What is a Circuit Breaker
4
What Do I Need From a Circuit breaker
5
Types of Circuit breakers
6
HV Circuit Breakers
Contact System
• Main Contacts
• Arching Contacts
Closed
10
Static Resistance Measurment(SRM)
Micro-Ohm
Meter
11
what about Arching Contacts ?
Main (30mohm)
Main
contact
Arching (1000mohm)
Total R = 30//1000 =
29.12 mohm
Arching Contact Closed
resistance Negligible
12
Dynamic Resistance Measurement
Doing Resistance Measurement during
Opening Operation
Arching (1000mohm)
Current
Resistance
Arching
Closed contacts only Opened
Very Difficult
to Find a
easy
number
How can I
make this
Better?
14
Travel Motion Test
Measurement Linear Angular
interface Type
Types of
Transducer
15
DRM + Travel Motion Test
Resistance curve
equal to voltage drop over breaker
[500 mΩ/div]
Movement starts
Travel curve
[10mm/div]
Small increase in resistance of
the main circuit when the main
contact fingers slide
Current curve
[100 A/div]
Arcing contact opens, current drops and
resistance is infinite.
22
18
Megger History in CB Testing
MA61 - 1994
DCM
Vibration testing – 2006
MA31 - 1988 1996
CABA - 1991 CABA Win - 1999
19
SDRM
STATIC / DYNAMIC RESISTANCE MEASUREMENT
ACCESSORY FOR EGIL/TM1700/TM1800
20
MOM2 , MOM200/600A ,
MOM690
DLRO100E/X/H ,
DLRO200/600
MJOLNER 200/600
21
Summery
22
Thank you
Any Questions
23