R410A

KXZ Lite Heat pump systems


8, 10HP (22.4kW · 28.0kW)
Model No. Nominal Cooling Capacity
Blue
FDC224KXZPE1 22.4kW Fin
FDC280KXZPE1 28.0kW

• Connect up to 8 indoor units/up to 120% capacity.


• High efficiency with COP (in cooling) up to 4.0.
• These units employ DC inverter multiport compressors with
concentrated winding motor.
• KXZ Lite extends a cooling range operation up to 50ºC.
• External static pressure is available up to 35 Pa.
• Tropical usage mode.

Total length: 150m Range of operation


Outdoor unit +50ºC
50

To the Height difference 40


first branch: 30m(outdoor unit above)
max 90m 30m(outdoor unit below)
Indoor unit 30

Cooling
20
Max height +15.5ºC
Indoor unit difference 10
between
indoor units: 0
From the first Indoor unit 18m Heating
branch to the -10

furthest indoor -15ºC


unit: 40m Furthest -20
-20ºC
indoor unit: 120m

Specifications
Item Model FDC224KXZPE1 FDC280KXZPE1
Nominal horse power 8HP 10HP
Power source 3 Phase 380-415V, 50Hz
Starting current A 5
Max current A 21 22
Cooling 22.4 28.0
Nominal capacity kW
Heating 22.4 28.0
Power Cooling 5.6 7.87
Electrical characteristics kW
consumption Heating 4.8 6.47
Exterior dimensions HxWxD mm 1505x970x370
Net weight kg 165
Sound pressure level Cooling/Heating dB(A) 59/60 60/63
Type / GWP R410A / 2088
Refrigerant
Charge kg/TCO2Eq 8.9 / 18.583
Liquid line ø9.52(3/8")
Refrigerant piping size mm(in)
Gas line ø19.05(3/4") ø22.22(7/8")
Capacity connection % 50~120
Number of connectable indoor units 8 8
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. Heating: Indoor temp. of 20ºCDB, and outdoor temp. of 7ºCDB, 6ºCWB. Piping length is 7.5m.
2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
3. ‘tonne(s) of CO2 equivalent’ means a quantity of greenhouse gases- expressed as the product of the weight of the greenhouse gases in metric tonnes and of their global warming potential.

34
Refrigerant piping
Outdoor unit (HP) 8 10 Branch pipes Header pipe

Gas pipe Furthest indoor unit ø19.05 ø22.22


Liquid pipe =<90m ø9.52
Gas pipe 90m ø22.22 ø25.4/ø28.58
Liquid pipe =<Furthest indoor unit ø9.52 DIS-22-1G HEAD4-22-1G
DIS-180-1G HEAD6-180-1G

Dimensions
All measurements in mm.

Notes:
I II III
*1 At the time of the installation at ( )
L1 Open Open 500 dimension,
L2 300 5 Open Secure space of 250mm in lateral
(L4) by unit movement at the time
L3 150 300 150 of the exchange work of the
L4 250 (5)*1 250 (5)*1 250 (5)*1 compressor.

Mark Content Notes:


(1) It must not be surrounded by walls on the four sides.
A Service valve connection of the (2) The unit must be fixed with anchor bolts.
ø19.05 (3/4") (Flare)
attached connecting pipe (gas side) An anchor bolt must not protrude more than 15mm.
B Service valve connection (liquid side) ø9.52 (3/8") (Flare) (3) Where the unit is subject to strong winds, lay it in such a direction that the
blower outlet faces perpendicularly to the dominant wind direction.
C Cable draw-out hole (front · side) ø30 x 2places (4) Leave 1m or more space above the unit.
D Cable draw-out hole (front · side) ø45 x 2places (5) A wall in front of the blower outlet must not exceed the units height.
E Cable draw-out hole (back) ø50 (6) The model name label is attached on the lower right corner of the front panel.
(7) Connect the Service valve with local pipe by using the pipe of the attachment.
F Pipe/cable draw-out hole 4places
(Gas side only) (Accessory pipe is used only by FDC280KXZPE1)
G Drain discharge hole ø20 x 3places (8) Regarding attaching the pipe of accessories, refer to an attached installation
H Anchor bolt hole M10 x 4places manual.