PP2028/2003/Issue 5

SERIES 60 DETECTORS FOR USE IN


HAZARDOUS AREAS
The Series 60 range of smoke and heat detectors
includes intrinsically safe versions, specifically
developed for use in hazardous areas.

AVAILABILITY
An ionisation smoke detector, integrating ionisation
smoke detector and five grades of heat detector are
available.

FUNCTION
The Series 60 IS detectors are functionally
equivalent to their standard Series 60 counterparts.
They differ in design only in that their circuits and
construction have been modified to conform to the
requirements of EN 50014: 1997 and amendments 1
& 2, EN 50020: 2002 and EN 50284: 1999. Part nos:
55000-212 Ionisation smoke detector
All types are certified EEx ia IIC T5 at ambient 55000-213 Integrating ionisation smoke detector
temperatures up to 40°C or T4 at ambient 55000-110 Grade 1 heat detector ( 60°C)
temperatures up to 60°C. 55000-111 Grade 2 heat detector ( 65°C)
55000-112 Grade 3 heat detector (75°C)
The EC-Type Examination certificate number, 55000-113 Range 1 heat detector ( 80°C)
applicable to all types, is BAS02ATEX1288. 55000-114 Range 2 heat detector (100°C)
45681-207 Base

MECHANICAL CONSTRUCTION The base is marked with the legend 'PART OF


Series 60 IS detectors use the same outer casings BASEEFA CERTIFIED DETECTOR - CERT NO
as the standard Series 60 detectors, and therefore BAS02ATEX1288'. Use of any other base will
share the same dimensions. The detectors are invalidate the approval.
identified as intrinsically safe by a printed legend
around the lid (see photo above). SYSTEM REQUIREMENTS
The detectors must be used in a system which
The detectors must be used with the certified includes suitable safety barriers and which is
Series 60 IS base which is considered for certified by BASEEFA or other competent body.
certification purposes to be part of the detector.
Apollo Fire Detectors has verified the performance ELECTRICAL CHARACTERISTICS
and obtained system certification for a system
The following characteristics apply at 24V DC
incorporating any of the following safety barriers:
and 25°C unless otherwise stated:
Any certified 28V/300 Ω shunt safety barrier Supply voltage 14 to 28V DC
MTL4061 (non-polarised)
Pepperl + Fuchs KFDO-ICS-Ex1.51 or Ex2.51 Quiescent current
Ionisation detectors 45µA
Other barriers have been approved and are Heat detectors 50µA
included in the system certification but system Alarm load 310Ω (typical)
compatibility must be checked due to dc loading in series with 2 volt drop
characteristics. Alarm current
The BASEEFA system certificate number is (minimum) 10mA
Ex97D2054. (maximum) 60mA
Minimum alarm voltage 5V
The system certification allows up to 20 Series 60 (at least 10V for good LED illumination)
IS detectors to be connected to a single barrier
All detectors are marked
circuit with an end-of-line resistor of not less than
1.8kΩ. However, it must be ensured that the voltage 0600
available at each detector is above the minimum INSTALLATION GUIDELINES
specified in the quiescent condition. It is also The detectors must be installed in accordance with
important to ensure that the alarm load is suitable the appropriate local code of practice eg BS5435
for the control and indicating equipment. in the UK. The following points should be noted in
addition:
The system certification also allows the use of
remote LED indicators. These may be connected It is important that detectors are installed in
to individual detectors or may use a connection such a way that all terminals and connections
common to two or more detectors as shown below: are protected to at least IP20 when the detector
L1 IN and L2 are L2 is a line in and When a remote indicator is is in the base. If the base is mounted on a
CONTROL polarity insensitive line out connection used L1 must be connected


UNIT
+
terminal to the positive line in conduit box with a diameter of less than 85mm
SAFETY then the base should be fitted with the Series
BARRIER

L1
IN
-R L1
IN
-R L1
IN
-R
60/XP95 Backplate, part number 45681-233.
L1OUT L2 L1OUT L2 L1OUTEnddevice
of line
L2
The base contains an earth terminal which is
provided simply as a convenient termination
Schematic wiring diagram of Series 60 IS monitored detector circuit point for cable screens. It is not essential for
Positive line is connected to Three detectors with the correct operation of the detector and is not
CONTROL L1 IN (detector 1) to enable common remote negative
connection to remote positive

UNIT
+
intended to be used for a safety (IS) earth.
SAFETY
BARRIER

L1
IN
-R L1
IN
-R L1
IN
-R
APPROVALS
End of line
The Product Certification Technical Files for the
L1 L2 L1 L2 L1 L2
OUT OUT OUT
device
Series 60 IS range are held by BASEEFA (2001) in
accordance with the requirements of the ATEX
Schematic wiring diagram of Series 60 IS monitored detector circuit with a
common remote indicator
Directive, 94/9/EC.
Note: Polarity must be observed on detectors which have a remote indicator connected.

Series 60 IS detectors have been approved by LPCB,


For information on the operating principles of
VdS, DBI, IFA and PAVUS to EN54. They have also
the Series 60 range, please refer to the Series
been approved for marine use by the following
60 Engineering Product Guide, PP1050. For an
bodies:
introduction to Intrinsic Safety and classification
of Hazardous Areas, please refer to the XP95 IS American Bureau of Shipping
Engineering Product Guide, PP1095. Bureau Veritas
Det Norske Veritas
Information given in this document is given in good
Germanischer Lloyd
faith, but Apollo Fire Detectors Limited cannot be
Lloyds Register of Shipping
held responsible for any omissions or errors. The
Maritime and Coastguard Agency
company reserves the right to change specifications
of products at any time without prior notice. Details of approvals held are available on request.
DO NOT SCALE IF IN DOUBT - ASK METRIC DIMENSIONS THIRD ANGLE PROJECTION

1 2 3 4 5 6 7 8 9 10 11 12

TABLE 1 HAZARDOUS AREA SAFE AREA


A
DEVICE TYPE CERTIFICATE No.
ION CHAMBER 55000-200 Ex 96D2439
SERIES BAS02ATEX1288 REFER TO
SMOKE DETECTOR NOTE 6
HEAT DETECTOR 55000-100 Ex 96D2439
SERIES BAS02ATEX1288
IN IN IN IN IN IN
B
-R L1 -R L1 -R L1 -R L1 -R L1 -R L1 +
END OF LINE

L2 DEVICE L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1
TABLE 2 OUT OUT OUT OUT OUT OUT

CAPACITANCE INDUCTANCE L/R RATIO REFER TO A COMBINATION OF UP TO 20 OF THE - 1. ANY SHUNT ZENER DIODE SAFETY
GROUP OR NOTE 7 BARRIER CERTIFIED BY BASEEFA
C uF mH uH/ohm CERTIFIED DEVICES LISTED IN TABLE 1
OR ANY EEC APPROVED CERTIFICATION
BODY TO [EEX ia] IIC HAVING THE
IIC * 0,083 4,2 55 FOLLOWING OR LOWER OUTPUT
PARAMETERS:

Uz = 28V
IIB 0,65 12,6 165 Io or I MAX : OUT = 93.3 mA
D Po or W MAX : OUT = 0,67 W

IIA 2,15 33,6 440 2. IN ANY SAFETY BARRIER USED


REFER TO THE OUTPUT CURRENT MUST BE
NOTE 6 LIMITED BY A RESISTOR "R"
* SEE NOTE 4 SUCH THAT :-
NOTE 1.
IN IN IN IN IN IN Io or I MAX : OUT = Uz
E EACH BARRIER FED CIRCUIT MUST BE A SEPARATE -R L1 -R L1 -R L1 -R L1 -R L1 -R L1 + R
END OF LINE
CIRCUIT & MUST NOT BE INTERCONNECTED WITH ANY
L2 DEVICE L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1
OTHER ELECTRICAL CIRCUIT. 1 11
OUT OUT OUT OUT OUT OUT

2 12
NOTE 2.
REFER TO A COMBINATION OF UP TO 20 OF THE - PEPPERL + FUCHS KHD0-ICS/Ex151
THE ELECTRICAL CIRCUIT IN THE HAZARDOUS AREA NOTE 7 CERTIFIED DEVICES LISTED IN TABLE 1 OR KFDO-CS/Ex151 CURRENT REPEATER,
MUST BE CAPABLE OF WITHSTANDING AN a.c. TEST BASEEFA CERTIFICATE No: Ex88B2331.
F OR KHD0-CS-Ex1.54 OR KFD0-CS-Ex1.54
VOLTAGE OF 500 VOLTS RMS. TO EARTH OR FRAME
CURRENT REPEATER.
OF THE APPARATUS FOR ONE MINUTE. BASEEFA CERTIFICATE No: Ex95C2064.
ATEX CERTIFICATE N0: BAS00ATEX7087.
NOTE 3.
THE INSTALLATION MUST COMPLY WITH NATIONAL
INSTALLATION REQUIREMENTS (e.g. IN THE UK
G BS5345-4:1977). REFER TO
NOTE 6
NOTE 4.
THE CAPACITANCE & EITHER THE INDUCTANCE OR THE
INDUCTANCE TO RESISTANCE (L/R) RATIO OF THE IN IN IN IN IN IN

-R L1 -R L1 -R L1 -R L1 -R L1 -R L1
HAZARDOUS AREA CABLES MUST NOT EXCEED THE END OF LINE

H PARAMETERS SPECIFIED IN TABLE 2. L2 DEVICE L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1


OUT OUT OUT OUT OUT OUT
INTEGRATING IONISATION DETECTORS TO Ex96D2439/2
SAFE AREA APPARATUS

CODED IIB, MUST NOT BE USED FOR GROUP IIC APPLICATIONS.


REFER TO A COMBINATION OF UP TO 20 OF THE AMENDED TO MEET NEW APROVAL
4 A2651
NOTE 5. NOTE 7 CERTIFIED DEVICES LISTED IN TABLE 1 REQUIREMENT. 8/02 LPC.

THE CABLE MAY BE SEPARATE CABLES OR A TWIN PAIR 3 A2301 NOTE 4 AMENDED. JAN,00 LPC.
I OR A PAIR CONTAINED IN A TYPE 'A' OR A TYPE 'B' A2002 PEPPERL & FUCHS KHD0-CS-Ex1.54,
+ 2 KHD0-CS-Ex2.54, KFD0-CS-Ex1.54 AND
MULTICORE CABLE (AS DEFINED IN CLAUSE 5.3 OF
KFD0-CS-Ex2.54 BARRIERS ADDED TO
BS5501-9:1982. EN50039) PROVIDED 1 11
- DIAGRAM. JAN,98 LPC.
THAT THE PEAK VOLTAGE OF ANY CIRCUIT CONTAINED 2 12
WITHIN THE MULTICORE DOES NOT EXCEED 60 VOLTS. 4 9 1 A1846 DESIGN FIRM 2-97, LPC.
+
5 10 A INTRODUCED 1/97 LPC
NOTE 6. REFER TO
NOTE 6 - ISS. D.C.N. CHANGE, DATE AND SIGNATURE
UNSPECIFIED EXCEPT THAT IT MUST NOT BE SUPPLIED FROM NOR CONTAIN UNDER NORMAL OR ABNORMAL
CONDITIONS A SOURCE OF POTENTIAL EXCEEDING 250 VOLTS RMS OR 250 VOLTS DC WITH RESPECT TO EARTH.

J PEPPERL + FUCHS KHD0-ICS/Ex251 MOD.


AN EXTERNAL LIGHT EMITTING DIODE (LED), MAY BE OR KFDO-CS/Ex251 CURRENT REPEATER, SPECIFICATION MATERIAL
CONNECTED TO TERMINALS 'L1 IN' OR 'L1 OUT' AND BASEEFA CERTIFICATE No: Ex88B2331.
'-R', FOR REMOTE INDICATION OF AN ALARM CONDITION. OR KHD0-CS-Ex2.54 OR KFD0-CS-Ex2.54
IN IN IN IN IN IN

-R L1 -R L1 -R L1 -R L1 -R L1 -R L1 CURRENT REPEATER.
AS AN ALTERNATIVE, ANY NUMBER OF DETECTORS MAY BE
END OF LINE BASEEFA CERTIFICATE No: Ex95C2064.
CONNECTED TO A COMMON LED INDICATOR BY A COMMON ATEX CERTIFICATE No: BAS00ATEX7087. TOLERANCES
L2 DEVICE L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1
CONNECTION OF THEIR -R TERMINALS. OUT OUT OUT OUT OUT OUT
K THE SURFACE AREA OF THE LED MUST LIE BETWEEN 20mm² FINISH
UNLESS STATED
AND 10cm². THE LED AND ITS TERMINATIONS MUST BE REFER TO A COMBINATION OF UP TO 20 OF THE SCALE
AFFORDED A DEGREE OF PROTECTION OF AT LEAST IP20. NOTE 7 CERTIFIED DEVICES LISTED IN TABLE 1
AND MUST BE SEGRAGATED FROM OTHER CIRCUITS AND
2
CONDUCTORS AS DEFINED IN CLAUSE 5 OF EN50 020:2002.
2

L NOTE 7.
AN END OF LINE RESISTOR OF MINIMUM VALUE 1K8/1W OR
A ZENER DIODE OF 18V TO 27V / 1.3W, MAY BE FITTED
TO THE LAST BASE ON A CIRCUIT. SYSTEM LABEL (EXAMPLE)
DESIGN TITLE
APPROVED
SERIES 60
APOLLO S60 I.S. FIRE DETECTOR
INTRINSICALLY SAFE
M SYSTEM EECS CERTIFIED PRODUCT APPROVED SYSTEM DRAWING.
NO MODIFICATIONS PERMITTED
BASEEFA WITHOUT THE APPROVAL OF BASEEFA CHECKED
No. Ex 97D2054 SYST DRG. No.
This drawing specification is the property of Apollo Fire Detectors Limited and may not be CAD
C reproduced or disclosed to a third party without the written permission of the company. DRAWN Z20983 SHT 1 OF 2
DO NOT SCALE IF IN DOUBT - ASK METRIC DIMENSIONS THIRD ANGLE PROJECTION

1 2 3 4 5 6 7 8 9 10 11 12

B
HAZARDOUS AREA SAFE AREA

C REFER TO
NOTE 6

IN IN IN IN IN IN

-R L1 -R L1 -R L1 -R L1 -R L1 -R L1 +
END OF LINE

L2 DEVICE L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1
6 2
D OUT OUT OUT OUT OUT OUT

7 3

REFER TO A COMBINATION OF UP TO 20 OF THE -


NOTE 7 MTL 3043 DC ISOLATORS
CERTIFIED DEVICES LISTED IN TABLE 1 BASEEFA CERTIFICATE No. Ex86B2285

REFER TO
NOTE 6
F
IN IN IN IN IN IN

-R L1 -R L1 -R L1 -R L1 -R L1 -R L1
END OF LINE

L2 DEVICE L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1
OUT OUT OUT OUT OUT OUT

G
REFER TO A COMBINATION OF UP TO 20 OF THE
NOTE 7 CERTIFIED DEVICES LISTED IN TABLE 1

+
H 2 9
- 8
3
5 12
+
6 11
REFER TO
SAFE AREA APPARATUS

NOTE 6
-
MTL4061 TWO CHANNEL INTERFACE
BASEEFA CERTIFICATE No. Ex94C2040. 4 A2651 AMENDED TO MEET NEW APROVAL
I ATEX CERTIFICATE No. BAS01ATEX7176. REQUIREMENT. 8/02 LPC.
IN IN IN IN IN IN

-R L1 -R L1 -R L1 -R L1 -R L1 -R L1 3 A2301 REFER TO SHEET 1. JAN,00 LPC.


END OF LINE
2 A2002 REFER TO SHEET 1. JAN,98 LPC.
L2 DEVICE L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1
OUT OUT OUT OUT OUT OUT 1 A1846 DESIGN FIRM 2-97, LPC.
A INTRODUCED JAN/97 LPC.
REFER TO A COMBINATION OF UP TO 20 OF THE
J NOTE 7 ISS. MOD. D.C.N. CHANGE, DATE AND SIGNATURE
CERTIFIED DEVICES LISTED IN TABLE 1
SPECIFICATION MATERIAL
UNSPECIFIED EXCEPT THAT IT MUST NOT BE SUPPLIED FROM NOR CONTAIN UNDER NORMAL OR ABNORMAL
CONDITIONS A SOURCE OF POTENTIAL EXCEEDING 250 VOLTS RMS OR 250 VOLTS DC WITH RESPECT TO EARTH.

TOLERANCES

K FINISH
UNLESS STATED
SCALE

DESIGN TITLE SERIES 60


APPROVED
INTRINSICALLY SAFE
M EECS CERTIFIED PRODUCT APPROVED SYSTEM DRAWING.
NO MODIFICATIONS PERMITTED
WITHOUT THE APPROVAL OF BASEEFA CHECKED
DRG. No.
This drawing specification is the property of Apollo Fire Detectors Limited and may not be CAD
C reproduced or disclosed to a third party without the written permission of the company. DRAWN Z20983 SHT 2 OF 2