八、 应用举例....………………………………………………………...……5
九、 设备使用与安装………………………………………………………...5
十、 故障分析……………………………..……………………………...…..8

Table of Contents(ENGLISH). 9

1、 Introduction……………………………………………………………….10
2、 Requirement for Optical Interface of Protective Relay System……….….10
3、 Requirement for Electrical Interface of Transmission System ..………….11
4、 Functions and Features ..………………………………………………….11
5、 Technical Specifications……………………………………………..……11
6、 Functional Assemblies Description…...………….……………………….13
7、 Equipment Architecture ..…………………………………………………13
8、 Installation and Operation…………………………………………… ...…15
9、 Malfunction Analysis...……………………………………………………18
10、 OC600 Soft Manual...………………………………...…………………19
OC600 使用说明(OC600 Operation Manual)

一、 简介

OC600 为电力继电保护系统的配套组件。

该产品应用在电力继电保护系统中,是与继电保护装置的光口相配套的通
信设备,即完成继电保护设备光接口到 PCM 2Mb/s 的转换。光接口兼容用户的
有效负载是 N × 64Kb/s,并适应 IEEEC37.94 关于继电保护设备和多路复用
设备之间 N×64kbit/s 光接口协议。继电保护的数据信息全透明通过。2Mb/s
电接口符合 ITU-T G.703、G.704。

二、 本设备光接口对继电保护设备的接口要求

1、 光接口指标

光纤类型 单模 多模
光纤连接器 FC、ST /PC FC、ST/PC
传输媒质 9/125 μm 62.5/125μm
传输波长 1310 nm 830nm ~ 850 nm
发光功率 < -10dBm -13 dBm ~ -17 dBm
光信号接收灵敏度 <-35dBm < -30dBm
饱和光功率 -3dBm -7dBm
消光比 10dB 10dB
推荐传输距离 ≤50km ≤1.0km

2、光接口编码

本设备实现光到成帧 2.048Mb/s 的转换,光接口数据速率包括两种类型,


本设备能适应以下两种继电保护设备光口数据类型。

(1) N×64Kb/s (N = 1, 2, 4, 8, 16 ) 光接口


(2) 512Kb/s 经 1B4B 编码形成 2048 Kb/s 光接口
(3) 帧结构符合 IEEE C37.94 光接口协议

1
OC600 使用说明(OC600 Operation Manual)

三、 本设备电接口对传输系统的要求
本设备必须成对使用,占用传输系统的一个 2.048Mb/s 带宽,该 2.048Mb/s
不可再上下别的业务。接口特性应符合以下要求:

接 口 : 符合 ITU-T G.703、G.704、G.823 等建议


比 特 率 : 2048Kbit/S ± 50ppm
线路码型 : HDB3
阻 抗 : 75Ω 非平衡

四、 功能与特点

(1) 光路可实现单模或多模,更换器件即可达到。
(2) 光口速率能适应不同厂家的多种型号,只要光口速率和编码符合前面所
述三种情况。
(3) 光口数据插入到成帧 2.048Mb/s。
(4) 主从时钟可设定。
(5) 设备具备声光告警。
(6) 2.048Mb/s 接口符合 G.703,G.704,G.823。

五、 技术指标

1、 光接口指标

光纤类型 单模 多模
光纤连接器 FC/PC FC/PC

传输媒质 9/125 μm 62.5/125μm


传输波长 1310 nm 850 nm
发光功率 -8dBm ~ -12dBm -13dBm ~ -17dBm
光信号接收灵敏度 < -35dBm < -30dBm
饱和光功率 -3dBm -7dBm
消光比 10dB 10dB
推荐传输距离 ≤50km ≤1.0km

2
OC600 使用说明(OC600 Operation Manual)

2、 光接口类型

本设备实现光到成帧 2.048Mb/s 的转换,光接口数据速率包括两种类型,


本设备能适应以下两种继电保护设备光口数据类型。

(1) N×64Kb/s (N=1,2,4,8,16)


(2) 512K Kb/s 经 1B4B 变换为 2048Kb/s
(3) 帧结构符合 C37.94 的 2048Kb/s

3、 2M 电接口指标和其它特性
接 口 : 符合 ITU-T G.703、G.704、G.823 等建议
比 特 率 : 2048Kb/s ± 50ppm
线路码型 : HDB3 阻抗 :75Ω非平衡
帧 结 构 : PCM31C 附加延时 :< 250μs
电 源 : -48V 直流(-36V ~ -72V) 功耗 : ≤5.0 W
温度范围 : 0℃ ~ 40℃ 相对湿度 : ≤85%(25℃时)
尺 寸 : 19 英寸 1U 机箱 重量 : < 2 Kg

六、 工作原理

该光电接口转换器可单独使用,实现用户光接口到 2M 成帧信号之间的转
换。 也可与 TY–3006 系列电路无损伤保护切换设备配合使用,并将两个设备
集成为一体,完成光电信号转换后实现传输路由保护切换。
用户光接口的有效负载是 N × 64K 型并适应 IEEEC37.94 关于继电保护
设备和多路复用设备之间 N×64kbit/s 光接口协议。
该产品可根据要求兼容多种不同用户光接口。
如果光口数据信号是经过编码(如 1B4B)后的信号,则信号需经过编解
码器进行编解码,否则信号将不进行编解码处理。





光 解 码
电 编 码 解

光电接口转换器工作原理图

3
OC600 使用说明(OC600 Operation Manual)

七、 设备结构

1、 前面板

OC600 Fiber Optic Converter


Optic E1
PWR1 ―O
PWR2
-3
LOS LOF 10 10 -6
LOS AIS LOF ERR WORK ACK ―O

1 2 3 4 5 6 7 8 9 10 11 12

1-光纤 LOS 告警指示灯 2-光纤 LOF 告警指示灯


3-光纤 10-3 误码指示灯 4-光纤 10-6 误码指示灯
5-E1 口 LOS 告警指示灯 6-E1 口 AIS 告警指示灯
7-E1 口 LOF 告警指示灯 8-E1 口 CRC4 误码指示灯
9-工作指示灯 10-清铃开关、指示灯
11-1、2 路电源指示灯 12-1、2 路电源开关

2、 后面板

Tx Rx Tx Rx
DC1-48 DC2-48 ALM SET RS232
+- +-

。 E1 F.O

1 2 3 4 5 6 7 8

1-电源 1 接线座 2-电源 2 接线座


3-告警输出座 4-设置拨码(配置拨码开关)
5-传输 E1 输入、输出接口 6-网管控制接口
7-光输入、输出接口 8-机箱接地端子

4
OC600 使用说明(OC600 Operation Manual)

八、 应用举例
本设备是专为电力系统的继电保护设备提供的光接口装置。该设备将继电

保护设备的光路转换为 2.048Mb/s 标准帧结构 PCM31C。应用连接图如下:

继电保护设备 接口转换
SDH 设备

继电保护设备
接口转换 传输网
SDH 设备

继电保护设备
接口转换 自
动 SDH 设备


继电保护设备
接口转换 自
动 传输网
切 SDH 设备

九、 设备使用与安装

(一)拨码开关的设置(0-ON,1-OFF)

地址 8 7 6 5 4 3 2 1
B3 B2 B1
用户可设置 ON-- 发时钟 未 未 ON--256K/s 光口透明传 未用 光口速率(参见光口
拨码开关 为主时钟。 用 用 输,不检测编码方式。 线路速率设置表)
低(ON)有效 OFF--发时钟 OFF--256K/s 由 64K/s 进
为从时钟。 行 1B4B 编码。

5
OC600 使用说明(OC600 Operation Manual)

光口线路速率设置表(0-ON,1-OFF)

B3B2B1 光口线路速率 占用 PCM-2M 时隙 编码方式


000 64K 1,5,9,13,17,21,25,29 和 0,4,6 透明码
001 128K 16 个奇时隙 透明码
010 C37.94 占用全部时隙
100 256K 1,9,17,25 和 0,4,6 透明码,1B4B 码
101 512K 1,5,9,13,17,21,25,29 和 0,4,6 透明码,1B4B 码
110 1024K 16 个奇时隙和 0,4,6 透明码,1B4B 码
111 2048K 1,5,9,13,17,21,25,29 和 0,4,6 1B4B 编码

注:“透明码”表示码型不是 1B4B 码,设备不进行解码,数据透明通过。

(二)安装

1、 光电转换/保护切换柜的安装

根据工程图纸安装光电转换/保护切换柜。固定好机柜后,正确连接交直流
线和地线;检查凤凰端子排和空气开关的连接,测量供电电压是否正常;固定
绑牢电源线和地线。对于已装有光电转换/保护切换柜的可直接进行下一步操
作。

2、 设备的安装

设备开箱,取出机器,安装固定在光电柜内,根据后面板的说明,正确连
接电源至本机,开启电源开关,电源指示灯亮,说明设备正常,否则应马上关
闭电源开关,进行检查。

6
OC600 使用说明(OC600 Operation Manual)

3、 按下图说明连接 2M 口和光口。

光电转换机柜

DC1-48V DC2-48V ALM RS232 Tx Rx TX RX


+ - + - SET


E1 F.O

2M 电缆

光纤
DDF
ODF
2M 电缆

通信机房 传输系统 2
光纤

继电保护
继电保护 装置
机房

设备连接示意图

7
OC600 使用说明(OC600 Operation Manual)

4、 正确设置设备的拨码开关。

按实际情况正确设置拨码开关,否则设备将不能正常工作。本设备的光口
线路速率和编码设置一定要和与它连接的继电保护设备的光口线路速率和编码
设置一致。例如:如果继电保护设备原始数据为 64Kb/s,通过 1B4B 编码形成
256Kb/s 的数据送光口,则应将 B3B2B1 设为 100,B5 设为 1。
时钟也应正确设置,本设备主从时钟可选。从时钟时将 B8 设为 1(OFF),
主时钟时设为 0(ON)。

5、 检查设备是否能正常工作

在其它设备都正常情况下,打开机器的电源,应能看到各告警指示灯相继
熄灭。如告警指示灯显示有告警,应检查相应端口是否连接正确,光口指标是
否相符。如告警指示灯能相继熄灭,则表示设备能正常工作,则设备安装完毕。

十、 故障分析

1、 电源指示灯不亮
应检查电源开关是否正常,电源线连接是否正确。注意系统配置为 -48V
直流供电正负极不要接反。
2、 2M 告警指示灯亮
则应检查 2M 信号线是否正确接入,传输网是否正常工作。
3、 光路告警指示灯亮
则应检查光路是否正确接入,光路指标是否匹配。
4、 光路误码指示灯亮
检查光口线路速率和编码设置是否和继电保护设备的光口速率相匹配。
5、 继电保护设备通信通道异常
测试继电保护设备处的收发光功率是否正常,中间的通信设备是否都工作正
常。

8
OC600 使用说明(OC600 Operation Manual)

OC600 Fiber Optical E1 Converter


Installation and Operation Manual

Safety Notice
The OC600 Fiber Optical E1 Converter contains potentially lethal voltages inside
the case. Extreme caution should be exercised when the cover is removed by
following the precautions listed below.
Never operate the equipment with the cover removed. Never remove the cover with
power applied. As a safety measure the power cord should be disconnected from the
unit when preparing to remove the cover.
This Fiber Optical E1 Converter is designed for indoor use. Do not operate this
equipment in a wet environment or outdoors.
Do not operate the Fiber Optical E1 Converter in an unsafe environment near
explosive or flammable gases or liquids.
Insure good grounding practices. The grounding lug on the rear of the Fiber Optical
E1 Converter should be connected to a good earth ground with low impedance cable
in rack installations.
The Fiber Optical E1 Converter is supplied with an DECA power inlet module
designed to accept a 3-wire mains connection consisting of an earth ground, neutral
and –48V.

EMC Notice
To maintain compliance with EMC standards the following precautions must be
observed.
The equipment must be operated with the cover and all cover screws in place.
All rear connections are designed to have integral shielding on the cable and
connector assembly. “D” type signal connectors must have grounding fingers on the
connector shell.

About This Manual


This manual is composed of several “Sections” or “Chapters”. This manual provides
Installation and Operating procedures for the Fiber Optical E1 Converter. This
manual is used to explain the operating procedures for the Fiber Optical E1
Converter and present its capabilities and specifications.

9
OC600 使用说明(OC600 Operation Manual)

1. Introduction

OC600 Fiber Optical E1 Converter, which is used in the Electrical Protective Relay
system, is the communication equipment interfaced to the optical ports of the
Protective Relay. It converts the optical signal of low rate from the Protective Relay
to the PCM 2048Kb/s electrical signal.
The equipment converts between the optical signal to or from the Protective Relay
and the PCM 2048Kb/s electrical signal to or from the transmission equipment. The
line rate of the optical interface can be N×64Kb/s type or can be adapt to IEEE
Standard C37.94 (C37.94 for N Times 64 Kilobit Per Second Optical Fiber
Interfaces Between the Teleprotection and the Multiplexer Equipment). The
information from the Protective Relay is transparent through the OC600 Equipment.
The PCM 2048Kb/s electrical interface meets ITU-T Standard G.703, G.704.

2. Requirement for Optical Interface of Protective Relay System


The Specifications Of the Optical Interface
Content Single Mode Multi Mode
Connector FC/PC or ST/PC FC/PC or ST/PC
Transmission medium 9/125 μm 62.5/125μm
Wave length 1310 nm 830nm ~ 850 nm
Tx power < -10dBm -13 dBm ~ -17 dBm
Rx sensitivity limit <-35dBm < -30dBm
Rx saturating power -3dBm -7dBm
Extinction ratio 10dB 10dB
Transmission length ≤50km ≤1.0km

The Line Rate and the Coding Way Of the Optical Interface
OC600 Fiber Optical E1 Converter has three types of line rate of the optical
interface. So the Protective Relay must meet one of the three types of optical
interfaces as listed as below.
1) N×64Kb/s line rate type ( N = 1,2,4,8,16 ).
2) 2048 Kb/s line rate type, which is converted from 512Kb/s by way of 1B4B
coding.

10
OC600 使用说明(OC600 Operation Manual)

3) 2048 Kb/s line rate type, with the frame architecture corresponding to IEEE
standard C37.94.

3. Requirement for Electrical Interface of Transmission System

A couple of OC600 Fiber Optical E1 Converters must be used at the two ends of a
Protective Relay system at the same time. The couple of OC600 converters occupy
one 2048Kb/s transmission link of the transmission system. The 2048Kb/s
transmission link can’t load other service any more.

The features of the electrical interface must meet the demands listed as below.

Interface: ITU-T G.703, G.704 and G.823


Bit rate: 2048Kb/s
Line code: HDB3
Impedance: 75 ohm

4. Functions and Features

1) Single mode or multimode optical interface.


2) Corresponds to different optical interfaces of many kinds of Protective Relays,
only if the Protective Relays have one of the three types of optical interfaces
listed in the foregoing.
3) Inserts the data from the optical port into the 2048Kb/s framing data.
4) Master and slave clock.
5) Alarms can be heard or seen on the equipment.
6) Meets the ITU-T G.703, G.704 and G.823 specifications.

5. Technical Specifications
The Specifications Of the Optical Interface
Content Single Mode Multi Mode
Optical fiber connector FC/PC FC/PC
Transmitting media 9/125 μm 62.5/125μm
Transmitting wave length 1310 nm 850 nm

11
OC600 使用说明(OC600 Operation Manual)

Tx power -8dBm ~ -12dBm -13dBm ~ -17dBm


Rx sensitivity limit < -35dBm < -30dBm
Rx saturating optical power -3dBm -7dBm
Extinction ratio 10dB 10dB

The Line Rate and the Coding Way Of the Optical Interface

OC600 Fiber Optical E1 Converter has three types of line rate of optical interface.
So it can be adapted to the three types of optical interface of the Protective Relay as
listed as below.
1) N×64Kb/s line rate type ( N = 1,2,4,8,16 ).
2) 2048 Kb/s line rate type, which is converted from 512Kb/s by way of 1B4B
coding.
3) 2048 Kb/s line rate type, with the frame architecture corresponding to IEEE
standard C37.94.

The 2048Kb/s Electrical Interface and other feture

l E1 interface: meets ITU-T G. 703 Recommendations


l Bit rate: 2048Kbit/s ± 50ppm
l E1 line code type: HDB3
l Impedance: 75 ohm non-balance
l Frame structure: PCM31C
l Extra delay: < 250 μs
l Power supply: DC-48V (-36V ~ -72V)
l Power consumption: ≤5.0W
l Size: 19-inch standard rack mounting, Height 1U
l Operation temperature: 0℃ ~ 40℃
l Operation Relative humidity: ≤85% (25℃)
l Net Weight: < 2 Kg

12
OC600 使用说明(OC600 Operation Manual)

6. Functional Assemblies Description

The original data rate or line rate after coding can be one of the following:
64Kb/s, 128Kb/s, 256Kb/s, 512Kb/s and 1024Kb/s
2048Kb/s (1B4B or C37.94)
If the line signal on the fiber is a coded one like 1B4B type, it will be passed to
the CODEC part. Otherwise this CODEC part will be bypassed.

Mux/
Dmux
O/E
CODEC

7. Equipment Architecture
7.1 Front Panel for OC600

Fiber Optical E1 Converter OC600


F.O E1
Pwr 1 ―O
Pwr 2
LOS LOF 10-310-6 LOS AIS LOF ERR WORK CLR
―O

1 2 3 4 5 6 7 8 9 10 11 12

1) LOS indication LED of the optical interface


2) LOF indication LED of the optical interface
3) 10-3 error rate indication LED of the optical interface
4) 10-6 error rate indication LED of the optical interface
5) LOS indication LED of the E1 interface
6) AIS indication LED of the E1 interface
7) LOF indication LED of the E1 interface
8) E1 CRC error
9) WORK indication LED of the local equipment
10) Alarm Clear button and indication LED
11) The two power indication LEDs
12) The two power switches

13
OC600 使用说明(OC600 Operation Manual)

7.2 Back Panel for OC600


DC1-48V DC2-48V ALM RS232 Tx Rx TX RX
+ - + - Set

。 F.O
E1

1 2 3 4 5 6 7 8

1) Power 1 inlet
2) Power 2 inlet
3) Alarm Out inlet
4) The Configue switch
5) NMS interface of RS232
6) In and Out ports of transmission E1 ports
7) TX and RX ports of the optical interface
8) Mask Ground

7.3 Applications

Protection Relay OC600


SDH

Protection Relay
OC600
SDH

Transmission network

Protection Relay OC600 Auto switching

SDH
Transmission network

Protection Relay Auto switching


OC600

SDH

14
OC600 使用说明(OC600 Operation Manual)

8. Installation and Operation


8.1 Setting
Setting Switch on the back panel ( 0-ON, 1-OFF)
bit 8 7 6 5 4 3 2 1
B3 B2 B1
Setting 0-Lcal clock No No 0-256K transparent No Line rate on the
(0– 1-slave clock use use 1-256K use optical interface
ON ) 1B4B from 64Kb/s

Line rate setting of the optical interface (the three least significant bits, 0-ON,
1-OFF)
B3B2B1 Line rate Slots used in PCM-2M Coding way
000 64K 1,5,9,13,17,21,25,29 和 0,4,6 transparent

001 128K 16 odd slots and 0,4,6 transparent


010 C37.94 All the slots 0-31
100 256K 1,9.17,25 和 0,4,6 transparent,1B4B
101 512K 1,5,9,13,17,21,25,29 and 0,4,6 transparent,1B4B
110 1024K 16 odd slots and 0,4,6 transparent,1B4B
111 2048K 1,5,9,13,17,21,25,29 and 0,4,6 1B4B
Note: the word “transparent” means the coding way is not 1B4B. The data will not
be put to the CODEC. It’s just transmitted to the next part transparently and the
coding way is not care.

8.2 Installation
8.2.1 Install the shelf
Fix the shelf first, and then connect the power and ground cords to the shelf
according to the engineering draft. Check the connection of the phoenix contacts and
the circuit breakers. Measure the power voltage to check if it is OK. Bind the power
and ground cords. If the shelf has been installed before hand, you can go to the next
step directly.

15
OC600 使用说明(OC600 Operation Manual)

8.2.2 Install the equipments


Take out the equipments from the case and then fix them into the shelf. Connect the
power cords to the back panel from the phoenix contacts according to the
instructions above and turn on the power. If the power LED is on, that’s OK.
Otherwise, turn off the power immediately and check the connection thoroughly.

RJ45:

Pin No. Direction Function

1 Not used

2 RxD Receive data

3 TxD Transmit data

4 Not used

5 GND Signal ground

6 Not used

7 Not used

8 Not used

16
OC600 使用说明(OC600 Operation Manual)

8.2.3Connect the 2M cables and fibers

The graph of the wiring

O/E Converter Shelf

DC1-48V DC2-48V ALM RS232 Tx Rx TX RX


+ - + - Set

。 F.O
E1

fiber

2M Cable

fiber
DDF
ODF
Communication 2M Cable
Room

Transmission
system 2 fiber

Protective
Protective Relay Relay
Room

17
OC600 使用说明(OC600 Operation Manual)

8.2.4 Set the Configue Switches correctly

The Configue switches should be set correctly before the converter works.
Otherwise it can’t work.
The rate and coding way setting should be set as same as that of the Protection Relay
equipment it connect to. For example, if the Protection Relay equipment has a rate
of 64Kb/s converted to 256Kb/s through 1B4B, you should set the B3B2B1 to 100
and B5 to 1(OFF).
At last, you should set the clock correctly. The clock of OC600 can be set master or
slave. Set the B8 to 1(OFF)if it use slave clock, and to 0(ON)if it use the master
or local clock.

8.2.5 Check the work of the equipment

Turn on the power and observe the work of the equipment please. If all the ALARM
indication LEDs are OFF, the equipment is OK. Otherwise, check the connection of
the E1 and optical ports, settings, optical specifications first, and then observe again.
If all is OK, you have finished the installation.

9. Malfunction Analysis

1) Power LED Not On


2) Check the connection of the power inlet. Make sure the power is –48v and you
don’t make a mismatch.
3) 2M Alarm LED On
4) Check the connection of the E1 ports. Make sure that the transmission system is
working.
5) Optical Alarm LED On
6) Check the connections of the optical ports. Make sure that the optical
specifications are met.
7) Optical Err LED on
8) Check the line rate of the optical ports. Make sure that the setting of the line rate
and coding way is as same as that of the Protection Relay Equipment.
9) Communicational Channel Error On the Protection Relay Equipment
10) Test the optical power to and from the Protection Relay Equipment. Make sure
all the connections are correct and all the middle equipments are working.

18
OC600 使用说明(OC600 Operation Manual)

10. OC600 SOFT MANUAL

Setting the Current Date and Time of the OC600


Set the date and time of the OC600 in order to produce OC600 Device Event Report
correctly. Implement the follow steps for setting current date and time of the OC600.

Step 1. Insert the CD from enclosed OC600 Fiber Optical E1 Converter into your
CD-ROM driver. Copy the OC600.EXE software into your PC. When
copy is complete, you can start software tool application.
Step 2. Make the RS232 cable connection between the OC600 and PC.
Step 3. Double click the OC600.EXE that has been copied into your PC. The
OC600 window such as Figure 1 should show on your PC screen.

Figure 1 OC600 Software Window

Step 4. Click Select Com button first. Then select RS232 serial communication
interface used from the COM drop-down list. Next click Set Com button.
Step 5. Input the current date from the Date drop-down list. And Input the current
time from the Time drop-down list. Click Set Device Time button.

19
OC600 使用说明(OC600 Operation Manual)

Step 6. Click Get Device Time button again and watch the date and time of the
TY-3006J showing in the Date drop-down list and Time drop-down list. If
the date and time are not correct you need continue Step 5 and Step 6.

Reading and Printing Event Record Report

In order to read and print the OC600 Device Events Report you follow the next steps.
The flash memory in each OC600 can store about 400 device events.

Step 2. Make the RS232 cable connection between the OC600 and PC.
Step 3. Double click the OC600.EXE that has been copied into your PC. The
OC600 window should show on your PC screen.

Figure 2 OC600 Software Window

Step 4. Click Select Com button first. Then select using RS232 serial interface
from the COM drop-down list. Next click Set Com button.
Step 5. Click Read Device Events button. All device events of the OC600 such as

20
OC600 使用说明(OC600 Operation Manual)

Figure 2 showed are listed since last click Clear Flash button.
Step 6. If you need a hard copy of these device events, you click Print Device
Events button. The OC600 Events Report (Figure3) can be printed out.
Step 7. If you need not keep all of these device event records, you click Clear
Flash button and delete all of these device events.

Figure 3 OC600 Events Report