Professional Documents
Culture Documents
By Zelalem Walie
WOLDIA, ETHOPIA
June, 26, 2013
POWER SYSTEM PROTECTION LABORATORY MANUAL
Declaration
This manual entitled ‘‘Power System Protection Laboratory Manual’’ has been carried out by me. No
portion of the work presented in this manual has been previously and concurrently submitted in support
of another award or qualification either at this institution or elsewhere.
Approval for Submission
This laboratory manual entitled with ‘‘Power System Protection Laboratory Manual’’ was prepared by
Mr. Zelalem from school of Electrical and Computer Engineering, in Woldia University.
Approved by,
Name Signature Date
1. _______________________ ______________ _________
2. _______________________ ______________ _________
Board of evaluator
Name signature Date
1. _______________________ ______________ _________
2. _______________________ ______________ _________
3. _______________________ ______________ _________
4. _______________________ ______________ _________
5. _______________________ ______________ _________
WDU Page I
POWER SYSTEM PROTECTION LABORATORY MANUAL
Acknowledgement
First of all I would like to thank our almighty GOD who guide me all the way. I also genuinely like to
thank Mr. Wondosen Tegegne for his support, and helping me for information throughout the period while
this work was carried out.
Finally I would also like to thank to Mr. Tesfahun Desalegn head of Electrical and computer Engineering
school and all the staff members of the department for giving me important comments while preparing
this manual.
WDU Page II
POWER SYSTEM PROTECTION LABORATORY MANUAL
Abstract
Power system protection is branch of electrical power engineering that deals with the protection of
electrical power system from faults through the isolation of faulted parts from the rests of the electrical
network. Power system protection is a taught in university as second semester subject for forth year degree
students in electrical engineering, which consists of theoretical and practical work. As the part of the
syllabus, the course learning outcome on practical work is to produce students that can handle any
practical work related to common protection system applied to power distribution system equipment. Most
practical work related to power system protection subject is done using simulation environment, where
the actual performance of protection equipment cannot be measured. This manual presents the
configuration of power system protection laboratory that involves four main and three sub experimental
set of practical work for department of power engineering students. Emphasis is given in to the stand
alone test for relay protection experimental set and fault current relay experimental set. This laboratory is
appropriate in facilitate the teaching process to demonstrate the realistic operating characteristics of
equipment protection switching and dynamic response system to relay protection to the student.
Table of Contents
Contents page
Declaration ................................................................................................................................................... I
Acknowledgement ..................................................................................................................................... II
List of Figure............................................................................................................................................. VI
1. Introduction ......................................................................................................................................... 1
3.2.1 Description of the 3 ~ Reverse Power Relay (Cat. no. 745 201) ........................................................ 5
4.2.1 Description of the 3 ~ Time Over- and under voltage Relay (Cat. no.745 181) ............................... 17
WDU Page IV
POWER SYSTEM PROTECTION LABORATORY MANUAL
6. Experiments with 3 phase Transformer differential protection relay (Cat. No. 745 331) ................. 46
WDU Page V
POWER SYSTEM PROTECTION LABORATORY MANUAL
List of Figure
Figure 1: Reverse Power Relay................................................................................................................... 5
Figure 2: Connection three-wire system ..................................................................................................... 7
Figure 3: Connection phase-to-phase voltage in four-wire system ............................................................ 7
Figure 4: Connection phase-to-neutral voltage in four-wire system .......................................................... 8
Figure 5: Contact positions of the output relays ......................................................................................... 8
Figure 6: Diagram of power calculation ..................................................................................................... 9
Figure 7: Front plate of the Reverse Power Relay .................................................................................... 10
Figure 8: Adjustment of rated voltage ...................................................................................................... 11
Figure 9: Adjusting example ..................................................................................................................... 12
Figure 10: Experiment assembly with the Power Relay ........................................................................... 13
Figure 11: Time Over- and under voltage Relay ...................................................................................... 17
Figure 12: Connecting two-wire system DIP-switch setting Y ................................................................ 19
Figure 13 : Connection three-wire system DIP-switch setting Δ.............................................................. 19
Figure 14: Connection four-wire system DIP-switch setting Y or Δ ........................................................ 19
Figure 15: Contact positions of the output relays ..................................................................................... 20
Figure 16: Front plate of the Time Over- and under voltage Relay.......................................................... 21
Figure 17: Adjustment of rated voltage .................................................................................................... 22
Figure 18: Adjustment of the switching hysteresis ................................................................................... 23
Figure 19: Adjustment example ................................................................................................................ 24
Figure 20: Experiment assembly with Time Over- and under voltage Relay........................................... 25
Figure 21: Time Over/Under current Relay .............................................................................................. 28
Figure 22: Connections ............................................................................................................................. 30
Figure 23: Contact positions of the output relays ..................................................................................... 31
Figure 24: Front plate of the Time Overcurrent Relay ............................................................................. 33
Figure 25: Setting the tripping characteristics .......................................................................................... 34
Figure 26: Adjustment example ................................................................................................................ 35
Figure 27: Characteristic of the definite time ........................................................................................... 36
Figure 28: Normal inverse ........................................................................................................................ 38
Figure 29: Very inverse ............................................................................................................................. 38
Figure 30: Extremely inverse .................................................................................................................... 39
Figure 31: Experiment assembly to study the overcurrent time relay ...................................................... 40
Figure 32: Characteristic of the relay (IDMT) .......................................................................................... 42
Figure 33: Experiment assembly to study the tripping in three-phase network ....................................... 43
WDU Page VI
POWER SYSTEM PROTECTION LABORATORY MANUAL
List of Table
Table 1: required equipment for the experiments on the three phase reverse power relay........................................ 4
Table 2: Function of DIP-switches .......................................................................................................................... 11
Table 3: Results of tripping value at different setting value of P> when v = 400V ................................................ 14
Table 4: Results of tripping value at different setting value of P> when v = 360V ................................................ 14
Table 5: Required Equipment for the experiments on the Three Phase Time Over/under voltage Relay ............... 16
Table 6: Function of DIP-switches .......................................................................................................................... 22
Table 7: Required Equipment for the experiments on the Three Phase Time Over/under current Relay ............... 28
Table 8: Functions of DIP-switches ........................................................................................................................ 34
Table 9: Setting ranges and graduation ................................................................................................................... 36
Table 10: Setting ranges and graduation ................................................................................................................. 39
Table 11: The measured and setting values of the relay when I</IN can be set to values of 0.5-2(IN=1A). .......... 41
Table 12: The measured and setting values of the relay when I</IN can be set to values of 0.5-2(IN = 1A). ........ 41
Table 13: Measurement results of current with respect to different setting values ................................................. 44
Table 14: Measurement results of current with respect to different setting values when tI> = 0.4 s ...................... 44
Table 15: Measurement results of current with respect to different setting values when tI> = 1s .......................... 44
Table 16: measurement results of current with respect to different setting values when I>/IN = 1and tI> =0.2s ... 44
Table 17: measurement results of current with respect to different setting values when I>/IN = 1and tI> =1s ...... 44
Table 18: Required Equipment for the experiments on the three phase Transformer differential protection relay 47
Table 19: The current readings with respective setting value of Id1 ....................................................................... 55
1. Introduction
The IEEE defines protective relays as: “relays whose function is to detect defective lines or apparatus or
other power system conditions of an abnormal or dangerous nature and to initiate appropriate control
circuit action”. Relays detect and locate faults by measuring electrical quantities in the power system
which are different during normal and intolerable conditions. The most important role of protective relays
is to first protect individuals, and second to protect equipment. In the second case, their task is to minimize
the damage and expense caused by insulation breakdowns which (above overloads) are called faults by
relay engineers. These faults could occur as a result from insulation deterioration or unforeseen events,
for example, lighting strikes or trips due to contact with trees and foliage.
Relays are not required to operate during normal operation, but must immediately activate to handle
intolerable system conditions. This immediate availability criterion is necessary to avoid serious outages
and damages to parts of or the entire power network. Theoretically speaking, a relay system should be
capable of responding to an infinite number of abnormalities that may happen within the network.
However, in practice, some compromises must be made by comparing risks. It is quite difficult to ensure
stability and security of the entire power system if only local measurements are employed in monitoring,
protection and control schemes. One promising way is to develop system wide protection and control
mechanisms, complementary to the conventional local and zonal protection strategies. In order to
implement such mechanisms, synchronized phasor measurement may serve as an effective data source
from which critical information about the system’s condition can be extracted. Synchronized phasor
measurement capabilities are now one of the features available in the most advanced protective relays
commercially available, and the use of this feature is proliferating.
WDU Page 1
POWER SYSTEM PROTECTION LABORATORY MANUAL
2. Safety Guidelines
To develop a healthy respect for electricity, it is important to understand how it acts, how it can be
directed, what hazards it presents, and how these hazards can be minimized through safe laboratory
procedures.
How Shock Occurs
Electricity can travel only in a closed or looped circuit. Normally, travel is through a conductor. Shock
occurs when the body becomes a part of the electric circuit. The current must enter the body at one point
and leave at another. Shock may occur in one of three ways; the person must come in contact with:
1. both wires of the electric circuit
2. one wire of an energized circuit and the ground or
3. A metallic part that has become “hot” by itself being in contact with an energized wire, while the
person is in contact with the circuit ground.
It is possible to receive a shock by touching only the energized wire, or an energized metallic part, and
the ground because of the nature of an electric circuit. To receive a shock, a person must become part of
an actual circuit; that is, the current must flow through his body as it would through a conductor. Under
certain conditions, a person may be exposed to electricity but, unless his body becomes part of a circuit,
no harm results. If, for instance, a person is standing on an insulating mat and touches only one wire of a
120-volt circuit, no complete circuit is established and he will feel no shock. If, however, a person should
touch both conductors of a circuit, even with the same finger, the finger becomes part of the circuit,
current flowing through the finger from one side of the circuit to the other. For this reason, shock occurs
when a finger is placed in a lamp socket.
Severity of the Shock
The severity of the shock received when a person becomes a part of an electrical circuit is affected by
three primary factors. These factors are:
1. the rate of flow of current through the body, measured in amperes
2. the path of the current through the body, and
3. the length of time the body is in the circuit
Remember that electric shock is no joke - for three reasons:
1. A shock, even a small one, is more harmful if it passes through the heart. Electrical leads should
be handled with one hand only, while the other is safely out of the way
2. Under certain conditions, electricity can produce a painful burn
3. A sudden, unexpected shock causes a fast reaction and the reaction can result in injury, either to
the person getting shocked, or a bystander.
WDU Page 2
POWER SYSTEM PROTECTION LABORATORY MANUAL
All students should be aware of elementary first aid and what to do if an accident occurs, either to them
or another student.
Few suggestions are:
DON’T ever turn power on until the circuit is checked.
DO be ready to turn the power off fast.
DO make connections with one hand.
DO turn the power off after every use.
DO be prepared ahead.
DO follow instructions.
Open and free wires shall be avoided before energizing the circuit.
Please check the voltage rating of any equipment before plugging into the table sockets.
Modification to the circuit may only be performed when the system is switched off.
After finishing the experiment, turn off all the supply and bring them back to zero reading before
dismantling the circuit.
Connect all the “PE” or ground connections present on any equipment to the “PE “connection of
the supply.
Push the emergency button “RED BUTTON” present on the experiment table/power supply in
case of any emergency or safety related events.
Lab Regulations:
Please adhere to the lab timings.
Safety shoes and clothing is strictly enforced for any activities in the lab
Keep good housekeeping while working in the lab and place the wires and other accessories at
their specified locations after finishing the work.
WDU Page 3
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 4
POWER SYSTEM PROTECTION LABORATORY MANUAL
For the present device the rated current is 1 A and may not be changed and calculate the rated power PN
of the device.
WDU Page 5
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 6
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 7
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 8
POWER SYSTEM PROTECTION LABORATORY MANUAL
C. Function
The incoming current from the main current transformer of the protected object is converted to a voltage
signal in proportion to the current via the input transformer and burden. The noise signals caused by
inductive and capacitive coupling are suppressed by an analog R-C filter circuit.
The analog voltage signals are fed to the A/D-converter of the microprocessor and transformed to digital
signals through Sample- and Hold- circuits. The measuring value detection takes with a sampling
frequency of 12 x fn, namely, a sampling rate of 1.66 ms for every measuring quantity at 50 Hz.
Measuring principle
Through multiplication of the actual current and voltage values p(t) = u(t) • i(t), the microprocessor
calculates the phase power. 12 instantaneous values are measured and recorded per cycle. Afterwards the
power value during one cycle is determined.
1 2𝜋
P= ∫ 𝑃(𝑡)𝑑𝑡
T 0
Consequently, the total three phase current is calculated from: Ptotal = P1 + P2 + P3
WDU Page 9
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 10
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 11
POWER SYSTEM PROTECTION LABORATORY MANUAL
Returning time
If DIP-switch 6 is in ON position, the returning time of P> and PR> is 40 ms. at the same time the tripping
values of tPR> and tP> are set to their minimum values irrespectively of their potentiometer setting.
b) Setting of the tripping values
The professional line units have the unique possibility of high accuracy fine adjustments. For this, two
potentiometers are used. The course setting potentiometer can be set in discrete steps of 5 % (or 20 %). A
second fine adjustment potentiometer is then used for continuously variable setting of the final 0 - 5 %
(or 0 - 20 %). Adding of the two values results in the precise tripping value.
Active power supervision
The tripping value can be set in the range from 1 - 120 % Pn with the aid of the potentiometer illustrated
on the following diagram.
Example:
A tripping value P> of 72 % Pn is to be set. The set value of the right potentiometer is just added to the
value of the coarse setting potentiometer. (The arrow of the coarse setting potentiometer must be inside
of the marked bar, otherwise no defined setting value).
WDU Page 12
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 13
POWER SYSTEM PROTECTION LABORATORY MANUAL
Set DIP-switch. DIP-switch no. 6 - 9 in position OFF. So that the returning time is set to 500 ms and
die tripping times can be set via the corresponding potentiometers in the range from 0 – 10 s. Set
the initialization value P> to 100% with the aid of the two corresponding potentiometers.
Set the time relay value to 0 via the corresponding potentiometers.
Experiment realization:
The setting value of the resistive load is 100% of the range and the three-phase transformer voltage value
is equal to 400V.
Reduce slowly the value of the resistive load, so that the consumption power rises and find out at which
value the relay trips (red LED P> or connect the acoustic indicator to the terminals 21 - 24).
Result
The relay trips at 690 W. This value corresponds (in the measuring accuracy) to the preset rated power
value 693 W (note, that the power meter measures in one phase and the display value have to be multiplied
by 3).
Experiment realization:
Repeat the experiment for the different setting values of P>:
Set P> [%] to: Current I [A] Read off P [W] P [%] to rated power
80 0.80 551 79.5
70 0.70 480 69.3
50 0.50 345 50.0
36 0.36 247 35.6
Table 3: Results of tripping value at different setting value of P> when v = 400V
Result:
For the setting value the relay trips in:
Ο no case
Ο certain cases
Ø all cases
Experiment realization:
Reduce the voltage of the three-phase transformer to 360 V and repeat the last measurements:
Set P> [%] to: Current I [A] Read off P [W] P [%] to rated power
80 0.89 555 80.0
70 0.79 490 70.7
50 0.56 348 50.2
36 0.40 248 35.8
Table 4: Results of tripping value at different setting value of P> when v = 360V
WDU Page 14
POWER SYSTEM PROTECTION LABORATORY MANUAL
Result:
For smaller voltages (decreasing values), the current values increase and the relay trips. The relay also
exactly trips at the preset power setting values, independently to the actual current level.
Experiment realization:
Invert the two terminals of the current input of the relay in order to change the power direction and
repeat randomly the measurement with several above values.
Result:
For the setting value the relay trips in:
Ø no case
Ο certain cases
Ο all cases
Experiment realization:
Change the power direction to the original direction and set the time delay to 6s via the
potentiometer tP>. Repeat the last experiment for the setting value 50% of the power P>.
Result
As expected the relay trips at the preset power value after a short time delay. By temporary exceeding of
the power setting value (here less than 6s), the relay do not trip. In practical applications, additional time
have to be included in the time delay adjustment to avoid tripping error by short time peak load (e.g.
motor starting).
3.2.4 Experiments with the relay as directional power relay
Objectives
To acquire knowledge about the behavior of the relay in its functioning as reverse power relay and
to study its reaction by different settings of parameters.
Keep the relay settings from the previous experiment. Set the initialization value for PR> with the aid of
both corresponding potentiometers to 30%.
Set the resistive load value to 100% and the three-phase transformer value to 400 V.
Experiment realization
Change the power direction by inverting both terminals of the current input of the relay.
Reduce slowly the value of the resistive load, so that the consumption power rises and determine at
which value the relay trips (red LED P> or acoustic indicator in the terminals 11 - 14).
Result
The relay trips at the value 210 W, which exactly corresponds to 30% of the rated power value (693W).
Experiment realization:
WDU Page 15
POWER SYSTEM PROTECTION LABORATORY MANUAL
Check the behavior of the relay at the setting value > 0 of the time delay. Set the value of the
potentiometer tPR> to 10s and repeat the last part of the experiment.
Result
The relay trips again at the preset power value after the determined time delay. By temporary time
exceeding of the power (here less than 10 s), the relay do not trip.
4. Experiments with 3 Phase Time Over/under voltage Relay
4.1 Introduction
The digital processing relay is a combination of a time over- and under voltage relay which can monitor
two, three and four-wire systems in low and medium voltage network. This protects, additional to
systems of power generation and distribution, consumers from high or from low voltages. Otherwise,
this is also adapted to supervise a phase sequence of the network. In three- phase networks, the
measurement can be carried out on the phase conductor voltage and on the star connection voltage.
Generally the relays cannot be used for short time peaks of voltage caused by lightening. Here, the
appropriate systems are the surge voltage arrester, which can in simple case be consisted of a spark
gap. The features of the Time over- and under voltage relay will be studied when connected to the
resistive load via a transformer in the mains. The experiment also could be carried out with a synchronous
generator which supply a load in isolated operation.
Equipment required
Amount Identification Number Equipment name
1 726 75 Three-Phase Supply Unit with FCCB
1 745 50 Three-Phase Transformer TL380KV
1 745 181 3 ~ Time Over/Under voltage relay
1 745 561 Power Circuit Breaker Module
1 727 230USB Multifunctional measuring instrument
1 727 421 Acoustic Continuity Tester
1 733 10 Resistive Load 1.0
1 313 033 Electronic Stop clock
1 726 256 Panel Frame-VT160, Three Level
1 500 851 Safety connecting Leads, 32 A, set of 32
1 500 852 Safety connecting Leads, yellow/green, set of 10
2 500 59 Safety bridging plugs, black, set of 10
1 500 591 Safety bridging plugs, yellow/green, set of 10
Table 5: Required Equipment for the experiments on the Three Phase Time Over/under voltage Relay
WDU Page 16
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 17
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 18
POWER SYSTEM PROTECTION LABORATORY MANUAL
Figure 13 : Connection three-wire system DIP-switch setting Δ Figure 14: Connection four-wire system
DIP-switch setting Y or Δ
a) Analog inputs
The analog input signals of AC voltages are connected to the protection device via terminals L1-L3 and N.
b) Auxiliary voltage supply
The unit relay can be supplied directly from the measuring quantity itself or by a secured auxiliary supply.
Therefore a DC or AC voltage must be used.
The unit relay has integrated wide range power supply. Voltages in the range from 19 - 55 V DC can be
applied at connection terminals A1 (L-) and A2 (L+).
WDU Page 19
POWER SYSTEM PROTECTION LABORATORY MANUAL
Terminals A1/A3 are to be used for voltages from 50 - 750 V DC or from 36 - 520 V AC (f = 100 - 480
Hz).
WDU Page 20
POWER SYSTEM PROTECTION LABORATORY MANUAL
Figure 16: Front plate of the Time Over- and under voltage Relay
The numbers in the control element of the device mean the following:
① LED to indicate the readiness for service (green)
② DIP-switch block
③ Test push button
④ LED indicator of the under voltage U< (red)
⑤ Setting of the under voltage tripping U<, 2 potentiometers
⑥ Time setting of the under voltage tripping tU<
⑦ LED indicator of the overvoltage U> (red)
⑧ Setting of the overvoltage tripping, 2 potentiometers
⑨ Time setting of the overvoltage tripping tU>
All operating elements needed for setting parameters are located on the front plate of the relay as well as
all display elements.
a) Setting of DIP-switches
The DIP-switch block on the front plate of the relay is used for adjustment of the nominal values and
setting of function parameters:
WDU Page 21
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 22
POWER SYSTEM PROTECTION LABORATORY MANUAL
If the phase-to-phase voltage is measured, a displacement of the neutral point will not be detected. Instead
of it the values of the three phase-to-phase voltages in the phase triangle will be detected.
The kind of connection Y or Δ is dependent on the item to be protected, i.e. a three phase motor (without
neutral) in a four wire system => select Δ.
Switching hysteresis
The switching hysteresis of both tripping relays can be adjusted with the aid of DIP switches 6 - 7 to 3, 6
or 10 % of the tripping values. As for the rated voltage, it has to be ensured that only one of the two DIP-
switches is switched on.
The following adjustments of the switching hysteresis for U> and U< are possible:
WDU Page 23
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 24
POWER SYSTEM PROTECTION LABORATORY MANUAL
Figure 20: Experiment assembly with Time Over- and under voltage Relay
Set the DIP-switch as shown in starting. To study the behavior of the relay by under voltage, the
initialization time has to be set to 110%. This value will not be reach in the present experiment so that
the overvoltage stage do not operate.
Set U< to the value 92%.The time delay value equates to 0 for the under voltage and the over voltage
stage.
First connect the summer to the terminals 11 and 12. The acoustic tester indicates the tripping of the
relay.
On the secondary side the VN supplies the three-phase transformer the voltage and the resistive load
equates to 100%, so that there are only a small current when the voltage supply is switching on. When
the resistive load is reduced the consumption voltage decreases and the relay trips at the under voltage.
Note, that it is important not to maintain the value of the current bigger than 1A for a long time
period to avoid overloading the three phase transformer.
Experiment realization:
WDU Page 25
POWER SYSTEM PROTECTION LABORATORY MANUAL
Increase slowly the current by reducing R until the under voltage relay trips. Afterward reduce the current
slowly until the relay drops out.
Read the initialization value and drop out value and compare those with the setting value.
Result
The relay trips at 369 V which value exactly corresponds to 92% of 400 V. This value is also equal to
the setting tripping value. This equates to 95% of 400 V and is equivalent to the setting tripping value
i.e. 97% of the chosen hysteresis of 3%.
Experiment realization:
Repeat the experiment with other settings (for example set initialization value of the under voltage relay
to 97% and the secondary voltage of the three phase transformer VN to +5%).
Result
In this case, the setting values also equate to the measuring values to operate the initialization and the
drop out of the relay.
Experiment realization:
Check the reaction of the time delay for the under voltage tripping time tU< equates to 2s and by
reducing for a short time the voltage with the aid of the resistive load.
As well, check if to the terminals L1, L2 and L3 a clockwise rotating field is applied when the DIP-
switch 4 is in the same time additionally on position ON.
The relay is as well appropriate to supervise single phase voltages. Disconnect the transformer terminals
on phases L2 and L3 to the relay and bridge instead the terminals L1, L2 and L3 on the relay input.
Result
In case of monitoring of a single voltage, the setting values also equate to the measured values for the
initialization and the drop out of the relay.
4.2.4 Experiments with the 3 ~ Time Over voltage Relay
Objectives
To acquire knowledge about the behavior of the relay in its functioning as overvoltage relay and
study its reaction by different settings of parameters.
Experiment realization:
In this part the behavior of the relay by appearing of overvoltage will be studied.
For this purpose, set the initialization value for U< to 80%. This value will not be reached and the case
of the under voltage stage will not be considered.
For U> choose the value 96%. The time delay 0 have to be set back for under voltage and the
overvoltage step. The acoustic tester is connected to the terminals 21 and 24.
WDU Page 26
POWER SYSTEM PROTECTION LABORATORY MANUAL
On the secondary side VN supplies the three-phase transformer and the resistive load is about 30%. Both
have to be adjusted in order to reach the current value 1A. Increase slowly the voltage by increasing R
until the relay trips.
Read the initialization and the drop out value and compare these with the setting values.
Result
The relay trips at 383 V. This value equates exactly to 96% von 400 V, i.e. this value is equivalent to
the setting tripping value. The drop out value is equal to 371 V. This corresponds to 93% of 400 V and is
equivalent to the setting tripping value i.e. 97% of the chosen hysteresis of 3%.
Repeat the experiment with other settings (for example, set initialization value of the overvoltage relay
to 100% and the secondary voltage of the three-phase transformer VN to +5%). Check also the reaction
of the relay by different time delay settings when he is connected to a single-phase voltage.
5. Experiments with 3 ~ Time Over/Under current Relay
5.1 Introduction
In systems for supplying electrical power, the most often disturbances are short circuit and overload faults.
Today low voltage systems are mostly be protected by fusible cut-outs against faults because of its low
prices.
In middle and high voltage systems the fusible cut-outs are no longer capable to interrupt the fault current.
Here overcurrent relays are appropriate for this purpose. They send a message in order to switch to the
corresponding power circuit breaker module when the setting threshold value are exceeded after a preset
time delay. There are different types of relays: those, which time delay is independently from the level
of the fault current and those, which time delay depends on characteristic of the fault current. The first
calls in abbr. IDMT-relay (independent time overcurrent protection) and the second in abbr. DMT-relay
(dependent time overcurrent). Nowadays the most existing relays can be separated in ‘dependent’ and
independent (according to the current level) by the consumers himself.
In the present experiment, such a relay will be studied when his is connected with a resistive load. The
resistive load is hooked up to the mains about a transformer.
WDU Page 27
POWER SYSTEM PROTECTION LABORATORY MANUAL
Equipment required
Required In Identification Equipment
Number Number
1 726 75 Three-Phase Supply Unit with FCCB
1 745 50 Three-Phase Transformer TL380KV
1 745 2311 3 ~ Time Over/Under current relay
1 745 561 Power Circuit Breaker Module
1 727 230USB Multifunctional measuring instrument
1 727 421 Acoustic Continuity Tester
1 733 10 Resistive Load 1.0
1 313 033 Electronic Stop clock
1 727 31 Moving Iron Meter 1 A
1 727 32 Moving Iron Meter 2.5 A
1 727 38 Moving Iron Meter 600 V
1 726 256 Panel Frame-VT160, Three Level
1 500 851 Safety connecting Leads, 32 A, set of 32
1 500 852 Safety connecting Leads, yellow/green, set of 10
2 500 59 Safety bridging plugs, black, set of 10
1 500 591 Safety bridging plugs, yellow/green, set of 10
Table 7: Required Equipment for the experiments on the Three Phase Time Over/under current Relay
5.2 Experiment procedure
5.2.1 Description of the 3 ~ Time Over/Under current Relay
WDU Page 28
POWER SYSTEM PROTECTION LABORATORY MANUAL
The digital overcurrent time relay can be used either as a definite time or as an inverse time overcurrent
protective. This means that its range of application is very broad; for example, the device can be
used as a selective overload and short-circuit protection facility for lines and consumers.
In both modes of operation – in definite time and inverse time overcurrent operation – in addition to the
overcurrent stage (T>) the device is also equipped with a so-called instantaneous overcurrent stage (I>>).
Standard peak currents arising during operation, for example during switch-on processes, thus do not
cause the relay to trip, whereas short-circuit currents with their very high values are switched off with
only a brief time delay.
The device measures the currents in all three phases of a three-phase system. If one or more currents
exceed the set value, excitation occurs and the relay trips after a time delay.
Operated values and time delays are in a wide range and can be preset with the aid of potentiometers. To
set the time delay by overcurrent stage and instantaneous overcurrent stage, two potentiometers are
available for this purpose. The range of the setting time for the overcurrent stage can additionally be
enlarged by a time factor of 10 or 100 with the aid of DIP-switches.
Additional DIP-switches serve to set the parameters of important functions like operating mode, for
example, as definite time or inverse time or to select the nominal frequency of 50 or 60 Hz. The
measurement inputs for the currents being monitored are designated 1S1 – 1S2, 2S1 – 2S2 and
3S1 – 3S2. Their nominal value IN amount to 1A each, whereby a continuous overload up to 4A is
possible.
The relay requires an auxiliary voltage (terminals A1 – A2) for its own operation. For this purpose the
built-in extended-range power supply unit provides either a DC voltage between 19 and 390 V or an AC
voltage between 36 and 275 V (40 up to 70 Hz). In the existing experiment the device is supplied with
an auxiliary voltage of 230 V AC.
In the case of starting the corresponding LED flashes while tripping causes the LED to remain
continuously on.
Command output is performed via one changeover contact in the case of overcurrent tripping (terminals
11,12, 14) and instantaneous overcurrent tripping (terminals 21, 22, 24). If the overcurrent tripping
and overcurrent instantaneous tripping are supposed to act jointly on a power circuit-breaker, the contacts
must be combined externally.
The relay is equipped with a test push button to check its operation. If this is kept pressed down for five
seconds, an internal hardware test takes place during which both tripping relays operate and the LED’s
indicating tripping light up.
A. Applications and features
WDU Page 29
POWER SYSTEM PROTECTION LABORATORY MANUAL
As an universal time overcurrent protection, it is the professional line generally used in radial and meshed
systems. Among other, it is applied as:
Selective overload and short-circuit protection relay for electric machines, lines and network
Load dependent connection and disconnection of consumers and electric power generators.
It is possible to select from the following tripping characteristics:
Definite time overcurrent protection (DMT)
Inverse time overcurrent protection (IDMT) with selectable tripping characteristics
- Normal Inverse
- Very Inverse
- Extremely Inverse
Furthermore, it can be employed as a back-up protection for differential and distance protection relays.
When compared to the conventional protection equipment all relays of the professional line reflect the
superiority of digital protection techniques with the following features:
High measuring accuracy by digital data processing
Fault indication via LEDs
Extremely wide operating ranges of the supply voltage by universal wide-range power supply
Very fine graded wide setting ranges
RMS measurement
Extremely short response time
Compact design by SMD-technology
B. Design
WDU Page 30
POWER SYSTEM PROTECTION LABORATORY MANUAL
a. Analog inputs
The analog input signals are connected to the protection device via terminals 1S1 - 1S2, 2S1 - 2S2 and
3S1 - 3S2.
b. Auxiliary voltage supply
The unit of relay needs a separate auxiliary voltage supply. Therefore a DC or AC voltage must be used.
The relay has an integrated wide range power supply. Voltages in the range from 19 - 390 V DC or 100 -
250V AC can be applied at connection terminals A1 and A2.
c. Contact positions
WDU Page 31
POWER SYSTEM PROTECTION LABORATORY MANUAL
are detected with a sampling frequency of 800 Hz (960 Hz), and a sampling rate of 1.25 ms (1.11 ms) for
each measurement (at 50 Hz (60 Hz)).
A pickup of a supervision circuit is indicated by flashing of the corresponding LED. At tripping the
flashing light changes to steady light.
Requirements for the main current transformers
The current transformers have to be rated in such a way, that a saturation should not occur within the
following operating current ranges:
Independent time overcurrent function K1 = 2
Inverse time overcurrent function K1 = 20
High-set function K1 = 20
K1 = Current factor related to set value with the current transformer not yet operating in the saturation
range.
Moreover, the current transformers have to be rated according to the maximum expected short circuit
currents of the network or the object to be protected.
The low consumption of the XI1, i.e. < 0.1 VA has a positive effect on the rating of the current
transformers. It implies that, if an electromechanical relay is replaced by XI1, a high accuracy limit factor
is automatically obtained by using the same current transformer.
WDU Page 32
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 33
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 34
POWER SYSTEM PROTECTION LABORATORY MANUAL
The professional line units have the unique possibility of high accuracy fine adjustments. For this, two
potentiometers are used. The course setting potentiometer can be set in discrete steps of 0.25 or 2.5 x In.
A second fine adjustment potentiometer is then used for continuously variable setting of the final. Adding
of the two values results in the precise tripping value.
Low set element
The tripping value can be set in the range from 0.5 - 2 x In with the aid of the potentiometer illustrated on
the following diagram.
Example:
A tripping value of 1.4 x In is to be set. The set value of the right potentiometer is just added to the value
of the coarse setting potentiometer. (The arrow of the coarse setting potentiometer must be inside of the
marked bar, otherwise no defined setting value).
WDU Page 35
POWER SYSTEM PROTECTION LABORATORY MANUAL
on the setting potentiometer for the time delay in the overcurrent stage is directly taken over (switch-
position “OFF”) or multiplied by the factor 10 (switch-position “ON”). The same correspondingly applies
for DIP switch 8, only here when the switch is set to “ON” the time value set by the potentiometer is
multiplied by a factor of 100. Only one of the two switches 7 or 8 may be set to “ON” at any given time.
By means of this setting combination time delays from 0 to 100 s may be set in the overcurrent stage.
The operate time of the current can be set to values of 0.5 – 2IN in the overcurrent stage with either a
coarse or a fine setting potentiometer (nominal current IN = 1A).
In the instantaneous overcurrent stage the selectable time delays lie between 0 and 2.5 s. The operate
time of the current can be set here to values of 1 – 15IN.
Below you find a copy of the characteristic including its possible setting ranges for the definite time over
current operation:
WDU Page 36
POWER SYSTEM PROTECTION LABORATORY MANUAL
used in practice as follows: “normal inverse”, “severely inverse” and “extremely inverse”. These
characteristics have been standardized according to IEC 255-4 or BS 142. Using DIP switch 1 the
characteristic is set to “normal inverse”, with DIP switch 2 the “severely inverse” characteristic is
selected and with DIP switch 3 the “extremely inverse” characteristic is set. Only one of the three
switches 1 to 3 may be set to “ON” at any given time.
In the experiments performed here only the “normal inverse” characteristic is made use of. (The same
experiment set-up can be used to test the operating response for the other two characteristics).
In the case of inverse time overcurrent operation the trip time is related to the so-called setting value IS
and not to the nominal current as in definite time overcurrent operation. This can be set to the values 0.5
– 2IN using the two potentiometers of the overcurrent stage (the nominal current IN amounts to 1 A as for
definite time overcurrent operation).
The trip time is still dependent on one other parameter, called the time multiplier. This is set with the aid
of the potentiometer for the time delay with overcurrent tripping. Similar to definite time operation the
setting range here can be expanded by a certain factor. Here this has the value 2 and can be set using
DIP-switch 7 (switch-position “ON”). When the switches set to “OFF” the factor has the default value
of 1. (DIP-switch 8 has no significance and must be set to the “OFF” setting). By means of this
combination the time multipliers can be set between 0.1 and 2. The trip times can be taken from the
corresponding diagram.
The overcurrent stage (I>) can also be blocked here with DIP-switch 4. The device then only trips
according to the set values of the instantaneous overcurrent stage. This demonstrates the same
characteristic as for operation as a definite time overcurrent relay.
The instantaneous overcurrent stage (I>>) can be blocked with DIP-switch 5 set to “ON”. The device then
only trips according to the set values of the overcurrent stage.
Furthermore, the mains frequency can be set between 5 Hz (setting “OFF”) and 60 Hz (setting “ON”)
using DIP-switch 6.
Tripping characteristics according to IEC 255-4 or BS 142:
Normal Inverse
0.14
t(s) = I 0.02
× tI> (s) >
( ) −1
I>
WDU Page 37
POWER SYSTEM PROTECTION LABORATORY MANUAL
100
10
t I> =
t[s]
2.0
1.5
1
1.0
0.8
0.6
0.5
0.4
0.3
0.2
0.1
0.1
1 2 3 4 5 678910 20
I/I S
WDU Page 38
POWER SYSTEM PROTECTION LABORATORY MANUAL
Extremely Inverse
80
t(s) = I 2
× tI> (s) >
( ) −1
I>
WDU Page 39
POWER SYSTEM PROTECTION LABORATORY MANUAL
practical cases the OFF command of the relay opens the power circuit-breaker module in order to protect
the load (or other components as for example lines) against over currents or short circuits.
According to the VDE (Verband Der Elektrotechnik) regulations, connect metal parts not under voltage-
carrying (e.g., case) to the protective earth (PE). The PE is determined exclusively for this function and
may not have to be connected in the circuit to the neutral point N. By any change in the experiment
assembly, the power circuit breaker module has always to be actuated before.
5.2.3 Experiment with the relay as IDMT-relay
Objectives
To study the functioning of the relay as IDMT-relay and its reaction for different settings.
Assemble the circuit as shown in the following figure.
WDU Page 40
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 41
POWER SYSTEM PROTECTION LABORATORY MANUAL
Repeat randomly the measurements for some other current setting ranges I>/IN and compare the desired
and actual value obtained for the tripping times. (The time setting t = 0 results in the operate time of the
relay and the power circuit-breaker module).
Plot the characteristic of the relay for the values I>/IN = 0.8 to 2.0 for different time delays.
Demonstrate that the tripping times are independent of the overcurrent’s magnitude.
WDU Page 42
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 43
POWER SYSTEM PROTECTION LABORATORY MANUAL
Table 16: measurement results of current with respect to different setting values when I>/IN = 1and tI> =0.2s
I>/IN = 1 and tI> = 1s
Set current (A) 1.0 1.5 2.0 2.5 3.0
Table 17: measurement results of current with respect to different setting values when I>/IN = 1and tI> =1s
Using the description of “normal inverse” the following approximate equation is specified in the
literature, which the tripping time as a function of the overcurrent:
0.14
t(s) = I 0.02
× tI> (s) >
( ) −1
I>
Using this equation randomly determine several tripping times and compare the computed values to the
measured ones. Plot the characteristic of the relay based on the measured tripping times of the first
experiment series.
WDU Page 44
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 45
POWER SYSTEM PROTECTION LABORATORY MANUAL
Before beginning the experiment the load resistor is set to 100%. If the power circuit breaker is now
switched on only a slight current flows which does not operate the relay. Slowly reduce the value of the
load resistor and observe the response of the relay.
Result
When reaching the set current value the relay is started and this is indicated by the flashing of the
overcurrent stage’s LED. After the set delay elapses (definite time overcurrent operation) the power
circuit breaker is opened. Thus there is no danger that a connected consumer will be overloaded.
To demonstrate the instantaneous overcurrent tripping the load resistor is set to a value of approx.
20% with the power circuit breaker switched off so that a higher current can then flow.
Switch on the instantaneous overcurrent stage on the relay (set DIP-switch 5 to “OFF”) and proceed
to carry out the following settings:
I>>/IN = 2, I>>/IN = 1(remains), tI>> = 0.5s.
What is the response demonstrated after the power circuit breaker module switched on
Result
AS expected the instantaneous overcurrent stage is started and the relay tripped after the set delay time of
0.5s elapsed. In practice the overcurrent protection facility is set so that the protective relay trips with
time delay at the maximum permissible current of the equipment being protected and instantaneous
for the lowest short-circuit current expected.
6. Experiments with 3 phase Transformer differential protection relay (Cat. No.
745 331)
6.1 Introduction
The relay is used for the selective protection of two-winding transformers. This involves a device which
is operated digitally and biased. The relay recognizes short-circuits between individual turns of a
winding, short-circuits between the primary and secondary winding as well as earth faults within the
transformer housing. Faults arising outside of the protective area do not lead to really tripping.
In real systems the relay receives its measurement values via one three-phase current transformer each
on the primary and the secondary side of the transformer under protection. Thus the transformer
procedures are also located within the protection area. In the experiments performed here the current
transformer can be dispensed with because the current flowing are in the order of 1 and can thus be
supplied directly to the relay.
WDU Page 46
POWER SYSTEM PROTECTION LABORATORY MANUAL
Equipment required
Required In Number Identification Number Equipment name
WDU Page 47
POWER SYSTEM PROTECTION LABORATORY MANUAL
The measurement inputs for the currents being monitored have been designated 1S1 – 1S2, 2S1 –
2S2 and 3S1 – 3S2 for the primary side (conventionally the high-voltage side of the transformer) as
well as 4S1 – 4S2, 5S1 – 5S2 and 6S1 – 6S2 for the secondary side (conventionally the low-voltage
side). Their nominal values amount to 1A each, whereby a continuous overload up to 4A is possible.
In order for the differential protection to be able to operate properly, the phase sequence of the
voltages must produce a clockwise rotating field. Another feature to be considered is that the default
setting of the relay used here has been set to star-star connection by the manufacturer for the
protection of the transformer. The power consumption of the measurement inputs (also referred to as
burden) lies under 0.1VA for the nominal current. The relay can be used in a frequency range from
50 – 60 Hz.
For operation it requires an auxiliary voltage (terminals A1 – A2). The built-in long-range power
supply permits for this either a DC voltage between 19 and 390 V or an AC voltage between with an
auxiliary voltage of 230 V AC.
The functional readiness of the relay is displayed by green LED. A successful starting is signaled by
the red LED with the designation “TRIP”. Furthermore one or more of the three LEDs L1, L2 or L3
light up on the phase affected. The other LED (designated D2 and shown with a transformer
symbol) is used in conjunction with the stabilization of the relay against magnetizing inrush. It lights
up when the relay is blocked briefly during switch on to avoid fault trips. Further the relay is required
with a reset button to acknowledge fault messages. The command output is performed via a
changeover contact (terminal 11, 12, and 14).
For the setting of the tripping characteristic the device has two stepping switches on the front panel
with a setting range of 5% to 42.5% respectively in 16 stages.
For current values Id lower than the nominal current (1A) the horizontal section of the characteristic
applies, while tripping of the relay is executed by the magnitude of the through-current. Tripping
occurs depending on the setting of the switch Id1, whose values are related to the nominal current.
The characteristic is suited for current values Id greater than the nominal current. Here the relay trips
in proportion to the through-current Is. This is identical to the through-current for currents higher than
the nominal.
The subsequent figure specifies the possible setting ranges for Id1 and Id2 and the tripping range of the
relay resulting from it. Bear in mind that the depiction is double-logarithmic scale.
WDU Page 48
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 49
POWER SYSTEM PROTECTION LABORATORY MANUAL
Adjustment to transformation ratio and connection groups without external interposing C.T.s
Two stage tripping characteristic
Galvanic insulation between all independent inputs
Self-supervision of stabilization circuits
Wide setting ranges
B. Design
WDU Page 50
POWER SYSTEM PROTECTION LABORATORY MANUAL
C. Working Principle
a. Operating principle of the differential protection
The fundamental operating principle of transformer differential protection is based on comparison of
the transformer primary and secondary winding currents. For an ideal transformer, having a 1:1 ratio
and neglecting magnetizing current, the currents entering and leaving the transformer must be equal.
During normal operation or when a short circuit has occurred outside the protected zone, the C.T.
secondary currents in the differential circuit neutralize each other. In case that a differential current
Id occurs, a fault in the transformer is detected.
WDU Page 51
POWER SYSTEM PROTECTION LABORATORY MANUAL
c. Transformer regulation steps
The XD1-T can universally be used i.e. also for regulating transformers with an adjustable
transformation ratio to stabilize voltage fluctuations of the supplying systems. Since, however, as a
result of vector group balance and transformation ratio balance the differential protection is adjusted
to the nominal transformation ratio of the transformer, an apparent differential current Id arises
proportionally to the flowing load current. Mal-operation of the protection is prevented by the load
proportional stabilizing current IS.
d. Working principle of the C.T. saturation detector SAT
With many transformer differential protection systems, relay instability may cause to trip if the main
current transformers saturate. In the transient condition of saturation the C.T.s on both ends of the
protected zones do not produce the correct secondary current according to the primary current. The
differential relay measures a differential current on the secondary C.T. side which is not present on
the primary side. Hence a nuisance tripping might occur.
Such transient phenomena causing C.T. saturation may occur due to:
Heavy through faults (external short circuit)
Starting of big motors
Magnetizing inrush currents of transformers
Internal faults
D. Operation and settings
All operating elements needed for setting parameters are located on the front plate of the XD1-T as
well as all display elements.
WDU Page 52
POWER SYSTEM PROTECTION LABORATORY MANUAL
Id1 represents the setting for the tripping area below nominal current. The Id1 setting relates to the
nominal current of the relay and is independent of the through current.
Id2 represents the setting for the tripping area above nominal current. The Id2 setting relates to the
"stabilizing current Is". Whereas Is is the current flowing through the protected zone. This biasing
area is important for external faults. The higher the current due to an external fault, the higher is the
biasing influence. On through faults, large differential currents may be produced by the transformer
tap changer or due to mismatching of the current transformers. The biased slope characteristic
prevents incorrect operation of the relay under these conditions.
With the additional module SAT the tripping characteristic changes to "coarse" in case of detected
transient phenomena, as explained above. The fixed tripping values for the coarse measurement are:
Id1 = 100 % IN
Id2 = 60 % Is
b. Setting recommendations
The tripping characteristic should be selected according to the known mismatch of the secondary
currents fed to the relay plus a safety margin of 10 to 15 %. This setting avoids mal-operation
caused by normal load conditions.
Mismatch of the currents may be produced by:
Ratio error and phase shifting of the C.T.s. E.g.: For protection C.T.s of 10P20 rating the
ratio error at nominal current is max. 3 %. At 20 times nominal current the ratio error
reaches 10 %.
Load tap changer (LTC). The automatic LTC may vary the ratio of the protected transformer
as much as ±10%. This causes a current mismatch of the same amount.
The deviation resulting from the transformer vector group should be compensated by the
internal converters and their burden.
Considering the example above, both settings Id1 and Id2 should be set to:
3% + 3% for C.T. errors
10% for transformer step changer
15% safety margin
Arrives to a setting of 31%. The nearest possible setting is 30%. Hence both DIP-switches should be
set to 30%. The pictures below show the DIP-switch setting as well as the actual tripping
characteristic.
WDU Page 53
POWER SYSTEM PROTECTION LABORATORY MANUAL
WDU Page 54
POWER SYSTEM PROTECTION LABORATORY MANUAL
To know the protection of a rotary transformer using a differential protection relay by design
a three-phase transformer double three- phase start connection.
Assemble the circuit according to the following figure.
Figure 44: Experiment assembly to investigate the response of a transformer differential protection
relay during single phase loads
The resistive load is set to a value of approx. 10%.
The tripping parameter Id1 of the relay is varied from 5% to 35% in steps of 10%; while the Id2
setting plays no role.
The voltage of the single-phase transformer is slowly increased beginning from 0V respectively,
until the relay closes. Afterwards the voltage is lowered until the relay releases again. The current
readings are entered into the Table below and used to form the reset ratio.
Setting value for Id1 (%) 5 15 25 35
Set current 1.73 A 0.087 0.26 0.433 0.606
Read off pick-up value (A) 0.09 0.29 0.45 0.63
Read off release value (A) 0.08 0.26 0.43 0.60
Resetting ratio 0.89 0.90 0.96 0.95
Table 19: The current readings with respective setting value of Id1
Randomly test the response of the relay when using other input transformers (terminals 2S1 – 2S2
and 3S1 – 3S2).
Result
WDU Page 55
POWER SYSTEM PROTECTION LABORATORY MANUAL
The protective shows an almost identical response at all of the inputs.
With any given input transformer used (e.g. 1S1 – 1S2) set a current value of approx. 1A (the position
of the switch for Id1 plays no role here) and then interrupt the current. Observe the response
of the relay when the current is switched back on again.
Result
During switch on a high current flows briefly (starting in-rush current). The relay detects this current
and is blocked for approx. 3s so that tripping does not occur. The corresponding LEDs light up for
the duration of the blocking.
The measurement of the power consumption is performed similar to other relays.
First determine the apparent power consumed power of the voltage being applied, i.e the current
flowing. Determine the consumed apparent power of a measurement circuit at a current of approx. 1
A flowing using the resistive load.
U = 26 mV, I = 1 A, S = 0.026 VA
To demonstrate the operation of the relay in a three-phase system, set up according to the following
figure in star connection and the rated voltage supplies the secondary side. The resistive load is
used as load, which is initially set to a value of approx. 20%. As a result the relay is very sensitive
against current differences on the primary and secondary side of the transformer. Switch the load on
and slowly reduce the current by increasing the value of the resistive load. What response is shown
by the relay?
Figure 45: Experiment assembly to protection of a rotary transformer using a differential protection
relay
WDU Page 56
POWER SYSTEM PROTECTION LABORATORY MANUAL
Result
At high current values the amount of magnetization current is relatively low thus no tripping is
caused. If the load current is reduced to a value of approx. 0.5A, the magnetization current is more
severe on the primary side. If the preset differential value is reached, the relay trips.
Now vary both tripping parameters to the value 32.5% and set the resistive load so that a current of
approx. 1A flows on the primary side of the transformer. Test the response of the relay for various
faults, which can be connected to the secondary side of the transformer: 1st short-circuit between
two phases, e.g. by connecting terminals 2U1 – 2V1.
Result
The relay immediately trips and thus protects the transformer. Due to the transient reaction there
are severe asymmetries in all three phases for a brief period of time causing all three LEDs to light
up.
WDU Page 57