P R O D U C T I N FO R M AT I O N
—
TEXLIM Surge Arresters are used for
the protection of switchgear,
transformers and other equipment
in high voltage systems against
atmospheric and switching
overvoltages. TEXLIM is an ideal
choice when lightning intensity,
energy capability and mechanical
demands are high – especially suited
for extreme seismic zones.
3
—
Table of contents
002 Introduction
005 Benefits
008 TEXLIM Q
010 TEXLIM P
012 TEXLIM T
—
TEXLIM Metal Oxide Surge Arrester
ABB’s family of composite-tube arresters
TEXLIM offers an ideal alternative to traditional TEXLIM surge arresters are designed to perform
porcelain-housed arresters. High mechanical under severe environmental conditions. They are
strength in combination with the polymeric best suited for applications with high mechanical
housing, gives a good combination of performance. strength demands, high seismic requirements, or
sea salt, soot or acid rain and other such harsh
The newly developed family of TEXLIM includes 3 environments. Applications include:
new types of surge arresters: Q, P and T. They have • Protection of substation equipment
been optimized to fulfill the market requirements • Loads requiring high mechanical strength
in the voltage segment 123 - 800 kV and can meet • Seismic areas
requirements of specific applications where higher • Polluted areas
mechanical loads are demanded. • Transformers and reactors
• Capacitor banks
—
Quick selection guide
—
TEXLIM Metal Oxide Surge Arrester
Benefits
For satisfactory performance, it is important that
the units are hermetically sealed for the lifetime of
the arresters. The sealing arrangement at each end
of the each unit consists of a pre-stressed stainless
steel plate with a rubber gasket against the inner
surface of the flanges and ensures effective sealing
even if the gasket “set” due to aging. It also serves
to fix the column of blocks in the longitudinal
direction by means of heavy spring washers.
TEXLIM Q
Classifications
IEC 60099-4, Ed. 3.0 Station; SM
Arrester classification IEEE Std. C62.11-2012 Station
Line discharge class IEC 60099-4, Ed. 2.2 3
Energy class IEEE Std. C62.11-2012 E
Performance data
Maximum system voltages (Vm) Vm 123 - 362 kVrms
Duty cycle rated voltages (Vr) Vr 90 - 288 kVrms
Classifying current (IEEE/ANSI) IEEE / ANSI 10 kA peak
(IEC) IEC 10 kA peak
High current 4/10 µs 100 kA peak
Discharge current withstand strength Low current 2000 µs 1000 A peak
Switching surge energy rating W th 9.0 kJ / kV MCOV
Short circuit / pressure relief capability 80 kA rms sym
Specified long-term load (SLL) 15,489 ft-lbs / 21 kNm
Mechanical strength Specified short-term load (SSL) 29,502 ft-lbs / 40 kNm
Ambient temperature -58 F to +113 F
Design altitude **6000 ft / 1830 m
Service conditions Frequency 15 - 62 Hz
TEXLIM P
Classifications
IEC 60099-4, Ed. 3.0 Station; SH
Arrester classification IEEE Std. C62.11-2012 Station
Line discharge class IEC 60099-4, Ed. 2.2 4
Energy class (switching surge energy) IEEE Std. C62.11-2012 G
Performance data
Maximum system voltages (Vm) Vm 123 - 550 kVrms
Duty cycle rated voltages (Vr) Vr 90 - 444 kVrms
Classifying current (IEEE/ANSI) IEEE / ANSI 10 / 15 kA peak
(IEC) IEC 20 kA peak
High current 4/10 µs 100 kA peak
Discharge current withstand strength Low current 2000 µs 1600 A peak
Switching surge energy rating W th 13.0 kJ / kV MCOV
Short circuit / pressure relief capability 80 kA rms sym
Specified long-term load (SLL) 15,489 ft-lbs / 21 kNm
Mechanical strength Specified short-term load (SSL) 29,502 ft-lbs / 40 kNm
Ambient temperature -58 F to +113 F
Design altitude **6000 ft / 1830 m
Service conditions Frequency 15 - 62 Hz
TEXLIM T
Classifications
IEC 60099-4, Ed. 3.0 Station; SH
Arrester classification IEEE Std. C62.11-2012 Station
Line discharge class IEC 60099-4, Ed. 2.2 Class 5
Energy class IEEE Std. C62.11-2012 J
Performance data
Maximum system voltages (Vm) Vm 123-800 kVrms
Duty cycle rated voltages (Vr) Vr 92-624 kVrms
Classifying current (IEEE/ANSI) IEEE / ANSI 10/15/20 kA peak
(IEC) IEC 20 kA peak
High current 4/10 µs 150 kA peak
Discharge current withstand strength Low current 2000 µs 2600 A peak
Switching surge energy rating W th 18.0 kJ/kV MCOV
Short circuit / pressure relief capability 80 kA rms sym
Specified long-term load (SLL) 15,489 f-lbs / 21 kNm
Mechanical strength Specified short-term load (SSL) 29,502 ft-lbs / 40 kNm
—
** Higher altitudes Ambient temperature -58 F to +113 F
designs available Design altitude **6000 ft / 1830 m
on request Service conditions Frequency 15 - 62 Hz
7
—
TEXLIM Q, P, T
Figures
— — —
Figure 1 Figure 2 Figure 3
— —
Figure 4 Figure 5
8
—
TEXLIM Q
Electrical characteristics
Ratings TOV
(kVrms) (kVrms) Maximum discharge voltage with different current waveforms
—
TEXLIM Q
Vertical mounting styles with standard and extra creepage distance
—
TEXLIM P
Electrical characteristics
Ratings TOV
(kVrms) (kVrms) Maximum discharge voltage with different current waveforms
—
TEXLIM P
Vertical mounting styles with standard and extra creepage distance
—
TEXLIM T
Electrical characteristics
Ratings TOV
(kVrms) (kVrms) Maximum discharge voltage with different current waveforms
—
TEXLIM T
Vertical mounting styles with standard and extra creepage distance
—
TEXLIM Q, P, T
Mountings and hardware
— —
Master Nameplate Drilling Plan
— —
Line Terminal (aluminum) Ground Terminal (galvanized)
T YPE TEXLIM SURGE ARRESTERS 123-800K V 15
— —
Insulating Base Kit High Strength Insulating Base Kit
Part No: 4F0090G01
*Reduces mechanical properties stated on page 6. *Consult factory.
— —
Adapter Plate Kit (3-Hole Mount) Adapter Plate Kit (6-Hole Mount)
Part No: 4F0094G01 Part No: 4F0094G02
— —
Insulating Base Kit with Adapter Insulating Base Kit with Adapter
Plate (3-Hole Mount) Plate (6-Hole Mount)
Part No: 4F0095G01 Part No: 4F0095G02
*Reduces mechanical properties stated on page 6. *Reduces mechanical properties stated on page 6.
—
ABB Inc.
High Voltage Surge Arresters
100 Distribution Circle
Mt. Pleasant, PA, USA 15666
Phone: +1 724-696-1500
abb.com/highvoltage
Additional information
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB does not
accept any responsibility whatsoever for
potential errors or possible lack of
information in this document.
2GNM110160 REV A 5.8.2018