Professional Documents
Culture Documents
CURRENT TRANSFORMER
PRINCIPLE OF CURRENT TRANSFORMER
P1 P2
Ip
S1 S2
PROTECTIVE CT MEASURING CT
Large Cross sectional area Small cross sectional area
Cold rolled grain oriented silicon steel use Nickel iron Core
as magnetic
Accuracy is not important as metering CT CT must not faithfully transform the fault
current ( otherwise measuring instrument
will be damaged)
Errors 10% are tolerable for IDMT over Error of measuring CT should be
current relay 0.5% to 1%
Errors 3% to 5% are tolerable for
differential relay
EQUIPMENT REQUIRED FOR TESTING
INSULATION RESISTANCE
POLARITY TESTER
MULTIMETER
VARIAC
LOADING TRANSFORMER
PRIMARY INJUCTION SET
TONG TESTER
MECHANICAL CHECK AND VISUAL
INSPECTION
Verify name plate ratings in accordance with the
approved drawings
Inspect of physical damage / defect and mechanical
condition
Verify correct connection of transformer with the
system requirements
Verify clearance exist between primary and secondary
winding
Verify all shorting blocks are in correct position
Verify tightness of all secondary control cable
RECOMMENDED STANDARD TEST’S
PRIMARY VALUES
Permissible limit of IR value should be >1000 MΩ.
SECONDARY VALUES
Permissible limit of IR value should be >50 MΩ.
INSULATION RESISTANCE TEST
Direction of
H2 Secondary Current
Direction of P2
Primary Current
X1 IEEE Secondary
S1
IEC Polarity
Marks
Primary
Polarity IEEE H1
Marks IEC P1
POLARITY TEST :
BURDEN TEST :
The burden of a current transformer can be
defined as the total impedance in ohms on
the secondary output terminals. The total
burden is a combination of impedance offered by
watt-hour meter coils, relay current coils, contact
resistance, terminal blocks, wire resistance and
test switches used in the secondary loop.
BURDEN TEST :
ZT = RCT + RL + ZB
ZT = Total burden in ohms (vector summation of resistance and inductance
components)
RCT = CT secondary resistance in ohms @75 deg C
RL = Resistance of leads in ohms (Total loop distance) ZB = Device impedance
in ohms
EXAMPLE:
Decide Whether 5A,20VA CT is sufficient for following circuit
What is 5P 15?
“400-200/1 Amp 15 (or 30) VA 5P 15”(where 5P is the class current)
It means that when primary current 200 Amps flows, the secondary current
will be 1 amp and can feed a burden of 15 ohms (30ohms). When primary current
reaches 15 times( during fault conditions) it can be still feed the burden of 15 ohms and
the composite error will not exceed 5 percent in the transformations.
ACCURACY CLASS
For instance in a large station with long runs from the switch yard to the relay
panel the lead resistance may be as 6 ohms.
with 5A CTs the normal burden imposed by the 6 ohm leads Is
I²R = 5²X6 =150VA
5A CT 1A CT
Resistance of the Resistance of the = 5ohm
secondary of Secondary of 1A CT
5A CT = 0.2ohm
Lead resistance = 6.0 ohm Lead resistance = 6 ohm
Total = 6.2 ohm Total = 11 ohm
Total burden I²R = 5²X6 .2 =155VA Total burden = 1² x11=11
Maximum voltage = 20x IR Maximum voltage = 20xIR
= 20X5X6.2 = 20X1X11
• = 620 Volts = 220 Volts
CT OPEN CIRCUIT
Primary current sec voltage vpeak/amps comments
5 110 22
49 900 18.37 Slight distortion
167 1400 8.38 Marked distortion
567 1800 3.17
813 2220 2.73 Saturated CT
1967 2600 1.32 Making noise
2337 3600 1.54 Fully Saturated
wave form