PERCENTAGE BIASED TRANSFORMER

DIFFERENTIAL RELAY

87
MD32-TM m Three-phase percentage biased differential relay
for two-winding transformers.
dA>

PROG/
I.R.F.
dB>

2H>
dC>

5H> BLOCK
INPUT

m Automatic correction of CTs mismatch and dA50.00n


Transformer Vector Group.
N80 -R0 m Two differential current levels.
nd th
m 2 and 5 harmonic adjustable restraint levels.
M-LINE MODE SELECT +

MULTIFUNCTION
m Programmable percentage bias curve. TRANSFORMER
DIFFERENTIAL
_

m Oscillographic recording. RELAY TYPE


MD32-TM
PROG.

m Modbus Communication Protocol.

M
ENTER/RESET

LINE

Three-phase percentage biased differential protection relay for 2 winding transformers or 3 winding with
only one source of supply.

The relay measures the incoming currents and operates the CT ratio and Power Transformer vector
group compensation without the need of using interposing CTs.

Real Time Measurements = IdA-IdB-IdC-Ido - I1A-I1B-I1C - I2A-I2B-I2C - IdIIA-IdIIB-IdIIC - IdVA-IdVB-IdVC


Maximum Demand and Inrush Recording = IdA-IdB-IdC-Ido - I1A-I1B-I1C - I2A-I2B-I2C - IdIIA-IdIIB-IdIIC - IdVA-IdVB-IdVC

Programmable Input Quantities


Fn = System frequency : (50 - 60)Hz
1In = Rated primary current of phase CTs HV side : (1 - 9999) A, step 1A
2In = Rated primary current of phase CTs LV side : (1 - 9999) A, step 1A
1V = Rated primary voltage of Transformer HV side : (0.2 - 380)kV, step 0.01kV
2V = Rated primary voltage of Transformer LV side : (0.2 - 380)kV, step 0.01kV
a = Selection of Transformer's vector group.
Connection Diagram

MS-SCE2080-R0

1/5
MD32-TM M N80-R0

1 - F87T : Low-set Phase Differential


Current setting range : d> = (0.1 - 0.5)In, step 0.01In

Instantaneous output : 0.03s

Bias percentage : R = (10 - 50)%, step 1%

2nd Harmonic restraint level : 2H = (0.1 - 0.3)Id, step 0.01Id

5th Harmonic restraint level : 5H = (0.2 - 0.4)Id, step 0.01Id

Time during which harmonic restraint level can be lowered at transformer energisation: tH = (0.05 - 90)s, step 0.01s

2nd Harmonic restraint level reduction during tH : R2H = (0.5 - 1)2H, step 0.01

5th Harmonic restraint level reduction during tH : R5H = (0.5 - 1)5H, step 0.01

2 - F87T : High-set Phase Differential


Current setting range : d>> = (2 - 20)In, step 0.01In

Detection time : 6ms < t < 20ms

Peak current detection with DC offset restraint.

Digital Inputs
B1 = Operation block input

B2 = Harmonic restraint's reduction

B3 = Oscillographic record external trigger

D Id I1 + I2
R % = 100 IR =
D IR 2
Is/In 4

18 Is Id
=
In In
3
2
DlR Dld Is Id I R%
DlR
= + ( R - 0,5)
In In In 100
R
1 1 2
Dld Is Id 2R% IR
ld/In
= +
In In 100
+ ( - 2,5)
In
d> IR/In
0
0,5 1 2 2,5 3 Is
Is= Effective relays operation differential current In
@ 18
Id= Relay set differential current = [d>]
IR= Relays through current

2/5
MD32-TM M N80-R0

2 Module - Overall Dimensions (mm)

PROTECTION
DEGREE IP44
(IP54 on request)
164

135

134
2 195
213
PANEL CUT-OUT
115x137 (LxH) 225

3/5
MD32-TM M N80-R0

Overall Dimensions - Multi-Modules (mm)

51

135
164

32 + (n x 51) 2 195
213

9 4 + (n x 51) 225

PROTECTION
DEGREE IP44
(IP54 on request)

PANEL CUT-OUT
(11+(n x 51)) x 137 (LxH)

Overall Dimensions - Rack 19- 3U (mm)

51
133
57
7

10.5 206
75+(n+51) 232

42+(n+51)

Double and single module relay


can be anyhow combined in the
same 19" 3U Rack Panel up to
a total of 8 modules

4/5
ELECTRICAL CHARACTERISTICS MD32-TM M N80-R0

APPROVAL : CE
REFERENCE STANDARDS IEC 60255 - CE Directive - EN/IEC61000 - IEEE C37 - BSI
Dielectric test voltage IEC 60255-5 2kV, 50/60Hz, 1 min.
Impulse test voltage IEC 60255-5 5kV (c.m.), 2 kV (d.m.) - 1,2/50ms
Insulation resistance >100 M

Environmental Std. Ref. (IEC 68-2-1 - 68-2-2 - 68-2-33)


Operation ambient
Environmental Std.temperature
Ref. (IEC 68-2-1 - 68-2-2 -10C / +55C
- 68-2-33)
Storage temperature -25C / +70C
Environmental testing (Cold) IEC60068-2-1
(Dry heat) IEC60068-2-2
(Change of temperature) IEC60068-2-14
(Damp heat, steady state) IEC60068-2-78 IEC68-2-3 RH 93% Without Condensing 40C

CE EMC Compatibility (EN61000-6-2 - EN61000-6-4 - EN50263)--


Electromagnetic radiated and conducted emission EN55011 Industrial Enviroment

Radiated electromagnetic field immunity test IEC61000-4-3 level 3 80-2000MHz10V/m


ENV50204 900MHz/200Hz 10V/m

Conducted disturbances immunity test IEC61000-4-6 level 3 0.15-80MHz10V

Electrostatic discharge test IEC61000-4-2 level 3 6kV contact / 8kV air

Power frequency magnetic test IEC61000-4-8 1000A/m, 50/60Hz

Pulse magnetic field IEC61000-4-9 1000A/m, 8/20ms

Damped oscillatory magnetic field IEC61000-4-10 100A/m, 0.1-1MHz

Immunity to conducted common mode disturbance 0/150KHz IEC61000-4-16 level 4

Electrical fast transient/burst IEC61000-4-4 level 4 2kV, 5kHz

HF disturbance test with damped oscillatory wave IEC60255-22-1 class 3 400pps, 2.5kV (m.c.), 1kV (d.m.)
(1MHz burst test)

Oscillatory waves (Ring waves) IEC61000-4-12 level 4 4kV(c.m.), 2kV(d.m.)

Surge immunity test IEC61000-4-5 level 4 2kV(c.m.), 1kV(d.m.)

Voltage interruptions IEC60255-4-11 50ms

Resistance to vibration and shocks IEC60255-21-1 - IEC60255-21-2

Typical Characteristics
Accuracy at reference value of influencing factors 2% In for measurement
2% +/- 10ms for times

Rated Current In = 1 or 5A

Current overload 200 A for 1 sec; 10A continuos

Burden on current inputs Phase : 0.01VA at In = 1A; 0.2VA at In = 5A


Neutral : 0.015VA at In = 1A ; 0.35VA at In = 5A

Average power supply consumption 8.5 VA

Output relays rating 5 A; Vn = 380 V


A.C. resistive switching = 1100W (380V max)
make = 30 A (peak) 0.5 sec.
break = 0.3 A, 110 Vcc,
L/R = 40 ms (100.000 op.)

via Alberelle 56/58, 20089 Rozzano, Milano (Italy)


Tel. +3902575731 - Fax +390257510940 / http://www.microelettrica.com - sales.relays@microelettrica.com
The performances and the characteristics reported in this catalogue are not binding and can modified at any moment without notice

5/5