% DIFFERENCE=
A (15/2/2022)
POINTS DIRECT UNDER LIGHTING DIRECT BETWEEN LIGHTING (VERTICAL)
1 31 30
2 34 31
3 31 27
4 33 22
5 24 21
6 31 23
7 29 20
8 27 23
9 30 22
10 39 31
AVERAGE 30.9 25
MIN/MAX 24/39 20/31
% DIFF TO PREVIOUS MEAS. 44.82% 39.02%
B (15/2/2022)
POINTS DIRECT UNDER LIGHTING DIRECT BETWEEN LIGHTING (VERTICAL)
1 34 21
2 38 23
3 32 23
4 33 25
5 33 23
6 31 20
7 25 20
8 25 14
9 31 34
10 42 39
AVERAGE 32.4 24.2
MIN/MAX 25/42 14/39
% DIFF TO PREVIOUS MEAS. 42.14% 40.98%
C (15/2/2022)
POINTS DIRECT UNDER LIGHTING DIRECT BETWEEN LIGHTING (VERTICAL)
1 37 30
2 32 19
3 26 24
4 28 20
5 30 22
6 27 16
7 24 15
8 22 18
9 21 19
10 50 32
AVERAGE 29.7 21.5
MIN/MAX 21/37 15/32
% DIFF TO PREVIOUS MEAS. 46.96% 47.56%
WALL (15/2/2022)
POINTS RIGHT WALL LEFT WALL
1 16 22
2 20 21
3 15 16
4 16 21
5 18 16
6 14 18
7 16 14
8 14 18
9 14 17
10 16 16
AVERAGE 15.9 17.9
MIN/MAX 14/20 14/22
% DIFF TO PREVIOUS MEAS. 38.85% 31.15%
SUMMARY
A DIRECT UNDER LIGHTING DIRECT BETWEEN LIGHTING (VERTICAL)
AVERAGE 30.9 25
MIN/MAX 24/39 20/31
% DIFF. TO PREVIOUS MEAS. 44.82% 39.02%
% LUX DECREASED/YEAR 14.94% 13.00%
In conclusion, the lux measurements will be decreased over the time. The readings were taken to measures the lux level
losses over the time. The % difference were calculated by differentiating the current readings average (15/2/2022) and
previous readings average from 3 years ago (11/9/2019). Based on the tables above, Most of the lighting points % difference
to previous readings are almost 50%. Based on the supplier's prediction, the lux level might decreased by 5% annually, but as
the result suggest the lux levels decreased around 10% to 15% annually (direct under lighting). So there are around 10%
difference compared to what the supplier mentioned. This may happens due to the aging or pollution of the lightings. When
the lux level direct under lighting decreased, it is possible that the area surrounding the point will also decreased. Given the
current result, the bulbs needs to be changed in 1 or 2 more years to maintain the optimum lux level for the chickens.
TASEK A LIGHTING LAYOUT AND LUX MEASUREMENTS
260.00
16 14 15 16 14 17 18 16 15 20 16
5.00
C 18 50 32 19 21 18 22 15 24 16 27 22 30 20 28 24 26 19 32 30 37
TASK LOCATION
21 41 19 17 20 21 25 25 27 28 28
FRONT
BACK
30.00 B 42 39 34 31 14 25 20 25 20 31 23 33 25 33 23 32 23 38 21 34
19 30 26 20 21 23 21 26 27 28 27
DIRECT BETWEEN LIGHTING
A 16 39 31 22 30 23 27 20 29 23 31 21 24 22 33 27 31 31 34 30 31
16 17 18 14 17 18 16 21 16 21 22
6.84 13.68