Professional Documents
Culture Documents
• Measuring IT
– Used in conjunction with ammeter,
wattmeter etc.
2
Instrument Transformers: - IEC 60044
IEC 185 & 186
9Current Transformer (CT).
3
Standards Related
• IEC BS 60044
• IEC BS 60185
• IEC BS 60186
4
CT Topics:
Construction.
Primary & secondary currents
Burden.
Open circuit & short circuit.
Secondary earthing.
Magnetic equivalent CKT.
CT specification & errors for measuring and protection.
Polarity.
• Loading of 100/1 A & 100/5 A.
• More dangerous 100/1 or 100/5 A in case of OC.
5
Symbols
two coils with the same core double core current transformer
6
Typical Current Transformers
7
knee-point of excitation curve
8
CT Accuracy Classes - BS
Class Current Ratio Error Phase Displ
Measuring - M
0.1 ±0.25Æ0.1% ±10'Æ5'
0.2 ±0.5Æ0.2% ±20'Æ10'
0.5 ±1.0Æ0.5% ±60'Æ30'
1 ±2.0Æ1.0% ±120'Æ60'
3 ±3% Not spec.
5 ±5% Not spec.
Protection - P
5P ±1% ±60'
10P ±3% ±60' 9
VT Accuracy Classes - BS
Class Votgae Ratio Error Phase Displ
Measuring - M
0.1 ±0.1% ±5'
0.2 ±0.2% ± 10'
0.5 ±0.5% ±20'
1 ±1.0% ±40'
3 ±3% Not Specified
Protection - P
3P ±3% ±120'
6P ±6% ±240'
10
Knee Point
– Point on magnetisation curve, at which
an increase of 10% of secondary
voltage would increase the magnetising
current by 50%.
11
Typical specification for a 11 kV CT
9System voltage:11 kV
9 Insulation level voltage (ILV) : 12/28/75 kV
9 Ratio: 200/1/1 A
9 Core 1: 1A, metering, 15 VA/class 1
9 Core 2: 1 A, protection, 15 VA/5P10
9 Short time rating:20 kA for 1 second
15VA : Burden
5 : Accuracy Limit Factor ( Guaranteed error up to 5%)
P :Protection
10 : Times of secondary voltage
Isec =1 , V= 15/1 =15 Volts , 15V * 10 =150Volts
13
Special Dangers With Current Transformers
14
Open Circuit Voltage
• Open secondary causes Φs to go to zero.
15
CT
16
Current Injection test
18
Primary Injection Test
19
Secondary Injection test
21
Ratio check
22
Magnetization Curve
9 System voltage: 11 kV
9 Insulation level voltage (ILV) : 12 /28/75 kV
9 Number of phases: Three
9 Vector Group: Star / Star
Ratio: 11 kV/ 110 V
9 Burden: 100 VA
Accuracy: Class 0.5
9 Voltage Factor: 1.2 continuous and 1.5 for 30 seconds
With provision for fuse
25
Vector Group
26
Classification of Faults
1- Faults are classified into two major groups
• Balanced
• Unbalanced
2- Balanced Faults are the most severe. They involve all three phases possibly
connecting the fault point directly to ground (arc-resistance neglected) they
cause extremely severe fault currents and system disturbances.
30
Relay Generations
Electromechanical Relays Electronic Relays
9 Overshooting Errors
9 Need more maintenance and 9Overshooting Errors-No
calibration. 9Setting through dip-switches
9Wide functions in same relay
9 Limited functions
9 Setting through dials & taps
31
Digital Relays
32
The next generation of protective relays
9Past – electromechanical
9Future - Intelligent?
(ANN, ES based, GA, etc …)
33
Inverse Over current Characteristic with different
TSM
34
Inverse Over current Connection
35
Over Current Relay Setting
/SC =
36
Short circuit current (i.e. calculated short circuit current at point of
fault)
Setting of an Inverse Time Overcurrent Relay
1-Connect the secondary injection current set to the relay (
coil and contact)
2- Applying the normal rated current should not affect the
relay to trip and current injection counter will continue
counting without stopping if the relay is healthy.
3-At the specified time dial, apply number of multiples of
the rated currents and record the tripping time for each
value.
4-The resultant records to be compared with the actual
values from relay characteristic curves as in Figure
5-Chang the time dial and repeat steps 4 and 5 to verify the
characteristic curves.
37
Inverse Over current Characteristic with different TSM
38
Example for Setting of an Inverse Time Overcurrent Relay
It is required to determine the current and timing settings
on an OCIT relay to give a 1.35s delay with a short-circuit
current of 5 000A. Full-load current is 450A and the CT
ratio is 400/1A.
/
400/1 FL = 450 /
SC = 5000
A A
450
Plug setting = x 100 = 112.5 (use 125%) Desired Time Delay
400 1.35 s
Effective current = 400 x 1.25 = 500 A
5000
Relay operating line = = 10 R
500
39
Directional Over-current Relay
• If non-directional relays are used, two or more lines may be tripped when a
fault occurs.
•Relays R1, R3 and R5 will trip for faults in the direction of S1,
R5 will have the highest setting.
•
•Relays R2, R4 ad R6, will trip for faults in the direction of S2, R2 will have
the highest setting.
• Relays R3 and R6 will not see a fault between breakers 4 and 5, and relays
R4 and R5 will pickup before any relays (e.g. R2) that can see the fault.
41
Inverse Time Over-current Relay
42
Inverse Time Over-current Relay
• It is set to extremely current sensitive and with a very short operating time
• The ground relay (G) can be set for a much lower pickup than the phase
relays.
• It is useful on Transmission Networks e.g. for a transformer, to cover “low-
44
end” winding faults
Unrestricted E/F
45
Restricted E/F (REF) - ANSI 64
47
Differential Protection
No Internal Fault
48
Differential Protection
Internal Fault
49
Percentage Differential Relay
• Operating current of 2A
• The relay would not operate if it were set on the 40% slope.
50
• Various slopes can be selected.
Operating Characteristics Of
Percentage Differential Relay
51
Percentage Differential Protection
OperatingCurrent
Slope% = X 100
Averagerestraincurrent
52
9Voltage Balance
53
Connection of VT’s and CT’s for Protection Relaying
56
Relay Code Numbers (ANSI)
57
Relay Code Numbers (ANSI)
58
Distance Relays
This relay calculates impedance from the voltage and current applied to it
It closes when the impedance is below its set-point (pick-up) of the relay.
59
Distance Relays
It will thus wish to close its contacts when the voltage is low and/or the
current is high.
62
Distance Relays
• Whenever the relay “sees” an impedance of 6.48 ohms or less, the relay
will operate.
• For normal load currents, the impedance seen by the relay will be too
high to cause it to operate.
63
Distance Relays
• Zone 1 of relay 1 is set with a reach of 90% of line A and trips the
breaker instantaneously.
It looks like an instantaneous over-current relay for all faults
within its range.
64
Distance Relays
• If a fault occurs in the middle 80% of the line, both relays will see a
zone 1 fault and trip instantaneously.
• The max. trip time delay allowed On all but minor sub-transmission and
distribution systems is 300 m. seconds
•This scheme uses the signals sent over the communication channel
to compare the phase angles of the currents at either end of the line.
• For an internal fault (at A), the currents at the busses are 180
degrees out of phase,
• For an external fault (at B), the two currents are almost in phase.
71
Pilot Wire Relaying
• The pilot wire relay is often used for protecting short lines ( <= 15 Km ).
72
Pilot Wire Relaying
•Over-current relays can not be used , the magnitude of fault current for a
fault on the protected line section and for faults on adjacent sections is not
much different.
• Distance relays can not be used where the accuracy in measuring the line
impedance (or distance) might be plus or minus a few kM.; this is sufficient
for a 40 to 100 kM line, but not for a line shorter than about 15 kM.
73
Pilot Wire Relaying
• If a pilot wire becomes open circuited the relay will, however, trip for an
internal or external fault.
• In order to assure that the relay will not trip for load current with an open-
circuited pilot wire, the relay pickup is set above the maximum anticipated
load current. 74
Pilot Wire Relaying
• If the pilot wire becomes shorted, one or both relays may be completely
disabled.
• It will not be able to discriminate between internal and external faults, and
will operate for both types of faults.
•A pilot wire is usually buried with the utility cable. In some cases the 75
circuit is rented from the local Telephone company.
Co-ordination procedure
The data required for a relay setting study are:
• The maximum and minimum values of short circuit currents that are
expected to flow through each protective device.
84
System Architecture - Busbar Protection Relay
85
Bus Zone Protection scheme - protecting double
Bus-bar with transfer bus 86
Sample of the functions implemented in relays can be split into five
main elements:
1. Operating system
2. System services software,
3. Platform software,
4. Communication software,
87
5. Protection and control software.