FD(Y)M-FA Series
— Cooling Only —
— Heat Pump —
ED40-017B
Table of Contents i
ED40-017B
10.Electric Characteristics..........................................................................68
10.1 Cooling Only...........................................................................................68
10.2 Heat Pump .............................................................................................69
11.Field Piping and Wiring .........................................................................70
11.1 Field Piping.............................................................................................70
11.2 Field Wiring ............................................................................................72
ii Table of Contents
ED40-017B
5. Piping Diagrams..................................................................................122
5.1 Cooling Only.........................................................................................122
5.2 Heat Pump ...........................................................................................123
6. Wiring Diagrams..................................................................................124
6.1 Cooling Only.........................................................................................124
6.2 Heat Pump ...........................................................................................127
7. Capacity Table ....................................................................................129
7.1 Cooling Only.........................................................................................129
7.2 Heat Pump ...........................................................................................132
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ..........134
8. Operation Limit....................................................................................135
8.1 Cooling Only.........................................................................................135
8.2 Heat Pump ...........................................................................................136
9. Sound Level ........................................................................................137
9.1 Overall Sound Level .............................................................................137
9.2 Octave Band Level ...............................................................................138
10.Electric Characteristics........................................................................140
10.1 Cooling Only.........................................................................................140
10.2 Heat Pump ...........................................................................................141
11.Field Piping and Wiring .......................................................................142
11.1 Field Piping...........................................................................................142
11.2 Field Wiring ..........................................................................................144
iv Table of Contents
ED40-017B
Part 1 1
Indoor Unit
FD(Y)M03~06FA
1. External Appearance and Features ........................................................2
2. Power Supply ..........................................................................................3
2.1 Cooling Only.............................................................................................3
2.2 Heat Pump ...............................................................................................4
3. Specification............................................................................................5
3.1 Cooling Only.............................................................................................5
3.2 Heat Pump .............................................................................................11
4. Optional Accessories ............................................................................16
4.1 Option List ..............................................................................................16
5. Dimensions ...........................................................................................17
6. Remote Controller .................................................................................19
6.1 Dimensions.............................................................................................19
6.2 Operation................................................................................................20
7. Wiring Diagrams....................................................................................22
8. Sound Level ..........................................................................................24
8.1 Overall Sound Level ...............................................................................24
8.2 Octave Band Level .................................................................................25
9. Fan Performance ..................................................................................26
10.Installation .............................................................................................28
FDM04FA
FDM05FA
FDM03FA FDYM04FA
FDYM03FA
FDYM05FA
FDYM06FA
Remote Controller
Features
Compact in size
Fits to the small ceiling spaces
Low operating sound: Top in the industry
Central control and group control are available
(by adopting the optional accessories)
Functions
2. Power Supply
1
2.1 Cooling Only
2.1.1 50Hz
Series Indoor Unit Cooling Only Power Supply
FDYM03FAV1 R71LUV1 ∗
1 phase 220–240V
FDYM04FAV1 R100LUV1 ∗
FDYM03FAV1 R71LUY1 ∗
R–LU
FDYM04FAV1 R100LUY1 ∗
FDYM05FAV1 R125LUY1 ∗
FDYM04FAV1×2 R200KUY1
FDYM05FAV1×2 R250KUY1
FDM03FAV1 R71FUV1
1 phase 220–240V
FDM04FAV1 R100FUV1
FDM05FAV1 R125FUY1
2.1.2 60Hz
Series Indoor Unit Cooling Only Power Supply
FDYM03FAVAL R71LUVAL ∗
1 phase 220V
FDYM04FAVAL R100LUVAL ∗
FDYM05FAVAL R125LUTAL ∗
R–LU 3 phase 220V
FDYM06FAVAL R140LUTAL ∗
FDYM05FAVAL R125LUYAL ∗
3 phase 380V (4 wires)
FDYM06FAVAL R140LUYAL ∗
FDYM06FAVAL R140KUTALK
FDYM04FAVAL×2 R200KUTAL
3 phase 220V
FDYM03FAVAL×3 R200KUTAL
FDYM05FAVAL×2 R250KUTAL
R–KU
FDYM06FAVAL R140KUYALK
FDYM04FAVAL×2 R200KUYAL
3 phase 380V (4 wires)
FDYM03FAVAL×3 R200KUYAL
FDYM05FAVAL×2 R250KUYAL
FDM03FAVAL R71FUVAL
1 phase 220V
R–FU FDM04FAVAL R100FUVAL
FDYM03FAV1 RY71LUY1 ∗
RY–LU
FDYM04FAV1 RY100LUY1 ∗
FDYM05FAV1 RY125LUY1 ∗
FDYM04FAV1×2 RY200KUY1
FDYM05FAV1×2 RY250KUY1
2.2.2 60Hz
Series Indoor Unit Heat Pump Power Supply
FDYM06FAVAL RY140LUTAL ∗ 3 phase 220V
RY–LU
FDYM06FAVAL RY140LUYAL ∗ 3 phase 380V (4 wires)
FDYM06FAVAL RY140KUTALK
FDYM04FAVAL×2 RY200KUTAL
3 phase 220V
FDYM03FAVAL×3 RY200KUTAL
FDYM05FAVAL×2 RY250KUTAL
RY–KU
FDYM06FAVAL RY140KUYALK
FDYM04FAVAL×2 RY200KUYAL
3 phase 380V (4 wires)
FDYM03FAVAL×3 RY200KUYAL
FDYM05FAVAL×2 RY250KUYAL
FDYM03FAVAL RY71FUVAL
1 phase 220V
RY–FU FDYM04FAVAL RY100FUVAL
3. Specification
1
3.1 Cooling Only
3.1.1 50Hz
FDYM–FA + R–LU
Indoor Unit FDYM03FAV1 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1
Model V1 R71LUV1 R100LUV1 — —
Outdoor Unit
Y1 R71LUY1 R100LUY1 R125LUY1 R140LUY1
kW 7.8/7.7/7.7 10.6/10.5/10.5 13.0/12.8/12.8 14.5/14.2/14.2
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 26,600/26,200/26,200 36,100/35,700/35,700 44,500/43,600/43,600 49,400/48,400/48,400
kcal/h 6,700/6,600/6,600 9,100/9,000/9,000 11,200/11,000/11,000 12,500/12,200/12,200
Indoor Unit FDYM03FAV1 FDYM04FAV1 FDYM05FAV1 FDYM06FAV1
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225 290
Air Flow Rate ∗2 m³/min (H) 20–22 (H) 26–28 (H) 35–40.5 (H) 37–42
External Static Pressure Pa 98 98 98 98
Sound Pressure Level ∗2 dB(A) (H) 39–41 (H) 39–41 (H) 44–46 (H) 46–48
Machine Weight kg 42 56 57 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C64
V1 R71LUV1 R100LUV1 — —
Outdoor Unit
Y1 R71LUY1 R100LUY1 R125LUY1 R140LUY1
Color Ivory
Dimensions H×W×D mm 770×900×320 1,170×900×320 1,170×900×320 1,345×900×320
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 2×52×2.0 2×60×2.0
Face Area m² 0.634 0.983 0.983 1.134
V1 ZR36K3–PFJ ZR48K3–PFJ — —
Model
Y1 ZR36K3–TFD ZR48K3–TFD JT160BC–YE JT170BC–YE
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 2.24 3.00 3.75 4.50
Model P47L11S P47L11S P47L11S×2 P47L11S×2
Type Propeller
Fan
Motor Output W 65 90 65+85 65+90
Air Flow Rate ∗2 m³/min 48–51 59–62 92–100 97–109
V1 72 87 — —
Weight kg
Y1 71 84 98 109
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure
Safety Devices Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (Y1). Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.2 1.2 1.5 1.6
Drawing No. 4D041138 4D041137
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB 50Hz, 220–240V cfm=m³/min×35.3
(1) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380–415V)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 50Hz, 220–240V
(2) 7.5m JIS B8616
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380–415V)
FDYM–FA + R–KU
Indoor Unit FDYM03FAV1×3 FDYM04FAV1×2 FDYM05FAV1×2
Model
Outdoor Unit R200KUY1 R200KUY1 R250KUY1
kW 22.5/22.2/22.0 22.5/22.2/22.0 27.1/26.6/26.3
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 76,800/75,800/75,100 76,800/75,800/75,100 92,500/90,800/89,800
kcal/h 19,400/19,100/18,900 19,400/19,100/18,900 23,300/22,900/22,600
Indoor Unit ∗3 FDYM03FAV1×3 FDYM04FAV1×2 FDYM05FAV1×2
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate ∗2 m³/min (H) 20–22 (H) 26–28 (H) 35–40.5
External Static Pressure Pa 98 98 98
Sound Pressure Level ∗2 dB(A) (H) 39–41 (H) 39–41 (H) 44–46
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C64
Outdoor Unit R200KUY1 R200KUY1 R250KUY1
Color Ivory
Dimensions H×W×D mm 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×40×2.0 2×40×2.0 2×50×2.0
Face Area m² 1.57 1.57 1.97
Model JT236D–P1YE JT236D–P1YE JT335D–P1YE
Comp. Type Hermetically Sealed Scroll Type
Motor Output kW 5.5 5.5 9.0
Model P52H11SM P52H11SM P52H11SM
Type Propeller
Fan
Motor Output W 230+190 230+190 230+190
Air Flow Rate ∗2 m³/min 150–154 150–154 175–179
Machine Weight kg 178 178 202
Liquid mm φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare)
Piping Connections Gas mm φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange)
Drain mm — — —
Safety Devices Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure
Switch. Over Current Relay (Compressor). Reverse Phase Protector. Fuse.
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 5.3 (Charged for 5m) 5.3 (Charged for 5m) 5.7 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 3.0 3.0 3.0
Drawing No. C : 4D029967 C : 4D029969
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB cfm=m³/min×35.3
(1) 5m 50Hz, 380–415V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB
(2) 5m 50Hz, 380–415V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB
(3) 7.5m 50Hz, 415V AS 1861
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
2. ∗2 AFR (Air flow rafe) and sound pressure level are shown at 380V–415V.
3. Capacities are net, including a deduction for cooling for indoor fan motor heat.
4. ∗3 Each value for indoor unit shows the specifications per one unit.
5. Wire for remote controller : Field supplied.
FDM–FA + R–FU 1
Indoor Unit FDM03FAV1 FDM04FAV1 FDM05FAV1
Model V1 R71FUV1 R100FUV1 —
Outdoor Unit
Y1 R71FUY1 R100FUY1 R125FUY1
kW 7.8/7.7/6.3 10.6/10.5/8.0 13.0/12.8/11.2
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 26,600/26,200/21,500 36,100/35,700/27,300 44,500/43,600/38,200
kcal/h 6,700/6,600/5,400 9,100/9,000/6,900 11,200/11,000/9,600
Indoor Unit FDM03FAV1 FDM04FAV1 FDM05FAV1
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate m³/min (H) 20 (H) 26 (H) 35
External Static Pressure Pa 98 98 98
Sound Pressure Level dB(A) (H) 39 (H) 39 (H) 44
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C64
V1 R71FUV1 R100FUV1 —
Outdoor Unit
Y1 R71FUY1 R100FUY1 R125FUY1
Color Ivory
Dimensions H×W×D mm 816×880×370 1,215×880×370 1,215×880×370
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×36×2.0 2×54×2.0 2×54×2.0
Face Area m² 0.653 0.979 0.979
V1 H23A35QABKA H23A46QABKA —
Model
Y1 H23A35QDBEA H23A46QDBEA H23A56QDBEA
Comp. Type Hermetically Sealed Type
No. of Cylinders 2 2 2
Motor Output kW 2.2 3.0 3.75
Model P45J11SM P45J11SM×2 P45J11SM×2
Type Propeller
Fan
Motor Output W 50 75+35 75+60
Air Flow Rate m³/min 46 80 87
V1 87 117 —
Machine Weight kg
Y1 84 109 110
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan motor and Indoor Fan Motor. Internal Pressure Relief Valve (Compressor).
Safety Devices
Motor Protector (Compressor).
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.1 (Charged for 5m) 2.4 (Charged for 5m) 2.8 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.48 1.63 1.63
Drawing No. C : 4D021049
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB 50Hz, 220–240V cfm=m³/min×35.3
(1) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380–415V)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 50Hz, 220–240V
(2) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380–415V)
3.1.2 60Hz
FDYM–FA + R–LU
Indoor Unit FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL FDYM06FAVAL
VAL R71LUVAL R100LUVAL — —
Model
Outdoor Unit TAL — — R125LUTAL R140LUTAL
YAL — — R125LUYAL R140LUYAL
kW 8.3/8.1 11.6/11.4 14.5/14.3 16.1/15.8
∗1 Cooling Capacity (1)/(2) Btu/h 28,200/27,800 39,700/38,900 49,600/48,800 55,000/53,900
kcal/h 7,100/7,000 10,000/9,800 12,500/12,300 13,800/13,500
Indoor Unit FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL FDYM06FAVAL
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1 3D18H2AF1
Type Sirocco Fan
Fan Motor Output W 125 135 225 290
Air Flow Rate m³/min (H) 22 (H) 28 (H) 38 (H) 40
External Static Pressure Pa 118 118 118 118
Sound Pressure Level dB(A) (H) 42 (H) 42 (H) 47 (H) 49
Machine Weight kg 42 56 57 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C64
VAL R71LUVAL R100LUVAL — —
Outdoor Unit TAL — — R125LUTAL R140LUTAL
YAL — — R125LUYAL R140LUYAL
Color Ivory
Dimensions H×W×D mm 770×900×320 1,170×900×320 1,170×900×320 1,345×900×320
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×34×2.0 2×52×2.0 2×52×2.0 2×60×2.0
Face Area m² 0.634 0.983 0.983 1.134
VAL ZR36K3–PFV ZR47K3–PFV — —
Model TAL — — JT160BC JT170BC
Comp. YAL — — JT160BC–YH JT170BC–YE
Type Hermetically Sealed Scroll Type
Motor Output kW 2.24 2.92 3.75 4.50
Model P47L11S P47L11S P47L11S×2 P47L11S×2
Type Propeller
Fan
Motor Output W 75 100 95+75 65+90
Air Flow Rate m³/min 49 59 94 97–109
Weight kg 75 92 98 109
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure
Safety Devices
Switch. Over Current Decive. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.2 1.2 1.5 1.6
Drawing No. 4D040215 4D040216
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB 60Hz, 220V cfm=m³/min×35.3
(1) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 60Hz 220V
(2) 7.5m JIS B8616
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.
FDYM–FA + R–KU 1
Indoor Unit FDYM06FAVAL FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2
Model TAL R140KUTALK R200KUTAL R200KUTAL R250KUTAL
Outdoor Unit
YAL R140KUYALK R200KUYAL R200KUYAL R250KUYAL
kW 16.1/15.8/14.0 22.5/22.2/20.0 22.5/22.2/20.0 27.1/26.6/24.1
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 55,000/53,900/47,800 76,800/75,800/68,300 76,800/75,800/68,300 92,500/90,800/82,300
kcal/h 13,800/13,500/12,000 19,400/19,100/17,200 19,400/19,100/17,200 23,300/22,900/20,700
Indoor Unit ∗2 FDYM06FAVAL FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2
Dimensions H×W×D mm 295×1,500×680 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.338 0.221 0.338 0.338
Model 3D18H2AF1 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 290 125 135 225
Air Flow Rate m³/min (H) 40 (H) 22 (H) 28 (H) 38
External Static Pressure Pa 118 118 118 118
Sound Pressure Level dB(A) (H) 49 (H) 42 (H) 42 (H) 47
Machine Weight kg 57 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ19.1 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C64
TAL R140KUTALK R200KUTAL R200KUTAL R250KUTAL
Outdoor Unit
YAL R140KUYALK R200KUYAL R200KUYAL R250KUYAL
Color Ivory
Dimensions H×W×D mm 1,345×880×370 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690
Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×40×2.0 2×50×2.0
Face Area m² 1.088 1.57 1.57 1.97
TAL JT170BC JT212D–P1 JT212D–P1 JT300D–P1
Model
YAL JT170BC–YH JT212D–P1YH JT212D–P1YH JT300D–P1YH
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 4.5 5.5 5.5 7.5
Model P45J11SM P52H11SM P52H11SM P52H11SM
Type Propeller
Fan
Motor Output W 120+100 230+190 230+190 230+190
Air Flow Rate m³/min 103 160 160 190
Weight kg 109 177 177 200
Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare)
Piping Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange)
Drain mm φ26.0 (Hole) — — —
Thermal Protector for Compressor (for R200 · 250KU), Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch.
Safety Devices
Low Pressure Switch. Over Current Relay (Compressor). Reverse Phase Protector. Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.7 (Charged for 5m) 5.3 (Charged for 5m) 5.3 (Charged for 5m) 5.7 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.6 3.0 3.0 3.0
Drawing No. C : 4D028027A C : 4D029968 C : 4D029970
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB 60Hz, 220V cfm=m³/min×35.3
(1) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB 60Hz, 220V
(2) 5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor : 29°C(84°F)DB, 19.0°C(66°F)WB 60Hz, 220V
(3) 7.5m SSA 385/386
Outdoor : 46°C(115°F)DB, 24°C(75°F)WB (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. ∗2 Each value for indoor unit shows the specifications per one unit.
4. In case of drain piping for outdoor unit, drain piping kit (option) is needed. (for R140KUTALK · YALK)
5. Wire for remote controller : Field supplied.
FDM–FA + R–FU
Indoor Unit FDM03FAVAL FDM04FAVAL FDM05FAVAL
Model VAL R71FUVAL R100FUVAL —
Outdoor Unit
TAL — — R125FUTAL
kW 8.3/8.1/6.7 11.6/11.4/9.0 14.5/14.3/12.5
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 28,200/27,800/22,900 39,700/38,900/30,700 49,600/48,800/42,700
kcal/h 7,100/7,000/5,800 10,000/9,800/7,700 12,500/12,300/10,800
Indoor Unit FDM03FAVAL FDM04FAVAL FDM05FAVAL
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate m³/min (H) 22 (H) 28 (H) 38
External Static Pressure Pa 118 118 118
Sound Pressure Level dB(A) (H) 42 (H) 42 (H) 47
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C64
VAL R71FUVAL R100FUVAL —
Outdoor Unit
TAL — — R125FUTAL
Color Ivory
Dimensions H×W×D mm 816×880×370 1,215×880×370 1,215×880×370
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×36×2.0 2×54×2.0 2×54×2.0
Face Area m² 0.653 0.979 0.979
VAL H23A35QABCA H23A46QABCA —
Model
TAL — — H23A62QDBLA
Comp. Type Hermetically Sealed Type
No. of Cylinders 2 2 2
Motor Output kW 2.2 3.0 3.75
Model P45J11SM P45J11SM×2 P45J11SM×2
Type Propeller
Fan
Motor Output W 80 90+60 90+80
Air Flow Rate m³/min 55 92 98
Machine Weight kg 87 117 110
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Iindoor Fan Motor. Internal Pressure Relief Valve (Compressor).
Safety Devices
Motor Protector (Compressor).
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.2 (Charged for 5m) 2.9 (Charged for 5m) 3.1 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.48 1.63 1.63
Drawing No. C : 4D020831A
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB cfm=m³/min×35.3
(1) Outdoor : 35°C(95°F)DB, 24°C(75°F)WB 5m 60Hz, 220V —
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
(1) Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB 5m 50Hz, 220–240V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380–415V)
(2) Indoor
: 27°C(81°F)DB, 19.0°C(66°F)WB Indoor : 20°C(68°F)DB 50Hz, 220–240V
7.5m JIS B8616
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380–415V)
FDYM–FA + RY–KU
Indoor Unit FDYM03FAV1×3 FDYM04FAV1×2 FDYM05FAV1×2
Model
Outdoor Unit RY200KUY1 RY200KUY1 RY250KUY1
kW 22.5/22.2/22.0 22.5/22.2/22.0 27.1/26.6/26.3
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 76,800/75,800/75,100 76,800/75,800/75,100 92,500/90,800/89,800
kcal/h 19,400/19,100/18,900 19,400/19,100/18,900 23,300/22,900/22,600
kW 22.6/22.7/22.4 22.6/22.7/22.4 28.3/28.4/28.0
∗1 Heating Capacity (1)/(2)/(3) Btu/h 77,200/77,500/76,500 77,200/77,500/76,500 96,600/97,000/95,600
kcal/h 19,400/19,500/19,300 19,400/19,500/19,300 24,300/24,400/24,100
Indoor Unit ∗3 FDYM03FAV1×3 FDYM04FAV1×2 FDYM05FAV1×2
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate ∗2 m³/min (H) 20–22 (H) 26–28 (H) 35–40.5
External Static Pressure Pa 98 98 98
Sound Pressure Level ∗2 dB(A) (H) 39–41 (H) 39–41 (H) 44–46
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C62
Outdoor Unit RY200KUY1 RY200KUY1 RY250KUY1
Color Ivory
Dimensions H×W×D mm 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×40×2.0 2×40×2.0 2×50×2.0
Face Area m² 1.57 1.57 1.97
Model JT236D–P1YE JT236D–P1YE JT335D–P1YE
Comp. Type Hermetically Sealed Scroll Type
Motor Output kW 5.5 5.5 9.0
Model P52H11SM P52H11SM P52H11SM
Type Propeller
Fan
Motor Output W 230+190 230+190 230+190
Air Flow Rate (C/H) ∗2 m³/min 150/138–154/142 150/138–154/142 175/161–179/165
Machine Weight kg 180 180 206
Liquid mm φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare)
Piping Connections Gas mm φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange)
Drain mm — — —
Safety Devices Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure
Switch. Over Current Relay (Compressor). Reverse Phase Protector. Fuse.
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 4.0 (Charged for 5m) 4.0 (Charged for 5m) 5.5 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 3.0 3.0 3.0
Drawing No. C : 4D029816 C : 4D029818
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
(1) Indoor
: 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB
5m 50Hz, 380V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB
(3) Indoor
: 27°C(81°F)DB, 19.0°C(66°F)WB Indoor : 21°C(70°F)DB
7.5m 50Hz, 415V AS 1861
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB
2. ∗2 AFR (Air flow rafe) and sound pressure level are shown at 380V–415V.
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. ∗3 Each value for indoor unit shows the specifications per one unit.
5. Wire for remote controller : Field supplied.
3.2.2 60Hz
1
FDYM–FA + RY–LU
Indoor Unit FDYM06FAVAL
Model TAL RY140LUTAL
Outdoor Unit
YAL RY140LUYAL
kW 16.1/15.8
∗1 Cooling Capacity (1)/(2) Btu/h 55,000/53,900
kcal/h 13,800/13,500
kW 18.1/18.1
∗1 Heating Capacity (1)/(2) Btu/h 61,900/61,900
kcal/h 15,600/15,600
Indoor Unit FDYM06FAVAL
Dimensions H×W×D mm 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75
Face Area m² 0.338
Model 3D18H2AF1
Type Sirocco Fan
Fan Motor Output W 290
Air Flow Rate m³/min (H) 40
External Static Pressure Pa 118
Sound Pressure Level dB(A) (H) 49
Machine Weight kg 57
Liquid mm φ9.5 (Flare)
Piping Connections Gas mm φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C62
TAL RY140LUTAL
Outdoor Unit
YAL RY140LUYAL
Color Ivory
Dimensions H×W×D mm 1,345×900×320
Type Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×60×2.0
Face Area m² 1.134
TAL JT170BC
Model
YAL JT170BC–YE
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 4.50
Model P47L11S×2
Type Propeller
Fan
Motor Output W 65+90
Air Flow Rate (C/H) m³/min 97–109
Machine Weight kg 112
Liquid mm φ 9 . 5 (Flare)
Piping Connections Gas mm φ 19.1 (Flare)
Drain mm φ 2 6 .0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan
Safety Devices Motor. High Pressure Switch. Low Pressure Switch. Over
Current Device. Reverse Phase Protector. Fuse.
Capacity Step % 100–0
Refrigerant Control Electronic Expansion Valve
Max. Length m 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30
Model R22
Refrigerant
Charge (Factory Charge) kg 4.1 (Charged for 30m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.6
Drawing No. 4D040216
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
(1) Indoor
: 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB 60Hz, 220V
5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380V)
FDYM–FA + RY–KU
Indoor Unit FDYM06FAVAL FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2
Model TAL RY140KUTALK RY200KUTAL RY200KUTAL RY250KUTAL
Outdoor Unit
YAL RY140KUYALK RY200KUYAL RY200KUYAL RY250KUYAL
kW 16.1/15.8/14.0 22.5/22.2/20.0 22.5/22.2/20.0 27.1/26.6/24.1
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 55,000/53,900/47,800 76,800/75,800/68,300 76,800/75,800/68,300 92,500/90,800/82,300
kcal/h 13,800/13,500/12,000 19,400/19,100/17,200 19,400/19,100/17,200 23,300/22,900/20,700
kW 18.1/18.1/17.0 22.6/22.7/22.4 22.6/22.7/22.4 28.3/28.4/28.0
∗1 Heating Capacity (1)/(2)/(3) Btu/h 61,900/61,900/58,000 77,200/77,500/76,500 77,200/77,500/76,500 96,600/97,000/95,600
kcal/h 15,600/15,600/14,600 19,400/19,500/19,300 19,400/19,500/19,300 24,300/24,400/24,100
Indoor Unit ∗2 FDYM06FAVAL FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2
Dimensions H×W×D mm 295×1,500×680 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.338 0.221 0.338 0.338
Model 3D18H2AF1 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 290 125 135 225
Air Flow Rate m³/min (H) 40 (H) 22 (H) 28 (H) 38
External Static Pressure Pa 118 118 118 118
Sound Pressure Level dB(A) (H) 49 (H) 42 (H) 42 (H) 47
Machine Weight kg 57 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ19.1 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 5)
(Option) Wireless BRC4C62
TAL RY140KUTALK RY200KUTAL RY200KUTAL RY250KUTAL
Outdoor Unit
YAL RY140KUYALK RY200KUYAL RY200KUYAL RY250KUYAL
Color Ivory
Dimensions H×W×D mm 1,345×880×370 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690
Type Cross Fin Coil Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)
Coil Row×Stages×Fin Pitch 2×60×2.0 2×40×2.0 2×40×2.0 2×50×2.0
Face Area m² 1.088 1.57 1.57 1.97
TAL JT170BC JT212D–P1 JT212D–P1 JT300D–P1
Model
YAL JT170BC–YH JT212D–P1YH JT212D–P1YH JT300D–P1YH
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 4.5 5.5 5.5 7.5
Model P45J11SM×2 P52H11SM P52H11SM P52H11SM
Type Propeller
Fan
Motor Output W 120+100 230+190 230+190 230+190
Air Flow Rate (C/H) m³/min 103/93 160/147 160/147 190/175
Machine Weight kg 112 179 179 204
Liquid mm φ9.5 (Flare) φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare)
Piping Connections Gas mm φ19.1 (Flare) φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange)
Drain mm φ26.0 (Hole) — — —
Thermal Protector for Compressor (for RY200 · 250KU), Outdoor Fan Motor and Indoor Fan Motor.
Safety Devices
High Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor). Reverse Phase Protector. Fuse.
Capacity Step % 100–0 100–0 100–0 100–0
Refrigerant Control Electronic Expansion Valve Capillary Tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30 30
Model R22 R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.7 (Charged for 5m) 4.0 (Charged for 5m) 4.0 (Charged for 5m) 5.5 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.6 3.0 3.0 3.0
Drawing No. C : 4D028027A C : 4D029817 C : 4D029819
Note:
Conversion Formulae
1. ∗1 The above data are based on the following conditions.
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
(1) Indoor
: 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB 60Hz, 220V
5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380V)
(2) Indoor
: 27°C(81°F)DB, 19.0°C(66°F)WB Indoor : 20°C(68°F)DB 60Hz, 220V
5m —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB (380V)
FDYM–FA + RY–FU 1
Indoor Unit FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL
Model VAL RY71FUVAL RY100FUVAL —
Outdoor Unit
TAL — — RY125FUTAL
kW 8.3/8.1/6.7 11.6/11.4/9.0 14.5/14.3/12.5
∗1 Cooling Capacity (1)/(2)/(3) Btu/h 28,200/27,800/22,900 39,700/38,900/30,700 49,600/48,800/42,700
kcal/h 7,100/7,000/5,800 10,000/9,800/7,700 12,500/12,300/10,800
kW 9.0/9.0/8.5 12.8/12.8/11.8 16.2/16.2/15.0
∗1 Heating Capacity (1)/(2)/(3) Btu/h 30,600/30,600/29,000 43,700/43,700/40,300 55,200/55,200/51,200
kcal/h 7,700/7,700/7,300 11,000/11,000/10,100 13,900/13,900/12,900
Indoor Unit FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL
Dimensions H×W×D mm 295×1,100×680 295×1,500×680 295×1,500×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×14×1.75 3×14×1.75 3×14×1.75
Face Area m² 0.221 0.338 0.338
Model 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1
Type Sirocco Fan
Fan Motor Output W 125 135 225
Air Flow Rate m³/min (H) 22 (H) 28 (H) 38
External Static Pressure Pa 118 118 118
Sound Pressure Level dB(A) (H) 42 (H) 42 (H) 47
Machine Weight kg 42 56 57
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32
Remote Controller Wired BRC1C61 (Note. 4)
(Option) Wireless BRC4C62
VAL RY71FUVAL RY100FUVAL —
Outdoor Unit
TAL — — RY125FUTAL
Color Ivory
Dimensions H×W×D mm 816×880×370 1,215×880×370 1,215×880×370
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×36×2.0 2×54×2.0 2×54×2.0
Face Area m² 0.653 0.979 0.979
VAL H23A38QABCA H23A50QABCA —
Model
TAL — — H23A62QDBLA
Comp. Type Hermetically Sealed Type
No. of Cylinders 2 2 2
Motor Output kW 2.2 3.0 3.75
Model P45J11SM P45J11SM×2 P45J11SM×2
Type Propeller
Fan
Motor Output W 80 90+60 90+80
Air Flow Rate m³/min 55 92 98
Machine Weight kg 91 120 115
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Connections Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Internal Pressure Relief Valve (Compressor).
Safety Devices
Motor Protector (Compressor).
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary tube
Max. Length m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 30 30 30
Model R22 R22 R22
Refrigerant
Charge (Factory Charge) kg 2.3 (Charged for 5m) 2.6 (Charged for 5m) 3.1 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.48 1.63 1.63
Drawing No. C : 4D020830A
Note:
1. ∗1 The above data are based on the following conditions. Conversion Formulae
Cooling Heating Piping Length Hz, Volts Standard kcal/h=kW×860
Btu/h=kW×3414
(1) Indoor
: 27°C(81°F)DB, 19.5°C(67°F)WB Indoor : 21°C(70°F)DB cfm=m³/min×35.3
5m 60Hz, 220V —
Outdoor : 35°C(95°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB
(3) Indoor
: 29°C(84°F)DB, 19.0°C(66°F)WB Indoor : 21°C(70°F)DB
7.5m 60Hz, 220V SSA 385/386
Outdoor : 46°C(115°F)DB, 24°C(75°F)WB Outdoor : 7°C(45°F)DB, 6°C(43°F)WB
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.
4. Optional Accessories
4.1 Option List
FD(Y)M–FA
FDYM03~06FAV1 / FAVAL
Name of Option
FDM03~05FAV1 / FAVAL
Wired Remote Controller BRC1C61
Wireless Heat Pump BRC4C62
Remote Controller Cooling Only BRC4C64
Set Back Time Clock BRC15A61
Central Remote Controller DCS302C61
Unified ON/OFF Controller DCS301B61
Schedule Timer DST301B61
intelligent Touch Controller DCS601B51
Wiring Adaptor for Electrical Appendices KRP4A51 (Note. 2)
Interface Adaptor for SkyAir Series DTA102A52
C : 4D021001A
Note: 1. Refer to the Option Hand Book for the detail.
2. Installation plate for adaptor PCB (KRP4A95) is necessary.
5. Dimensions
1
FDM03FA
FDYM03FA
3D020891C
Unit (mm)
FDM04FA
FDM05FA
FDYM04FA
FDYM05FA
FDYM06FA
3D020892B
Unit (mm)
6. Remote Controller
1
6.1 Dimensions
BRC1C61
Unit (mm)
3D028952
3D007898
6.2 Operation
6.2.1 Wired Remote Controller
Fig. 1 5 11 4 2 1
3
7 hr
9
C L H
hr NOT 10
6 TEST AVAILABLE
8 12
13 20
19
TEST
18
15 14 16 17 3PN02535-7L-0
Fig.1 Fig.2
1
7. Wiring Diagrams
FDYM03FAV1 / FDYM03FAVAL
FDYM04FAV1 / FDYM04FAVAL
FDYM05FAV1 / FDYM05FAVAL
FDYM06FAV1 / FDYM06FAVAL
3D019816D
FDM03FAV1 / FDM03FAVAL
FDM04FAV1 / FDM04FAVAL
1
FDM05FAV1 / FDM05FAVAL
3D019815D
8. Sound Level
8.1 Overall Sound Level
8.1.1 50Hz
dB(A)
Model 220V 240V Measuring Location
FDM03FAV1
39 41
FDM04FAV1
FDM05FAV1 44 46
FDYM03FAV1
39 41
FDYM04FAV1
FDYM05FAV1 44 46
4D021067A
FDYM06FAV1 46 48
8.1.2 60Hz
dB(A)
Model 220V Measuring Location
FDM03FAVAL
42
FDM04FAVAL
FDM05FAVAL 47
FDYM03FAVAL
42
FDYM04FAVAL
FDYM05FAVAL 47
4D021068A
FDYM06FAVAL 49
FDYM06FAV1 Note:
V1 : 220V
V1 : 240V
4D021073
8.2.2 60Hz
FDM03FAVAL FDM04FAVAL FDM05FAVAL
FDYM03FAVAL FDYM04FAVAL FDYM05FAVAL
FDYM06FAVAL Note:
VAL : 220V
4D021074
9. Fan Performance
FDM03FA
FDYM03FA
3D020899B
FDM04FA
FDYM04FA
3D020900A
FDM05FA
FDYM05FA
1
3D020901A
FDYM06FA
3D020904A
10. Installation
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g.
BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.
Part 2
Outdoor Unit
LU Series 2
1. External Appearance.............................................................................38
2. Power Supply ........................................................................................39
2.1 Cooling Only...........................................................................................39
2.2 Heat Pump .............................................................................................39
3. Specification..........................................................................................40
4. Dimensions and Service Space ............................................................41
4.1 Dimensions.............................................................................................41
4.2 Installation Service Space ......................................................................43
5. Piping Diagrams....................................................................................45
5.1 Cooling Only...........................................................................................45
5.2 Heat Pump .............................................................................................47
6. Wiring Diagrams....................................................................................49
6.1 Cooling Only...........................................................................................49
6.2 Heat Pump .............................................................................................52
7. Capacity Table ......................................................................................55
7.1 Cooling Only...........................................................................................55
7.2 Heat Pump .............................................................................................60
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ............63
8. Operation Limits ....................................................................................64
8.1 Cooling Only...........................................................................................64
8.2 Heat Pump .............................................................................................64
9. Sound Level ..........................................................................................65
9.1 Overall Sound Level ...............................................................................65
9.2 Octave Band Level .................................................................................66
10.Electric Characteristics..........................................................................68
10.1 Cooling Only...........................................................................................68
10.2 Heat Pump .............................................................................................69
11.Field Piping and Wiring .........................................................................70
11.1 Field Piping.............................................................................................70
11.2 Field Wiring ............................................................................................72
1. External Appearance
R71LU R100LU
RY71LU RY100LU
R125LU R140LU
RY125LU RY140LU
2. Power Supply
2.1 Cooling Only
2.1.1 50Hz
Series Indoor Unit Cooling Only Power Supply
FDYM03FAV1 R71LUV1 ∗
FDYM04FAV1 R100LUV1 ∗
1 phase 220–240V 2
FDYM03FAV1 R71LUY1 ∗
R–LU
FDYM04FAV1 R100LUY1 ∗
3 phase 380–415V (4 wires)
FDYM05FAV1 R125LUY1 ∗
FDYM06FAV1 R140LUY1 ∗
2.1.2 60Hz
Series Indoor Unit Cooling Only Power Supply
FDYM03FAVAL R71LUVAL ∗
1 phase 220V
FDYM04FAVAL R100LUVAL ∗
FDYM05FAVAL R125LUTAL ∗
R–LU 3 phase 220V
FDYM06FAVAL R140LUTAL ∗
FDYM05FAVAL R125LUYAL ∗
3 phase 380V (4 wires)
FDYM06FAVAL R140LUYAL ∗
FDYM03FAV1 RY71LUY1 ∗
RY–LU
FDYM04FAV1 RY100LUY1 ∗
3 phase 380–415V (4 wires)
FDYM05FAV1 RY125LUY1 ∗
FDYM06FAV1 RY140LUY1 ∗
2.2.2 60Hz
Series Indoor Unit Heat Pump Power Supply
FDYM06FAVAL RY140LUTAL ∗ 3 phase 220V
RY–LU
FDYM06FAVAL RY140LUYAL ∗ 3 phase 380V (4 wires)
3. Specification
FDYM–FA + R(Y)–LU
Optional Accessories
R71~140LU
Kit Name
Name of Option
R71LU R100LU R125LU R140LU
Central Drain Plug KKPJ5F180
Year-Round Cooling Kit KRK5F80V1 KRK5F140V1 KRK5F160V1
3D039655
RY71~140LU
Kit Name
Name of Option
RY71LU RY100LU RY125LU RY140LU
Central Drain Plug KKPJ5F180
3D039655
R71LU
RY71LU
Unit (mm)
2
3D039213
R100LU
RY100LU
Unit (mm)
3D039214
R125LU
RY125LU
Unit (mm)
3D039215
R140LU
RY140LU
Unit (mm)
3D039216
3D039172-1
3D039172-2
5. Piping Diagrams
5.1 Cooling Only
R71LU
3D039739
R100LU
3D039740
R125LU
3D039741
R140LU
3D039742
RY71LU
3D039734
RY100LU
3D039735
RY125LU
3D039736
RY140LU
3D039737
6. Wiring Diagrams
6.1 Cooling Only
6.1.1 50Hz
R71LUV1
R100LUV1 2
3D037640C
R71LUY1
R100LUY1
3D037642C
R125LUY1
R140LUY1
3D037644C
6.1.2 60Hz
R71LUVAL
R100LUVAL
3D037935C
R125LUTAL
R140LUTAL
3D037936C
R125LUYAL
R140LUYAL
3D037937C
RY71LUV1
RY100LUV1
3D037639C
RY71LUY1
RY100LUY1
3D037641C
RY125LUY1
RY140LUY1
3D037643C
6.2.2 60Hz
RY140LUTAL
3D037938C
RY140LUYAL
3D037939C
7. Capacity Table
7.1 Cooling Only
7.1.1 50Hz
FDYM03FAV1 + R71LUV1
FDYM03FAV1 + R71LUY1 2
3D039613A
FDYM04FAV1 + R100LUV1
FDYM04FAV1 + R100LUY1
3D039626A
FDYM05FAV1 + R125LUY1
3D039635
FDYM06FAV1 + R140LUY1
3D039644
7.1.2 60Hz
FDYM03FAVAL + R71LUVAL
3D039615A
FDYM04FAVAL + R100LUVAL
3D039628
FDYM05FAVAL + R125LUTAL
3D039637
FDYM05FAVAL + R125LUYAL
3D039638
FDYM06FAVAL + R140LUTAL
3D039648
FDYM06FAVAL + R140LUYAL
3D039652
FDYM03FAV1 + RY71LUV1
FDYM03FAV1 + RY71LUY1
3D039611A
FDYM04FAV1 + RY100LUV1
FDYM04FAV1 + RY100LUY1
3D039624
FDYM05FAV1 + RY125LUY1
3D039633
FDYM06FAV1 + RY140LUY1
3D039642
7.2.2 60Hz
FDYM06FAVAL + RY140LUTAL
3D039646
FDYM06FAVAL + RY140LUYAL
3D039650
90
100
85
71
125
80 140
75
0 5 7.5 10 15 20 25 30 35 40 45 50 (m)
Length of refrigerant piping (Total length)
C : 3D006500C
8. Operation Limits
8.1 Cooling Only
R71LUV1 / R71LUY1 / R71LUVAL
R100LUV1 / R100LUY1 / R100LUVAL
R125LUY1 / R125LUTAL / R125LUYAL
R140LUY1 / R140LUTAL / R140LUYAL
3D039657
3D039656
9. Sound Level
9.1 Overall Sound Level
9.1.1 Cooling Only
dB(A)
50Hz 60Hz
Model
220V 240V 220V
Measuring Location 2
R71LU 48 49 —
R100LU 49 50 —
380V 415V 220V
R71LU 48 49 49
R100LU 49 50 51
R125LU 49 50 —
R140LU 54 55 —
R125LUTAL — — 51
R140LUTAL — — 55 4D039813
380V
R125LUYAL — — 51
R140LUYAL — — 55
R140LUY1 Note:
V1 : 220V, Y1 : 380V
V1 : 240V, Y1 : 415V
4D039808
60Hz
R71LUVAL R100LUVAL R125LUTAL
R125LUYAL
R140LUTAL Note:
R140LUYAL TAL : 220V, YAL : 380V
4D039813
4D039808 4D039809
60Hz
RY140LUTAL (Cooling) RY140LUTAL (Heating) Note:
RY140LUYAL (Cooling) RY140LUYAL (Heating) TAL : 220V, YAL : 380V
4D039813 4D039814
10.1.2 60Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
FDYM03FAVAL R71LUVAL 60 – 220 19.9 24.0 30 99 14.3 0.075 0.8 0.125 1.2
FDYM04FAVAL R100LUVAL 60 – 220 23.8 28.2 40 143 17.3 0.1 0.9 0.135 1.3
0.075 0.8
FDYM05FAVAL R125LUTAL 60 – 220 Max.60Hz 242V 22.6 25.3 30 137 15.1 + + 0.225 2.0
Min.60Hz 198V 0.095 0.9
0.075 0.8
FDYM06FAVAL R140LUTAL 60 – 220 23.3 31.9 40 146 15.5 + + 0.270 2.2
0.100 0.9
0.075 0.8
FDYM05FAVAL R125LUYAL 60 – 380 14.2 16.3 20 66 8.4 + + 0.225 2.0
Max.60Hz 418V 0.095 0.9
Min.60Hz 342V 0.075 0.8
FDYM06FAVAL R140LUYAL 60 – 380 14.5 18.9 25 75 8.5 + + 0.270 2.2
0.100 0.9
3D039576C
3D039577A
3D039578A
3D039579A
10.2.2 60Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
0.075 0.8
Max.60Hz 242V
FDYM06FAVAL RY140LUTAL 60 – 220 Min.60Hz 198V 23.2 31.9 40 146 15.4 + + 0.270 2.2
0.100 0.9
0.075 0.8
Max.60Hz 418V
FDYM06FAVAL RY140LUYAL 60 – 380 Min.60Hz 342V 14.5 18.9 25 75 8.5 + + 0.270 2.2
0.100 0.9
3D039579A
Indoor unit
One-way length of pipe (L):
L1
• Select the amount of refrigerant which matches a length which exceeds the charge-less length from
Table 1, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.
Table 1 (The maximum allowable pipe length is 50 meters.) <unit : kg>
Pipe Excess Length over 30 Meters 10 m or less 20 m or less
RY71 0.50 1.00
Heat Pump Type
RY100~160 0.75 1.50
Straight Cooling Type R71~140 0.25 0.50
1PN05248B-1
11.1.4 Pumping-down Operation Method
The outdoor unit is equipped with a low-pressure switch to protect the compressor.
Take the following steps to perform the pumping-down operation.
Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to
provide a trap at an appropriate place in the riser gas piping.
Gas piping
Liquid piping
∗15m
Note: A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.
1PN05248B-2
C : 4D001694A
11.2.2 60Hz
C : 4D006674A
Part 3
Outdoor Unit
KU Series
1. External Appearance.............................................................................76 3
2. Power Supply ........................................................................................77
2.1 Cooling Only...........................................................................................77
2.2 Heat Pump .............................................................................................77
3. Specification..........................................................................................78
4. Dimensions and Service Space ............................................................79
4.1 Dimensions.............................................................................................79
4.2 Installation Service Space for R(Y)140KU .............................................81
4.3 Installation Service Space for R(Y)200 · 250KU ....................................83
5. Piping Diagrams....................................................................................84
5.1 Cooling Only...........................................................................................84
5.2 Heat Pump .............................................................................................85
6. Wiring Diagrams....................................................................................89
6.1 Cooling Only...........................................................................................89
6.2 Heat Pump .............................................................................................91
7. Capacity Table ......................................................................................94
7.1 Cooling Only...........................................................................................94
7.2 Heat Pump .............................................................................................96
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ............99
8. Operation Limits ..................................................................................100
8.1 Cooling Only.........................................................................................100
8.2 Heat Pump ...........................................................................................101
9. Sound Level ........................................................................................102
9.1 Overall Sound Level .............................................................................102
9.2 Octave Band Level ...............................................................................103
10.Electric Characteristics........................................................................105
10.1 Cooling Only.........................................................................................105
10.2 Heat Pump ...........................................................................................106
11.Field Piping and Wiring .......................................................................107
11.1 Field Piping (R(Y)140KU).....................................................................107
11.2 Field Piping (R(Y)200 · 250KU)............................................................109
11.3 Field Wiring ..........................................................................................112
1. External Appearance
R140KU
RY140KU
R200KU R250KU
RY200KU RY250KU
2. Power Supply
2.1 Cooling Only
2.1.1 50Hz
Series Indoor Unit Cooling Only Power Supply
FDYM04FAV1×2 R200KUY1
FDYM05FAV1×2 R250KUY1
2.1.2 60Hz
Series Indoor Unit Cooling Only Power Supply 3
FDYM06FAVAL R140KUTALK
FDYM04FAVAL×2 R200KUTAL
3 phase 220V
FDYM03FAVAL×3 R200KUTAL
FDYM05FAVAL×2 R250KUTAL
R–KU
FDYM06FAVAL R140KUYALK
FDYM04FAVAL×2 R200KUYAL
3 phase 380V (4 wires)
FDYM03FAVAL×3 R200KUYAL
FDYM05FAVAL×2 R250KUYAL
FDYM05FAV1×2 RY250KUY1
2.2.2 60Hz
Series Indoor Unit Heat Pump Power Supply
FDYM06FAVAL RY140KUTALK
FDYM04FAVAL×2 RY200KUTAL
3 phase 220V
FDYM03FAVAL×3 RY200KUTAL
FDYM05FAVAL×2 RY250KUTAL
RY–KU
FDYM06FAVAL RY140KUYALK
FDYM04FAVAL×2 RY200KUYAL
3 phase 380V (4 wires)
FDYM03FAVAL×3 RY200KUYAL
FDYM05FAVAL×2 RY250KUYAL
3. Specification
FDYM–FA + R(Y)–KU
Optional Accessories
R140KU
Kit Name
Name of Option
R140KU
Central Drain Plug KKPJ5F180
Year-Round Cooling Kit KRK5F160V1
3D014872B
RY140KU
Kit Name
Name of Option
RY140KU
Central Drain Plug KKPJ5F180
3D014872B
R(Y)200 · 250KU
Kit Name
Name of Option Remark
R(Y)200KU R(Y)250KU
For Twin Type KHD58C23A KHD58C24A
Branch Piping Kit For Triple Type KHR58P322H —
For Double Twin Type KHRJ5F224F KHRJ5F280F
4D029784A
R140KU
RY140KU
Unit (mm)
C : 3D027710A
R200KU
RY200KU
Unit (mm)
3D029265
R250KU
RY250KU
Unit (mm)
3D029264
3D001951A-1
3D001951A-2
3D006578A
5. Piping Diagrams
5.1 Cooling Only
R140KU
C : 3D014832A
3D030194
3D030195
RY140KU
140
C : 3D014830B
3D029823
3D029827
3D030158
3D030163
3D029825
3D030160
6. Wiring Diagrams
6.1 Cooling Only
6.1.1 50Hz (Including 60Hz YAL Models)
R200KUY1 / R200KUYAL
R250KUY1 / R250KUYAL
3D029091A
6.1.2 60Hz
R140KUTALK
3D015463D
R140KUYALK
3D015461E
R200KUTAL
R250KUTAL
3D029092
RY200KUY1
RY200KUYAL
3D028900A
RY250KUY1
RY250KUYAL
3D028901A
6.2.2 60Hz
RY140KUTALK
3D027416A
RY140KUYALK
3D027413A
RY200KUTAL
3D028902A
RY250KUTAL
3D028903A
7. Capacity Table
7.1 Cooling Only
7.1.1 50Hz
FDYM04FAV1 × 2 + R200KUY1
FDYM03FAV1 × 3 + R200KUY1
3D030166
FDYM05FAV1 × 2 + R250KUY1
3D030168
7.1.2 60Hz
FDYM06FAVAL + R140KUTALK
FDYM06FAVAL + R140KUYALK
3D028068
3D030167
FDYM05FAVAL × 2 + R250KUTAL
FDYM05FAVAL × 2 + R250KUYAL
3D030169
FDYM04FAV1 × 2 + RY200KUY1
FDYM03FAV1 × 3 + RY200KUY1
3D029856
FDYM05FAV1 × 2 + RY250KUY1
3D029853
7.2.2 60Hz
FDYM06FAVAL + RY140KUTALK
FDYM06FAVAL + RY140KUYALK
3D028060
FDYM04FAVAL × 2 + RY200KUTAL
FDYM04FAVAL × 2 + RY200KUYAL
FDYM03FAVAL × 3 + RY200KUTAL
FDYM03FAVAL × 3 + RY200KUYAL
3D029857
FDYM05FAVAL × 2 + RY250KUTAL
FDYM05FAVAL × 2 + RY250KUYAL
3D029855
140~250
95
90
200
3
85 250
80
140
75
0 5 10 15 20 25 30 35 40 45 50 (m)
Length of refrigerant piping (Total length)
C : 3D006500C
8. Operation Limits
8.1 Cooling Only
R140KUTALK
R140KUYALK
3D028099
[50Hz] [60Hz]
R200KUY1 R200KUTAL / R200KUYAL
R250KUY1 R250KUTAL / R250KUYAL
3D030170 3D030170
3D028098
3D029783
9. Sound Level
9.1 Overall Sound Level
9.1.1 Cooling Only
dB(A)
Model 50Hz 380V 50Hz 415V 60Hz 220 · 380V Measuring Location
R140KU — — 56 R140KU
R200KU 60 61 60
R250KU 61 62 61
MIKE
4D028089B
R200 · 250KU
MIKE
4D030106
MIKE
4D028089B
RY200 · 250KU
MIKE
4D030106
4D027632 4D027634
60Hz
R140KUTALK R200KUTAL R250KUTAL
R140KUYALK R200KUYAL R250KUYAL
Note:
TAL : 220V, YAL : 380V
4D027633
60Hz
RY140KUTALK (Cooling) RY140KUTALK (Heating) RY200KUTAL (Cooling)
RY140KUYALK (Cooling) RY140KUYALK (Heating) RY200KUYAL (Cooling)
Note:
TAL : 220V, YAL : 380V
10.1.2 60Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
0.12 1.1
FDYM06FAVAL R140KUTALK 60 – 220 24.5 32.2 40 165 16.2 + + 0.270 2.2
0.10 1.0
0.23 1.8 0.135
FDYM04FAVAL×2 R200KUTAL 60 – 220 35.3 39.0 50 161 23.4 + + 1.3×2
0.19 1.6 ×2
Max.60Hz 242V
Min.60Hz 198V 0.23 1.8 0.125
FDYM03FAVAL×3 R200KUTAL 60 – 220 36.3 40.0 50 161 23.4 + + 1.2×3
0.19 1.6 ×3
10.2.2 60Hz
Unit Combination Power Supply Comp OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
0.12 1.1
FDYM06FAVAL RY140KUTALK 60 – 220 25.0 32.2 40 165 16.6 + + 0.270 2.2
0.10 1.0
0.23 1.8 0.135
FDYM04FAVAL×2 RY200KUTAL 60 – 220 35.3 39.0 50 161 23.4 + + 1.3×2
0.19 1.6 ×2
Max.60Hz 242V
Min.60Hz 198V 0.23 1.8 0.125
FDYM03FAVAL×3 RY200KUTAL 60 – 220 36.3 40.0 50 161 23.4 + + 1.2×3
0.19 1.6 ×3
Indoor unit
One-way length of pipe (L):
L1
• Select the amount of refrigerant which matches a length which exceeds the charge-less length from
Table 1, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.
Table 1 (The maximum allowable pipe length is 50 meters.) <Unit : kg>
Length of Pipe Connected 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Additional Charging Amount — 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25
<PRECAUTION>
Contact your DAIKIN dealer when installing the unit using pipes of 3 m or less.
C : 3PN00281-21R-1
11.1.4 Pumping-down Operation Method
The outdoor unit is equipped with a low-pressure switch to protect the compressor.
Take the following steps to perform the pumping-down operation.
Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to
provide a trap at an appropriate place in the riser gas piping.
Gas piping
Liquid piping
Outdoor unit
Note: A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.
C : 3PN00281-21R-2
1PN04787B-1
1PN04788A-1
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.
1PN04788A-2
1PN04787B-2
C : 4D006674A
3D029782
Part 4
Outdoor Unit
FU Series
1. External Appearance...........................................................................116
2. Power Supply ......................................................................................117
2.1 Power Supply .......................................................................................117
3. Specification........................................................................................118
4. Dimensions and Service Space ..........................................................119 4
4.1 Dimensions...........................................................................................119
4.2 Installation Service Space ....................................................................120
5. Piping Diagrams..................................................................................122
5.1 Cooling Only.........................................................................................122
5.2 Heat Pump ...........................................................................................123
6. Wiring Diagrams..................................................................................124
6.1 Cooling Only.........................................................................................124
6.2 Heat Pump ...........................................................................................127
7. Capacity Table ....................................................................................129
7.1 Cooling Only.........................................................................................129
7.2 Heat Pump ...........................................................................................132
7.3 Capacity Correction Factor by the Length of Refrigerant Piping ..........134
8. Operation Limit....................................................................................135
8.1 Cooling Only.........................................................................................135
8.2 Heat Pump ...........................................................................................136
9. Sound Level ........................................................................................137
9.1 Overall Sound Level .............................................................................137
9.2 Octave Band Level ...............................................................................138
10.Electric Characteristics........................................................................140
10.1 Cooling Only.........................................................................................140
10.2 Heat Pump ...........................................................................................141
11.Field Piping and Wiring .......................................................................142
11.1 Field Piping...........................................................................................142
11.2 Field Wiring ..........................................................................................144
1. External Appearance
R100FU
R71FU R125FU
RY71FU RY100FU
RY125FU
2. Power Supply
2.1 Power Supply
2.1.1 Cooling Only
50Hz
Series Indoor Unit Cooling Only Power Supply
FDM03FAV1 R71FUV1
1 phase 220–240V
FDM04FAV1 R100FUV1
FDM05FAV1 R125FUY1
60Hz
Series Indoor Unit Cooling Only Power Supply
FDM03FAVAL R71FUVAL 4
1 phase 220V
R–FU FDM04FAVAL R100FUVAL
3. Specification
FD(Y)M–FA + R(Y)–FU
Optional Accessories
R(Y)71~125FU
Kit Name
Name of Option
71 100 125
Central Drain Plug KKPJ5F180
C : 4D006664
R71FU
RY71FU
Unit (mm)
3D001674A
R100 · 125FU
RY100 · 125FU
Unit (mm)
3D001672A
3D001951A-1
3D001951A-2
5. Piping Diagrams
5.1 Cooling Only
R71FU
R100FU
R125FU
3D001310A
RY71FU
RY100FU
RY125FU
3D005825
6. Wiring Diagrams
6.1 Cooling Only
6.1.1 50Hz
R71FUV1
3D010789A
R71FUY1
3D000995C
R100FUV1
3D010788
R100FUY1
R125FUY1
3D001007C
6.1.2 60Hz
R71FUVAL
3D005375C
R100FUVAL
3D005376C
R125FUTAL
3D005377A
RY71FUVAL
3D005370B
RY100FUVAL
3D005371B
RY125FUTAL
3D005372A
7. Capacity Table
7.1 Cooling Only
7.1.1 50Hz
FDM03FAV1 + R71FUV1
FDM03FAV1 + R71FUY1
3D001843F
FDM04FAV1 + R100FUV1
FDM04FAV1 + R100FUY1
3D001844G
FDM05FAV1 + R125FUY1
3D001845F
7.1.2 60Hz
FDM03FAVAL + R71FUVAL
3D007447F
FDM04FAVAL + R100FUVAL
3D007448E
FDM05FAVAL + R125FUTAL
3D007449F
FDYM03FAVAL + RY71FUVAL
3D007444E
FDYM04FAVAL + RY100FUVAL
3D007445E
FDYM05FAVAL + RY125FUTAL
3D007446E
71~125
95
90
85 100
71
125
80
75
0 5 10 15 20 25 30 35 40 45 50 (m)
Length of refrigerant piping (Total length)
C : 3D006500C
8. Operation Limit
8.1 Cooling Only
8.1.1 50Hz
R71FUV1 / R71FUY1
R100FUV1 / R100FUY1
— / R125FUY1
3D001318
8.1.2 60Hz
R71FUVAL
R100FUVAL
R125FUTAL
3D006659
RY71FUVAL
RY100FUVAL
RY125FUTAL
3D006675
9. Sound Level
9.1 Overall Sound Level
9.1.1 Cooling Only
50Hz dB(A)
Model 220V Measuring Location
R71FUV1 52
R100FUV1 56
Model 380V
R71FUY1 52 Microphone
R100FUY1 56
4D002309
R125FUY1 57
60Hz dB(A)
Model 220V Measuring Location
R71FUVAL 53 4
R100FUVAL 57
Microphone
R125FUTAL 59 4D007392
RY71FUVAL 53 55
RY100FUVAL 57 59
Microphone
RY125FUTAL 59 61 4D007382
60Hz
R71FUVAL R100FUVAL R125FUTAL
Note:
V1 · VAL · TAL : 220V, Y1 : 380V
Note:
VAL · TAL : 220V
10.1.2 60Hz
Unit Combination Power Supply Compressor OFM IFM
Indoor Outdoor Hz – Volts Voltage Range MCA TOCA MFA LRA RLA kW FLA kW FLA
FDM03FAVAL R71FUVAL 60 – 220 20.1 26.0 30 87 14.5 0.080 0.8 0.125 1.2
0.090 0.8
FDM04FAVAL R100FUVAL 60 – 220 Max.60Hz 242V 28.1 39.7 45 118 20.3 + + 0.135 1.3
0.060 0.6
Min.60Hz 198V
0.090 0.8
FDM05FAVAL R125FUTAL 60 – 220 22.5 27.9 35 124 15.1 + + 0.225 2.0
0.080 0.8
3D007342E
3D007348E
3D007347E
Indoor unit
One-way length of pipe (L):
L1
• Select the amount of refrigerant which matches a length which exceeds the charge-less length from
Table 1, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.
Table 1 (The maximum allowable pipe length is 50 meters.) <Unit : kg>
Length of Pipe Connected 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Straight Cooling Type — 0.13 0.25 0.38 0.50 0.63 0.75 0.88 1.00 1.13
Heat Pump Type — 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25
<PRECAUTION>
Contact your DAIKIN dealer when installing the unit using pipes of 3 m or less.
C : 1PN01324A-1
C : 3PN00281-7V-1
5. Close the liquid-side stop valve fully. If the valve is not fully closed it could cause burn-out of
(Refer to Fig.1) the compressor.
6. After the pressure gauge indication has dropped to
0 kgf/cm2G, close the gas stop valve fully and press —
the Stop button on the remote controller.
Liquid piping
Outdoor unit
Note: A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.
C : 1PN01324A-2
C : 3PN00281-7V-2
C : 4D001694A
C : 4D006674A
Dealer
Head Office:
Umeda Center Bldg., 4-12, Nakazaki-Nishi
2-chome, Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 18-1, Konan
2-chome, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
The specifications, designs, and information in this brochure are subject to change without notice.
ED 40-017B
This book is made of recycled paper. Printed in Japan 12/2004 FS