CALCULATION
Revisions report:
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 3/13
TABLE OF CONTENT
1. INTRODUCTION ................................................................................................................................................................. 4
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 4/13
1. INTRODUCTION
Downstream General Directorate (DGD), one of Sudanese Petroleum Corporation (SPC) directorates,
has authorization & holding rights for the establishment and development of the petroleum sector
infrastructure and facilities in Sudan, therefore and as a part of its strategic plan, that includes the
development of petroleum products transportation pipelines and distribution network, SPC intends to
install a new 12" multiproduct pipeline connecting Elgaily area with Madani strategic storage depots.
Whereas SPPC, one of SPC subsidiaries, is the sale custodian of MOP/SPC’s petroleum products
pipelines, therefore it has been awarded the contract of the aforesaid project; being EPCC of Khartoum –
Madani Petroleum Products pipeline project (KMPP).
The Pipeline shall consist of 12", 220 km long multiproduct transport Pipeline from Alrawyan Station at
Khartoum to Madani Storage Terminal Station at Madani City. The facilities will have provisions for the
future connection of branch connection with 10” block valves with blind flanges at Suba and Aljinid areas
in addition to 12" Midpoint intermediate station (valve + Booster station future Tie-in point).
The new petroleum products pipeline shall be initially designed to operate at maximum allowable capacity
using the existing main pumps, currently feeding Alshagara and Port Sudan pipelines, and with future
provision for expansion to a maximum design capacity that could be achieved by an intermediate pumping
station.
1.2 SCOPE
This document cover the calculation for earthing and lightning protection systems for: KHARTOUM-
MADANI PETROLEUM PRODUCTS PIPELINE Project.
1.3.1 DEFINITIONS
For the purpose of this document the following definitions shall apply:
Supplier/ Vendor: The party (s) which manufactures and/or supplies equipments, and/or
services to perform the duties specified.
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 5/13
1.3.2 ABBREVIATIONS
All electrical systems shall conform to the latest editions and supplements of the appropriate standards,
codes and regulations. Generally, electrical equipment will be designed, manufactured, tested and installed
according to relevant IEC standards.
The choice of cable belt grounding will meet the technical specification of the project. The determination
of conductor cross sections will be based on rules of the following international codes:
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 6/13
3. REFERENCES DOCUMENT
4. DESIGN CONDITIONS
The entire electrical system appropriate to environmental influences and climatic conditions. In particular,
cable grounding should ensure the safety of persons and protection of equipment during electrical faults
and lightning strikes, and the functioning of the devices.
The minimum cross-sectional area of the earthing conductor is given by the following formula:
I rm s
S t
K
Where:
I: value of fault current for a fault of negligible impedance, which can flow through the protective device
in amperes
I cc
I rms 13.33KA
3
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 7/13
13333 .33
S 1 58.479 mm²
228
Conclusion: The minimum cross-sectional area of the earthing conductor is 58.478 mm²; section to use is
made with 70 mm² bare copper.
For the determination of resistance of the earthing conductor, to be carried by a bare copper wire 95 mm²
sections, we use the following formula:
1 1 1
RC 1
L 20 A 1 h 20 / A
Where:
Rc : loop resistance in Ohm (Ω).
L : the total length of the protective conductor in meters (m).
A : Area covered by the earth electrodes
ξ : Soil resistivity
h : depth of the earth electrodes
1 1 1
R C 22.85 1 0,05 1
4294 20 * 56949 1 0,8 20 / 56949
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 8/13
7.1 GENERAL 0
The lightning protection system will be considered for new electrical substations, for tanks and others
structures.
The electrical substation will be protected against lightning in accordance with standard NFPA 780.
The protection of structures and steel structures against the effects of lightning will be considered by their
grounding in accordance with current regulations (The standard NFPA.780).
We refer in our protective system calculation against the thunderbolt at norm NFPA.780 .This system is
constituted of several facilities.
Early Streamer Emission (ESE) protection system is composed of a tip captrice, a device of
priming and a stem support on which are a system of connection of the coming down conductor
to the earth. To know that Early Streamer Emission (ESE) protection system must be situated at
least 2m over the top of zone that he protects.
A joint of control by conductor of coming down.
One or several conductor of coming down according to the position of Early Streamer Emission
(ESE) protection system.
A hold of earth lightning conductor.
For the determination of the protective level to satisfy as well as the protective radius to consider, a
calculation is established according to NFPA 780, the density of thunderbolt to ground (Ng) is considered
equal to (1) impact/year/Km² (superior limit of the average), seen localization and the topology of the
site.
We refer in our calculation to the norm NFPA 780. All undefined parameter can be found in this
reference norm.
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 9/13
The protective radius R for Early Streamer Emission (ESE) protection system is determined as follow:
Nc = 5.5*10-3/C; where C =C2*C3*C4*C5: see table n°B5, B6, B7, B8 for suitable value
Nd = Ngmax*Ae*C1*10-6
Ngmax = 2*Ng = Nk/10
According to the value of E we determine the value of D as indicates the table B9:
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 10/13
There are two areas to protect, each with its own lightning protection systems:
Zone A: zone contain Electrical and control room
Zone B : zone of tanks and others structures
We refer at norm NFPA780; certain types of structures used for the storage of liquids that can produce
the flammable vapours or used to store flammable gases are essentially self-protecting against damage
from lightning strokes and shall need no additional protection.
Ae = L*l + 6*H (L + l) + 9 π H²
H= 11.4 m
l = 13.6 m
L = 19.4 m
Considering the approximate dimensions for electrical and control building is about 19.4 m x 13.6 m x
11.4 m
Ae = 6193.71 m²
Nc = 5.5*10-3/C;
Nc =0.0055
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 12/13
Where considering the height of the electrical and control building is about 11.4 m, we confirm strongly
that the total height of electrical and control building equipped with of Early Streamer Emission (ESE)
lightning protection system is less than 20 m.
Ae = 9.π.H²
H = 20 m
Ae = 11304 m²
7.3.2.3 FREQUENCY FORESEEN OF DIRECT STROKE THUNDERBOLT ON THE STRUCTURE ND
Nd = 0.022608
Nc = 5.5*10-3/C;
Nc =0.0055
002/AR10/16 11/16
CALCULATION FOR EARTHING AND LIGHTNING NO. KMPP-06-ELE-CA-004
Rev. 0
PROTECTION SYSTEMS – TERMINAL STATION
PAGE: 13/13
Where considering the height of the lighting tower is about 18 m, we confirm strongly that the total height
of lighting Tower 3 equipped with of Early Streamer Emission (ESE) lightning protection system is about
20 m.