System of
Air Circuit Breakers
UW2-40H
4 Pole 100%N
4000 A 12 kV
Ue Ics = Icu
:
400 / 440 V 80 kA
:
500 / 550 V 70 kA
660 / 690 V 55 kA
Icw 80 kA 1.0 s
80 kA
50 kA 3.0 s
UW1-25H
4 Pole 100%N
2500 A 12 kV
Ue Ics = Icu
:
400 / 440 V 80 kA
500 / 550 V 65 kA
660 / 690 V 55 kA
I =
Icw 80 kA 1.0 s
44 kA 3.0 s
UW1-16N
3 Pole 100%N
1600 A 12 kV
Ue Ics = Icu
400 / 440 V 50 kA
500 / 550 V 42 kA
660 / 690 V 36 kA
Icw 50 kA 1.0 s
26 kA 3.0 s
Sr.No.:
SYSTEM OF
AIR CIRCUIT BREAKER
Version : Fr1 3P EDO
Rating : 1600A
Cat. No. :
Serial No. :
Before Unpacking,
A) Inspect the carton for any damage. In case of visible damage to the carton, contact nearest L&T
branch office before unpacking.
B) Verify the breaker version and rating written on the carton with your order.
Weights:
Before proceeding with unpacking, it is important to know the gross weight of the breaker for proper
selection of handling equipment.
Approx. Gross Weight of breaker with packing , adaptors & accessories (kg)
Rating Specification Parameters
Frame I II III
Version N S H NN08*/D10*/S H S H N/S N08/N10/H N S N08/N10/H S H N08*/H V H V
Rated Uninterrupted current at 50deg.C In (A) 400-1600 2000 2500 400 - 2500 3200 4000 400-5000 6300#
Fixed 3P 60 62 69 64 64 69 69 69 76 83 83 83 83 83 83 130 130 138
138
Weight ACB 4P (100%N) 73 76 85 79 79 85 85 85 120 132 132 132 132 132 143 143
132 170 170
kg 3P 87 91 103 94 98 103 103 103 113 125 125 125 125 136 136 198 198 227 227
Drawout
ACB 4P (100%N) 104 109 127 112 115 127 127 127 168 181 181 181 181 195 195 248 248 285 285
50% N
Rating Specification Parameters
Frame I II III
Version N S H S H N S H S H H V
Rated Uninterrupted current at 50deg.C In (A) 400-2000 2500 400 - 3200 4000 3200 - 5000
Weight Fixed 4P (50% N) 79 79 85 85 132 132 132 132 132 137 137
kg D/O 4P (50% N) 112 115 127 127 181 181 181 195 195 223 223
200% N
Rating Specification Parameters
Frame I II III
Version N S S H S H S H
Rated Uninterrupted current at 50deg.C In (A) 400 -1250 1600 2000 2000 - 2500
Weight Fixed 4P (200% N) 85 85 132 132 132 132 123 123
kg D/O 4P (200% N) 127 127 181 181 195 195 185 185
# 40 deg C
* N08 : In Frame-1 available from 400-2000A, In Frame-3, available upto 4000A
Note: All weights are with Vertical configuration of Cradle adaptors
Step 1: Cut & remove the straps Step 2: Lift the carton and remove any accessories taped to the
breaker or kept loose on the palette.
Step 3: Remove Breaker mounting nuts (8 Nos.) as indicated by arrows from both left and right sides
Step 1: Cut & remove the straps Step 2: Lift the carton and remove any accessories taped to the
breaker or kept loose on the palette.
Step 3: Remove Transportation Cushion Step 4: Rack-out the breaker & remove breaker from cradle (Details in Section 2.3)
Step 5: Remove Cradle fixing bracket and nuts 1 and 2 (8 Nos.) as shown below
from both left and right sides
Ensure that no loose hardwares are left out in the cradle
2
1
12 O UW2-25N 29a
29k 4 Pole 100%N
I 29b
Ue
2500 A 12 kV
Ics = Icu
29c
400 / 440 V 50 kA
UW2 -25N 29h 500 / 550 V 42 kA 29g
DISCHARGED 4 Pole 100%N 660 / 690 V 36 kA
2500 A 12 kV
50 kA 1.0 s
13 Icw
I = Icu
Ue cs
400 / 440 V
500 / 550 V
660 / 690 V
50 kA
42 kA
36 kA
26 kA 3.0 s 29j
CHARGED
Icw 50 kA 1.0 s
26 kA 3.0 s
29d
29e
29m 29f
29l
Charging Device
240V~,240V
TEST
DISCONNECTED
15
ocations
25 Withdrawal Rails
ation 26 Door Racking Interlock
15 Racking Handle 27 Breaker Pull-out Handle
16 Smart Racking Shutter 34 Guide for
16
For D/O Breakers remove the Transportation
Cushion (2 Nos.) & it’s instruction label,before
doing racking operation of the breaker. Remove
Remove Transportation Cushion
Caution Flap
Keeping OFF button (11a) pressed, open the Racking Shutter (16). In case
Breaker is out of the panel or the panel door is open, gently press Racking
Interlock (26) to defeat it.
Insert the racking handle &
Note: Once racking shutter is opened, the breaker can not be closed, even by
rotate anti-clockwise
Note: After removing the racking handle (15), the racking shutter
Take out the handle automatically recloses only in distinct ‘Connected’ / ‘Test’ and
‘Disconnected’ positions (17). Hence, Breaker cannot be closed in
CONNECTED
any Intermediate positions to ensure User safety.
Excessive, forceful Racking-out beyond
DISCONNECTED
CAUTION Disconnected position may lead to Product damage.
Up to 690V AC
FRAME I II III
Rating specific parameters Neutral Unit Symbol
Rated uninterrupted Current at 50 deg. C A In 400-1600 2000 2500 400-2500 3200 4000 400-5000 6300**
Version N S H N S H S H N S H N S H S H H V H V
Rated Ultimate 415/440V ~ 50/60 Hz kA 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
S.C. Breaking 500/550V ~ 50/60 Hz kA Icu 42 55 65 42 55 65 55 65 42 55 70 42 55 70 55 70 70 85 70 85
Capacity 660/690V ~ 50/60 Hz kA 36 50 55 36 50 55 50 55 36 50 55 36 50 55 50 55 65 75 65 75
Rated Service 415/440V ~ 50/60 Hz
S.C. Breaking 500/550V ~ 50/60 Hz kA Ics 100% Icu
Capacity 660/690V ~ 50/60 Hz
Rated Short 0.5 sec kA 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
Time Withstand 1.0 sec kA Icw 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
Capacity 3.0 sec kA 26 36 44 26 36 44 36 44 26 44 50 26 44 50 44 50 65 75 65 75
415/440V ~ 50/60 Hz kA 105 143 176 105 143 176 143 176 105 143 176 105 143 176 143 176 176 220 176 220
Rated S.C
500/550V ~ 50/60 Hz kA Icm 88 121 143 88 121 143 121 143 88 121 154 88 121 154 121 154 154 187 154 187
Making Capacity
660/690V ~ 50/60 Hz kA 76 105 121 76 105 121 105 121 76 110 121 76 110 121 110 121 143 165 143 165
Break Time 25
ms
Closing time 60
Width - 3P mm W 347 447 647
Fixed Width - 4P 100% mm W 447 581 847
ACB Depth mm D 324 324 334
Height mm H 430
Dimensions
Width - 3P mm W 347 447 647
Drawout Width - 4P 100% mm W 447 581 847
ACB Depth mm D 421 421 431
Height mm H 433
Mechanical Life - With Maintenance no. of cycles 20000 15000 10000
Frequency of Operations - Mechanical cycles/hour 60
Electrical Life - Without Maintenance# no. of cycles 10000 5000 5000 5000 2000
Frequency of Operations - Electrical cycles/hour 40 20
Pitch I/C - O/G mm 105
Ph-Ph mm 100 133 200
Pitch
Ph-N 100% mm 100 133 200
Fixed 3P kg 60 62 69 67 64 69 69 69 76 76 83 83 83 83 83 83 130 130 138 138
Gross Weight ACB 4P 100% kg 73 76 85 79 79 85 85 85 120 120 132 132 132 132 132 132 143 143 170 170
(Max.) Drawout 3P kg 87 91 103 94 98 103 103 103 113 113 125 125 125 125 136 136 198 198 227 227
ACB 4P 100% kg 104 109 127 112 115 127 127 127 168 168 181 181 181 181 195 195 248 248 285 285
Break Time 25
ms
Closing time 60
Width - 3P mm W 347 447 647
50%N
R a t ing S pe c if ic a t io n P a ra m e t e rs S ym bo l
Frame I II III
Versio n N S H S/H N/S/H S/H H/V
Rated Uninterrupted Current at 50deg. C In (A ) 400-2000 2500 400-3200 4000 3200-5000
Fixed Width 4P 50% W (mm) 447 447 581 581 747
Dimensio ns
D/O Width 4P 50% W (mm) 447 447 581 581 747
P itch P h-N 50% N mm 100 100 133.3 133.3 150
Fixed 4P 50% N kg 79 79 85 85 132 132 137
Weight
D/O 4P 50% N kg 112 115 127 127 181 195 223
200%N
Frame I II III
Versio n N&S S&H S&H H
Rated Uninterrupted Current at 50deg. C In (A ) 400-1250 1600 2000 2000-2500
Fixed A CB 200% W (mm) 447 581 581 647
Dimensio ns
Drawo ut A CB 200% W (mm) 447 581 581 647
P itch P h-N 200% N mm 100 133.3 133.3 200
Fixed 4P 200% N kg 85 132 132 123
Weight
D/O 4P 200% N kg 127 181 195 185
300 min
300 min
VERSION DIM. B
400-2000A N, N08, D10 &S 326
400-2000A H 324
2500A S & H 324
142
C
N, S, H 45 70
N08/D10 300 300
DISCONNECTED
25.5
421
(250) (47.5)
(62.4)
(280)
300 min
300 min
VERSION DIM. B
C
N, S, H 45 70
N08/D10 300 300
DISCONNECTED
25.5
421
(280)
300 min
300 min
VERSION DIM. B
N, S, H 45 70
C
N08 300 300
DISCONNECTED
25.5
421
(280)
300 min
300 min
VERSION DIM. B
N, S, H 45 70
C
N08, N10 300 300
DISCONNECTED
(280)
These 3 supports
are must
300 min
300 min
C
C
DIM. C DIM. C*
VERSION (min.)
(min.)
H, V 45 70
N08 300 300
DISCONNECTED
35.5
431
(100) (250) (47.5)
(49.5)
(62.4)
These 3 supports
(250)
(280)
are must
300 min
300 min
C
DIM. C DIM. C*
VERSION (min.) (min.)
H, V 45 70
N08 300 300
DISCON-
NECTED
35.5
431
(49.5) (200) (100) (250) (47.5)
(62.4)
These 4 supports
are must
(250)
(280)
Vertical termination
Horizontal
recommended
Vertical
termination
recommended
Width : 65mm Width : 98mm Width : 100mm Width : 165mm Width : 165mm
CL60963OOOO CL60964OOOO CL60316OOOO CL60073OOOO CL60966OOOO
Vertical
Height : 65mm Height : 98mm Height : 150mm Height : 125mm Height : 125mm Height : 150mm
CL60963OOOO CL60964OOOO CL60965OOOO CL60128OOOO(1EA) CL60067OOOO(1EA) CL60965OOOO(1EA)
Fixed Version
Fr Frame 1 Frame 2 Frame 3
#
Ver N/N08/D10/S H S/H N/S N*/N08*/N10*/S/H N08 /H/V
A 400A-2000A 400A-2000A 2500A 400A-2500A 400A-4000A 400A-4000**A 5000**A 6300A
Horizontal
Vertical
Vertical termination termination
recommended recommended
Height : 65 mm Height : 65 mm Height : 100 mm Height : 100 mm Height : 100 mm Height : 65 mm Height : 75 mm Height : 100 mm
CL60976OOOO (1EA)
3-11
15 max
X
X
X = 100 -150 mm
3-12
Termination - Fixed Breakers
Flat Termination C
400A-1600A N/N08/D10/S/H Fr.1-3P 32
A
B
M10
105
A
B
32
122
C
41
Bolt length
FRAME 1 A B C D 100 100
400-1600A N 24 50 50 11 347
15
400-1600A N08/D10/S 24 50 65 11
Bolt length for mounting 400-1600A H 30 55 65 9
link(s) on Flat Terminals M10 bolts to be used for link termination
to be cumulative link(s) Holes (on both sides) for Earthing Tightening torque: 3.0 kgfm
thickness + 15 mm. connections by M10/Equivalent BS bolt
BREAKER DIMENSION
69
RATING A
400 - 2000A N/N08/D10/S 74
400 - 2000A H 72
40
69
108.8
19
Ø12.9 27
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm 100 100
3-13
Termination - Fixed Breakers
Vertical Terminals
A
400A-1600A N/N08/D10/S/H Fr.1-3P BREAKER ADAPTOR 19
2000A N/N08/D10/S/H Fr.1-3P RATING CAT NO.
400 - 2000A N/N08/D10/S CL60967OOOO
65
27
400 - 2000A H CL60968OOOO
40
BREAKER DIMENSION
RATING A
400 - 2000A N/N08/D10/S 74
65
400 - 2000A H 72
Ø12.9
117.5
100 100
63
15
100 100
Vertical Terminals 72
2500A S/H Fr.1-3P 19
63
(Adaptor-CL60976OOOO)
27 27
100
45
100
Ø12.9
80.8
100 100
20
100 100
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm
3-14
Termination - Fixed Breakers Bolt length Bolt length for
mounting link(s) on
FRAME 1 A B C D
400 -1600A N 24 50 50 11
Flat Terminals
400 -1600A N08/D10/S 24 50 65 11
to be cumulative
Flat Termination link(s) thickness + 400 -1600A H 30 55 65 9
400A-1600A N/N08/D10/S/H Fr.1-4P 15 mm.
C
32
A
B
M10
105
B
122
C
41
Horizontal Termination
400A-1600A N/N08/D10/S/H Fr.1-4P BREAKER ADAPTOR A
RATING CAT NO. 63
2000A N/N08/D10/S/H Fr.1-4P 15
400-2000A N/N08/D10/S CL60967OOOO
69
400-2000A H CL60968OOOO
BREAKER DIMENSION
40
RATING A
400 - 2000A N/N08/D10/S 74
400 - 2000A H 72
69
108.8
19
27
Ø12.9 100 100 100
3-15
Termination - Fixed Breakers
Vertical Terminals A
19
400A-1600A N/N08/D10/S/H Fr.1-4P &
2000A N/N08/D10/S/H Fr.1-4P
65
27
400 - 2000A N/D10/N08/S CL60967OOOO
CL60968OOOO
40
BREAKER DIMENSION
RATING A
400 - 2000A N/D10/N08/S 74
65
400 - 2000A H 72 Ø12.9
15
M12 / Equivalent BS bolts to be used for link termination 100 100 100
Tightening torque: 3.2 kgfm
72
63
19
23 27 27
100
45
100
Ø12.9
80.8
20
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm 100 100 100
3-16
Termination - Fixed Breakers
Flat Termination Bolt length
Bolt length for mounting
400A-1600A N/N08/N10/S/H Fr.2-3P link(s) on Flat Terminals
to be cumulative link(s)
thickness + 15 mm.
VERSION A B C
M10
9
55
105
55
122
41
15 133.3 133.3 90
Holes (on both sides) for Earthing
connections by M10 / Equivalent BS bolt 447
BREAKER DIMENSION
48
RATING A
400 - 2500A N/S 74
3200A N/S 72
74
400-3200A N08/N10/H 72
103.8
19
27
20 54
133.3 133.3
3-17
Termination - Fixed Breakers
Vertical Termination
400A-4000A N*/N08*/N10*/S/H Fr.2-3P
VERSION ADAPTOR
BREAKER DIMENSION
RATING A
400 - 2500A N/S 74
3200-4000A N*/S 72
400-4000A N08*/N10*/H 72
A
63
19
100
133.3 133.3
54
27
53
100
133.3 133.3 20
77.2
3-18
Termination - Fixed Breakers
Top: Horizontal
Bottom: Vertical
Termination
4000A S/H Fr-2-3P
VERSION ADAPTOR
4000A S/H CL60977OOOO
72
63
20
100
53
27 27 Ø12.9
19
19
63
27
100
27
133.3 133.3
77.2
M12 / Equivalent BS bolts to be used for links termination Details of 4P(200% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-19
Termination - Fixed Breakers
VERSION A B C
Flat Termination 400-1600A N/S 24 24 81.2
400A-1600A N/N08/N10/S/H Fr.2-4P
400-16000A N08/N10/H 30 30 98.4
c
32
9
M10
55
105
55
122
41
BREAKER DIM. A
RATING
48
400-3200A N08/N10/H 72
103.8
27 27 20
19
Ø12.9 100
133.3 133.3 133.3
3-20
Termination - Fixed Breakers
Vertical Termination
400A-4000A N*/N08*/N10*/S /H Fr.2-4P (100% N)
VERSION ADAPTOR
BREAKER DIMENSION
RATING A
400-2500A N/S 74
3200-4000A N*/S 72
400-4000A N08*/N10*/H 72
A
63
19
100
54
27
20
133.3 133.3 133.3
77.2
3-21
Termination - Fixed Breakers
Top: Horizontal
Bottom: Vertical
Termination
4000A S/H Fr-2-4P
VERSION ADAPTOR
4000A S/H CL60977OOOO
72
63
20
100
Ø12.9
27 27
19
53
63
19
27
100
M12 / Equivalent BS bolts to be used for links termination Details of 4P(200% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-22
Termination - Fixed Breakers
Bolt length Bolt length for mounting
Flat Termination link(s) on Flat Terminals
400A-1600A N08/H/V Fr.3-3P to be cumulative link(s)
165 thickness + 15 mm.
65
32
M10
30
56
10
105
56
30
122
41
27
Ø12.9
100 100 100 100 100
3-23
Termination - Fixed Breakers
Adaptor
Breaker Rating Dim. A
Cat. No.
400-4000A CL60968OOOO 15
5000A CL60982OOOO 20
82
63
19
27
65
19
40
65
117.5
SEE
100 DETAIL
100 A 100 100 100
82
A
63
19
27 27
100
23
45
100
Ø12.9
80.8
20
100 100 100 100 100
M12 / Equivalent BS bolts to
be used for links termination
Tightening torque: 3.2 kgfm
3-24
Termination - Fixed Breakers
65
32
M 10
9
56
30
10
105
56
30
122
41
30
69
108.8
Ø12.9
19
27 65
100 100
100 100
100 100
100 100
100 100
100 100
100
3-25
Termination - Fixed Breakers
Vertical Termination
400A-4000A N08/H/V Fr.3-4P (100% N)
& 5000A H/V Fr.3-4P (100% N)
82
63
19
65
27
19
40
65
117.5
100 100 100 100 100 100 100
Breaker Rating
Adaptor Dim. A
Cat. No.
400-4000A CL60968OOOO 15
5000A CL60982OOOO 20
A
100 100 100 100 100 100 100
Vertical Termination
6300A H/V Fr.3-4P (100% N)
Adaptor-CL60976OOOO
82
19 Ø12.9
27 27
100
23
45
100
80.8
3-26
Termination - Draw-out Breakers
3-27
Termination - Draw-out Breakers
3-28
Termination - Draw-out Breakers
400A-2000A, N/N08/D10/S/H, Fr.1-3P
Flat Terminals
SEE DETAIL A
400A-1600A, N/N08/D10/S/H
DETAIL A
56.8
14.5
10.4
105
36
Ø12.5
150
36
25.5
Bolt length
16 347
Bolt length for mounting link(s) on M12 bolts to be used for link termination
Flat Terminals to be cumulative link(s) Tightening torque: 3.2 kgfm
Thickness + 20 min to 25 max
36 65
Horizontal Terminals
400A-2000A N/N08/D10/S/H
M12
Adaptor - CL60963OOOO 22.5
15
105 36
2 HOLES Ø12.9
27 PITCH
45
150
15
100 100
88.5 16 73.5
347
Vertical Terminals 36 65
400A - 2000A N/N08/D10/S/H
15
Adaptor - CL60963OOOO
M12
FOR 2500A REFER PAGE 3-30
22.5
27
36
65
105
Ø12.9
45
150
15
100 100
73.5
88.5 16 347
3-29
Termination - Draw-out Breakers
2500A, S/H, 3P & 4P (Fr.1)
Vertical Terminals
FOR 2500A - 3P S/H
Adapter - CL60964OOOO 65 20 36
95.5
70
20 Ø12.9
27 27
36
98
105
Ø12.9
150
15
100 100
16 73.5
347
M12 / Equivalent BS bolts to be used for links termination
Tightening torque: 3.2 kgfm
Vertical Terminals 20
FOR 2500A - 4P S/H 65 36
Adapter - CL60964OOOO
95.5
70 Ø 12.9
20
27 27
36
98
105
Ø12.9
150
73.5
16 447
M12 / Equivalent BS bolts to be used for links termination
Tightening torque: 3.2 kgfm All Dimensions in mm
3-30
Termination - Draw-out Breakers
DETAIL A
65
56.8
14.5 36
Ø 12.5
105
56.8
36
150
10.4
25.5
Bolt length
15
Bolt length for mounting link(s) on Flat M12 bolts to be used for link termination
Terminals to be cumulative link(s) Tightening torque: 3.2 kgfm
thickness +20 min to 25 max.
Horizontal Terminals 36 65
400A - 2000A N/N08/D10/S/H
Adaptor - CL60963OOOO
Adaptor - CL60963OOOO
M12
2 HOLES Ø12.9
27 PITCH
105 36
15
22.5
45
150
88.5
100 100 100
15
16 73.5
447
Vertical Terminals 36
15
65
400A - 2000A N/N08/D10/S/H
Adaptor - CL60963OOOO
For 2500A REFER PAGE 3-30 M12
22.5
36
27
65
105
Ø12.9
45
150
88.5
100 100 100
M12 / Equivalent BS bolts
15
3-31
Termination - Draw-out Breakers
400A-3200A, N/N08/N10/S/H Fr.2-3P
65
36
Flat Terminals
400A-1600A, N/N08/N10/S/H
M12
77.2
36
105
77.2
36
140
Bolt length
25.5
15
16 133.3 133.3 90
447
Bolt length for mounting link(s) on M12 bolts to be used for link termination
Flat Terminals to be cumulative link(s) Tightening torque: 3.2 kgfm
thickness+20 min to 25 max
Horizontal Terminals 98
400A-3200A, N/N08/N10/S/H
Adaptor - CL60964OOOO 95.5
M12
20
20
65
105
45
3 HOLES Ø12.9
27 PITCH
140
133.3 133.3 90
15
16 447
Vertical Terminals
36 20 20
400A-3200A, N/N08/N10/S/H
Adaptor - CL60964OOOO
95.5
20 M12
Ø12.9
27 27
98
36
105
98
36
140
45 36
133.3 133.3 90
447
15
16
3-32
Termination - Draw-out Breakers
4000A, S/H, Fr.2-3P (100% N)
Vertical Terminals
4000A, S/H
Adaptor - CL60965OOOO 20 65
95.5
12.9
45
21 27 27 27 27
165
150
36 36
20
29
58
36
21 27 27 27 27
178.5
150
15
70
16 90.5 133.3 133.3
25.5
447
95.5
3 HOLES 12.9
100
72
32
20
83.8
35
45
36
21 27 27 27 27
179
150
20
M12 / Equivalent BS bolts to be used for links termination.
Tightening torque: 3.2 kgfm 23 27 27
3-33
Termination - Draw-out Breakers
400A-3200A, N/N08/N10/S/H, Fr.2-4P (100% N)
Flat Terminals 65
400A-1600A, N/N08/N10/S/H 36
M12
77.2
36
105
77.2
36
140
25.5
Bolt length
90 133.3
15
16 133.3 133.3
581
Horizontal Terminals
400A-3200A, N/N08/N10/S/H
Adaptor - CL60964OOOO 98 36
95.5 N M12
20
20
65
36
105
45
3 HOLES Ø12.9
140
27 PITCH
15
Vertical Terminals
400A-3200A N/N08/N10/S/H 20 36 65
Adaptor - CL60964OOOO
95.5
M12
Ø 12.9 20
27 27
98
36
105
98
140
45
16
15
3-34
Termination - Draw-out Breakers
4000A, S/H, Fr.2-4P (100% N)
Vertical Terminals
4000A, S/H
Adaptor - CL60965OOOO 20 65
95.5
12.9
45
21 27 27 27 27
165
36 36
150
28
20
58
36
21 27 27 27 27
178.5
150
70
16 581
25.5
95.5
3 HOLES 12.9
100
72
32
20
35
83.8
45
36
178.5
21 27 27 27 27
150
581
12.9
20
3-35
Termination - Draw-out Breakers
400A-4000A N08/H/V Fr.3-3P, 5000A H/V Fr.3-3P
& 6300A, H/V Fr.3-3P
Flat Terminals
400A-1600A N08/H/V
165
36
56
36
105
ø12.9
36
56
179
25.5
15
Bolt length for mounting link(s) on M12 bolts to be used for link termination
Flat Terminalsto be cumulative link(s) Tightening torque: 3.2 kgfm
thickness+20 min to 25 max
6 HOLES - Ø12.9
PITCH 27 mm.
36
65
40
22.5
15
183
45
63 35.5
15
16
73.5 100 100 100 100 100
647
6 HOLES - Ø12.9
3-36
Termination - Draw-out Breakers
400A-4000A N08/H/V Fr.3-3P, 5000A H/V Fr.3-3P
& 6300A H/V Fr.3-3P
Vertical Terminals
400A-4000A N08/H/V 165 15
Adaptor - 36 M12
CL60128OOOO
45
Ø12.9
22 27 27 27
125
134
36
40
22.5
58
36
22 27 27 27
183
Bolt length 35.5
70
15
16
73.5 100 100 100 100 100
Hole (on both sides)
Bolt length for mounting link(s) on for Earthing connections
647
Flat Terminalsto be cumulative link(s) by M10 / Equivalent BS bolt
thickness+20 min to 25 max
134
36
40
20
58
36
22 27 27 27
183
35.5
70
15
16
73.5 100 100 100 100 100
647
Vertical Terminals
6300A H/V
Adaptor - 165 20
36 M12
CL60965OOOO
45
Ø12.9
21 27 27 27 27
150
36 36
165
20
28
58
36
21 27 27 27 27
183
35.5
70
15
16
73.5 100 100 100 100 100
M12 / Equivalent BS bolts to be used for links termination. 647
Tightening torque: 3.2 kgfm
3-37
Termination - Draw-out Breakers
400A-4000A N08/H/V Fr.3-4P (100% N),5000A H/V Fr.3-4P (100% N) Bolt length
56
36
105
ø12.9 36
56
179
25.5
15
Hole (on both sides) 100 100 100 100 100 100 100 73.5
16 for Earthing connections 847
by M10 / Equivalent BS bolt
6 HOLES - Ø12.9
PITCH 27 mm.
36
65
22.5
40
15
8
183
63
45
22.5
63 35.5
27 27 27 27 27
15
TOP VIEW OF 16 73.5 100 100 100 100 100 100 100
CL60073OOOO 847
6 HOLES - Ø12.9
PITCH 27 mm.
36
65
20
40
20
183
45
15
70
70 35.5
20
27 27 27 27 27
15
134
125
36
22.5
58
40
36
22 27 27 27
183
Bolt length
35.5
70
15
16
Hole (on both sides) 73.5 100 100 100 100 100 100 100
Bolt length for mounting link(s) on for Earthing connections
Flat Terminals to be cumulative link(s) 847
by M10 / Equivalent BS bolt
thickness+20 min to 25 max
165 20
Vertical Terminals 36
M12
5000A H/V
Adaptor -
CL60067OOOO
Ø12.9 45
134
22 27 27 27
125
36
40
20
58
36
22 27 27 27
183
35.5
70
73.5 100 100 100 100 100 100 100
15
16
847
Vertical Terminals
6300A H/V 165 20
Adaptor - 36 M12
CL60965OOOO
Ø12.9 45
21 27 27 27 27
150
36 36
165
28
20
58
36
21 27 27 27 27
183
35.5
70
15
3-39
Termination - Draw-out Breakers
400A-4000A H/V Fr.3-4P (50% N) & 5000A H/V Fr.3-4P (50% N) 165
36
Flat Terminals
400A-1600A H/V 10*
Bolt length
56
36
105
ø12.9
36
56
179
*For Phase poles R, Y, B only
Not applicable for Neutral pole 25.5
Bolt length for mounting link(s) on
15
Flat Terminals to be cumulative link(s) 16 Hole (on both sides) 100 100 100 100 100 100 73.5
thickness+20 min to 25 max for Earthing connections
by M10 / Equivalent BS bolt 747
Adaptor - CL60073OOOO
- CL60963OOOO
45
6 HOLES - Ø12.9
PITCH 27 mm.
36
40 65
22.5
15
POLES A
183
63
Phase: R, Y, B 35.5
A
Neutral: N 25.5
15
Vertical Terminals
165 15
400A-4000A H/V 36 M12
Adaptor - CL60128OOOO
Ø12.9 45
22 27 27 27
125
134
36
22.5
58
40
36
22 27 27 27
183
POLES A A
Phase: R, Y, B 35.5
70
Neutral: N 25.5
15
16
73.5 100 100 100 100 100 100
747
134
36
20
40
58
36
22 27 27 27
183
POLES A
Phase: R, Y, B 35.5 A
Neutral: N 25.5 70
15
3-40
Termination - Fixed Breakers
FRAME 1 A B C D
50 11
Flat Termination 400 - 800A N
400 - 800A S
24
24
50
50 65 11
400A-800A N/S/H Fr.1-4P (200% N) 400 - 800A H 30 55 65 9
C
32
A
B
M10
105
B
A C
122
41
Bolt length for mounting link(s) on M10 bolts to be used for link termination
Flat Terminals to be cumulative link(s)
thickness + 15 mm. Tightening torque: 3.0 kgfm
400-1000A H CL60968OOOO
69
BREAKER DIMENSION
RATING A
400 - 1000A N/S 74
40
400 - 1000A H 72
69
108.8
19
27
Ø12.9 100 100 100
3-41
Termination - Fixed Breakers
Vertical Terminals BREAKER ADAPTOR
400A-1000A N/S/H Fr.1-4P (200% N) RATING CAT. No. A
400-1000A N/S CL60967OOOO 19
400-1000A H CL60968OOOO
65
27
BREAKER DIMENSION
RATING A
40
400 - 1000A N/S 74
400 - 1000A H 72
65
Ø12.9
117.5
100 100 100
15
100 100 100
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm
72
Vertical Terminals 63
1250A N/S/H Fr.1-4P (200% N) 19
(Adaptor-CL60976OOOO)
23 27 27
100
45
100
Ø12.9
80.8
20
M12 / Equivalent BS bolts to be used for link termination
100 100 100
Tightening torque: 3.2 kgfm
3-42
Termination - Fixed Breakers VERSION A B C D E
c
32
D
M10
A
E
105
B
E
122
41
Horizontal Termination
400A-2000A N*/S/H Fr.2-4P (200% N) VERSION ADAPTOR A
20 63
400 -1250A N/S CL60122OOOO
1600 - 2000A N*/S CL60977OOOO
74
VERSION DIMENSION
A
400 - 1250A N/S 74
74
400-2000A H 72
103.8
27 27
19
20
Ø12.9
100
133.3 133.3 133.3
3-43
Termination - Fixed Breakers
Vertical Termination
400A-2000A N*/S/H Fr.2-4P (200% N)
VERSION ADAPTOR
63
Ø 12.9 19
27
100
54
23
20
133.3 133.3 133.3
77.2
* Available till 1600A M12 / Equivalent BS bolts to be used for links termination
Tightening torque: 3.2 kgfm
3-44
Termination - Fixed Breakers
Bolt length
M10
30
56
105
56
30
122
41
15 73.5
100 100 100 100 100
647
Holes (on both sides) for Earthing connections by
M10 / Equivalent BS bolt M10 to be used for links termination
Tightening torque: 3.0 kgfm
27 N
Ø12.9
100 100 100 100 100
3-45
Termination - Fixed Breakers
Vertical Termination Breaker Rating
Adaptor
Dim. A
Cat. No.
400A-2000A H/V Fr.3-4P
400-2000A CL60968OOOO 15
& 2500A H/V Fr.3-4P (200% N)
2500A CL60982OOOO 20
72
63
SEE
100 DETAIL
100 A 100 100 100
19
27
65
Ø12.9
19
40
A N
100 100 100 100 100
A AA C
65
117.5
3-46
Termination - Draw-out Breakers
400A-1000A, N/S/H, Fr.1-4P (200%N)
Flat Terminals
400A-1000A, N/S/H
SEE DETAIL A
DETAIL A
65
14.5 36
M12
105
(Ø 12.5)
56.8
36
150
10.4
25.5
Bolt length
100 100 100
15
16 73.5
447
Bolt length for mounting link(s) on Flat M12 bolts to be used for link termination
Terminals to be cumulative link(s) Tightening torque: 3.2 kgfm
thickness +20 min to 25 max.
Horizontal Terminals 65 36
400A - 1000A N/S/H
Adaptor - CL60963OOOO
M12
2 HOLES Ø12.9
27 PITCH
36
15
105
22.5
45
150
88.5
100 100 100
15
16 447 73.5
Vertical Terminals
15 65 36
400A - 1000A N/S/H
Adaptor - CL60963OOOO
M12
22.5
27
65
36
105
Ø12.9
150
45
88.5
100 100 100
M12 / Equivalent BS bolts
15
16 73.5
to be used for links termination 447
Tightening torque: 3.2 kgfm
All Dimensions in mm
3-47
Termination - Draw-out Breakers
Flat Terminals
400A-1600A, N/S/H, Fr.2-4P (200% N) 65
36
Ø12.9
77.2
36
105
77.2
36
140
25.5
Bolt length
15
16
90.5 133.3 133.3 133.3
581
Bolt length for mounting link(s) on
Flat Terminals to be cumulative link(s) M12 bolts to be used for link termination
thickness+20 min to 25 max Tightening torque: 3.2 kgfm
Horizontal Terminals
400A-1600A N/S/H (200% N) 98 36
Adaptor - CL60964OOOO
95.5 N M12
20
20
65
36
45
105
3 HOLES-Ø12.9
140
PITCH-27mm
15
Vertical Terminals 20 36 65
Ø 12.9 20
36
27 27
98
105
140
98
45
133.3 133.3 133.3 90.5
581
16
15
3-48
Termination - Draw-out Breakers
400A-2000A H/V,Fr.3-4P (200%N) *10 mm Terminal height difference
165 due to equalizer for Neutral.
36
Flat Terminals
400A-1600A H/V
10*
56
36
105
ø12.9
36
56
179
Bolt length 25.5
N
15
Hole (on both sides) 100 100 100 100 100 73.5
16
for Earthing connections 647
Bolt length for mounting link(s) on by M10 / Equivalent BS bolt
Flat Terminals to be cumulative link(s)
thickness+20 min to 25 max
Horizontal Terminals (Bus Coupler Application Only) 165
400A-2000A H/V M12
Adaptor - CL90747OOOO 36
65
10*
HOLES - Ø12.9
PITCH 27 mm.
36
65
45
40
22.5
15
183
63
35.5
N
15
Vertical Terminals
*10 mm Terminal height difference
400A-2000A H/V 165 due to equalizer for Neutral.
Adaptor - CL60963OOOO
36 M12 A
45
Ø12.9 10*
65
19 27
40
22.5
36
183
63
35.5
N
74.4 100 100 100 100 100
15
16
647
M12 / Equivalent BS bolts to be used for links termination.
All Dimensions in mm
Tightening torque: 3.2 kgfm
3-49
Termination - Draw-out Breakers
Vertical Terminals *10 mm Terminal height difference
FOR 2500A H/V,Fr.3-4P(200%N) due to equalizer for Neutral.
Adaptor - CL60067OOOO
165 20
36 M12
10*
Ø12.9 45
22 27 27 27
125
134
36
20 40
58
36
22 27 27 27
183
35.5
N
70
15
Vertical Terminals
FOR 1250A S/H,Fr.1-4P (200%N)
Adapter - CL60964OOOO 20 65 36
90.5
65
15 Ø 12.9
27 27
98
36
Ø12.9
150105
15
16 73.5
447
M12 / Equivalent BS bolts to be used for links termination.
All Dimensions in mm
Tightening torque: 3.2 kgfm
3-50
External Neutral CT:
For Earth fault protection and protection of Neutral against overloads, Neutral
CT is required. For 4-Pole breakers, the CT is provided inside the breaker, to be
used on 4 wire system whereas for 3-pole breakers, external CT is available
separately.
1, 2 & 3 400/630/800
19
19
1, 2 & 3 1000/1250/1600
42
42
(ref. Page 2-6 for Frame size details)
72 19
72
TERMINAL THICKNESS 15 mm.
42
19
19
90
Frame Size Rating
12.5
12.5 40 13
1 2000/2500
19
19
(ref. Page 2-6 for Frame size
45.5
45.5
details)
72
72
TERMINAL THICKNESS 30 mm.
45.5
19
65
19
98.3
65
Frame Size Rating
12.5 40 40
40 40
40 13
13
3 5000/6300
19
19
45.5
19
3-51
Installation of Phase Barriers:
#0.13
28.8
128.4
350
13.8
R2
6.2
130
90
R1
5
R5
3-52
3-53
3.4 Control Circuit Connections:
SICs & SIC Bridge
system of ACB’s Secondary Isolating
Contacts (8b) facilitate Control circuit wiring with
following features,
1
2
3
4
5
6
7
8
Disconnected Test Connected
3-54
Control Termination:
For UW-MTX1.0/1G/1Gi/1.5G/1.5Gi/2.5/2.5G/3.5/3.5EC/3.5H
*
Electrical Aux. Aux. Aux. Aux. Under Common Ready Protection &
ZSI
Charging Contact Contact Contact Contact Voltage Fault to Remote Control
Terminals
Device # “NC” “NC” “NC” “NC” Release # Indication Close Reset Unit
2 3 3 3 3 4 1m 1m 1
}}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
CMN
DCN
GO1
CH1
SO1
EC1
TCS
CH2
RR+
SO2
AS+
AS+
EC2
TST
AL+
M-G
GO2
C-G
131
101
RR-
Z-H
AS-
GI1
AS-
SI1
132
134
102
104
GI2
C-L
AL-
C-H
Z-L
CN
SI2
A1
C1
X1
D1
N1
V1
41
A2
C2
X2
V2
21
V3
31
D2
N2
D+
V0
42
43
44
22
23
24
32
11
33
34
12
13
14
D-
X
Legend
Control
circuit
equipment
Ref. No.
The above diagram gives a generic configuration for control termination on the breaker. For specific details, refer Connection diagram
(pages 79 to 84) specific to the P&C unit installed in the breaker.
# For using electrical accessories with DC Control Supply, it is recommended to connect D1/A1/C1 to +ve and D2/A2/C2 to -ve.
3-55
(UW-MTX 1.0)
Connection Details
RR+
DCN
D1
TST
41
CH1
A1
TCS
EC1
21
31
33
43
CN
13
C1
134
23
11
132
122
124
104
102
112
114
N R Y B
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
UW-MTX 1.0
.4
.4
.4
.4
.2
.2
.2
.2
CMN
CH2
EC2
RR-
121
131
111
101
D2
C2
A2
LOAD
34
44
22
12
14
24
32
42
Electric Spring U/V Closing Shunt Ready
Charging Charge Release Release Release to
Device Indication Close
1 2 2m 3 4 5 6 1m 7 4m/6m 8e
(UW-MTX 1G)
Connection Details
RR+
DCN
CH1
D1
TST
41
A1
TCS
EC1
21
31
33
43
CN
13
C1
134
23
11
132
122
124
104
102
112
114
N R Y B
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
UW-MTX 1G
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
CMN
EC2
CH2
RR-
121
131
111
101
LOAD
D2
C2
A2
34
44
22
12
14
24
32
42
Electric Spring U/V Closing Shunt Ready
Charging Charge Release Release Release to
Device Indication Close
1 2 2m 3 4 5 6 1m 7 4m/6m 8e
3-57
3-58
(UW-MTX 1.5G)
Connection Details
RR+
DCN
CH1
D1
TST
41
A1
TCS
EC1
21
31
33
43
CN
13
C1
134
23
11
132
122
104
124
102
112
114
N R Y B
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
UW-MTX 1.5G
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
CMN
EC2
CH2
RR-
121
131
111
101
LOAD
D2
C2
A2
34
44
22
12
14
24
32
42
Electric Spring U/V Closing Shunt Ready
Charging Charge Release Release Release to
Device Indication Close
1 2 2m 3 4 5 6 1m 7 4m/6m 8e
3-59
RR+
134
104
114
124
TCS
132
102
112
122
EC1
TST
N R Y B
CN
13
23
33
43
D1
A1
C1
11
21
31
41
GO1
GI1
SO1
SI1
AS+
ACB STATUS
.1 .2
.3
.3
.3
.3
.1
.1
.1
.1
CFM
RR
UR
CR
EC
AX .2
AX .2
AX .2
AX .2
SR
PI
UW-MTX 1.0Gi/1.5Gi
.4
.4
.4
.4
N1
N2
ACB STATUS
CMN
CH2
GO2
GI2
SO2
SI2
AS-
EC2
LOAD
131
101
111
121
RR-
D2
C2
14
24
34
44
A2
12
22
32
42
U/V Fault Signal
Electric Spring Common Ready
/Shunt Trip Signal Electrical Remote
Auxiliary Contacts U/V Closing Shunt
Main Circuit Protection & Control Unit Charging Charge Fault to Position
4NO + 4 NC Release Release Release Indication (only one can Reset
Device Indication Close be used)
Indication
Ref. No 2 2m 3 4 5 6 1m 7 4m/6m 8e
N R Y B
LOAD
UW-MTX 2.5
1
AS- AS+
Charging Charge
Electric Spring
EC2 EC1
Device Indication
EC
2
CH2 CH1
2m
12 .4 .3 11
AX
14 .2 .1 13
22 .4 .3 21
AX
24 .2 .1 23
.3 31
3
32 .4
AX
34 .2 .1 33
42 .4 .3 41
AX
44 .2 .1 43
Release Release Release
U/V Closing Shunt
D2 D1
4
UR
A2 A1
CR
5
SR/SRW
C2
6
.2 .1 C1
TCS
134
CFM
131
1m
132
104
Ready
Close
101
to
102
7
114
111
112
4m/6m
124
121
122
CN
CMN TST
PI
8e
DCN
RR- RR+
RR
(UW-MTX 2.5)
Connection Details
3-61
N R Y B
LOAD
N1
UW-MTX 2.5G
N2
1
AS- AS+
Charging Charge
Electric Spring
EC2 EC1
Device Indication
EC
2
CH2 CH1
2m
12 .4 .3 11
AX
14 .2 .1 13
22 .4 .3 21
AX
24 .2 .1 23
.3 31
3
32 .4
AX
34 .2 .1 33
42 .4 .3 41
AX
44 .2 .1 43
Release Release Release
U/V Closing Shunt
D2 D1
4
UR
A2 A1
CR
5
SR/SRW
C2
6
.2 .1 C1
TCS
134
CFM
131
1m
132
104
Ready
Close
101
to
102
7
114
111
112
4m/6m
124
121
122
CN
CMN TST
PI
8e
DCN
RR- RR+
RR
(UW-MTX 2.5G)
Connection Details
3-62
N R Y B
LOAD
N1 ACB STATUS
N2
D+
ACB STATUS
UW-MTX 3.5
M-G
D-
C-G AL+
AL- C-H
C-L
1
Z-H
Z-L
AS+
AS-
V0 V1
V2 V3
Charging Charge
Electric Spring
EC2 EC1
Device Indication
EC
2
CH2 CH1
2m
12 .4 .3 11
AX
14 .2 .1 13
22 .4 .3 21
AX
24 .2 .1 23
.3 31
3
32 .4
AX
34 .2 .1 33
42 .4 .3 41
AX
44 .2 .1 43
Release Release Release
U/V Closing Shunt
D2 D1
4
UR
A2 A1
CR
5
SR/SRW
C2
6
.2 .1 C1
TCS
134
CFM
131
1m
132
104
Ready
Close
101
to
102
7
114
111
112
4m/6m
124
121
122
CN
CMN TST
PI
8e
DCN
RR- RR+
RR
(UW-MTX 3.5)
Connection Details
3-63
N R Y B
LOAD
N1 ACB STATUS
UW-MTX 3.5EC/3.5H
N2
D+
ACB STATUS
M-G
D-
C-G AL+
AL- C-H
C-L
1
Z-H
Z-L
AS+
AS-
V0 V1
V2 V3
Charging Charge
Electric Spring
EC2 EC1
Device Indication
EC
2
CH2 CH1
2m
12 .4 .3 11
AX
14 .2 .1 13
22 .4 .3 21
AX
24 .2 .1 23
.3 31
3
32 .4
AX
34 .2 .1 33
42 .4 .3 41
AX
44 .2 .1 43
Release Release Release
U/V Closing Shunt
D2 D1
4
UR
A2 A1
CR
5
SR/SRW
C2
6
.2 .1 C1
TCS
134
CFM
131
1m
132
104
Ready
Close
101
to
102
7
114
111
112
4m/6m
124
121
122
CN
CMN TST
PI
8e
DCN
RR- RR+
RR
(UW-MTX 3.5EC/3.5H)
Connection Details
Section 4
System of ACB’s
Accessories: Features & Mounting
4.1 Cradle Mounted Accessories
4.2 Breaker Mounted Accessories
4.1 Cradle Mounted Accessories
4-1
4-2
4-3
4-4
4-5
4-6
4-7
4.2 Breaker Mounted Accessories
4-8
Auxiliary Contact Undervoltage Closing Shunt
Block (3a) Release (4) Release (5) Release (6)
Common Fault
12 34 5 Indication
6
Several Breaker-mounted accessories are located on the
front top side of the breaker and have specific positions.
Undervoltage
release
controller (4c)
Operation
Undervoltage
Shunt Trip Counter (10)
Trip Indication
Indication
b. Shunt Release - SR :
Function: To trip the breaker from a remote location
Features: Available with the following control voltages,
Type Normal Voltage Short-time Power Operating
Consumption Limit
C2
110, 220, 240, 415 Vac 50/60Hz
200 VA
SR 24, 30, 48, 60, 110, 70-110% C1 TCS
0.5s
125/127, 220, 250 Vdc
Installation: Drop fit the Shunt release in the assigned slot and slide
backwards to lock. Also, fix the pre-wired Auxiliary Contact Block.
4-9
4-10
4-11
4-12
4-13
j. Locking ‘OFF’ Button (18):
Installation:
Lock Type Lock Components for ‘Locking Arrangement’ Assembly on the Lock
Actuator Lock plate Adaptors & Plugs
Castell
Ronis
Kirk
Profalux
Remove click-fit cap and drill 2 holes Ensure that lock is in ‘Locked’ position.
(dia 7mm), at depressed locations Mount the lock using LOPB rivets
4-14
Section 5
UW-MTX1.0 UW-MTX 1G
UW - MTX1.0
Identification Label UW - MTX1G
Power ON LED
OLED OLED
Display Display
TO ACCESS TEST KIT SOCKET & BREAKER RATING, REMOVE THIS FLAP TO ACCESS TEST KIT SOCKET & BREAKER RATING, REMOVE THIS FLAP TO ACCESS TEST KIT SOCKET & BREAKER RATING, REMOVE THIS FLAP
1 2 3 4 5
1 2 3 4 5 1 2 3 4 5
5-1
5.1 Identification
Identification Label
Power ON LED
OLED Display }
Fault Indication LEDs
Communication Module
Configurator*
Metering Module
* Available as accessory
5-2
2.Feature List
5-3
5.3 Detailed Overview
Note: This symbol indicates that DIP Switch is ON and indicates that DIP Switch is OFF.
Mismatch between actual breaker rating and setting on
the P&C unit will result in error in Protection
CAUTION Parameters & current measurement displayed .
5-4
Protection Settings for UW-MTX2.5/2.5G/3.5/3.5EC/3.5H
5-5
Parameter UW-MTX2.5 UW-MTX2.5G UW-MTX3.5 UW-MTX3.5EC UW-MTX3.5H Factory Settings
5-6
Protection Characteristics
2
Overload I T (for UW-MTX1.0)
10000
1000
100
10
10s
0.1
5-7
Protection Characteristics
2
Overload I T (for UW-MTX1.0,1G,1Gi,1.5G,1.5Gi,2.5,2.5G,3.5,3.5EC,3.5H)
10000
1000
100
Trip Time (s)
30 s
10 24 s
18 s Tolerance
Trip Time: ±20%
12 s
6s
4s
1
2s
1s
0.5 s
0.1
1 1.2 2 3 4 5 6 7 8 9 10
Current Multiples (x Ir)
5-8
Protection Characteristics
4
Overload I T for (UW-MTX2.5/2.5G/3.5/3.5EC/3.5H)
100000
10000
1000
100
10
0.1
0.01
1 2 3 4 5 6 7 8 9 10
5-9
Protection Characteristics
Overload SI (for UW-MTX2.5/2.5G/3.5/3.5EC/3.5H)
10000
1000
100
10
0.1
1 2 3 4 5 6 7 8 9 10
5-10
Protection Characteristics
Overload LI/VI(for UW-MTX2.5/2.5G/3.5/3.5EC/3.5H)
10000
1000
100
10
0.1
1 2 3 4 5 6 7 8 9 10
5-11
Protection Characteristics
2
Short Circuit I T ON(for UW-MTX1G/1.5G/1Gi/1.5Gi/2.5/2.5G/3.5/3.5EC/3.5H)
10000
1000
0.6 12
100
10
Trip Time (s)
0.4
0.3
0.2
0.1
0.1
0.02
0.01
0.01 0.1 1 10 50
Current Multiples (x In)
5-12
Protection Characteristics
2
Short Circuit I T OFF(for UW-MTX1.0,1G,1Gi,1.5G,1.5Gi,2.5,2.5G,3.5,3.5EC,3.5H)
10000
1000
0.6
100 0.6 12
10
Trip Time (s)
0.4
0.3
0.2
0.1 0.1
0.02
0.01
0.1 1 10 50
Current Multiples (x In)
5-13
Protection Characteristics
100
10
1.5 15
Trip Time (s)
0.1
0.01
0.01 0.1 1 10
Current Multiples (x In)
5-14
Protection Characteristics
10000
1000
0.2
0.3
100
0.4
0.5
0.6
0.8 2.4
10
Trip Time (s)
0.4 s
0.1 0.1 s
0.01
0.8 2.4
0.01 0.1 1 10 50
Current Multiples (x In)
5-15
Protection Characteristics
2
Earth Fault I T OFF(UW-MTX1G/1Gi/1.5G/1.5Gi)
100
0.2 0.6
10
Trip Time (s)
1
1 0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.1
0.01
0.1 1 10 50
Current Multiples (x In)
5-16
Protection Characteristics
2
Earth Fault I T ON (for UW-MTX 2.5G/3.5/3.5EC/3.5H)
0.1
0.4 2.4
5-17
Protection Characteristics
2
Earth Fault I T OFF(UW-MTX2.5G/3.5/3.5EC/3.5H)
100
0.2 0.6
10
Trip Time (s)
1 1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1 0.1
0.01
0.1 1 10 50
Current Multiples (x In)
5-18
Section 6
Putting System Of
Breakers in Operation
6.1 Re-loading in panel
6.2 Checking ON-OFF operation
6.3 Testing
6.4 Setting P&C unit
6.5 Trip simulation of P&C unit
6.6 ACB’s in Connected Position
6.7 Securing
6.1 Re-loading in panel:
6-1
6.2. Checking ON-OFF Operation:
O DISCHARGED
CHARGED
O
I
DISCHARGED
DISCHARGED
Now, the Breaker is O and Spring is
6-2
6.3 Testing (Control circuit & Interlocks):
(if breaker is equipped with accessories)
6-3
6.4 Configuring P&C Unit
Configuring UW-MTX1.0/1G/1Gi/1.5G/1.5Gi
UW-MTX1.0/1G/1Gi/1.5G/1.5Gi
ZSI ZSI
E/F S/C
Protection To activate ZSI E/F and ZSI S/C , set the ZSI E/F and ZSI S/C
DIP Switch to ON position.
6-4
6.4 Configuring UW-MTX2.5/2.5G/3.5/3.5EC
1. System Settings
Save Settings ?
É
Yes No
Note: To apply any parameter change in System settings in P&C unit , reset the power supply
once settings are saved.
6-5
2. Unit Settings
I1
I2
I3
Current
: 0A
: 0A
: 0A
Menu
Settings
View Records
Metering
Settings
Config Mode
View Mode
Password
**** É
Select “Settings” by Select “Config” Mode” Enter the password “0000”
Press “SEL” key SEL key (Factory set: default)
6-6
3. Protection
Press “SEL” key in the Select “Settings” by Select “Config” Mode” Enter the password “0000”
overlay SEL key (Factory Set: default)
Set Group 1
I Protection
V Protection
Freq Protection
Overload :It’s a protection against over current. The characteristics provided are I2t, I4t
LI, SI, VI with Thermal memory. Thermal memory help to reduce the trip time of the
unit in case of recursions of overload.
Short Circuit :Excessive currents though the conductors can cause circuit damage ,fire ,explosion .
This protection prevents such conditions.
Directional SC :The protection is a short circuit protection with the ability to recognize the direction of the
phases current during the fault period. The current direction makes it possible to determine
whether the fault is on the supply or load side of the circuit-breaker. Particularly in ring
distribution systems, this makes it possible to identify and disconnect the distribution
feeder where the fault has occurred, whilst keeping the rest of the system running.
Instantaneous :This protection works as short circuit protection with no intentional time delay
which means release operates in 20milliseconds as soon as the fault current
exceeds the set pick-up.
Note: Refer UW-MTX Release manual for the programming of further protections in detail.
6-7
3. Protection....continued
Earth Fault :When fault current flows from phase to earth due to rupturing of insulation,
this can lead to arc flash events and electric shock. This causes more damage to
the distribution system. This feature provides protection against earth fault current.
Neutral Overload :This provides protection against neutral overload at 50%, 100% & 200% of rated
current. It follows overload characteristics.
Restricted EF :It works in the restricted zone of source side. It functions similar to normal earth
fault protection
Earth Leakage :Earth leakage current is harmful to human body. Sensing of fault current & communicating
occurrence of fault signal to the main release is being done by an earth leakage module.
Under current :Decrease in any phase current below threshold leads to under current.
Current Unbalance :It provides protection against any unbalance in phase currents .
Enable O/L protection Select O/L char. from the Select delay from drop down list
drop down list.
Save Settings ? After programming the settings, press É key to escape from menu and
confirm the changes in Save Settings. After doing all the settings Save the
Yes No Set Group by pressing the escape key . “Save in Progress” message
confirms the Set Group has saved.
Note: Refer UW-MTX Release manual for the programming of further protections in detail.
6-8
Protections under V- protection:
Under voltage :When the voltage in one of the phases reduces than threshold, this
protection gets activated.
Over voltage :When the voltage in one of the phases increases above threshold, this
protection gets activated.
Voltage unbalance :Voltage unbalance creates damage to the distribution system. This protection
checks voltage unbalance in all three phases.
Residual voltage :Gives protection against the residual voltage present in the system.
Under frequency
Over frequency
} applicable for both control frequencies 50Hz & 60Hz.
Reverse power : When the direction of the total active power reverses to that of
the set direction, this protection gets activated. The direction of power depends on
that of the current flowing.
Leading PF : It checks whether the power factor is increasing beyond the set value when load is
capacitive.
Lagging PF : When the power factor for inductive load goes below the set value, this protection
gets activated. It’s important for any plant to maintain the power factor to unity.
MD active
MD reactive
MD apparent
} When max. demand of active, reactive & apparent power exceeds the set
value, then this protection gets activated.
Phase sequence :Mostly used for motor applications where phase reversal can be seen.
Breaker failure : In case if the breaker fails to open under fault condition (mechanism jam,
FSD malfunctions etc.) release issues one more trip command to FSD to operate
the breaker as per the set delay through this protection.
Note: Refer UW-MTX Release manual for the programming of further protections in detail.
6-9
6.5 Trip Simulation of P & C Unit :
6-10
6.6 U-POWER Omega ACBs in Connected Position:
5 6
b
a
UN-RS2GT
POWER
50% 60 70 80 90 100% ON
x Ir
PICK-UP (Ir) DELAY (Tr)(s) OVER
0.4 0.5 LOAD
1.0 0.5 30 1
Metering display: 0.6 24 2
0.7 18 3
0.85 0.75 12 4
0.8 x In
POWER ON
LED
6-11
6.7 Securing your Breaker:
U-POWER Omega offers several security features to prevent unauthorized access and inadvertent operation.
Padlocking
both buttons
Locking any
one button
Sealing
Either/Both buttons
6-12
Section 7
CAUTION
Nature of
Schedule/Frequency Actions Reference
Maintenance
POWER ON
LED
7-1
Door Racking Interlock defeat (26):
Tools required: None
Door Racking interlock prevents opening of smart racking
shutter (16) and thus, racking in/out of the breaker when
panel door is open.
If it is necessary to rack-out the breaker with panel door open,
racking interlock must be defeated. For opening racking shutter
Up to 690V AC
Rear Side of
Arc Chute
Once Arc chutes are opened, contacts are visible and can be inspected for erosion.
This feature is only for indication purposes and contacts should be replaced
after cleaning major fault/on completion of electrical life indicated.
Isometric View of
moving contact
7.1h Greasing of Mechanism:
Greasing schedule Mechanism : 1 Year or 500 operations, whichever is Non-adherence to greasing schedule
earlier. Grease to be used in Mechanism - Parts 1 to 6: Red or using other-than-specified grease
Grease(MobilithSHC-100 of Mobill); Parts 10 & 11 (plastic parts) on right may lead to malfunction.
hand side of Mechanism: White Grease (MOLYKOTE 33 MEDIUM)
Greasing schedule Cradle : 1 Year or 50 operations, whichever is earlier
CAUTION Ensure that ACB is OFF and Spring is
Grease to be used on parts 1 to 9 of Cradle: Red Grease (MobilithSHC-100 Discharged, before commencing
of Mobill) greasing operation.
The following components can be greased, without dismantling any
accessory or component, using a brush. 1 : Racking Screw
2 : Racking Cam & Drop Pin joint
1 : Pole shaft bearing (all) 3 : Base Plate
2 : Bearings (both sides of mechanism) 4 : Rail Sliding surface on Side plate
3 : Cam Profile 5 : Racking Cam & Service Latch follower
4 : Top surface of links (2) 6 : Gear Teeth & Rack Slots
5 : Top surface of link 7 : Bottom & side Sliding Surfaces of Rails on Side Plate
6 : Rubbing surface of link 8 : Service Latch on Side Plates
9 : Guiding surface of cradle SIC Bridge
10
A
C
5
11 4
8
2
1
7
3
6
Apply grease to the specified components at Simplified diagram for identification of Simplified diagram for identification of
rubbing surfaces components to be greased. components to be greased.
Fault identification:
3) Select versions of UW-MTX 2.5 & 2.5G (Ref. page 5-2) provide separate
remote indication of fault type, when auxiliary supply is available..
4
Reclosing the breaker:
7-4
Moving part of the pole can now
be removed
To take out fixed part of the pole, remove 1 screw from rear side
and 2 screws from top as shown.
7-7
7.2 Accessories & Spares
200 V CL90364OOOO
250 V CL90359OOOO
400 V CL90361OOOO
2 Shunt Release AC 110 V CL90816OAOO
(SR) 50/60 Hz 220 V CL90816OBOO
Shunt Release
240V~, 220V.
240 V CL90816OBOO
415 V CL90816ODOO
DC 24 V CL90816O4OO
30 V CL90816O4OO 1 1
Shunt Release
48 V CL90816O5OO
240V~, 220V.
60 V CL90816O5OO
110 V CL90816OAOO
125/127 V CL90816O1OO
220 V CL90816OBOO
250 V CL90816OBOO
SRW AC 240 V CL90823OBOO
(Wide band 10-130%) 50 Hz 415 V CL90823ODOO
3 Undervoltage Release AC 110 V CL90818AOOO
(With/Without Delay -UVR) 50/60Hz 240 V CL90818BOOO
415 V CL90818DOOO
24/30 V CL908184OOO 1 1
UV Release
415V-, 415V~.
DC 48 V CL908185OOO
110 V CL90818AOOO
220 V CL90818BOOO
4 Closing Release AC 110 V CL90817AOOO
(CR) 50/60Hz 220 V CL90817BOOO
240 V CL90817BOOO
415 V CL90817DOOO
DC 24 V CL908174OOO 1 1
30 V CL908174OOO
48 V CL908175OOO
Closing Release
240V~, 220V.
60 V CL908175OOO
110 V CL90817AOOO
125/127 V CL908171OOO
220 V CL90817BOOO
250 V CL90817BOOO
7-8
Sr. Component Cat No. Units per Units per
No. Cat No. ACB#
5 Protection&Control Units UW-MTX1.0 CL91966OOOO
UW-MTX1.0G CL91971OOOO
UW-MTX1.0Gi CL90562OOOO
UW-MTX1.5G CL91965OOOO
UW-MTX1.5Gi CL90552OOOO
UW-MTX 2.5 CL90112OOOO
UW-MTX 2.5G CL90610OOOO 1 1
UW-MTX 3.5 CL90113OOOO
UW-MTX 3.5EC CL90700OOOO
UW-MTX 3.5H CL91975OOOO
UW-MTX 4.5 CL90611OOOO
Power Supply Module UN-PS CL90722OOOO 1 1
6 External Simulation kit Matrix CL90724OOOO 1 1
7 Terminal Adaptor for one side Frame-1
3 for 3 Pole
(Incoming or Outgoing) 400-2000A Horiz./Vert. CL60963OOOO
4 for 4 Pole
Drawout ACBs 2500A Vertical CL60964OOOO
Frame-2
400-3200A Horiz./Vert. CL60964OOOO 3 for 3 Pole
Vertical CL60965OOOO 1 4 for 4 Pole
4000A
Horizontal CL60316OOOO
Frame-3 Vertical
Vertical CL60128OOOO 6 for 3 Pole
400-4000A
Horizontal## CL60073OOOO 8 for 4 Pole
Vertical CL60067OOOO Horizontal
5000A ##
Horizontal CL60966OOOO 3 for 3 Pole
6300A Vertical CL60965OOOO 4 for 4 Pole
Fixed ACBs Frame-1
400-2000A N/N08/D10/S Horiz./Vert. CL60967OOOO 3 for 3 Pole
400-2000A H Horiz./Vert. CL60968OOOO 4 for 4 Pole
2500A S/H Vertical CL60976OOOO
Frame-2
400-2500A N/S Horiz./Vert. CL60122OOOO
1 3 for 3 Pole
3200-4000A N*/S Horiz./Vert. CL60977OOOO
4 for 4 Pole
400-4000A N08*/N10*/H Horiz./Vert. CL60977OOOO
Frame-3
400-4000A Horiz./Vert. CL90668OOOO 6 for 3 Pole
5000A Vertical CL60982OOOO 8 for 4 Pole
6300A Vertical CL90669OOOO
Auxiliary contacts
8 (4NO+4NC) CL90745OOOO 1 1
7-9
Sr. Component Cat No. Units per Units per
No. Cat No. ACB*
7-10
Sr. No. Component CAT No. Units per CAT No. Units per ACB*
23 Mechanical Interlock 2 Incomers (2m) CL90810OOOO
(2 metre, 3 metre and 5 metre) 3 Incomers (2m) CL90811OOOO
1 set 1 set per scheme
2 Incomers & 1 Standby (2m) CL90812OOOO
2 Incomers & 1 Buscoupler (2m) CL90813OOOO
2 Incomers (3m) CL90659OOOO
3 Incomers (3m) CL90660OOOO
1 set 1 set per scheme
2 Incomers & 1 Standby (3m) CL90661OOOO
2 Incomers & 1 Buscoupler (3m) CL90662OOOO
2 Incomers (5m) CL90663OOOO
3 Incomers (5m) CL90664OOOO
1 set 1 set per scheme
2 Incomers & 1 Standby (5m) CL90665OOOO
2 Incomers & 1 Buscoupler (5m) CL90666OOOO
24 Arc Chute Frame 1 N/S/H CL91153OOOO
Frame 1 N08 CL90591OOOO 3 for 3 pole
Frame 2 N/S/H CL92153OOOO 4 for 4 pole
1
Frame 2 N08/N10 CL90534OOOO
Frame 3 N/S/H/V CL91153OOOO 6 for 3 pole
Frame 3 N08 CL90591OOOO 8 for 4 pole
25 Main Contacts Assembly Fr. 1 : 400-1600A N Version CL91181OOOO
Fr. 1 : 2000A N Version CL90192OOOO
Fr. 1 : 400-2000A N08 Version CL90596OOOO
Fr. 1 : 400-1600A S Version CL91182OOOO
Fr. 1 : 2000A S Version CL90296OOOO
Fr. 1 : 2500A S Version CL91183OOOO
3 for 3 pole
Fr. 1 : 400-2500A H Version CL91183OOOO
4 for 4 pole
Fr. 2 : 400-2500A N/S Version CL90331OOOO
1
Fr. 2 : 3200A N Version CL90642OOOO
Fr. 2 : 3200A S Version CL92181OOOO
Fr. 2 : 400-3200A H Version CL92182OOOO
Fr. 2 : 400-3200A N08/N10 Version CL90539OOOO
Fr. 2 : 4000A S/H Version CL90643OOOO
Fr. 3 : 400-6300A H Version CL93181OOOO
6 for 3 pole
Fr. 3 : 400-6300A V Version CL93182OOOO
8 for 4 pole
Fr. 3 : 400-4000A N08 Version CL90639OOOO
26 Jaw Contacts Fr. 1 : 400-1600A N Version Per Pole - 4
Fr. 1 : 2000A N Version Per Pole - 6
Fr. 1 : 400-1600A S Version Per Pole - 6
Fr. 1 : 2000A N08/S Version Per Pole - 8
Fr. 1 : 2500A S Version Per Pole - 12
Fr. 1 : 400-2500A H Version Per Pole - 12
Fr. 2 : 400-2500A N/S Version CL91184OOOO 12 Per Pole - 12
Fr. 2 : 3200A N/S Version Per Pole - 16
Fr. 2 : 400-3200A N08/N10/H Version Per Pole - 16
Fr. 2 : 4000A S/H Version Per Pole - 20
Fr. 3 : 400-4000A N08/H/V Version Per Pole - 12
Fr. 3 : 5000A H/V Version Per Pole - 12
Fr. 3 : 6300A H/V Version Per Pole - 20
27 Locking Arrangement for OFF Button for Castell Lock CL90814OOOO
for Ronis Lock CL90815OOOO
1 1
for Kirk Lock CL90863OOOO
for Profalux Lock CL90864OOOO
28 Locking Arrangement for Disconnected for Castell Lock CL90982OOOO
Position for Ronis Lock CL90865OOOO
1 1 or 2 as required
for Kirk Lock CL90866OOOO
for Profalux Lock CL90867OOOO
7-11
Sr. No. Component CAT No. Units per CAT No. Units per ACB*
29 Locking Arrangement for all Position for Castell Lock CL90981OOOO
for Ronis Lock CL90927OOOO 1 or 2 as
1
for Kirk Lock CL90868OOOO required
for Profalux Lock CL90869OOOO
30 C.T. Wire Harness for Matrix Frame 1-3P CL00687OOOO
Frame 1-4P CL00688OOOO
Frame 2-3P CL00689OOOO
Frame 2-4P CL00690OOOO 1 1
Frame 3-3P CL00691OOOO
Frame 3-4P CL00692OOOO
Frame 3-4P, 50% N CL00693OOOO
31 Current Transformer 400/630/800A CL00700OOOO
(Internal) Frame 1 1000/1250/1600A CL00701OOOO
2000/2500A CL00702OOOO
3 for 3 pole
400/630/800A CL00725OOOO
4 for 4 pole
1000/1250/1600A CL00703OOOO
Frame 2
2000A/2500A/
CL00704OOOO 1
3200/4000A
400/630/800A CL00726OOOO
1000/1250/1600A CL00727OOOO
6 for 3 pole
Frame 3 2000A/2500A/
CL00705OOOO 8 for 4 pole
3200A/4000A
5000A/6300A CL00706OOOO
32 Current Transformer for 400/630/800A CL00717OOOO
Frame 1,2,3
External Neutral 1000/1250/1600A CL00718OOOO
Frame 1 2000/2500A CL00719OOOO
1 1
2000A/2500A/
Frame 2,3 CL00720OOOO
3200A/4000A
Frame 3 5000A/6300A CL00721OOOO
33 Trip Indication for Undervoltage release CL90947OOOO 1 1
Shunt release CL90951OOOO 1 1
Common fault indication CL90949OOOO 1 1
Ready-to-Close indication CL90953OOOO 1 1
7-12
Section 8
Useful Hints
Useful Hints
Smart Racking Shutter is open Close the Smart Racking Shutter (Insert
Racking Handle once & pull back)
close
the breaker
Smart Racking Shutter does not Breaker is in-between Rack-in or out the
re-close automatically after Connected/Test/Disconnected breaker to any of the
racking handle is pulled out position. Position Indicator distinct positions
is not aligned with any of
the positions
8-1
Useful Hints
75 - 2 runs 75 - 2 runs
800 800 75 - 2 runs - - - - - -
50 - 3 runs 50 - 3 runs
Note: Above table is based on extensive study of popular bus-bar sizes used to terminate Air Circuit Breakers. However other
bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-bar cross section recommended by IS & IEC.
De-rating of switchgear depends upon various factors such as cross section area, orientation and material of bus bar,
healthiness of bus-bar joints, panel construction, and ventilation, etc.
#
4000 7200* - - 100 - 6 runs - - 150 - 4 runs
# For Fr-2 4000A, for Aluminum termination, first link COPPER of 300mm length (minimum) to be used.
Note: Above table is based on extensive study of popular bus-bar sizes used to terminate Air Circuit Breakers. However other
bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-bar cross section recommended by IS & IEC.
De-rating of switchgear depends upon various factors such as cross section area, orientation and material of bus bar,
healthiness of bus-bar joints, panel construction, and ventilation, etc.
8-2
Useful Hints
4000 7200* - 150 - 5 runs 150 - 4 runs - 125 - 6 runs 125 - 5 runs
50 -1 run 50 -1 run
800 500 - 60 - 1 run - - - - -
60 - 1 run 60 - 1 run
Note: Above table is based on extensive study of popular bus-bar sizes used to terminate Air Circuit Breakers. However other
bus- bar sizes (in terms of thickness & width) can also be used to achieve bus-bar cross section recommended by IS & IEC.
De-rating of switchgear depends upon various factors such as cross section area, orientation and material of bus bar,
healthiness of bus-bar joints, panel construction, and ventilation, etc.
8-3
Useful Hints
Note: Above table is based on extensive study of popular bus-bar sizes used to terminate Air Circuit Breakers.
However other bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-
Bar cross section recommended by IS & IEC. De-rating of switchgear depends upon various factors
Such as cross section area, orientation and material of bus bar, healthiness of bus-bar joints,
panel construction, and ventilation, etc.
Note: Above table is based on extensive study of popular bus-bar sizes used to terminate Air Circuit Breakers.
However other bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-bar
Cross section recommended by IS & IEC. De-rating of switchgear depends upon various factors
Such as cross section area, orientation and material of bus bar, healthiness of bus-bar joints,
panel construction, and ventilation, etc.
8-4
Useful Hints
Current carrying capacity with copper bus-bars with orientation: Top - Vertical & Bottom - Vertical with adaptors
Please refer to Pages 113-115 to get the corresponding bus-bar cross section area required with different current rating of Air Circuit Breaker.
Note: The values indicated in the above tables are for general guideline for product selection. These values have been extrapolated from test
data and theoretical calculations. They cannot replace practical industrial application or a temperature rise test. However de-rating of
switchgear depends on others factors such as cross section area, orientation and material of bus-bar, healthiness of bus-bar joints, panel
construction, and ventilation, etc.
8-5
Useful Hints
8-6
Bar code