Professional Documents
Culture Documents
Engineering Faculty
Energy Engineering Department
I. The first question that arises is why wind power is different from the
conventional power.
۞ There are three main reasons—the very first reason is that wind
speed is often varying.
۞ The variations occur on all time scales (i.e., seconds, minutes, hours,
days, months, seasons and years) resulting in varying power supplied
to the grid, leading to operational problems.
1-Jun-22 3
9.1 Introduction Cont.
۞ Secondly, WPPs/wind farms are usually connected to distribution
networks or low and medium voltage networks such as 33 kV/66 kV
sub-transmission lines different from the conventional power stations.
1-Jun-22 4
9.1 Introduction Cont.
II. The second question that arises in one’s mind is what are the other
equipment that affect the grid power quality other than the WPPs and how
they are addressed.
۞ The wind power quality depends on the interaction between the WPP and
grid. In most of the WPPs, the output is the standard 690 V AC.
1-Jun-22 5
9.1 Introduction Cont.
۞ The WPPs have step-up transformers either in the nacelle or at the
tower bottom that are connected by a medium voltage (MV) electrical
network in the range 11 kV–33 kV.
1-Jun-22 6
9.1 Introduction Cont.
۞ The point of common coupling (PCC) is the grid point at which the
WPP/wind farm is connected to the grid.
1-Jun-22 7
9.2 Wind Power Impact
۞ The impact of wind power in the electric power system depends, to
a large extent, on the following:
o Wind penetration of 5% is not an issue to the grid operators. Above 5%, the
effect of wind power is felt.
1-Jun-22 8
9.2 Wind Power Impact Cont.
۞ Wind capacity penetration looks at how the total installed wind power
capacity in a certain region is related to the peak load in this region over a
certain time period.
1-Jun-22 9
9.2 Wind Power Impact Cont.
۞ Maximum share of wind power looks at the power balance in a
certain region, taking into account the minimum demand, the maximum
wind power generated and the exchange with neighboring regions or
countries.
۞ This figure must remain below 100% to ensure the correct power
balance in the region. The nearer to 100%, the closer will be the
system to its limits (when wind power would need to be curtailed).
1-Jun-22 10
9.2 Wind Power Impact Cont.
۞ Normally, single WPPs have fast, autonomous self-protecting regulation
of their terminal voltages and they respond rapidly and correctly for grid
voltage events while the Wind Farm Management System (WFMS) and
wind power management software SCADA provide wind farm level
controls to meet the performance requirements (e.g. voltage regulation) at
the PCC by:
1-Jun-22 11
9.2 Wind Power Impact Cont.
۞ Generally, connecting loads to an electric grid reduces the voltage,
while connecting power producing units (like WPPs) increases the
voltage level. In both cases, there are two kinds of impacts on the
network:
1. Impact of WPPs on the grid
2. Impact of grid disturbances on the WPPs
1-Jun-22 12
9.2 Wind Power Impact Cont.
۞ There is the local impact and system wide impact due to the grid
connection of the WPPs/wind farms that affect the electrical power
quality within the ambit of the above two situations.
1-Jun-22 13
9.2 Wind Power Impact Cont.
(a) Local Impacts
۞ These are electrical impacts that can occur in the immediate vicinity
(i.e., localized) due to the connection of a large capacity WPP/wind
farm or due to the electric grid disturbance or both.
1-Jun-22 14
9.2 Wind Power Impact Cont.
(b) System wide Impacts
۞ This global effect may lead to loss of synchronism of synchronous
generators attributed to individual WPPs or wind farms anywhere on
the grid network, not necessarily in the immediate vicinity.
1-Jun-22 15
9.3 Local Impacts Of Wind Power
۞ Since the WPPs are generally located in rural areas in the electric
distribution networks of the grid, power fed by them into the network
could lead to some local impacts which are:
1-Jun-22 16
9.3.1 Node Voltages and Branch Flows
۞ A node is defined as a point where:
1-Jun-22 17
9.3.1 Node Voltages and Branch Flows Cont.
۞ Distribution networks consisting resistance therefore, these remote node
voltages in distribution grids are controlled mainly by changing the
turns ratio of the transformer that connect the distribution grid to higher
voltage level and also by devices that generate or consume reactive
power such as shunt reactors and capacitors.
۞ Transmission networks have lower resistance and the node voltages are
controlled by changing the reactive power generation and consumption
of large scale centralized generators connected to the transmission
lines.
1-Jun-22 18
9.3.2 Fault Currents and Grid Connected WPP
۞ The voltage at the WPP generator is given by:
1-Jun-22 19
9.3.2 Fault Currents and Grid Connected WPP Cont.
۞ Whenever there is a short circuit (fault), the power system is
disturbed.
1-Jun-22 20
9.3.2 Fault Currents and Grid Connected WPP Cont.
۞ The fault level M is an indication of the strength of the network. The
higher the fault level, the stronger will be the grid:
The short circuit apparent power Ssc is defined by the product of the
rated voltage and the short circuit current for a short circuit at the PCC
of the WPP/wind farm.
1-Jun-22 21
9.3.3 Voltage Quality
۞ Voltage quality due to a WPP/wind farm could be defined as the change in
the RMS value of the voltage in a time span of minute or more,
ranging from slow voltage variations to transients..
1-Jun-22 22
9.3.3 Voltage Quality Cont.
۞ To analyze the voltage variation caused by a WPP connected to the
grid of impedance Zs, an impedance model can be used where the
active power is P and reactive power is Q.
1-Jun-22 23
9.3.3 Voltage Quality Cont.
۞ IEC 38 recommends 230 V/400 V as the standard voltage for 50 Hz
systems. consumer’s terminal should not differ more than ±10% of
the rated voltage.
1-Jun-22 24
9.3.3 Voltage Quality Cont.
(a) Slow Voltage Variations
۞ Slow voltage variations (almost considered as steady state voltage) can
be defined as the changes in the RMS value of the voltage occurring
in a time span of many minutes or more caused by variations in load
and power production units.
۞ The steady state voltage variations, generally, should not exceed 2.5%
for a distribution feeder.
۞ If WPPs are connected to it, then the variations should not exceed
5%.
1-Jun-22 25
9.3.3 Voltage Quality Cont.
(b) Rapid Voltage Variations (Flicker)
۞ Voltage flicker is a momentary sag in line voltage, either periodic or
aperiodic, that results in perceptible fluctuations in the intensity of
light from lamps.
۞ In variable speed WPPs, the starting and stopping is smoother, hence the
flicker problem is almost absent.
1-Jun-22 26
9.3.3 Voltage Quality Cont.
(c) Voltage Transients
۞ Voltage and current transients (usually of very short durations of μs
or ms) are undesirable, momentary, but significant deviations from the
normal levels.
۞ These are usually caused by system faults due to the starting and
stopping large constant speed WPPs or lightning discharges.
1-Jun-22 27
9.3.3 Voltage Quality Cont.
(d) Voltage Dip (or Sag)
۞ A voltage dip (or sag or collapse) is a sudden reduction in voltage in the
electric grid followed by a rapid return to its normal value.
۞ Dips between 10% and 15% of the terminal voltage are commonly
due to switching of loads. Whereas, larger dips may be caused by
lightning, trees falling on overhead line or other faults.
1-Jun-22 28
9.3.3 Voltage Quality Cont.
(e) Voltage Swell (Overvoltage)
۞ Voltage swells are those that increase rapidly over the nominal voltage
for a short duration for more than half a cycle or less than one
minute.
1-Jun-22 29
9.3.3 Voltage Quality Cont.
(f) Voltage Imbalance (Unbalance)
۞ Voltage unbalance is usually caused by the reactive power consumption
during the magnetization of the constant speed WPP’s induction
generators at start-ups.
1-Jun-22 30
9.3.3 Voltage Quality Cont.
(f) Voltage Imbalance (Unbalance) Cont.s
۞ Network voltage unbalance is the difference in phase to neutral or
phase-to-phase voltage magnitudes or phase angles of the three-phase
electrical system.
1-Jun-22 31
9.3.3 Voltage Quality Cont.
(g) Voltage Step Changes
۞ A step change in voltage may result in a step change in the torque of
the gearbox of the WPP.
۞ Constant speed Type-A WPPs can cause voltage step changes when
starting or when changing between generators (in case of two
generators or dual- speed windings).
۞ The other three types of generators, i.e., Type-B, Type-C and Type-D
can control their step voltage changes to some extent by varying degrees.
1-Jun-22 32
9.3.3 Voltage Quality Cont.
(h) Harmonics
۞ Harmonics are periodic sinusoidal distortions of the supply voltage or load
current.
1-Jun-22 33
9.3.3 Voltage Quality Cont.
(h) Harmonics Cont.
۞ The effects of harmonics are overheating and equipment failure.
۞ Interharmonics are those components which have frequencies in
between the harmonics of the supply frequency. In other words, they
are distortions of the sinusoidal wave at frequencies which are not
integral multiples of the fundamental.
1-Jun-22 34
9.4 System wide Impacts Of Wind Power
۞ System wide impacts are those, the cause of which cannot be
localized but are a consequence of wind power that cannot be directly
related to individual WPP/wind farm.
1. Reactive power
2. Stability
3. System balancing and frequency
1-Jun-22 35
9.4.1 Reactive Power and WPPs
۞ WPPs are mainly connected on distribution networks where the
resistance of the lines are high, as well as the R/X ratio is high
unlike transmission networks.
۞ Therefore, reactive power and voltage control are the key issues for
integrating wind power into low voltage (LV) and medium voltage
(MV) networks.
1-Jun-22 36
9.4.2 Power System Stability and WPPs
۞ Stability of a power system is defined as the ability of a system to
return to a steady state after a disturbance. Power system stability
can be at the local level or at the global level.
1-Jun-22 37
9.4.2 Power System Stability and WPPs Cont.
(a) Voltage Stability
۞ Voltage stability is the ability of the network to maintain steady voltage at
all buses within the operational ranges under normal conditions and after
being subjected to disturbances.
۞ Sufficient reactive power support is essential for the voltage stability and
voltage control in a grid network.
1-Jun-22 38
9.4.2 Power System Stability and WPPs Cont.
(a) Voltage Stability Cont.
۞ Voltage stability margin is normally presented in the form of P–V
curves which plot the load bus voltage as a function of power that may be
sent over a transmission line at a given load power factor.
1-Jun-22 39
9.4.2 Power System Stability and WPPs Cont.
(b) Thermal Stability
۞ Thermal stability helps in verifying that the transmission lines,
transformers and other equipment are not overloaded due to the
WPP/wind farm power infeed.
1-Jun-22 40
9.4.2 Power System Stability and WPPs Cont.
(c) Steady State Stability
۞ Steady state stability of power system refers to the ability of a system
to return to the steady state after a disturbance of small and gradual
changes in the load with conventional excitation and governor
controls.
1-Jun-22 41
9.4.2 Power System Stability and WPPs Cont.
(d) Transient Stability
۞ Transient stability of a power system refers to the ability of a power system
to return to a stable operating condition following a major disturbance such
as a transmission line short circuit or tripping of a large generating
power plant.
۞ Transient stability depends on both the initial operating state and the
severity of the disturbance which is usually cleared by opening up the
circuit breakers to isolate the fault.
1-Jun-22 42
9.4.2 Power System Stability and WPPs Cont.
(e) Dynamic Stability
۞ Dynamic stability refers to the stability of a power system subjected to
a relatively small and sudden power system disturbance that can be
described by linear differential equations and can be stabilized by a linear
and continuous supplementary stability control.
1-Jun-22 43
9.4.3 Frequency and WPPs
۞ Frequency is the number of changes or cycles per second of the voltage
and current in an AC system and is measured in hertz (Hz).
۞ In Afghanistan ,India and Europe, the nominal value of frequency is 50
Hz and when this is maintained at 50±0.1 Hz, the power system is
said to be stable.
1-Jun-22 44
9.4.3 Frequency and WPPs Cont.
WPPs and Frequency Variations
۞ Electrical grids operating with WPPs connected to weak, isolated
grids can have difficulty in maintaining the normal system frequency.
۞ The system frequency varies when gusty winds cause the power output
of WPPs to change rapidly.
۞ But modern variable speed WPPs using PECs, interface with the grid and
limit the output during gusty (or strong wind periods) winds.
1-Jun-22 45
9.5 Wind Power Variability
۞ The wind power variability is a major problem for the integration of
wind power into the grid network.
۞ The variations in net wind power output that can be expected for a
given time period are within the minute, hour, hour-to-hour, monthly to
seasonal, annual and interannual variable.
1-Jun-22 46
9.5 Wind Power Variability Cont.
b) Variations within an Hour: The intra-hour variations are important
especially when the WPPs reach their cut-out wind speeds and shut
down rapidly from supplying full power to zero power during storms.
1-Jun-22 47
9.5 Wind Power Variability Cont.
d) Monthly and Seasonal Variations: Although these monthly and
seasonal variations are not very important for day-to-day operation and
management of the grid, yet they are important for power system
planning and electricity trading due to forward contracts where the
wind power volume has an influence on price.
1-Jun-22 48
9.6 Islanding
۞ If a section of a grid is isolated (islanded) from the rest of it and if
the WPP/wind farm continues to function as a power source on that
section of the grid, then this phenomenon is called islanding.
1-Jun-22 49
9.6 Islanding Cont.
۞ With regard to system wide impacts, the WPP responses to electric grid
disturbances are summarized in this Table.
1-Jun-22 50
9.6 Islanding Cont.
۞ With regard to system wide impacts, the WPP responses to electric grid
disturbances are summarized in this Table.
1-Jun-22 51
9.7 WPP Electrical Safety And Grid
۞ From safety point of view, every WPP is mandatorily equipped with
some basic essential electrical protective provisions and some critical
features are duplicated to address the system wide impact. Some of
them are highlighted below:
1-Jun-22 52
9.7.1 Active Power Control of WPP
۞ Any form of active power control of a WPP requires a reduction in the
output power.
1-Jun-22 53
9.8 WPP Inertia
۞ All rotating generating systems have inertia. Each element of a
rotating body contributes to the stored energy in the system. This
energy is released as the body reduces speed.
۞ For a WPP, the sum of the energy in all such elements like blades,
hub, shaft, gearbox and generator rotor is the stored energy.
1-Jun-22 54
9.9 Plant Load Factor (Or Capacity Factor)
۞ A power plant with 100% load factor is one which runs every day
at full 100% rated power throughout the year (8760 hours). There is no
downtime for repairs or refueling which is an impossible goal for any
power plant.
۞ Typically, coal plants have 75% capacity rating, since they can run
day and night during any season of the year, if coal is available in
stock.
۞ Fossil fuel plants generally have a capacity factor of 75% (in 8760
hours) typically.
1-Jun-22 55
9.9 Plant Load Factor (Or Capacity Factor) Cont.
۞ WPPs are different from the conventional power plants. The wind is
not available 100% of the time. WPPs depend on the speed of the
wind.
1-Jun-22 56
9.9 Plant Load Factor (Or Capacity Factor) Cont.
1-Jun-22 57
Example
1-Jun-22 58
9.10 Capacity Credit
۞ Due to variability, wind power raises the issue of the displacement of
conventional generating units (e.g. thermal units). WPPs connected to the
utility grid function as fuel savers.
1-Jun-22 59
9.10 Capacity Credit
۞ Capacity credit of wind power may be defined as the power of
conventional generating power plants (e.g. thermal units) that can be
substituted by a variable generation (e.g. wind power or photovoltaic)
without decreasing the power system’s reliability.
1-Jun-22 60
Example
1-Jun-22 61
1-Jun-22 62