mm φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C62
TAL RY140LUTAL
Outdoor Unit
YAL RY140LUYAL
Color Ivory
Dimensions H×W×D mm 1,345×900×320
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×60×2.0
Face Area m² 1.134
TAL JT170BC
Model
YAL JT170BC–YE
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 4.50
Model P47L11S×2
Type Propeller
Fan
Motor Output W 65+90
Air Flow Rate (C/H) m³/min 97–109
Machine Weight kg 112
Liquid mm φ 9 . 5 (Flare)
Piping Connections Gas mm φ 19.1 (Flare)
Drain mm φ 2 6 .0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan
Safety Devices Motor. High Pressure Switch. Low Pressure Switch. Over
Current Device. Reverse Phase Protector. Fuse.
Capacity Step % 100–0
Refrigerant Control Electronic Expansion Valve
Max. Length m 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30
Model R22
Refrigerant
Charge (Factory Charge) kg 4.1 (Charged for 30m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.6
Drawing No. 4D040216

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
(1) Indoor
: 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB 60Hz, 220V
5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380V)

(2) Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB


Indoor : 20°C(68°F)DB 60Hz, 220V
7.5m JIS B8616
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380V)
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.

Indoor Unit FD(Y)M03~06FA 13


Specification ED40-017B

FDYM–FA + RY–KU
Indoor Unit FDYM06FAVAL FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2
Model TAL RY140KUTALK RY200KUTAL RY200KUTAL RY250KUTAL
Outdoor Unit
YAL RY140KUYALK RY200KUYAL RY200KUYAL RY250KUYAL
kW 16.1/15.8/14.0 22.5/22.2/20.0 22.5/22.2/20.0 27.1/26.6/24.1
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 55,000/53,900/47,800 76,800/75,800/68,300 76,800/75,800/68,300 92,500/90,800/82,300
kcal/h 13,800/13,500/12,000 19,400/19,100/17,200 19,400/19,100/17,200 23,300/22,900/20,700
kW 18.1/18.1/17.0 22.6/22.7/22.4 22.6/22.7/22.4 28.3/28.4/28.0
∗1 Heating Capacity (1)/(2)/(3) Btu/h 61,900/61,900/58,000 77,200/77,500/76,500 77,200/77,500/76,500 96,600/97,000/95,600
kcal/h 15,600/15,600/14,600 19,400/19,500/19,300 19,400/19,500/19,300 24,300/24,400/24,100
Indoor Unit ∗2 FDYM06FAVAL FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2
Dimensions H×W×D mm 295×1,500×680 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.338 0.221 0.338 0.338
Model 3D18H2AF1 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 290 125 135 225
Air Flow Rate m³/min (H) 40 (H) 22 (H) 28 (H) 38
External Static Pressure Pa 118 118 118 118
Sound Pressure Level dB(A) (H) 49 (H) 42 (H) 42 (H) 47
Machine Weight kg 57 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ19.1 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C62
TAL RY140KUTALK RY200KUTAL RY200KUTAL RY250KUTAL
Outdoor Unit
YAL RY140KUYALK RY200KUYAL RY200KUYAL RY250KUYAL
Color Ivory
Dimensions H×W×D mm 1,345×880×370 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690
Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×40×2.0 2×50×2.0
Face Area m² 1.088 1.57 1.57 1.97
TAL JT170BC JT212D–P1 JT212D–P1 JT300D–P1
Model
YAL JT170BC–YH JT212D–P1YH JT212D–P1YH JT300D–P1YH
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 4.5 5.5 5.5 7.5
Model P45J11SM×2 P52H11SM P52H11SM P52H11SM
Type Propeller
Fan
Motor Output W 120+100 230+190 230+190 230+190
Air Flow Rate (C/H) m³/min 103/93 160/147 160/147 190/175
Machine Weight kg 112 179 179 204
Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare)
Piping Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange)
Drain mm φ26.0 (Hole) — — —
Thermal Protector for Compressor (for RY200 · 250KU), Outdoor Fan Motor and Indoor Fan Motor.
Safety Devices
High Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor). Reverse Phase Protector. Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.7 (Charged for 5m) 4.0 (Charged for 5m) 4.0 (Charged for 5m) 5.5 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.6 3.0 3.0 3.0
Drawing No. C : 4D028027A C : 4D029817 C : 4D029819

Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
(1) Indoor
: 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB 60Hz, 220V
5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380V)

(2) Indoor
: 27°C(81°F)DB, 19.0°C(66°F)WB Indoor : 20°C(68°F)DB 60Hz, 220V
5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380V)

(3) Indoor : 29°C(84°F)DB, 19.0°C(66°F)WB Indoor : 21°C(70°F)DB


7.5m
60Hz, 220V
SSA 385/386
Outdoor : 46°C(115°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380V)
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed. (for RY140KUTALK · YALK)
4. ∗2 Each value for indoor unit shows the specifications per one unit.
5. Wire for remote controller : Field supplied.

14 Indoor Unit FD(Y)M03~06FA


ED40-017B Specification

FDYM–FA + RY–FU 1
Indoor Unit FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL
Model VAL RY71FUVAL RY100FUVAL —
Outdoor Unit
TAL — — RY125FUTAL
kW 8.3/8.1/6.7 11.6/11.4/9.0 14.5/14.3/12.5
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 28,200/27,800/22,900 39,700/38,900/30,700 49,600/48,800/42,700
kcal/h 7,100/7,000/5,800 10,000/9,800/7,700 12,500/12,300/10,800
kW 9.0/9.0/8.5 12.8/12.8/11.8 16.2/16.2/15.0
∗1 Heating Capacity (1)/(2)/(3) Btu/h 30,600/30,600/29,000 43,700/43,700/40,300 55,200/55,200/51,200
kcal/h 7,700/7,700/7,300 11,000/11,000/10,100 13,900/13,900/12,900
Indoor Unit FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate m³/min (H) 22 (H) 28 (H) 38
External Static Pressure Pa 118 118 118
Sound Pressure Level dB(A) (H) 42 (H) 42 (H) 47
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C62
VAL RY71FUVAL RY100FUVAL —
Outdoor Unit
TAL — — RY125FUTAL
Color Ivory
Dimensions H×W×D mm 816×880×370 1,215×880×370 1,215×880×370
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×36×2.0 2×54×2.0 2×54×2.0
Face Area m² 0.653 0.979 0.979
VAL H23A38QABCA H23A50QABCA —
Model
TAL — — H23A62QDBLA
Comp. Type Hermetically Sealed Type
No. of Cylinders 2 2 2
Motor Output kW 2.2 3.0 3.75
Model P45J11SM P45J11SM×2 P45J11SM×2
Type Propeller
Fan
Motor Output W 80 90+60 90+80
Air Flow Rate m³/min 55 92 98
Machine Weight kg 91 120 115
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Internal Pressure Relief Valve (Compressor).
Safety Devices
Motor Protector (Compressor).
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.3 (Charged for 5m) 2.6 (Charged for 5m) 3.1 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.48 1.63 1.63
Drawing No. C : 4D020830A

Note:
1. ∗1 The above data are based on the following conditions. Conversion Formulae
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
(1) Indoor
: 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB cfm=m³/min×35.3
5m 60Hz, 220V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB

(2) Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB


Indoor : 20°C(68°F)DB
5m 60Hz, 220V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB

(3) Indoor
: 29°C(84°F)DB, 19.0°C(66°F)WB Indoor : 21°C(70°F)DB
7.5m 60Hz, 220V SSA 385/386
Outdoor : 46°C(115°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.

Indoor Unit FD(Y)M03~06FA 15


Optional Accessories ED40-017B

4. Optional Accessories
4.1 Option List

FD(Y)M–FA
FDYM03~06FAV1 / FAVAL
Name of Option
FDM03~05FAV1 / FAVAL
Wired Remote Controller BRC1C61
Wireless Heat Pump BRC4C62
Remote Controller Cooling Only BRC4C64
Set Back Time Clock BRC15A61
Central Remote Controller DCS302C61
Unified ON/OFF Controller DCS301B61
Schedule Timer DST301B61
intelligent Touch Controller DCS601B51
Wiring Adaptor for Electrical Appendices KRP4A51 (Note. 2)
Interface Adaptor for SkyAir Series DTA102A52
C : 4D021001A
Note: 1. Refer to the Option Hand Book for the detail.
2. Installation plate for adaptor PCB (KRP4A95) is necessary.

16 Indoor Unit FD(Y)M03~06FA


ED40-017B Dimensions

5. Dimensions
1
FDM03FA
FDYM03FA

3D020891C
Unit (mm)

Indoor Unit FD(Y)M03~06FA 17


Dimensions ED40-017B

FDM04FA
FDM05FA
FDYM04FA
FDYM05FA
FDYM06FA

3D020892B
Unit (mm)

18 Indoor Unit FD(Y)M03~06FA


ED40-017B Remote Controller

6. Remote Controller
1
6.1 Dimensions

BRC1C61

Unit (mm)

3D028952

BRC4C62 (Wireless Type)


BRC4C64 (Wireless Type)
Unit (mm)

3D007898

Indoor Unit FD(Y)M03~06FA 19


Remote Controller ED40-017B

6.2 Operation
6.2.1 Wired Remote Controller
Fig. 1 5 11 4 2 1

3
7 hr
9
C L H
hr NOT 10
6 TEST AVAILABLE

8 12
13 20
19
TEST
18

15 14 16 17 3PN02535-7L-0

NAME AND FUNCTION OF EACH DISPLAY “ ” (FAN SPEED)


9
SWITCH AND DISPLAY ON THE This display shows the set fan speed.
REMOTE CONTROLLER 10
DISPLAY “ ” (TIME TO CLEAN AIR
FILTER)
The illustrations in this operating manual correspond
to the remote control format BRC1C type. Although Not applied on this model.
the display and shape of the buttons on the BRC1B DISPLAY “ ” (DEFROST)
type are slightly different, they may be operated in 11
the same manner.
NON-FUNCTIONING DISPLAY
ON/OFF BUTTON If that particular function is not available,
1 Press the button and the system will start. pressing the button may display the words
Press the button again and the system will stop. “NOT AVAILABLE” for a few seconds.
OPERATION LAMP (RED) 12 When running multiple units simultaneously
2 The “NOT AVAILABLE” message will only be
The lamp lights up during operation.
appear if none of the indoor units is equipped
DISPLAY “ ” (UNDER with the function. If even one unit is equipped
CENTRALIZED CONTROL) with the function, the display will not appear.
3
When this display shows, the system is TIMER MODE START/STOP BUTTON
UNDER CENTRALIZED CONTROL. 13
DISPLAY “ ”“ ”“ ”“ ” TIMER ON/OFF BUTTON
(VENTILATION/AIR CLEANING) 14
4 This display shows that the total heat
INSPECTION/TEST OPERATION BUTTON
exchange and the air cleaning unit are in
operation (These are optional accessories).
15 This button is used only by qualified service
persons for maintenance purposes.
DISPLAY “ ” “ ” “ ”“ ”“ ”
(OPERATION MODE) PROGRAMMING TIME BUTTON
16 Use this button for programming “START
5 This display shows the current OPERATION
and/or STOP” time.
MODE. For cooling only type, “ ” (Auto) and
“ ” (Heating) are not installed. TEMPERATURE SETTING BUTTON
17
Use this button for SETTING TEMPERATURE.
DISPLAY “ TEST” (INSPECTION/TEST
OPERATION) FILTER SIGN RESET BUTTON
18
6 When the INSPECTION/TEST OPERATION Not applied on this model.
BUTTON is pressed, the display shows the FAN SPEED CONTROL BUTTON
system mode is in. 19 Press this button to select the fan speed,
hr
HIGH or LOW, of your choice.
DISPLAY “ ” (PROGRAMMED TIME) OPERATION MODE SELECTOR BUTTON
hr

7 20 Press this button to select OPERATION


This display shows the PROGRAMMED TIME MODE.
of the system start or stop.
NOTE
DISPLAY “ C ” (SET TEMPERATURE) For the sake of explanation, all indications are
8 shown on the display in figure 1 contrary to
This display shows the set temperature. actual running situations.
3PN02535-7L-4

20 Indoor Unit FD(Y)M03~06FA


ED40-017B Remote Controller

6.2.2 Wireless Remote Controller

Fig.1 Fig.2
1

Indoor Unit FD(Y)M03~06FA 21


Wiring Diagrams ED40-017B

7. Wiring Diagrams
FDYM03FAV1 / FDYM03FAVAL
FDYM04FAV1 / FDYM04FAVAL
FDYM05FAV1 / FDYM05FAVAL
FDYM06FAV1 / FDYM06FAVAL

3D019816D

22 Indoor Unit FD(Y)M03~06FA


ED40-017B Wiring Diagrams

FDM03FAV1 / FDM03FAVAL
FDM04FAV1 / FDM04FAVAL
1
FDM05FAV1 / FDM05FAVAL

3D019815D

Indoor Unit FD(Y)M03~06FA 23


Sound Level ED40-017B

8. Sound Level
8.1 Overall Sound Level
8.1.1 50Hz
dB(A)
Model 220V 240V Measuring Location
FDM03FAV1
39 41
FDM04FAV1
FDM05FAV1 44 46
FDYM03FAV1
39 41
FDYM04FAV1
FDYM05FAV1 44 46
4D021067A
FDYM06FAV1 46 48

8.1.2 60Hz
dB(A)
Model 220V Measuring Location
FDM03FAVAL
42
FDM04FAVAL
FDM05FAVAL 47
FDYM03FAVAL
42
FDYM04FAVAL
FDYM05FAVAL 47
4D021068A
FDYM06FAVAL 49

24 Indoor Unit FD(Y)M03~06FA


ED40-017B Sound Level

8.2 Octave Band Level


8.2.1 50Hz 1
FDM03FAV1 FDM04FAV1 FDM05FAV1
FDYM03FAV1 FDYM04FAV1 FDYM05FAV1

4D021067A 4D021069 4D021071

FDYM06FAV1 Note:
V1 : 220V
V1 : 240V

4D021073

8.2.2 60Hz
FDM03FAVAL FDM04FAVAL FDM05FAVAL
FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL

4D021068A 4D021070 4D021072

FDYM06FAVAL Note:
VAL : 220V

4D021074

Indoor Unit FD(Y)M03~06FA 25


Fan Performance ED40-017B

9. Fan Performance
FDM03FA
FDYM03FA

3D020899B

FDM04FA
FDYM04FA

3D020900A

26 Indoor Unit FD(Y)M03~06FA


ED40-017B Fan Performance

FDM05FA
FDYM05FA
1

3D020901A

FDYM06FA

3D020904A

Indoor Unit FD(Y)M03~06FA 27


Installation ED40-017B

10. Installation

28 Indoor Unit FD(Y)M03~06FA


ED40-017B Installation

Caution to be taken when brazing refrigerant piping


“Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux.”
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux
is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.

(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g.
BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.

Indoor Unit FD(Y)M03~06FA 29


Installation ED40-017B

30 Indoor Unit FD(Y)M03~06FA


ED40-017B Installation

Indoor Unit FD(Y)M03~06FA 31


Installation ED40-017B

32 Indoor Unit FD(Y)M03~06FA


ED40-017B Installation

Indoor Unit FD(Y)M03~06FA 33


Installation ED40-017B

34 Indoor Unit FD(Y)M03~06FA


ED40-017B Installation

Indoor Unit FD(Y)M03~06FA 35


Installation ED40-017B

36 Indoor Unit FD(Y)M03~06FA


ED40-017B

Part 2
Outdoor Unit
LU Series 2

1. External Appearance.............................................................................38
2. Power Supply ........................................................................................39
2.1 Cooling Only...........................................................................................39
2.2 Heat Pump .............................................................................................39
3. Specification..........................................................................................40
4. Dimensions and Service Space ............................................................41
4.1 Dimensions.............................................................................................41
4.2 Installation Service Space ......................................................................43
5. Piping Diagrams....................................................................................45
5.1 Cooling Only...........................................................................................45
5.2 Heat Pump .............................................................................................47
6. Wiring Diagrams....................................................................................49
6.1 Cooling Only...........................................................................................49
6.2 Heat Pump .............................................................................................52
7. Capacity Table ......................................................................................55
7.1 Cooling Only...........................................................................................55
7.2 Heat Pump .............................................................................................60
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ............63
8. Operation Limits ....................................................................................64
8.1 Cooling Only...........................................................................................64
8.2 Heat Pump .............................................................................................64
9. Sound Level ..........................................................................................65
9.1 Overall Sound Level ...............................................................................65
9.2 Octave Band Level .................................................................................66
10.Electric Characteristics..........................................................................68
10.1 Cooling Only...........................................................................................68
10.2 Heat Pump .............................................................................................69
11.Field Piping and Wiring .........................................................................70
11.1 Field Piping.............................................................................................70
11.2 Field Wiring ............................................................................................72

Outdoor Unit LU Series 37


External Appearance ED40-017B

1. External Appearance

R71LU R100LU
RY71LU RY100LU

R125LU R140LU
RY125LU RY140LU

38 Outdoor Unit LU Series


ED40-017B Power Supply

2. Power Supply
2.1 Cooling Only
2.1.1 50Hz
Series Indoor Unit Cooling Only Power Supply
FDYM03FAV1 R71LUV1 ∗

FDYM04FAV1 R100LUV1 ∗
1 phase 220–240V 2
FDYM03FAV1 R71LUY1 ∗
R–LU
FDYM04FAV1 R100LUY1 ∗
3 phase 380–415V (4 wires)
FDYM05FAV1 R125LUY1 ∗

FDYM06FAV1 R140LUY1 ∗

2.1.2 60Hz
Series Indoor Unit Cooling Only Power Supply
FDYM03FAVAL R71LUVAL ∗
1 phase 220V
FDYM04FAVAL R100LUVAL ∗

FDYM05FAVAL R125LUTAL ∗
R–LU 3 phase 220V
FDYM06FAVAL R140LUTAL ∗

FDYM05FAVAL R125LUYAL ∗
3 phase 380V (4 wires)
FDYM06FAVAL R140LUYAL ∗

Note: 1. ∗ : New Model or Changed Model


2. Power Supply Intake : Outdoor Unit

2.2 Heat Pump


2.2.1 50Hz
Series Indoor Unit Heat Pump Power Supply
FDYM03FAV1 RY71LUV1 ∗
1 phase 220–240V
FDYM04FAV1 RY100LUV1 ∗

FDYM03FAV1 RY71LUY1 ∗
RY–LU
FDYM04FAV1 RY100LUY1 ∗
3 phase 380–415V (4 wires)
FDYM05FAV1 RY125LUY1 ∗

FDYM06FAV1 RY140LUY1 ∗

2.2.2 60Hz
Series Indoor Unit Heat Pump Power Supply
FDYM06FAVAL RY140LUTAL ∗ 3 phase 220V
RY–LU
FDYM06FAVAL RY140LUYAL ∗ 3 phase 380V (4 wires)

Note: 1. ∗ : New Model or Changed Model


2. Power Supply Intake : Outdoor Unit

Outdoor Unit LU Series 39


Specification ED40-017B

3. Specification
FDYM–FA + R(Y)–LU

Refer to “Specification” in Part 1 on page 5, 8, 11, 13.

Optional Accessories

R71~140LU
Kit Name
Name of Option
R71LU R100LU R125LU R140LU
Central Drain Plug KKPJ5F180
Year-Round Cooling Kit KRK5F80V1 KRK5F140V1 KRK5F160V1
3D039655

RY71~140LU
Kit Name
Name of Option
RY71LU RY100LU RY125LU RY140LU
Central Drain Plug KKPJ5F180
3D039655

40 Outdoor Unit LU Series


ED40-017B Dimensions and Service Space

4. Dimensions and Service Space


4.1 Dimensions

R71LU
RY71LU
Unit (mm)
2

3D039213

R100LU
RY100LU
Unit (mm)

3D039214

Outdoor Unit LU Series 41


Dimensions and Service Space ED40-017B

R125LU
RY125LU
Unit (mm)

3D039215

R140LU
RY140LU
Unit (mm)

3D039216

42 Outdoor Unit LU Series


ED40-017B Dimensions and Service Space

4.2 Installation Service Space

3D039172-1

Outdoor Unit LU Series 43


Dimensions and Service Space ED40-017B

3D039172-2

44 Outdoor Unit LU Series


ED40-017B Piping Diagrams

5. Piping Diagrams
5.1 Cooling Only

R71LU

3D039739

R100LU

3D039740

Outdoor Unit LU Series 45


Piping Diagrams ED40-017B

R125LU

3D039741

R140LU

3D039742

46 Outdoor Unit LU Series


ED40-017B Piping Diagrams

5.2 Heat Pump

RY71LU

3D039734

RY100LU

3D039735

Outdoor Unit LU Series 47


Piping Diagrams ED40-017B

RY125LU

3D039736

RY140LU

3D039737

48 Outdoor Unit LU Series


ED40-017B Wiring Diagrams

6. Wiring Diagrams
6.1 Cooling Only
6.1.1 50Hz

R71LUV1
R100LUV1 2

3D037640C

R71LUY1
R100LUY1

3D037642C

Outdoor Unit LU Series 49


Wiring Diagrams ED40-017B

R125LUY1
R140LUY1

3D037644C

6.1.2 60Hz

R71LUVAL
R100LUVAL

3D037935C

50 Outdoor Unit LU Series


ED40-017B Wiring Diagrams

R125LUTAL
R140LUTAL

3D037936C

R125LUYAL
R140LUYAL

3D037937C

Outdoor Unit LU Series 51


Wiring Diagrams ED40-017B

6.2 Heat Pump


6.2.1 50Hz (Including 60Hz YAL Models)

RY71LUV1
RY100LUV1

3D037639C

RY71LUY1
RY100LUY1

3D037641C

52 Outdoor Unit LU Series


ED40-017B Wiring Diagrams

RY125LUY1
RY140LUY1

3D037643C

6.2.2 60Hz

RY140LUTAL

3D037938C

Outdoor Unit LU Series 53


Wiring Diagrams ED40-017B

RY140LUYAL

3D037939C

54 Outdoor Unit LU Series


ED40-017B Capacity Table

7. Capacity Table
7.1 Cooling Only
7.1.1 50Hz

FDYM03FAV1 + R71LUV1
FDYM03FAV1 + R71LUY1 2

3D039613A

FDYM04FAV1 + R100LUV1
FDYM04FAV1 + R100LUY1

3D039626A

Outdoor Unit LU Series 55


Capacity Table ED40-017B

FDYM05FAV1 + R125LUY1

3D039635

FDYM06FAV1 + R140LUY1

3D039644

56 Outdoor Unit LU Series


ED40-017B Capacity Table

7.1.2 60Hz

FDYM03FAVAL + R71LUVAL

3D039615A

FDYM04FAVAL + R100LUVAL

3D039628

Outdoor Unit LU Series 57


Capacity Table ED40-017B

FDYM05FAVAL + R125LUTAL

3D039637

FDYM05FAVAL + R125LUYAL

3D039638

58 Outdoor Unit LU Series


ED40-017B Capacity Table

FDYM06FAVAL + R140LUTAL

3D039648

FDYM06FAVAL + R140LUYAL

3D039652

Outdoor Unit LU Series 59


Capacity Table ED40-017B

7.2 Heat Pump


7.2.1 50Hz

FDYM03FAV1 + RY71LUV1
FDYM03FAV1 + RY71LUY1

3D039611A

FDYM04FAV1 + RY100LUV1
FDYM04FAV1 + RY100LUY1

3D039624

60 Outdoor Unit LU Series


ED40-017B Capacity Table

FDYM05FAV1 + RY125LUY1

3D039633

FDYM06FAV1 + RY140LUY1

3D039642

Outdoor Unit LU Series 61


Capacity Table ED40-017B

7.2.2 60Hz

FDYM06FAVAL + RY140LUTAL

3D039646

FDYM06FAVAL + RY140LUYAL

3D039650

62 Outdoor Unit LU Series


ED40-017B Capacity Table

7.3 Capacity Correction Factor by the Length of Refrigerant Piping


The cooling and heating capacity of the unit has to be corrected in accordance with the length of refrigerant
piping. (The distance between the indoor unit and the outdoor unit)
Reference Data
100
Cooling (Heating) capacity correction factor
71~140 2
95

90

100
85
71
125

80 140

75
0 5 7.5 10 15 20 25 30 35 40 45 50 (m)
Length of refrigerant piping (Total length)
C : 3D006500C

Note: 1. line: Correction factor for cooling capacity


line: Correction factor for heating capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below the
indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the
unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the
range of its limitation.

Outdoor Unit LU Series 63


Operation Limits ED40-017B

8. Operation Limits
8.1 Cooling Only
R71LUV1 / R71LUY1 / R71LUVAL
R100LUV1 / R100LUY1 / R100LUVAL
R125LUY1 / R125LUTAL / R125LUYAL
R140LUY1 / R140LUTAL / R140LUYAL

3D039657

8.2 Heat Pump


RY71LUV1 / RY71LUY1
RY100LUV1 / RY100LUY1
RY125LUY1
RY140LUY1 / RY140LUTAL / RY140LUYAL

3D039656

64 Outdoor Unit LU Series


ED40-017B Sound Level

9. Sound Level
9.1 Overall Sound Level
9.1.1 Cooling Only
dB(A)
50Hz 60Hz
Model
220V 240V 220V
Measuring Location 2
R71LU 48 49 —
R100LU 49 50 —
380V 415V 220V
R71LU 48 49 49
R100LU 49 50 51
R125LU 49 50 —
R140LU 54 55 —
R125LUTAL — — 51
R140LUTAL — — 55 4D039813
380V
R125LUYAL — — 51
R140LUYAL — — 55

Note: Operation sound is measured in an anechoic chamber.

9.1.2 Heat Pump


dB(A)
50Hz 60Hz
Model 220V 240V 220V Measuring Location
Cooling Heating Cooling Heating Cooling Heating
RY71LU 48 49 49 50 — —
RY100LU 49 52 50 53 — —
380V 415V 220 · 380V
Cooling Heating Cooling Heating Cooling Heating
RY71LU 48 49 49 50 — —
RY100LU 49 52 50 53 — —
RY125LU 49 52 50 53 — —
RY140LU 54 56 55 57 55 57
4D039813

Note: Operation sound is measured in an anechoic chamber.

Outdoor Unit LU Series 65


Sound Level ED40-017B

9.2 Octave Band Level


9.2.1 Cooling Only
„ 50Hz
R71LUV1 R100LUV1 R125LUY1
R71LUY1 R100LUY1

4D039802 4D039804 4D039806

R140LUY1 Note:
V1 : 220V, Y1 : 380V
V1 : 240V, Y1 : 415V

4D039808

„ 60Hz
R71LUVAL R100LUVAL R125LUTAL
R125LUYAL

4D039810 4D039811 4D039812

R140LUTAL Note:
R140LUYAL TAL : 220V, YAL : 380V

4D039813

66 Outdoor Unit LU Series


ED40-017B Sound Level

9.2.2 Heat Pump


„ 50Hz
RY71LUV1 (Cooling) RY71LUV1 (Heating) RY100LUV1 (Cooling)
RY71LUY1 (Cooling) RY71LUY1 (Heating) RY100LUY1 (Cooling)

4D039802 4D039803 4D039804

RY100LUV1 (Heating) RY125LUY1 (Cooling) RY125LUY1 (Heating)


RY100LUY1 (Heating)

4D039805 4D039806 4D039807

RY140LUY1 (Cooling) RY140LUY1 (Heating) Note:


V1 : 220V, Y1 : 380V
V1 : 240V, Y1 : 415V

4D039808 4D039809

„ 60Hz
RY140LUTAL (Cooling) RY140LUTAL (Heating) Note:
RY140LUYAL (Cooling) RY140LUYAL (Heating) TAL : 220V, YAL : 380V

4D039813 4D039814

Outdoor Unit LU Series 67


Electric Characteristics ED40-017B

10. Electric Characteristics


10.1 Cooling Only
10.1.1 50Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
50 – 220 82 13.7
FDYM03FAV1 R71LUV1 50 – 230 18.6 23.5 30 78 13.1 0.065 0.6 0.125 0.9
50 – 240 Max.50Hz 264V 75 12.5
50 – 220 Min.50Hz 198V 114 17.4
FDYM04FAV1 R100LUV1 50 – 230 23.6 27.8 40 109 16.6 0.09 0.8 0.135 1.0
50 – 240 105 15.9
50 – 380 / 220 40 5.0
FDYM03FAV1 R71LUY1 50 – 400 / 230 7.8 9.0 15 38 4.8 0.065 0.6 0.125 0.9
50 – 415 / 240 37 4.6
50 – 380 / 220 50 6.4
FDYM04FAV1 R100LUY1 50 – 400 / 230 Max.50Hz 9.8 11.8 15 48 6.1 0.09 0.8 0.135 1.0
50 – 415 / 240 456 / 264V 46 5.9
50 – 380 / 220 Min.50Hz 51 7.8 0.065 0.6
FDYM05FAV1 R125LUY1 50 – 400 / 230 342 / 198V 12.6 15.7 20 53 7.8 + + 0.225 1.4
50 – 415 / 240 56 7.9 0.085 0.7
50 – 380 / 220 67 8.2 0.065 0.6
FDYM06FAV1 R140LUY1 50 – 400 / 230 13.6 18.0 25 71 8.2 + + 0.270 1.6
50 – 415 / 240 74 8.5 0.090 0.8
3D039576C
3D039577A
3D039578A
3D039579A

10.1.2 60Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
FDYM03FAVAL R71LUVAL 60 – 220 19.9 24.0 30 99 14.3 0.075 0.8 0.125 1.2
FDYM04FAVAL R100LUVAL 60 – 220 23.8 28.2 40 143 17.3 0.1 0.9 0.135 1.3
0.075 0.8
FDYM05FAVAL R125LUTAL 60 – 220 Max.60Hz 242V 22.6 25.3 30 137 15.1 + + 0.225 2.0
Min.60Hz 198V 0.095 0.9
0.075 0.8
FDYM06FAVAL R140LUTAL 60 – 220 23.3 31.9 40 146 15.5 + + 0.270 2.2
0.100 0.9
0.075 0.8
FDYM05FAVAL R125LUYAL 60 – 380 14.2 16.3 20 66 8.4 + + 0.225 2.0
Max.60Hz 418V 0.095 0.9
Min.60Hz 342V 0.075 0.8
FDYM06FAVAL R140LUYAL 60 – 380 14.5 18.9 25 75 8.5 + + 0.270 2.2
0.100 0.9
3D039576C
3D039577A
3D039578A
3D039579A

68 Outdoor Unit LU Series


ED40-017B Electric Characteristics

10.2 Heat Pump


10.2.1 50Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
50 – 220 82 13.4
FDYM03FAV1 RY71LUV1 50 – 230 18.3 23.5 30 78 12.8 0.065 0.6 0.125 0.9
50 – 240 Max.50Hz 264V 75 12.3 2
50 – 220 Min.50Hz 198V 114 17.1
FDYM04FAV1 RY100LUV1 50 – 230 23.2 27.8 40 109 16.3 0.09 0.8 0.135 1.0
50 – 240 105 15.6
50 – 380 / 220 40 4.9
FDYM03FAV1 RY71LUY1 50 – 400 / 230 7.6 9.0 15 38 4.7 0.065 0.6 0.125 0.9
50 – 415 / 240 37 4.5
50 – 380 / 220 50 6.3
FDYM04FAV1 RY100LUY1 50 – 400 / 230 Max.50Hz 9.7 11.8 15 48 6.0 0.09 0.8 0.135 1.0
50 – 415 / 240 456 / 264V 46 5.8
50 – 380 / 220 Min.50Hz 51 7.6 0.065 0.6
FDYM05FAV1 RY125LUY1 50 – 400 / 230 342 / 198V 12.5 15.7 20 53 7.7 + + 0.225 1.4
50 – 415 / 240 56 7.8 0.085 0.7
50 – 380 / 220 67 8.1 0.065 0.6
FDYM06FAV1 RY140LUY1 50 – 400 / 230 13.6 18.0 25 71 8.1 + + 0.270 1.6
50 – 415 / 240 74 8.5 0.090 0.8
3D039576C
3D039577A
3D039578A
3D039579A

10.2.2 60Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
0.075 0.8
Max.60Hz 242V
FDYM06FAVAL RY140LUTAL 60 – 220 Min.60Hz 198V 23.2 31.9 40 146 15.4 + + 0.270 2.2
0.100 0.9
0.075 0.8
Max.60Hz 418V
FDYM06FAVAL RY140LUYAL 60 – 380 Min.60Hz 342V 14.5 18.9 25 75 8.5 + + 0.270 2.2
0.100 0.9
3D039579A

Symbols: MCA : Min. Circuit Amps


TOCA : Total Over-Current Amps
MFA : Max. Fuse Amps (See note 7)
LRA : Locked Rotor Amps
RLA : Rated Load Amps
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
kW : Fan Motor Rated Output

Note: 1. RLA is based on the following conditions.


Indoor temp. 27°CDB/19.0°CWB
Outdoor temp. 35°CDB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit
terminals is not below or above listed range limits.
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 × RLA + ea. FLA
MFA ≤ 2.25 × RLA + ea. FLA
(Next lower standard fuse rating, Min. 15A)
6. Select wire size based on the larger value of MCA or TOCA.
7. Instead of fuse, use circuit breaker.

Outdoor Unit LU Series 69


Field Piping and Wiring ED40-017B

11. Field Piping and Wiring


11.1 Field Piping
11.1.1 Maximum Allowable Piping Length and Level Difference
R(Y)71~140LU
Max. Allowable Piping Length 50 m (Equivalent Length 70 m)
Max. Allowable Level Difference 30 m

11.1.2 Additional Refrigerant Charge


• This unit requires additional charging of refrigerant according to the length of pipe connected at the site.
The range where no charging is required. (R(Y)71~140LU : 30 m or less.)
Take the following steps for proper charging.
When connected to one indoor unit (pair system)

Main pipe (L1)

Indoor unit
One-way length of pipe (L):
L1
• Select the amount of refrigerant which matches a length which exceeds the charge-less length from
Table 1, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.
Table 1 (The maximum allowable pipe length is 50 meters.) <unit : kg>
Pipe Excess Length over 30 Meters 10 m or less 20 m or less
RY71 0.50 1.00
Heat Pump Type
RY100~160 0.75 1.50
Straight Cooling Type R71~140 0.25 0.50

11.1.3 Recharging Refrigerant


When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the
amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is
an addition of the amount stated on the nameplate and the additional charging amount.

1PN05248B-1
11.1.4 Pumping-down Operation Method
The outdoor unit is equipped with a low-pressure switch to protect the compressor.
Take the following steps to perform the pumping-down operation.

Caution: Never short-circuit the low-pressure switch in this operation.


Procedure Precautions
Confirm that stop valves both on the liquid and gas side
1. Start the fan operation with the remote controller. are open. Take care when the procedure 2 is done first
because the indoor unit fan may operate automatically.
2. Push the pumping-down button on the PC board of the Compressor and outdoor fan will start operation
outdoor unit. automatically.
3. Continue operation for 1 min. until operation condition —
stabilizes.
4. Close the stop valve on the liquid side securely. Insecure closing of the valve may result in burning of
(Refer to Fig. 1) the compressor.
5. When the low-pressure switch is activated, the unit
stops working. At this time, close the stop valve on the —
gas side.
This is the end of pumping-down operation.
After pumping-down operation, the remote controller shows “U4” even when ON button on the remote
controller is pressed, and it will not operate. Although the remote controller may or may not indicate “U4”
according to circumstances at this time, it is normal. When the remote controller indicates “U4”, the indoor
unit fan may operate (for about max 30 minutes). Turn off the main power supply switch and turn it on again
in need of operation.

70 Outdoor Unit LU Series


ED40-017B Field Piping and Wiring

How to use the stop valve (Refer to Fig. 1)


Have a hex wrench ready. (4 mm and 6 mm) (Gas side)
Opening direction
1. Open the valve.
a. Place the hex wrench on the valve bar and turn counter-clockwise. (Liquid side)
Opening direction
b. Stop when the valve bar no longer turns. It is now open.
2. Close the valve.
a. Place the hex wrench on the valve bar and turn clockwise.
b. Stop when the valve bar no longer turns. It is now closed.
2
Fig. 1

Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to
provide a trap at an appropriate place in the riser gas piping.

Trap installation spacing


Indoor unit
Oil trap

Gas piping

Liquid piping
∗15m

∗Marks. Install trap at


each difference in
height 15m.
Outdoor unit

Note: A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.

Caution to be taken when brazing refrigerant piping


“Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux
has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)

(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.

1PN05248B-2

Outdoor Unit LU Series 71


Field Piping and Wiring ED40-017B

11.2 Field Wiring


11.2.1 50Hz

C : 4D001694A

72 Outdoor Unit LU Series


ED40-017B Field Piping and Wiring

11.2.2 60Hz

C : 4D006674A

Outdoor Unit LU Series 73


Field Piping and Wiring ED40-017B

74 Outdoor Unit LU Series


ED40-017B

Part 3
Outdoor Unit
KU Series
1. External Appearance.............................................................................76 3
2. Power Supply ........................................................................................77
2.1 Cooling Only...........................................................................................77
2.2 Heat Pump .............................................................................................77
3. Specification..........................................................................................78
4. Dimensions and Service Space ............................................................79
4.1 Dimensions.............................................................................................79
4.2 Installation Service Space for R(Y)140KU .............................................81
4.3 Installation Service Space for R(Y)200 · 250KU ....................................83
5. Piping Diagrams....................................................................................84
5.1 Cooling Only...........................................................................................84
5.2 Heat Pump .............................................................................................85
6. Wiring Diagrams....................................................................................89
6.1 Cooling Only...........................................................................................89
6.2 Heat Pump .............................................................................................91
7. Capacity Table ......................................................................................94
7.1 Cooling Only...........................................................................................94
7.2 Heat Pump .............................................................................................96
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ............99
8. Operation Limits ..................................................................................100
8.1 Cooling Only.........................................................................................100
8.2 Heat Pump ...........................................................................................101
9. Sound Level ........................................................................................102
9.1 Overall Sound Level .............................................................................102
9.2 Octave Band Level ...............................................................................103
10.Electric Characteristics........................................................................105
10.1 Cooling Only.........................................................................................105
10.2 Heat Pump ...........................................................................................106
11.Field Piping and Wiring .......................................................................107
11.1 Field Piping (R(Y)140KU).....................................................................107
11.2 Field Piping (R(Y)200 · 250KU)............................................................109
11.3 Field Wiring ..........................................................................................112

Outdoor Unit KU Series 75


External Appearance ED40-017B

1. External Appearance

R140KU
RY140KU

R200KU R250KU
RY200KU RY250KU

76 Outdoor Unit KU Series


ED40-017B Power Supply

2. Power Supply
2.1 Cooling Only
2.1.1 50Hz
Series Indoor Unit Cooling Only Power Supply
FDYM04FAV1×2 R200KUY1

R–KU FDYM03FAV1×3 R200KUY1 3 phase 380–415V (4 wires)

FDYM05FAV1×2 R250KUY1

2.1.2 60Hz
Series Indoor Unit Cooling Only Power Supply 3
FDYM06FAVAL R140KUTALK

FDYM04FAVAL×2 R200KUTAL
3 phase 220V
FDYM03FAVAL×3 R200KUTAL

FDYM05FAVAL×2 R250KUTAL
R–KU
FDYM06FAVAL R140KUYALK

FDYM04FAVAL×2 R200KUYAL
3 phase 380V (4 wires)
FDYM03FAVAL×3 R200KUYAL

FDYM05FAVAL×2 R250KUYAL

Note: 1. Power Supply Intake : Outdoor Unit

2.2 Heat Pump


2.2.1 50Hz
Series Indoor Unit Heat Pump Power Supply
FDYM04FAV1×2 RY200KUY1

RY–KU FDYM03FAV1×3 RY200KUY1 3 phase 380–415V (4 wires)

FDYM05FAV1×2 RY250KUY1

2.2.2 60Hz
Series Indoor Unit Heat Pump Power Supply
FDYM06FAVAL RY140KUTALK

FDYM04FAVAL×2 RY200KUTAL
3 phase 220V
FDYM03FAVAL×3 RY200KUTAL

FDYM05FAVAL×2 RY250KUTAL
RY–KU
FDYM06FAVAL RY140KUYALK

FDYM04FAVAL×2 RY200KUYAL
3 phase 380V (4 wires)
FDYM03FAVAL×3 RY200KUYAL

FDYM05FAVAL×2 RY250KUYAL

Note: 1. Power Supply Intake : Outdoor Unit

Outdoor Unit KU Series 77


Specification ED40-017B

3. Specification
FDYM–FA + R(Y)–KU

Refer to “Specification” in Part 1 on page 6, 9, 12, 14.

Optional Accessories
R140KU
Kit Name
Name of Option
R140KU
Central Drain Plug KKPJ5F180
Year-Round Cooling Kit KRK5F160V1
3D014872B

RY140KU
Kit Name
Name of Option
RY140KU
Central Drain Plug KKPJ5F180
3D014872B

R(Y)200 · 250KU
Kit Name
Name of Option Remark
R(Y)200KU R(Y)250KU
For Twin Type KHD58C23A KHD58C24A
Branch Piping Kit For Triple Type KHR58P322H —
For Double Twin Type KHRJ5F224F KHRJ5F280F
4D029784A

78 Outdoor Unit KU Series


ED40-017B Dimensions and Service Space

4. Dimensions and Service Space


4.1 Dimensions

R140KU
RY140KU

Unit (mm)

C : 3D027710A

R200KU
RY200KU

Unit (mm)

3D029265

Outdoor Unit KU Series 79


Dimensions and Service Space ED40-017B

R250KU
RY250KU

Unit (mm)

3D029264

80 Outdoor Unit KU Series


ED40-017B Dimensions and Service Space

4.2 Installation Service Space for R(Y)140KU

3D001951A-1

Outdoor Unit KU Series 81


Dimensions and Service Space ED40-017B

3D001951A-2

82 Outdoor Unit KU Series


ED40-017B Dimensions and Service Space

4.3 Installation Service Space for R(Y)200 · 250KU

3D006578A

Outdoor Unit KU Series 83


Piping Diagrams ED40-017B

5. Piping Diagrams
5.1 Cooling Only

R140KU

C : 3D014832A

R200KU (Twin System)


R250KU (Twin System)

3D030194

84 Outdoor Unit KU Series


ED40-017B Piping Diagrams

R200KU (Triple System)

3D030195

5.2 Heat Pump

RY140KU

140

C : 3D014830B

Outdoor Unit KU Series 85


Piping Diagrams ED40-017B

RY200KUY1 (Twin System)

3D029823

RY250KUY1 (Twin System)

3D029827

86 Outdoor Unit KU Series


ED40-017B Piping Diagrams

RY200KUTAL (Twin System)


RY200KUYAL (Twin System)

3D030158

RY250KUTAL (Twin System)


RY250KUYAL (Twin System)

3D030163

Outdoor Unit KU Series 87


Piping Diagrams ED40-017B

RY200KUY1 (Triple System)

3D029825

RY200KUTAL (Triple System)


RY200KUYAL (Triple System)

3D030160

88 Outdoor Unit KU Series


ED40-017B Wiring Diagrams

6. Wiring Diagrams
6.1 Cooling Only
6.1.1 50Hz (Including 60Hz YAL Models)

R200KUY1 / R200KUYAL
R250KUY1 / R250KUYAL

3D029091A

6.1.2 60Hz

R140KUTALK

3D015463D

Outdoor Unit KU Series 89


Wiring Diagrams ED40-017B

R140KUYALK

3D015461E

R200KUTAL
R250KUTAL

3D029092

90 Outdoor Unit KU Series


ED40-017B Wiring Diagrams

6.2 Heat Pump


6.2.1 50Hz (Including 60Hz YAL Models)

RY200KUY1
RY200KUYAL

3D028900A

RY250KUY1
RY250KUYAL

3D028901A

Outdoor Unit KU Series 91


Wiring Diagrams ED40-017B

6.2.2 60Hz

RY140KUTALK

3D027416A

RY140KUYALK

3D027413A

92 Outdoor Unit KU Series


ED40-017B Wiring Diagrams

RY200KUTAL

3D028902A

RY250KUTAL

3D028903A

Outdoor Unit KU Series 93


Capacity Table ED40-017B

7. Capacity Table
7.1 Cooling Only
7.1.1 50Hz

FDYM04FAV1 × 2 + R200KUY1
FDYM03FAV1 × 3 + R200KUY1

3D030166

FDYM05FAV1 × 2 + R250KUY1

3D030168

94 Outdoor Unit KU Series


ED40-017B Capacity Table

7.1.2 60Hz

FDYM06FAVAL + R140KUTALK
FDYM06FAVAL + R140KUYALK

3D028068

FDYM03FAVAL × 3 + R200KUTAL / FDYM03FAVAL × 3 + R200KUYAL


FDYM04FAVAL × 2 + R200KUTAL / FDYM04FAVAL × 2 + R200KUYAL

3D030167

Outdoor Unit KU Series 95


Capacity Table ED40-017B

FDYM05FAVAL × 2 + R250KUTAL
FDYM05FAVAL × 2 + R250KUYAL

3D030169

7.2 Heat Pump


7.2.1 50Hz

FDYM04FAV1 × 2 + RY200KUY1
FDYM03FAV1 × 3 + RY200KUY1

3D029856

96 Outdoor Unit KU Series


ED40-017B Capacity Table

FDYM05FAV1 × 2 + RY250KUY1

3D029853

7.2.2 60Hz

FDYM06FAVAL + RY140KUTALK
FDYM06FAVAL + RY140KUYALK

3D028060

Outdoor Unit KU Series 97


Capacity Table ED40-017B

FDYM04FAVAL × 2 + RY200KUTAL
FDYM04FAVAL × 2 + RY200KUYAL
FDYM03FAVAL × 3 + RY200KUTAL
FDYM03FAVAL × 3 + RY200KUYAL

3D029857

FDYM05FAVAL × 2 + RY250KUTAL
FDYM05FAVAL × 2 + RY250KUYAL

3D029855

98 Outdoor Unit KU Series


ED40-017B Capacity Table

7.3 Capacity Correction Factor by the Length of Refrigerant Piping


The cooling and heating capacity of the unit has to be corrected in accordance with the length of refrigerant
piping. (The distance between the indoor unit and the outdoor unit)
Reference Data

Cooling (heating) capacity correction factor 100

140~250
95

90

200
3
85 250

80
140

75
0 5 10 15 20 25 30 35 40 45 50 (m)
Length of refrigerant piping (Total length)
C : 3D006500C

Note: 1. line: Correction factor for cooling capacity


line: Correction factor for heating capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below the
indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the
unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the
range of its limitation.

Outdoor Unit KU Series 99


Operation Limits ED40-017B

8. Operation Limits
8.1 Cooling Only
R140KUTALK
R140KUYALK

3D028099

[50Hz] [60Hz]
R200KUY1 R200KUTAL / R200KUYAL
R250KUY1 R250KUTAL / R250KUYAL

3D030170 3D030170

100 Outdoor Unit KU Series


ED40-017B Operation Limits

8.2 Heat Pump


RY140KUTALK
RY140KUYALK

3D028098

RY200KUY1 / RY200KUTAL / RY200KUYAL


RY250KUY1 / RY250KUTAL / RY250KUYAL

3D029783

Outdoor Unit KU Series 101


Sound Level ED40-017B

9. Sound Level
9.1 Overall Sound Level
9.1.1 Cooling Only
dB(A)
Model 50Hz 380V 50Hz 415V 60Hz 220 · 380V Measuring Location
R140KU — — 56 R140KU
R200KU 60 61 60
R250KU 61 62 61

MIKE

4D028089B

R200 · 250KU

MIKE

4D030106

Note: Operation sound is measured in an anechoic chamber.

9.1.2 Heat Pump


dB(A)
50Hz 380V 50Hz 415V 60Hz 220 · 380V
Model Measuring Location
Cooling Heating Cooling Heating Cooling Heating
RY140KU — — — — 56 58 RY140KU
RY200KU 60 62 61 63 60 62
RY250KU 61 63 62 64 61 63

MIKE

4D028089B

RY200 · 250KU

MIKE

4D030106

Note: Operation sound is measured in an anechoic chamber.

102 Outdoor Unit KU Series


ED40-017B Sound Level

9.2 Octave Band Level


9.2.1 Cooling Only
„ 50Hz
R200KUY1 R250KUY1 Note:
Y1 : 380V
Y1 : 415V

4D027632 4D027634

„ 60Hz
R140KUTALK R200KUTAL R250KUTAL
R140KUYALK R200KUYAL R250KUYAL

4D028089B 4D030106 4D030108

Note:
TAL : 220V, YAL : 380V

Outdoor Unit KU Series 103


Sound Level ED40-017B

9.2.2 Heat Pump


„ 50Hz
RY200KUY1 (Cooling) RY200KUY1 (Heating) RY250KUY1 (Cooling)

4D027632 4D027631 4D027634

RY250KUY1 (Heating) Note:


Y1 : 380V
Y1 : 415V

4D027633

„ 60Hz
RY140KUTALK (Cooling) RY140KUTALK (Heating) RY200KUTAL (Cooling)
RY140KUYALK (Cooling) RY140KUYALK (Heating) RY200KUYAL (Cooling)

4D028089B 4D028049A 4D030106

RY200KUTAL (Heating) RY250KUTAL (Cooling) RY250KUTAL (Heating)


RY200KUYAL (Heating) RY250KUYAL (Cooling) RY250KUYAL (Heating)

4D030105 4D030108 4D030107

Note:
TAL : 220V, YAL : 380V

104 Outdoor Unit KU Series


ED40-017B Electric Characteristics

10. Electric Characteristics


10.1 Cooling Only
10.1.1 50Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
50 – 380 / 220 87 12.6 0.23 1.3
0.135
FDYM04FAV1×2 R200KUY1 50 – 400 / 230 20.8 22.5 30 92 12.4 + + ×2 1.0×2
50 – 415 / 240 95 13.0 0.19 1.2
50 – 380 / 220 Max.50Hz 87 12.6 0.23 1.3
456 / 264V 0.125
FDYM03FAV1×3 R200KUY1 50 – 400 / 230 Min.50Hz 21.5 23.2 30 92 12.4 + + ×3 0.9×3
50 – 415 / 240 95 13.0 0.19 1.2
50 – 380 / 220
342 / 198V
128 16.3 0.23 1.3
0.225
3
FDYM05FAV1×2 R250KUY1 50 – 400 / 230 26.8 29.3 40 135 15.7 + + ×2 1.4×2
50 – 415 / 240 140 17.2 0.19 1.2
C : 3D029999
C : 3D030000

10.1.2 60Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
0.12 1.1
FDYM06FAVAL R140KUTALK 60 – 220 24.5 32.2 40 165 16.2 + + 0.270 2.2
0.10 1.0
0.23 1.8 0.135
FDYM04FAVAL×2 R200KUTAL 60 – 220 35.3 39.0 50 161 23.4 + + 1.3×2
0.19 1.6 ×2
Max.60Hz 242V
Min.60Hz 198V 0.23 1.8 0.125
FDYM03FAVAL×3 R200KUTAL 60 – 220 36.3 40.0 50 161 23.4 + + 1.2×3
0.19 1.6 ×3

0.23 1.8 0.225


FDYM05FAVAL×2 R250KUTAL 60 – 220 42.3 53.4 60 225 27.9 + + 2.0×2
0.19 1.6 ×2

Max.60Hz 418V 0.12 1.1


FDYM06FAVAL R140KUYALK 60 – 380 14.8 19.2 25 69 8.5 + + 0.270 2.2
Min.60Hz 342V 0.10 1.0
0.23 1.8 0.135
FDYM04FAVAL×2 R200KUYAL 60 – 380 / 220 23.0 24.0 30 81 13.6 + + 1.3×2
0.19 1.6 ×2
Max.60Hz
418 / 242V 0.23 1.8 0.125
FDYM03FAVAL×3 R200KUYAL 60 – 380 / 220 24.0 25.0 30 81 13.6 + + 1.2×3
Min.60Hz 0.19 1.6 ×3
342 / 198V
0.23 1.8 0.225
FDYM05FAVAL×2 R250KUYAL 60 – 380 / 220 29.0 31.4 40 107 17.3 + + 2.0×2
0.19 1.6 ×2
C : 3D028200B
C : 3D029999
C : 3D030000

Outdoor Unit KU Series 105


Electric Characteristics ED40-017B

10.2 Heat Pump


10.2.1 50Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
50 – 380 / 220 87 12.6 0.23 1.3
0.135
FDYM04FAV1×2 RY200KUY1 50 – 400 / 230 20.8 22.5 30 92 12.4 + + ×2 1.0×2
50 – 415 / 240 95 13.0 0.19 1.2
50 – 380 / 220 Max.50Hz 87 12.6 0.23 1.3
456 / 264V 0.125
FDYM03FAV1×3 RY200KUY1 50 – 400 / 230 Min.50Hz 21.5 23.2 30 92 12.4 + + ×3 0.9×3
50 – 415 / 240 95 13.0 0.19 1.2
342 / 198V
50 – 380 / 220 128 16.3 0.23 1.3
0.225
FDYM05FAV1×2 RY250KUY1 50 – 400 / 230 26.8 29.3 40 135 15.7 + + ×2 1.4×2
50 – 415 / 240 140 17.2 0.19 1.2
C : 3D029820
C : 3D029821

10.2.2 60Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
0.12 1.1
FDYM06FAVAL RY140KUTALK 60 – 220 25.0 32.2 40 165 16.6 + + 0.270 2.2
0.10 1.0
0.23 1.8 0.135
FDYM04FAVAL×2 RY200KUTAL 60 – 220 35.3 39.0 50 161 23.4 + + 1.3×2
0.19 1.6 ×2
Max.60Hz 242V
Min.60Hz 198V 0.23 1.8 0.125
FDYM03FAVAL×3 RY200KUTAL 60 – 220 36.3 40.0 50 161 23.4 + + 1.2×3
0.19 1.6 ×3

0.23 1.8 0.225


FDYM05FAVAL×2 RY250KUTAL 60 – 220 42.3 53.4 60 225 27.9 + + 2.0×2
0.19 1.6 ×2

Max.60Hz 418V 0.12 1.1


FDYM06FAVAL RY140KUYALK 60 – 380 15.2 19.2 25 69 8.8 + + 0.270 2.2
Min.60Hz 342V 0.10 1.0
0.23 1.8 0.135
FDYM04FAVAL×2 RY200KUYAL 60 – 380 / 220 23.0 24.0 30 81 13.6 + + 1.3×2
0.19 1.6 ×2
Max.60Hz
418 / 242V 0.23 1.8 0.125
FDYM03FAVAL×3 RY200KUYAL 60 – 380 / 220 24.0 25.0 30 81 13.6 + + 1.2×3
Min.60Hz 0.19 1.6 ×3
342 / 198V
0.23 1.8 0.225
FDYM05FAVAL×2 RY250KUYAL 60 – 380 / 220 29.0 31.4 40 107 17.3 + + 2.0×2
0.19 1.6 ×2
C : 3D028200B
C : 3D029820
C : 3D029821
Symbols: MCA : Min. Circuit Amps
TOCA : Total Over-Current Amps
MFA : Max. Fuse Amps (See note 7)
LRA : Locked Rotor Amps
RLA : Rated Load Amps
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
kW : Fan Motor Rated Output

Note: 1. RLA is based on the following conditions.


Indoor temp. 27°CDB/19.0°CWB
Outdoor temp. 35°CDB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit
terminals is not below or above listed range limits.
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 × RLA + ea. FLA
MFA ≤ 2.25 × RLA + ea. FLA
(Next lower standard fuse rating, Min. 15A)
6. Select wire size based on the larger value of MCA or TOCA.
7. Instead of fuse, use circuit breaker.

106 Outdoor Unit KU Series


ED40-017B Field Piping and Wiring

11. Field Piping and Wiring


11.1 Field Piping (R(Y)140KU)
11.1.1 Maximum Allowable Piping Length and Level Difference
R(Y)140KU
Max. Allowable Piping Length 50 m (Equivalent Length 70 m)
Max. Allowable Level Difference 30 m

11.1.2 Additional Refrigerant Charge


• This unit requires additional charging of refrigerant according to the length of pipe connected at the site.
The range where no charging is required. (R(Y)140KU : 5 m or less.)
Take the following steps for proper charging.
3
When connected to one indoor unit (pair system)

Main pipe (L1)

Indoor unit
One-way length of pipe (L):
L1
• Select the amount of refrigerant which matches a length which exceeds the charge-less length from
Table 1, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.
Table 1 (The maximum allowable pipe length is 50 meters.) <Unit : kg>
Length of Pipe Connected 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Additional Charging Amount — 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25

<PRECAUTION>
Contact your DAIKIN dealer when installing the unit using pipes of 3 m or less.

11.1.3 Recharging Refrigerant


When the entire refrigerant pipe length is within 5 meters, charge the refrigerant in accordance with the
amount mentioned on the nameplate, and when the pipe length exceeds 5 meters, the charging amount is
an addition of the amount stated on the nameplate and the additional charging amount.

C : 3PN00281-21R-1
11.1.4 Pumping-down Operation Method
The outdoor unit is equipped with a low-pressure switch to protect the compressor.
Take the following steps to perform the pumping-down operation.

Caution: Never short-circuit the low-pressure switch in this operation.


Procedure Precautions
1. Start the fan operation with the remote controller. Confirm that stop valves both on the liquid and gas side
are open. Take care when the procedure 2 is done first
because the indoor unit fan may operate automatically.
2. Push the pumping-down button on the PC board of Compressor and outdoor fan will start operation
the outdoor unit. automatically.
3. Continue operation for 1 min. until operation

condition stabilizes.
4. Close the stop valve on the liquid side securely. Insecure closing of the valve may result in burning of
(Refer to Fig. 1) the compressor.
5. When the low-pressure switch is activated, the unit
stops working. At this time, close the stop valve on —
the gas side.
This is the end of pumping-down operation.
After pumping-down operation, the remote controller shows “U4” even when ON button on the remote
controller is pressed, and it will not operate. Although the remote controller may or may not indicate “U4”
according to circumstances at this time, it is normal. When the remote controller indicates “U4”, the indoor
unit fan may operate (for about max 30 minutes). Turn off the main power supply switch and turn it on again
in need of operation.

Outdoor Unit KU Series 107


Field Piping and Wiring ED40-017B

Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to
provide a trap at an appropriate place in the riser gas piping.

Trap installation spacing


Indoor unit
Oil trap

Gas piping

Liquid piping

Outdoor unit

Note: A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.

Caution to be taken when brazing refrigerant piping


“Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux
has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)

(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.

C : 3PN00281-21R-2

108 Outdoor Unit KU Series


ED40-017B Field Piping and Wiring

11.2 Field Piping (R(Y)200 · 250KU)


11.2.1 Maximum Allowable Piping Length and Level Difference

1PN04787B-1

Outdoor Unit KU Series 109


Field Piping and Wiring ED40-017B

11.2.2 Additional Refrigerant Charge & Recharging Refrigerant

1PN04788A-1

110 Outdoor Unit KU Series


ED40-017B Field Piping and Wiring

11.2.3 Pumping-down Operation Method

Caution to be taken when brazing refrigerant piping


“Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux
has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)

(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.

1PN04788A-2
1PN04787B-2

Outdoor Unit KU Series 111


Field Piping and Wiring ED40-017B

11.3 Field Wiring


11.3.1 60Hz R(Y)140KU

C : 4D006674A

112 Outdoor Unit KU Series


ED40-017B Field Piping and Wiring

11.3.2 50 · 60Hz R(Y)200 · 250KU

3D029782

Outdoor Unit KU Series 113


Field Piping and Wiring ED40-017B

114 Outdoor Unit KU Series


ED40-017B

Part 4
Outdoor Unit
FU Series
1. External Appearance...........................................................................116
2. Power Supply ......................................................................................117
2.1 Power Supply .......................................................................................117
3. Specification........................................................................................118
4. Dimensions and Service Space ..........................................................119 4
4.1 Dimensions...........................................................................................119
4.2 Installation Service Space ....................................................................120
5. Piping Diagrams..................................................................................122
5.1 Cooling Only.........................................................................................122
5.2 Heat Pump ...........................................................................................123
6. Wiring Diagrams..................................................................................124
6.1 Cooling Only.........................................................................................124
6.2 Heat Pump ...........................................................................................127
7. Capacity Table ....................................................................................129
7.1 Cooling Only.........................................................................................129
7.2 Heat Pump ...........................................................................................132
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ..........134
8. Operation Limit....................................................................................135
8.1 Cooling Only.........................................................................................135
8.2 Heat Pump ...........................................................................................136
9. Sound Level ........................................................................................137
9.1 Overall Sound Level .............................................................................137
9.2 Octave Band Level ...............................................................................138
10.Electric Characteristics........................................................................140
10.1 Cooling Only.........................................................................................140
10.2 Heat Pump ...........................................................................................141
11.Field Piping and Wiring .......................................................................142
11.1 Field Piping...........................................................................................142
11.2 Field Wiring ..........................................................................................144

Outdoor Unit FU Series 115


External Appearance ED40-017B

1. External Appearance

R100FU
R71FU R125FU
RY71FU RY100FU
RY125FU

116 Outdoor Unit FU Series


ED40-017B Power Supply

2. Power Supply
2.1 Power Supply
2.1.1 Cooling Only
50Hz
Series Indoor Unit Cooling Only Power Supply
FDM03FAV1 R71FUV1
1 phase 220–240V
FDM04FAV1 R100FUV1

R–FU FDM03FAV1 R71FUY1

FDM04FAV1 R100FUY1 3 phase 380–415V (4 wires)

FDM05FAV1 R125FUY1

60Hz
Series Indoor Unit Cooling Only Power Supply
FDM03FAVAL R71FUVAL 4
1 phase 220V
R–FU FDM04FAVAL R100FUVAL

FDM05FAVAL R125FUTAL 3 phase 220V

2.1.2 Heat Pump


60Hz
Series Indoor Unit Heat Pump Power Supply
FDYM03FAVAL RY71FUVAL
1 phase 220V
RY–FU FDYM04FAVAL RY100FUVAL

FDYM05FAVAL RY125FUTAL 3 phase 220V

Note: 1. Power Supply Intake : Outdoor Unit

Outdoor Unit FU Series 117


Specification ED40-017B

3. Specification
FD(Y)M–FA + R(Y)–FU

Refer to “Specification” in Part 1 on Page 7, 10, 15.

Optional Accessories
R(Y)71~125FU
Kit Name
Name of Option
71 100 125
Central Drain Plug KKPJ5F180
C : 4D006664

118 Outdoor Unit FU Series


ED40-017B Dimensions and Service Space

4. Dimensions and Service Space


4.1 Dimensions

R71FU
RY71FU

Unit (mm)

3D001674A

R100 · 125FU
RY100 · 125FU

Unit (mm)

3D001672A

Outdoor Unit FU Series 119


Dimensions and Service Space ED40-017B

4.2 Installation Service Space

3D001951A-1

120 Outdoor Unit FU Series


ED40-017B Dimensions and Service Space

3D001951A-2

Outdoor Unit FU Series 121


Piping Diagrams ED40-017B

5. Piping Diagrams
5.1 Cooling Only

R71FU
R100FU
R125FU

3D001310A

122 Outdoor Unit FU Series


ED40-017B Piping Diagrams

5.2 Heat Pump

RY71FU
RY100FU
RY125FU

3D005825

Outdoor Unit FU Series 123


Wiring Diagrams ED40-017B

6. Wiring Diagrams
6.1 Cooling Only
6.1.1 50Hz

R71FUV1

3D010789A

R71FUY1

3D000995C

124 Outdoor Unit FU Series


ED40-017B Wiring Diagrams

R100FUV1

3D010788

R100FUY1
R125FUY1

3D001007C

Outdoor Unit FU Series 125


Wiring Diagrams ED40-017B

6.1.2 60Hz

R71FUVAL

3D005375C

R100FUVAL

3D005376C

126 Outdoor Unit FU Series


ED40-017B Wiring Diagrams

R125FUTAL

3D005377A

6.2 Heat Pump


6.2.1 60Hz

RY71FUVAL

3D005370B

Outdoor Unit FU Series 127


Wiring Diagrams ED40-017B

RY100FUVAL

3D005371B

RY125FUTAL

3D005372A

128 Outdoor Unit FU Series


ED40-017B Capacity Table

7. Capacity Table
7.1 Cooling Only
7.1.1 50Hz

FDM03FAV1 + R71FUV1
FDM03FAV1 + R71FUY1

3D001843F

FDM04FAV1 + R100FUV1
FDM04FAV1 + R100FUY1

3D001844G

Outdoor Unit FU Series 129


Capacity Table ED40-017B

FDM05FAV1 + R125FUY1

3D001845F

7.1.2 60Hz

FDM03FAVAL + R71FUVAL

3D007447F

130 Outdoor Unit FU Series


ED40-017B Capacity Table

FDM04FAVAL + R100FUVAL

3D007448E

FDM05FAVAL + R125FUTAL

3D007449F

Outdoor Unit FU Series 131


Capacity Table ED40-017B

7.2 Heat Pump


7.2.1 60Hz

FDYM03FAVAL + RY71FUVAL

3D007444E

FDYM04FAVAL + RY100FUVAL

3D007445E

132 Outdoor Unit FU Series


ED40-017B Capacity Table

FDYM05FAVAL + RY125FUTAL

3D007446E

Outdoor Unit FU Series 133


Capacity Table ED40-017B

7.3 Capacity Correction Factor by the Length of Refrigerant Piping


The cooling and heating capacity of the unit has to be corrected in accordance with the length of refrigerant
piping. (The distance between the indoor unit and the outdoor unit)
Reference Data

Cooling (heating) capacity correction factor 100

71~125
95

90

85 100
71
125
80

75
0 5 10 15 20 25 30 35 40 45 50 (m)
Length of refrigerant piping (Total length)
C : 3D006500C

Note: 1. line: Correction factor for cooling capacity


line: Correction factor for heating capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below the
indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the
unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the
range of its limitation.

134 Outdoor Unit FU Series


ED40-017B Operation Limit

8. Operation Limit
8.1 Cooling Only
8.1.1 50Hz

R71FUV1 / R71FUY1
R100FUV1 / R100FUY1
— / R125FUY1

3D001318

8.1.2 60Hz

R71FUVAL
R100FUVAL
R125FUTAL

3D006659

Outdoor Unit FU Series 135


Operation Limit ED40-017B

8.2 Heat Pump


8.2.1 60Hz

RY71FUVAL
RY100FUVAL
RY125FUTAL

3D006675

136 Outdoor Unit FU Series


ED40-017B Sound Level

9. Sound Level
9.1 Overall Sound Level
9.1.1 Cooling Only
„ 50Hz dB(A)
Model 220V Measuring Location
R71FUV1 52
R100FUV1 56
Model 380V
R71FUY1 52 Microphone
R100FUY1 56
4D002309
R125FUY1 57

„ 60Hz dB(A)
Model 220V Measuring Location

R71FUVAL 53 4
R100FUVAL 57
Microphone

R125FUTAL 59 4D007392

9.1.2 Heat Pump


„ 60Hz dB(A)
220V
Model Measuring Location
Cooling Heating

RY71FUVAL 53 55

RY100FUVAL 57 59
Microphone

RY125FUTAL 59 61 4D007382

Outdoor Unit FU Series 137


Sound Level ED40-017B

9.2 Octave Band Level


9.2.1 Cooling Only
„ 50Hz
R71FUV1 R100FUV1 R125FUY1
R71FUY1 R100FUY1

4D002309 4D002416 4D002417

„ 60Hz
R71FUVAL R100FUVAL R125FUTAL

4D007392 4D007393 4D007394

Note:
V1 · VAL · TAL : 220V, Y1 : 380V

138 Outdoor Unit FU Series


ED40-017B Sound Level

9.2.2 Heat Pump


„ 60Hz
RY71FUVAL (Cooling) RY71FUVAL (Heating) RY100FUVAL (Cooling)

4D007382 4D007383 4D007386

RY100FUVAL (Heating) RY125FUTAL (Cooling) RY125FUTAL (Heating)


4

4D007387 4D007390 4D007391

Note:
VAL · TAL : 220V

Outdoor Unit FU Series 139


Electric Characteristics ED40-017B

10. Electric Characteristics


10.1 Cooling Only
10.1.1 50Hz
Unit Combination Power Supply Compressor OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
50 – 220
FDM03FAV1 R71FUV1 50 – 230 17.0 22.5 25 78 12.4 0.050 0.6 0.125 0.9
50 – 240 Max.50Hz 264V
50 – 220 Min.50Hz 198V 0.075 0.7
FDM04FAV1 R100FUV1 50 – 230 23.0 34.2 35 100 16.6 + + 0.135 1.0
50 – 240 0.035 0.5
50 – 380 / 220
FDM03FAV1 R71FUY1 50 – 400 / 230 6.8 8.5 15 35 4.2 0.050 0.6 0.125 0.9
50 – 415 / 240
50 – 380 / 220 0.075 0.7
Max.50Hz 456V
FDM04FAV1 R100FUY1 50 – 400 / 230 Min.50Hz 342V 9.1 9.2 15 45 5.5 + + 0.135 1.0
50 – 415 / 240 0.035 0.5
50 – 380 / 220 0.075 0.7
FDM05FAV1 R125FUY1 50 – 400 / 230 11.3 12.3 15 62 6.8 + + 0.225 1.4
50 – 415 / 240 0.060 0.7
3D007342E
3D007348E
3D007347E

10.1.2 60Hz
Unit Combination Power Supply Compressor OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
FDM03FAVAL R71FUVAL 60 – 220 20.1 26.0 30 87 14.5 0.080 0.8 0.125 1.2
0.090 0.8
FDM04FAVAL R100FUVAL 60 – 220 Max.60Hz 242V 28.1 39.7 45 118 20.3 + + 0.135 1.3
0.060 0.6
Min.60Hz 198V
0.090 0.8
FDM05FAVAL R125FUTAL 60 – 220 22.5 27.9 35 124 15.1 + + 0.225 2.0
0.080 0.8
3D007342E
3D007348E
3D007347E

Symbols: MCA : Min. Circuit Amps


TOCA : Total Over-Current Amps
MFA : Max. Fuse Amps (See note 7)
LRA : Locked Rotor Amps
RLA : Rated Load Amps
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
kW : Fan Motor Rated Output

Note: 1. RLA is based on the following conditions.


Indoor temp. 27°CDB/19.5°CWB
Outdoor temp. 35°CDB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit
terminals is not below or above listed range limits.
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 × RLA + ea. FLA
MFA ≤ 2.25 × RLA + ea. FLA
(Next lower standard fuse rating, Min. 15A)
6. Select wire size based on the larger value of MCA or TOCA.
7. Instead of fuse, use circuit breaker.

140 Outdoor Unit FU Series


ED40-017B Electric Characteristics

10.2 Heat Pump


10.2.1 60Hz
Unit Combination Power Supply Compressor OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
FDYM03FAVAL RY71FUVAL 60 – 220 22.9 35.0 35 97 16.7 0.080 0.8 0.125 1.2
0.090 0.8
FDYM04FAVAL RY100FUVAL 60 – 220 28.6 41.2 45 138 20.7 + + 0.135 1.3
Max.60Hz 242V 0.060 0.6
Min.60Hz 198V
0.090 0.8
FDYM05FAVAL RY125FUTAL 60 – 220 22.0 27.9 35 124 14.7 + + 0.225 2.0
0.080 0.8
C : 3D007115E
C : 3D007340E
C : 3D007346F

Symbols: MCA : Min. Circuit Amps


TOCA : Total Over-Current Amps
MFA : Max. Fuse Amps (See note 7)
LRA : Locked Rotor Amps
RLA : Rated Load Amps
4
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
kW : Fan Motor Rated Output

Note: 1. RLA is based on the following conditions.


Indoor temp. 27°CDB/19.5°CWB
Outdoor temp. 35°CDB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit
terminals is not below or above listed range limits.
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 × RLA + ea. FLA
MFA ≤ 2.25 × RLA + ea. FLA
(Next lower standard fuse rating, Min. 15A)
6. Select wire size based on the larger value of MCA or TOCA.
7. Instead of fuse, use circuit breaker.

Outdoor Unit FU Series 141


Field Piping and Wiring ED40-017B

11. Field Piping and Wiring


11.1 Field Piping
11.1.1 Maximum Allowable Piping Length and Level Difference
R(Y)71~125FU
Max. Allowable Piping Length 50 m (Equivalent Length 70 m)
Max. Allowable Level Difference 30 m

11.1.2 Additional Refrigerant Charge


• This unit requires additional charging of refrigerant according to the length of pipe connected at the site.
The range where no charging is required. (R(Y)71~125FU : 5 m or less.)
Take the following steps for proper charging.
When connected to one indoor unit (pair system)

Main pipe (L1)

Indoor unit
One-way length of pipe (L):
L1

• Select the amount of refrigerant which matches a length which exceeds the charge-less length from
Table 1, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.
Table 1 (The maximum allowable pipe length is 50 meters.) <Unit : kg>
Length of Pipe Connected 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Straight Cooling Type — 0.13 0.25 0.38 0.50 0.63 0.75 0.88 1.00 1.13
Heat Pump Type — 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25

<PRECAUTION>
Contact your DAIKIN dealer when installing the unit using pipes of 3 m or less.

11.1.3 Recharging Refrigerant


When the entire refrigerant pipe length is within 5 meters, charge the refrigerant in accordance with the
amount mentioned on the nameplate, and when the pipe length exceeds 5 meters, the charging amount is
an addition of the amount stated on the nameplate and the additional charging amount.

C : 1PN01324A-1
C : 3PN00281-7V-1

11.1.4 Pumping-down Operation Method


Take the following steps to perform the pumping-down operation.
1. In case of Cooling Only
Procedure Precautions
1. Connect a pressure gauge to the service port of the Carry out an air purge of the charge hose.
stop valve.
2. Perform fan operation by the remote controller. Make sure that the liquid-side and gas-side stop valves
are fully open.
3. Perform cooling operation by the remote controller. Check that the compressor and outdoor fan are
operating.
4. Run the unit for one minute until the operation
stabilizes. —

5. Close the liquid-side stop valve fully. If the valve is not fully closed it could cause burn-out of
(Refer to Fig.1) the compressor.
6. After the pressure gauge indication has dropped to
0 kgf/cm2G, close the gas stop valve fully and press —
the Stop button on the remote controller.

142 Outdoor Unit FU Series


ED40-017B Field Piping and Wiring

2. In case of Heat Pump


Procedure Precautions
1. Start the fan operation with the remote controller. Confirm that stop valves both on the liquid and gas side
are open.
2. Push the pumping-down button on the PC board of Compressor and outdoor fan will start operation
the outdoor unit. automatically.
3. Continue operation for 1 min. until operation —
condition stabilizes.
4. Close the stop valve on the liquid side securely. Insecure closing of the valve may result in burning of
(Refer to Fig. 1) the compressor.
5. After about 1 minute passed, close the stop valve on After pushing the pumping down button, compressor
the gas side. and outdoor fan will stop 3 minutes later.

This is the end of pumping-down operation.


After pumping-down operation, the remote controller shows “U4” even
when ON button on the remote controller is pressed, and it will not
operate. Although the remote controller may or may not indicate “U4”
according to circumstances at this time, it is normal. When the remote
controller indicates “U4”, the indoor unit fan may operate (for about max
30 minutes). Turn off the main power supply switch and turn it on again
4
in need of operation.

Necessity of a trap Trap installation spacing


Since there is fear of the oil held inside the riser piping
flowing back into the compressor when stopped and Indoor unit
causing liquid compression phenomenon, or cases of Oil trap
deterioration of oil return, it will be necessary to provide a
trap at an appropriate place in the riser gas piping. Gas piping

Liquid piping

Outdoor unit

Note: A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.

Caution to be taken when brazing refrigerant piping


“Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”. (Flux
has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)

(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.
C : 1PN01324A-2
C : 3PN00281-7V-2

Outdoor Unit FU Series 143


Field Piping and Wiring ED40-017B

11.2 Field Wiring


11.2.1 50 · 60Hz

C : 4D001694A
C : 4D006674A

144 Outdoor Unit FU Series


The air conditioners manufactured All Daikin Industries locations and About ISO 14001
by Daikin Industries have received subsidiaries in Japan have ISO 14001 is the standard defined by the International
ISO 9001 certification for quality received environmental Organization for Standardization (ISO) relating to
assurance. management system standard environmental management systems. Our group has
ISO 14001 certification. been acknowledged by an internationally accredited
Certificate Number.
(ISO9001) JMI-0107 compliance organisation as having an appropriate
Daikin Industries, Ltd.
JQA-0495 Domestic Group programme of environmental protection procedures
JQA-1452 Certificate Number. EC99J2044 and activities to meet the requirements of ISO 14001.

Dealer
Head Office:
Umeda Center Bldg., 4-12, Nakazaki-Nishi
2-chome, Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 18-1, Konan
2-chome, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved

The specifications, designs, and information in this brochure are subject to change without notice.

ED 40-017B