You are on page 1of 1

LOT 241 EQUIPMENTS POWER CONSUMPTION GP HOUSE

INFO Single motor specification Total motor specification


Apparent power Apparent power
EQUIPMENTS BD Material No MOTOR VOLTAGE PHASE NO OF DRIVES [A] kW [A]
[ kVA ] [ kVA ]
MPF drive 400 3 12 3 2.08 36 24.94
Flexvey drive 400 3 1 2 1.39 2 1.39
Servo motor 230 1 1 0.6 0.14 0.6 0.14
Cooling pump 400 3 2 2.5 1.73 5 3.46
VC130-3-1.5HP fan 400 3 11 3 2.08 33 22.86
EWA drive 230 1 1 3.5 0.81 3.5 0.81
MB drive 400 3 8 2 1.39 16 11.09
Vertical manure drive 400 3 1 5 3.46 5 3.46
Cross manure drive 400 3 1 4 2.77 4 2.77
light group under 1 dimmer ERS110 230 1 1 10 2.30 10 2.30
Heater box 230 1 2 10 2.30 20 4.60
FC050-4EQ fan 230 1 2 2.3 0.53 4.6 1.06
VC130-3-1.5HP fan 400 3 1 3 2.08 3 2.08
6D92-Q fan 400 3 2 1.7 1.18 3.4 2.36
Flexvey drive 400 3 2 2 1.39 4 2.77
Lift* 415 1 1 30 12.45 30 12.45
TOTAL SUM 180.1 98.53

Total per block 330.2 Amp


* Lift is one per block
(GP-2 Storey) 184.6 Kva

You might also like