VERSION INFORMATION
Tripping module:
TRIP+2101 restricted to 110 V DC application,
TRIP+2201 became available and recommended
for new designs with rated voltage 220 V DC
PSTP+ module:
Card drawings updated, PE symbol added
Minor corrections
New modules added:
CPU+0281, CPU+0501, CPU+1401, CPU+1091
PSTP+2102, PSTP+4202
VS+0031
Mechanical data:
Notes on solid and perforated rack covers for 84
and 42 HP devices added. Peter
1.39 08.2015. Mounting methods: Budenszki
Semi-flush mounting of 24 HP panel instrument Gabor Nagy
case figure updated.
Wall mounting method figures updated.
IP54 rated mounting kit for 42 HP devices
chapter updated.
No mounting chapter added.
Minor corrections
New modules added:
ATO+0002, ATO+0004,
CPU+A001, CPU+A011, COM+1801,
CT+5111, CT+5154, CT+5155, CT+5253,
R1T+0001,
RTD+1200,
CVS+0001, CVSR+0001,
INJ+0005, INJ+0015,
RAI+01, RAI+11, RINJ+21,
PS3F+1001, PS+2303,
PSR2+2101,
RBOX+A201.
Current input module:
Thermal withstand data updated.
Accuracy data removed.
Max. measured current data updated.
Voltage input module:
Accuracy data removed. Peter
1.40 10.2018. Max. measured current data updated. Budenszki
Signaling module: Zoltan Bido
Main features updated.
Unused modules have been removed.
Tripping module:
TRIP+1101 restricted to 110 V DC.
RTD input module:
RTD module wiring figures updated.
Power supply module:
PS+4401 nominal 60 V DC input voltage range
added.
PSTP+ module:
PSTP+4201 nominal voltage and input voltage
range updated.
Special devices:
TRCS has been added.
Mounting methods:
IP54 rated mounting kit for 84 HP devices
Minor corrections
CONTENTS
1 System design
The EuroProt+ protection device family is a scalable hardware platform to adapt to different
applications. Data exchange is performed via a 16-bit high-speed digital non-multiplexed parallel
bus with the help of a backplane module. Each module is identified by its location and there is no
difference between module slots in terms of functionality. The only restriction is the position of the
CPU module because it is limited to the “CPU” position. The built-in self-supervisory function
minimizes the risk of device malfunctions.
BACKPLANE CONNECTOR
STATION
SA0...15
BUS SDRAM (64 MB) SDRAM (64 MB)
RD0...15
FIBER P2
BUS CONTROL
BUS CONTROL
RD0...15
CD0...15
RA0...15
CA0...15
RJ45
SB REDU. CUART P3 125 MHz 125 MHz 12,5 MHz
FIBER FIB/PLA/G BACKPLANE
BUA0...13 BUA0...13
PROCESS
BUD0...15
P4 SPI SPI BUD0...15
PROCESS CUART RUART
DRIVER/
BUS
RA0...15 HIGH 12,5 MHz RECEIVER
BUS +
FIBER
DRIVER HIGH SPEED BUS RD0...15
SPEED PROTECTION
ETHERNET SWITCH
CIRCUITS
SPORT0
SPORT1
LOGIC BACK- BACK-
CUART TFT SIGNALS CCPU RCPU 125 MHz PLANE PLANE
PPI
CONTROL CONTROL
TOUCHSCREEN 500 MHz 500 MHz SLAVE CPU
GPIO
SIGNALS FUNCTIONS
MAC MAC
3,3 V 12 V
DC/DC
CMII JTAGs
▪ Front panel TFT display handling: the interactive menu set is available through the TFT
and the touchscreen interface
▪ Other communication:
o RS422/RS485 interfaces (galvanic interface to support legacy or other serial
protocols, ASIF)
o Plastic or glass fiber interfaces to support legacy protocols, ASIF
o Proprietary process bus communication controller on COM+ module
o Telecommunication interfaces: G.703, IEEE C37.94
CPU+0007 - - - - - +
CPU+0091 - - - - + SM SH +
CPU+0201 - + - - - +
CPU+0281 - + - - + SM LH +
CPU+0291 - + - - + SM SH +
CPU+0301 - - - + POF - +
CPU+0501 - - - + Galv. RS485/422 - +
CPU+1001 + MM - - - - +
CPU+1011 + MM - - - + MM +
CPU+1091 + MM - - - + SM SH +
CPU+1101 + MM - + MM - - +
CPU+1111 + MM - + MM - + MM +
CPU+1181 + MM - + MM - + SM LH +
CPU+1191 + MM - + MM - + SM SH +
CPU+1201 + MM + - - - +
CPU+1211 + MM + - - + MM +
CPU+1281 + MM + - - + SM LH +
CPU+1291 + MM + - - + SM SH +
CPU+1301 + MM - - + POF - +
CPU+1311 + MM - - + POF + MM +
CPU+1331 + MM - - + double POF - +
CPU+1381 + MM - - + POF + SM LH +
CPU+1391 + MM - - + POF + SM SH +
CPU+1401 + MM - - + GS - +
CPU+1411 + MM - - + GS + MM +
CPU+1481 + MM - - + GS + SM LH +
CPU+1491 + MM - - + GS + SM SH x
CPU+1501 + MM - - + Galv. RS485/422 - +
CPU+1511 + MM - - + Galv. RS485/422 + MM +
CPU+1581 + MM - - + Galv. RS485/422 + SM LH +
CPU+1611 + MM - - + Galvanic sync + MM +
CPU+1681 + MM - - + Galvanic sync + SM LH +
CPU+9201 + SM SH + - - - +
CPU+9291 + SM SH + - - + SM SH +
CPU+9501 + SM SH - - + Galv. RS485/422 - +
+ MM
CPU+A001 - - - - +
PRP/HSR
+ MM
CPU+A011 - - - + MM +
PRP/HSR
+ MM
CPU+A081 - - - + SM LH +
PRP/HSR
+ MM
CPU+A091 - - - + SM SH +
PRP/HSR
For legacy CPU cards (e.g. CPU+0001, ...) see Product availability chapter.
CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+
0007 0091 0201 0281 0291 0301 0501 1001 1011 1091 1101 1111
CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+
1181 1191 1201 1211 1281 1291 1301 1311 1331 1381 1391 1401
MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
SBW SBW SB SB SB SB SB SB SB SB SB SB
Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx
CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+
1411 1481 1491 1501 1511 1581 1611 1681 9201 9291 9501 A001
SM SH SM SH SM SH PRP/HSR
MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST FCPC FCPC FCPC MM/LC
SB_LAN_A SB_LAN_B
Rx
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
Tx
SB SB SB SB SB SB SB SB SB SB SB
Rx
Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx
Tx
SB_LAN_A SB_LAN_B
SB_LAN_A SB_LAN_B
SB_LAN_A SB_LAN_B
Rx Rx Rx
Tx Tx Tx
Rx Rx Rx
Tx Tx Tx
A B I A B I A B I
LINK/ACT LINK/ACT LINK/ACT
SM LH SM SH
MM/ST
FCPC FCPC
Tx Tx Tx
PB PB PB
Rx Rx Rx
Interface types:
▪ 100Base-FX Ethernet:
o MM/ST 1300 nm, 50/62.5/125 μm connector, (up to 2 km) fiber
o SM/FC 1550 nm, 9/125 μm connector, (LH: long haul, up to 120 km)
o SM/FC 1550 nm, 9/125 μm connector, (SH: short haul, up to 50 km)
o MM/LC 1300 nm, 50/62.5/125 μm connector, (up to 2 km) fiber
▪ 10/100 Base-TX Ethernet: RJ-45-8/8
▪ Service port on HMI:
o 10/100 Base-T Ethernet: RJ-45-8/8
o EOB interface: attachable to the front panel by a proprietary magnetic connector;
the connector box ends in a RJ-45 8/8 plug. It is 10Base-T full duplex interface.
The EOB2 accessory enables 10/100Base TX communication with service
computers.
▪ ASIF: Asynchronous Serial Interface
o plastic optical fiber (ASIF-POF)
o glass with ST connector (ASIF-GS)
o galvanic RS485/422 (ASIF-G)
MM/ST MM/ST
MM/LC MM/LC
Tx Tx
Tx Tx
LINE 1 LINE 1 LINE 1 LINE 1
Rx Rx
Rx Rx LINK 1 LINK 1
Tx Tx
LINE 2 LINE 2
MM/ST MM/ST Rx Rx
Tx Tx LINK 2 LINK 2
Tx Tx
LINE 2 LINE 2 LINE 3 LINE 3
Rx Rx
Rx Rx LINK 3 LINK 3
Tx Tx
LINE 4 LINE 4
Signal MM/ST Rx Rx
LINK 4 LINK 4
Tx
Syb Sya Tx
LINE 3 LINE 5
Rx
Rxb Rxa Rx LINK 5
Txb Txa
G.703 E0
NUMBER OF UNIT
MODULE TYPE INTERFACE TYPE APPLICATION
INTERFACES WIDTH
Line differential
COM+0091 G703.1 (64 kbit/s) 1 4 HP protection via telecom
network
Transmitter
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
OPTICAL OUTPUT POWER PO BOL*: -19
- -14 dBm avg.
62.5/125 μm, NA = 0.275 FIBER EOL*: -20
OUTPUT OPTICAL POWER PO BOL*: -22.5
- -14 dBm avg.
50/125 μm, NA = 0.20 FIBER EOL*: -23.5
10 %
OPTICAL EXTINCTION RATIO ER - -
-10 dB
Receiver sensitivity is measured with 223 – 1 PRBS pattern within BER = 2.5 × 10-10
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
Transmitter
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
Receiver sensitivity is measured with 223 – 1 PRBS pattern within BER = 2.5 × 10-10
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
Transmitter
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
Receiver sensitivity is measured with 223 – 1 PRBS pattern within BER = 2.5 × 10-10
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
HYSTERESIS PHYS - 3 - dB
Transmitter
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
Receiver sensitivity is measured with 223 – 1 PRBS pattern within BER = 2.5 × 10-10
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
HYSTERESIS PHYS - 3 - dB
Transmitter
JUMPER
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
SETTINGS
PEAK EMISSION
λPK - 660 - nm
WAVELENGTH
EFFECTIVE DIAMETER D - 1 - mm
NUMERICAL
NA - 0.5 -
APERTURE
Receiver
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
EFFECTIVE DIAMETER D - 1 - mm
These characteristics are valid for both POF interfaces in CPU+1331 module.
Receiver
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
Driver
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
Receiver
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
Receiver
± 1.5 dB difference between alarm-on and
LOSS OF SIGNAL ALARM LEVEL
alarm-off
Transmitter
CPU+
A001
PRP/HSR
MM/LC
SB_LAN_A SB_LAN_B
Rx
Tx
Rx
Tx
A B I
LINK/ACT
DANP DANP
SAN
„A” frame
„B”
frame
LAN_A LAN_B
Bridge Bridge
„A” frame
„B”
SAN frame SAN
RedBox
DANP
Destination
Single attached node (SAN): Network device that connects to a network with only one port.
Double attached node implementing PRP (DANP): Network device which connects to a network
with two ports implementing PRP redundancy.
„A” frame
SAN SAN SAN
„B” frame
Not HSR frame between host and ring
Source
DANH DANH
Bridge
CPU CPU
RedBox
Single attached node (SAN): Network device that connects to a network with only one port.
Double attached node implementing HSR (DANH): Network device which connects to a network
with two ports implementing HSR redundancy.
RBOX+
A201
PRP/HSR
MM/LC
A
PRP/HSR
B
RJ-45
INTERLINK
3 Backplane module
The backplane board itself is a passive board but it provides a 16-bit bus, power supply
distribution, a two-wire interface (TWI) supporting module inventory management and module
identification. It is designed to meet the requirements for high speed digital buses and to comply
with electromagnetic emission standards.
Three versions are available: one is 84 HP wide with 21 module slots, the 42 HP wide, which
supports 10 module slots and the 24 HP, which supports 6 module slots. In case of applications
where more modules need to be supported or mounting space is critical, it is possible to
interconnect the racks (called double rack). The 24 HP case is not a modular system, and it has
fixed module layout.
MODULE
RACK CONFIGURATION
SLOTS
The following illustrations only for showing the different types of rack/case configurations. For the
full scale of our available HMI modules please see the Human Machine Interface (HMI) module
chapter in the next pages.
84 HP single rack
(3 U)
42 HP single rack
(3 U)
[normal rack and with
cover profile]
42 HP double rack
with cover profile
(6 U)
24 HP panel
instrument case
Remote HMI
Protecta provides an alternative solution in that
case if the IED can be only mounted in a non-
practical way for managing the device via usual
Human-Machine Interface.
By using a remote HMI (terminal HMI device)
customers are able to place the HMI at longest 3
meters far from the IED itself (host device) and
mount the IED in any possible way that is
applicable. The connection between the remote
HMI and the IED is provided by a custom
galvanic interface with DA-15 connector on the Figure 4-1 42 HP Remote HMI
remote side.
In such applications where remote display is used the HMI module can be only 42 or 84 HP wide
HMI+3502 or 84 HP wide HMI+5702.
Depending on the size of the HMI module you can use any applicable mounting methods that
described in the Mounting methods chapter (Flush mounting, Semi-flush mounting, Rack
mounting).
MODULE SERVICE
DISPLAY RACK SIZE ILLUSTRATION
TYPE PORT
42 HP
84 HP
42 HP
84 HP
*Obsolete module. These modules are not recommended for new designs! For the full list of
obsolete modules see our Product availability chapter.
**Smart Line S24 special selection modules. For further information please contact our sales
team: sales@protecta.hu
Function Description
CHANGEABLE LED
Describes user LED functionality
DESCRIPTION LABEL
COM LED
Optical
interface
for factory
usage
Touch keys
Ethernet
service
port
M AXIMUM NUMBER
ACCEPTABLE
DOT-DEFECT TYPE
3.5" 5.7"
1 dot 4 4
IN TOTAL 4 5
1 dot 4 5
IN TOTAL 4 5
IN TOTAL 6 10
For further information please contact our Application Team. (application@protecta.hu)
SELECTABLE RATED
1 5 1 5
CURRENT, IN [A]
M AX. MEASURED
50 × IR 50 × IR
CURRENT (± 10 %)
POWER CONSUMPTION
0.01 0.25 0.01 0.25
AT RATED CURRENT [VA]
THERMAL WITHSTAND
[A]
CONTINUOUSLY 20 20
10 s 175 175
1s 500 500
10 ms 1200 1200
*Special module. For further information see our Product availability chapter.
**Ring lug connector (CT+5151R)
SELECTABLE RATED
1 5 1 5 1 5
CURRENT, IN [A]
M AX. MEASURED
12.5 × IR 2 × IR 2 × IR
CURRENT (± 10 %)
POWER CONSUMPTION
0.02 0.45 0.1 1.55 0.1 1.55
AT RATED CURRENT [VA]
THERMAL WITHSTAND
[A]
CONTINUOUSLY 20 7 7
10 s 120 50 50
Special protection
General 3Ph
applications where
RECOMMENDED measurement
the overcurrent in the DGBV applications.
APPLICATION applications.
secondary circuit can
DGBV applications.
not exceed 10 × In.
*Special module. For further information see our Product availability chapter.
**Obsolete module. For further information see our Product availability chapter.
SELECTABLE RATED
1 5 0.2 1 1 5 0.2 1
CURRENT, IN [A]
M AX. MEASURED
50 × IR 50 × IR 50 × IR 12.5 × IR
CURRENT (± 10 %)
POWER CONSUMPTION
0.01 0.25 0.001 0.01 0.01 0.25 0.005 0.1
AT RATED CURRENT [VA]
THERMAL WITHSTAND
[A]
CONTINUOUSLY 20 20 20 7
SELECTABLE RATED
0.01 0.05 1 5 0.001 0.005
CURRENT, IN [A]
POWER CONSUMPTION AT
0.005 0.1 0.01 0.25 0.005 0.1
RATED CURRENT [VA]
CONTINUOUSLY 7 20 7
10 s 50 175 50
CONTINUOUSLY 20 7 20
10 s 175 50 175
POWER CONSUMPTION AT
0.06 1.3 0.6 0.004 0.0004 0.06 1.3 0.6 0.004 0.0004
RATED CURRENT [VA]
CONTINUOUSLY 20 7 20 7
10 s 165 50 165 50
DMD.
RECOMMENDED
Sensitive earth fault Circuit breaker diagnostics.
APPLICATION
protection applications.
*Special module. For further information see our Product availability chapter.
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
CT4 CT3 CT2 CT1
CHANNEL NUMBER 4 4
CONTINUOUS VOLTAGE
250 V 250 V
WITHSTAND
SHORT TIME
275 V AC / 350 V DC 275 V AC / 350 V DC
OVERLOAD (1 S)
VOLTAGE MEASURING
0.05 UR – 1.3 UR 0.05 UR – 1.3 UR
RANGE (± 10 %)
FREQUENCY
Ux ≥ 25 % of rated voltage
MEASUREMENT RANGE
Special protection
applications.
The 4th channel of VT+2215
RECOMMENDED General protection
is for special voltage
APPLICATION applications.
transformers where low
power consumption is
needed.
*Special module. For further information see our Product availability chapter.
**Screwed type connector. (VT+2211F)
CHANNEL NUMBER 4 3
Type 200:
200
, 200 V
SELECTABLE VOLTAGE 3
RANGE Type 400:
400
3
CONTINUOUS VOLTAGE
400 V
WITHSTAND
SHORT TIME
420 V AC / 560 V DC
OVERLOAD (1 S)
VOLTAGE MEASURING
0.05 UR – 1.3 UR
RANGE (± 10 %)
FREQUENCY
Ux ≥ 25 % of rated voltage
MEASUREMENT RANGE
RECOMMENDED
Special protection applications for 400 V AC secondary voltage.
APPLICATION
*Special module. For further information see our Product availability chapter.
**Increased isolation to 6kV
1 1 1 1 1
VT1
VT1
VT1
VT1
VT1
2 2 2 2 2
3 3 3 3 3
VT3 VT2
VT3 VT2
VT3 VT2
VT3 VT2
VT3 VT2
4 4 4 4 4
5 5 5 5 5
6 6 6 6 6
7 7 7 7
VT4
VT4
VT4
VT4
8 8 8 8
CHANNEL NUMBER 8 8 8 8
THERMAL WITHSTAND
72 V 100 V 250 V 320 V
VOLTAGE
CHANNEL NUMBER 12 12 12 12
THERMAL WITHSTAND
72 V 72 V 250 V 320 V
VOLTAGE
CHANNEL NUMBER 12 12
TIME
configured by EuroCAP configured by EuroCAP
SYNCHRONIZATION
24 V DC / 48 V DC 110 V DC / 220 V DC
RATED VOLTAGE user selectable on channel user selectable on channel
basis by jumpers basis by jumpers
THERMAL WITHSTAND
72 V 320 V
VOLTAGE
CHANNEL NUMBER 16 16 16 16
TIME
- - - -
SYNCHRONIZATION
THERMAL WITHSTAND
72 V 100 V 250 V 320 V
VOLTAGE
Thermal withstand voltage: continuous with 60 % of the input channels are energized.
Main features:
• Digitally filtered per channel
• Current drain:
o max. 1.6 mA per channel at 220 V DC
o max. 1.8 mA per channel at 110 V DC
o max. 2 mA per channel at 48 V DC
o max. 3 mA per channel at 24 V DC
• In such applications where the input voltage is 60 V the modules with 48 V rated
voltage can be used.
• Input voltage type can be either DC or AC voltage. If AC voltage is used make
sure that the type and the parameters of the binary inputs are configured properly
in EuroCap tool.
1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2
3 3 3 3 3 3 3 3
4 4 4 4 4 4 4 4
5 5 5 5 5 5 5 5
6 6 6 6 6 6 6 6
7 7 7 7 7 7 7 7
8 8 8 8 8 8 8 8
9 9 9 9 9 9 9 9
10 10 10 10 10 10 10 10
11 11 11 11 11 11 11 11
12 12 12 12 12 12 12 12
13 13 13 13 13 13 13 13
14 14 14 14 14 14 14 14
15 15 15 15 15 15 15 15
16 16 16 16 16 16 16 16
1 1 2 2 2 2
2 2 3 3 3 3
3 3 4 4 4 4
4 4 5 5 5 5
5 5 6 6 6 6
6 6 7 7 7 7
7 7 8 8 8 8
8 8 9 9 9 9
9 9 10 10 10 10
10 10 11 11 11 11
11 11 12 12 12 12
12 12 13 13 13 13
13 13 14 14 14 14
14 14 15 15 15 15
15 15 16 16 16 16
16 16 17 17 17 17
18 18 18 18
8 Signaling module
The signaling module has 4, 8, 12 or 16 relay outputs with dry contacts.
RATED VOLTAGE 250 V AC/DC 250 V AC/DC 250 V AC/DC 250 V AC/DC
CONTINUOUS
8A 8A 8A 8A
CARRY
Receptacle:
Weidmüller
SLA 12/90 Receptacle: Weidmüller SLA 16/90
CONNECTOR TYPE
Plug: Plug: Weidmüller BLA 16/180
Weidmüller
BLA 12/180
*Special module. For further information see our Product availability chapter.
CONTINUOUS CARRY 8A 8A 8A
CH12 NC
CONTACT VERSIONS 8 NC 12 NO
others NO
Receptacle:
Weidmüller SLA 16/90
Receptacle: Weidmüller SLA 16/90
CONNECTOR TYPE Plug: Weidmüller BLA
Plug: Weidmüller BLA 16/180
16/180
*Special module. For further information see our Product availability chapter.
CONTINUOUS
8A 8A 8A
CARRY
CONTINUOUS
8A 8A 32 A
CARRY**
CONTACT
4 CO 4 CO 1 NO
VERSIONS
Receptacle: Weidmüller
Receptacle: Weidmüller SLA 12/90 STVS6 SS
CONNECTOR TYPE
Plug: Weidmüller BLA 12/180 Plug: Weidmüller
STVS6 SB
*Special module. For further information see our Product availability chapter.
**If the signaling is performed only via a solid state relay (SSR), the continuous carry value is
120 mA.
***Thyristor module. Can be used only unipolarly. For further information see our Product
availability chapter.
1 1 1 1
2 2 2 2
1 1 1 3 3 3 3
2 2 2 4 4 4 4
3 3 3 5 5 5 5
4 4 4 6 6 6 6
5 5 5 7 7 7 7
6 6 6 8 8 8 8
7 7 7 9 9 9 9
8 8 8 10 10 10 10
9 9 9 11 11 11 11
10 10 10 12 12 12 12
11 11 11 13 13 13 13
12 12 12 14 14 14 14
15 15 15 15
16 16 16 16
1 1 2 2 2
2 2 3 3 3
3 3 4 4 4
4 4 5 5 5
5 5 6 6 6
6 6 7 7 7 1
7 7 8 8 8 2
8 8 9 9 9 3
9 9 10 10 10 4
10 10 11 11 11 5
11 11 12 12 12 6
12 12 13 13 13
13 13 14 14 14
14 14 15 15 15
15 15 16 16 16
16 16 17 17 17
18 18 18
9 Tripping module
The tripping module is a proprietary and patented solution that facilitates direct control of a circuit
breaker.
CHANNEL NUMBER 4 4 4 4 4
24 V DC and
RATED VOLTAGE 110 V DC 220 V DC 110 V DC 110 V DC
48 V DC
THERMAL
WITHSTAND 72 V DC 132 V DC 242 V DC 132 V DC 242 V DC
VOLTAGE
CONTINUOUS
8A 8A 8A 8A 8A
CARRY
BREAKING L/R = 40 ms: L/R = 40 ms: L/R = 40 ms: L/R = 40 ms: L/R = 40 ms:
CAPACITY 4 A DC 4 A DC 4 A DC 4 A DC 4 A DC
1+ 1+ 1+ 1+ 1+
2 - 2 - 2 - 2 - 2 -
3 NO 3 NO 3 NO 3 NO 3 NO
4+ 4+ 4+ 4+ 4+
5 - 5 - 5 - 5 - 5 -
6 NO 6 NO 6 NO 6 NO 6 NO
7+ 7+ 7+ 7+ 7+
8 - 8 - 8 - 8 - 8 -
9 NO 9 NO 9 NO 9 NO 9 NO
10 + 10 + 10 + 10 + 10 +
11 - 11 - 11 - 11 - 11 -
12 NO 12 NO 12 NO 12 NO 12 NO
TRIP+ module + +
Circuit breaker
TCS – –
(TRIP Circuit
Supervision)
No –
It is possible to use parallel connected TRIP+ modules. In this case the negative contacts must
be common.
+ A+
TRIP+ module
Circuit breaker
TCS –
–
(TRIP Circuit
Supervision)
No –
+ B+
TRIP+ module
TCS
–
(TRIP Circuit
Supervision)
No
Figure 9-3 3-wire TRIP+ wiring using parallel connected TRIP+ modules
Circuit breaker
TCS
(TRIP Circuit
Supervision)
No –
+ A+
TRIP+ module
Circuit breaker
TCS
(TRIP Circuit
Supervision)
No –
+ B+
TRIP+ module
TCS
(TRIP Circuit
Supervision)
No
Figure 9-5 2-wire TRIP+ wiring using parallel connected TRIP+ modules
If the circuit breaker needs two-pole switching TRIP+ modules can be connected series as you
can see in Figure 9–6.
+ +
TRIP+ module
Circuit breaker
TCS
(TRIP Circuit
Supervision)
No
TRIP+ module +
TCS
(TRIP Circuit
Supervision)
No –
Figure 9-6 2-wire TRIP+ wiring using series connected TRIP+ modules
CHANNEL NUMBER 1 4 1
Pt100/Ni100
Ni120/Ni120US
Pt250/Ni250
SENSOR TYPE Service-Ohm Pt1000/Ni1000 Service-Ohm
Cu10
Service-Ohm
(60 Ω … 1.6 kΩ)
Resistance-based
RECOMMENDED
DRL. temperature DRL.
APPLICATION
measurement.
11
12
13
14
15
16
A
1 RA
B
2
RTD+
RTD
module C
3
D
4 RD
A
5
A
1 RA
B
2 RB
RTD+
RTD
module C
3 RA ≈ RD
D
4 RD
A
5
A
1 RA
B
2 RB
RTD+
RTD
module C
3 RC
D
4 RD
A
5
A
1 RA
B
2 RB
RTD+
Potentiometer
module C
3 RC
D
4 RD
A
5
CHANNEL NUMBER 4 4
± 20 mA ± 20 mA
MEASUREMENT RANGES (typical 0-20, 4-20 mA) (typical 0-20, 4-20 mA)
RLOAD = 56 Ω RLOAD = 56 Ω
*Obsolete module. These modules are not recommended for new designs! For the full list of
obsolete modules see our Product availability chapter.
AIC+ AIC+
0200 0201
1 1 12 Vout
2 2
3 3
4 4 12 Vout
5 5
6 6
7 7 12 Vout
8 8
9 9
10 10 12 V
out
11 11
12 12
External
source
1
+ PS -
+ 2
Analog input
Transmitter mA / Vout
module
- 3
4
Figure 11-2 2-wire AI wiring without 12 V excitation
+ 1 12 V excitation
Transmitter mA / Vout
- 2
Analog input
module
3
4
Figure 11-3 2-wire AI wiring with 12 V excitation
1 12 V excitation
+ PS -
+ 2
Analog input
Transmitter mA / Vout
module
- 3
4
Figure 11-4 3-wire AI wiring with 12 V excitation
CHANNEL NUMBER 2 4
M AXIMUM LOAD
500 Ω 500 Ω
(RCABLE + RRECEIVER)
± 20 mA ± 20 mA
OUTPUT RANGES 0 - 20 mA 0 - 20 mA
4 - 20 mA 4 - 20 mA
ATO+ ATO+
0002 0004
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
Shield
1 +
mA Receiver
Analog output
module
2 -
CHANNEL NUMBER 4U 4U 4I 4U 4I
CONTINUOUS VOLTAGE
35 V DC 35 V DC 35 V DC
WITHSTAND
M AX. MEASURED
1.6 UR 1.8 UR 50 IR 2.1 UR 50 IR
CURRENT (± 10 %)
RELATIVE ACCURACY ≤ 0.5 % (0.1 UR – 1.2 UR) ≤ 0.5 % (0.1 UR – 1.2 UR) ≤ 0.5 % (0.1 UN – 1.2 UR)
For more information about more available nominal values please contact our Application Team.
(application@protecta.hu)
RJ45_1 RJ45_1
4 1 dI 4
I 2 5
1 3 dt
U 6 7
3 U 8
RJ45_2 RJ45_2
4 1 dI 4
I 2
1 3 dt 5
U 6 7
3 U 8
RJ45_3 RJ45_3
4 1 dI 4
I 2 5
1 3 dt
U 6 7
3 U 8
RJ45_4 RJ45_4
4 1 dI 4
1 3 I 2 5
dt
U 6 7
3 U 8
(4) „n”
(1) „a” (3) not connected
( FRONT VIEW)
1.: S1
2.: S2
3.: “a”
6.: “n”
Figure 13-3 CVS module connector pinout
4.: S1
5.: S2
8.: “n”
7.: “a”
Figure 13-4 CVSR module connector pinout
14 INJ module
Complex module for controlling the Petersen coil, which contains an injector function for the
measurements, an enabling and a blocking input, and a fault relay what signs if there is any
fault in the injection circuit.
INJECTED CURRENT 2A 4A
ADDITIONAL RESISTANCE
Not available function 265 kΩ ± 1%
FOR VOLTAGE INPUT
RECOMMENDED
DRL. DMD.
APPLICATION
*Special module. For further information see our Product availability chapter.
INJ+ INJ+
0005 0015
1 11 1 11
2 12 2 12
3 13 3 13
4 14 4 14
5 15 5 15
6 16 6 16
7 7
8 8
9 9
10 10
88 - 264 V DC
INPUT VOLTAGE RANGE N/A N/A
80 - 250 V AC
THERMAL WITHSTAND
CONTINUOUS: 15 mA 10 mA 20 mA
30 SEC: 20 mA 20 mA
Receptacle: Weidmüller STVS8 SB
CONNECTOR TYPE
Plug: Weidmüller STVS8 SS
1 1 1
2 2 2
3 3 3
4 4 4
5 5 5
6 6 6
7 7 7
8 8 8
DC
DC
M AXIMUM INPUT
250 V 350 V 600 V 1200 V
VOLTAGE
SERIES RESISTANCE ON
12.6 kΩ 18 kΩ 35 kΩ 30 kΩ
SIDES
• Middle-grounded rotors
If the excitation voltage is lower than 250 V, then it is enough to use the RAI+01-AUX_01 auxiliary
box. If the excitation voltage is higher than 250 V, than the RAI+01-AUX_02 auxiliary box shall be
used. With this auxiliary box the protection shall be used up to 350 V excitation voltage.
P
R
O
T RAIXX+AUX_XX
E
C
T
A
RAI+ RINJ+
11 21
RAI+11-AUX_12 RAI+11-AUX_11
1 3 1 3
Ug+
1 1
Ug-
6 4 6 4 2 2
3 3
4 4
5 5
6 6
7 UPS
+7
8 -8
DC
DC
RAI+
01
RAI+01-AUX_01
CON. A
1 3
Ug+
4
1
2
3
3
6 4
4
Ug- 5
CON. B
6
7
8
IMPORTANT
Depending on the hardware configuration, the power consumption of the devices can be different.
We reserve the right to make the decision about which PS+ module must be used.
For most applications where the power consumption does not reach 30 W we use one of our 4
HP wide PS+ modules.
PS+4201 PS+2101
MODULE TYPE
(4 HP wide) (4 HP wide)
24 V DC / 110 V DC /
NOMINAL VOLTAGE
48 V DC / 60 V DC 220 V DC
NOMINAL POWER 20 W 20 W
50 ms at nominal input
INPUT VOLTAGE min. 100 ms in the
voltages
INTERRUPTION TIME specified input voltage
min. 40 ms in the specified
(AT NOMINAL LOAD) range
input voltage range
Power connector:
Receptacle: Weidmüller SLA 2/90
Plug: Weidmüller BLA 2/180
CONNECTOR TYPE
Fault relay connector:
Receptacle: Weidmüller SLA 3/90
Plug: Weidmüller BLA 3/180
IMPORTANT
In case of the power consumption of the device reach or exceed 20 W we select from the following
8 HP wide modules.
*Special module. For further information see our Product availability chapter.
**Can be connected in parallel.
NOMINAL 48 V DC /
110 V DC 110 V DC 220 V DC 48 V DC
VOLTAGE 60 V DC
INPUT
88 - 132 V DC 88 - 132 V DC 176 - 264 V DC
VOLTAGE 38.4 - 57.6 V DC 38.4 - 72 V DC
95 - 130 V AC 95 - 130 V AC 160 - 250 V AC
RANGE
NOMINAL
60 W 60 W 60 W 25 W 30 W
POWER
*Special module. PS+1602 supports auxiliary voltage measurement. The module is calibrated
to DC voltage measurement. For further information see our Product availability chapter.
**Can be connected in parallel.
NOMINAL POWER 20 W
Main features:
• Fault relay contacts (NC and NO): device fault contact and also assignable to
user functions. All the three relay contact points are accessible to users.
• Redundant applications (nominal power and reliability can be increased by using
parallel power supplies)
• On-board self-supervisory circuits: temperature and voltage monitors
• Short-circuit-protected outputs
• Efficiency: > 70 %, power consumption = nominal power / efficiency
• Passive heatsink
• Early power failure indication signals to the CPU the possibility of power outage,
thus the CPU has enough time to save the necessary data to non-volatile memory
• Inrush current (until 0.1 s): < 10 A for all types excluding PS+4401 which has <
21 A inrush current.
• Common features for internal fuses:
o 5 mm x 20 mm (0.20" x 0.79")
o TT characteristics (very inverse time-lag)
o 35 A @ 250 V AC rated breaking capacity
• Recommended external protection: miniature circuit breaker, 6 A (C char.)
3 3 3 3 3 3
4 FAULT 4 FAULT 4 FAULT 4 FAULT 4 FAULT 4 FAULT
5 RELAY 5 RELAY 5 RELAY 5 RELAY 5 RELAY 5 RELAY
DC DC DC
AC
DC DC AC
L/+ L/+ + +
+
1 AC
DC
1 AC
DC
1 DC 1 DC 1 L/+ 1 1 L1
L2
2 N/-
DC 2 N/-
DC 2 -
DC 2 -
DC 2 N/- 2 - 2
FAULT FAULT 3 L3
RELAY RELAY
3 3 3 3 3 3 4
4 4 FAULT
FAULT 4 FAULT 4 FAULT 4 4 FAULT
RELAY RELAY RELAY RELAY
5 5 RELAY 5 5 5 5 5
6
7
PSTP+2101 PSTP+4201
MODULE TYPE PSTP+2131**
(PSTP+2102*) (PSTP+4202*)
88 - 264 V DC 88 - 264 V DC
INPUT VOLTAGE RANGE 19.2 - 72 V DC
80 - 250 V AC 80 - 250 V AC
NOMINAL POWER 20 W 20 W 20 W
50 ms at nominal input
INPUT VOLTAGE min. 100 ms in the min. 100 ms in the voltages
INTERRUPTION TIME specified input voltage specified input voltage min. 40 ms in the
(AT NOMINAL LOAD) range range specified input voltage
range
TRIPPING CHARACTERISTICS
CHANNEL NUMBER 2 2 2
THERMAL WITHSTAND
242 V DC 242 V DC 72 V DC
VOLTAGE
CONTINUOUS CARRY 8A 8A 8A
Main features:
• High-speed operation: with pre-trip 0.5 ms, without pre-trip typically 10 ms,
maximally 22 ms.
• Trip circuit supervision for each trip contact
• 1 unit wide (4 HP) modules
• Inrush current (until 0.1 s): < 10 A
• Common features for internal fuses:
o 5 mm x 20 mm (0.20" x 0.79")
o TT characteristics (very inverse time-lag)
o 35 A @ 250 V AC rated breaking capacity
• Recommended external protection: miniature circuit breaker, 6 A (C char.)
1 L/+
1 + 1 L/+
1 + 1 L/+
2 N/-
2 - 2 N/-
2 - 2 N/-
FAULT FAULT FAULT FAULT FAULT
RELAY RELAY RELAY RELAY RELAY
3 3 3 3 3
4 4 4 4 4
5 5 5 5 5
6+ 6+ 6+ 6+ 6+
7- 7- 7- 7- 7-
8 NO 8 NO 8 NO 8 NO 8 NO
9+ 9+ 9+ 9+ 9+
10 - 10 - 10 - 10 - 10 -
11 NO 11 NO 11 NO 11 NO 11 NO
88 - 264 V DC
INPUT VOLTAGE RANGE
80 - 250 V AC
NOMINAL POWER 20 W
INPUT VOLTAGE
min. 100 ms in the specified input
INTERRUPTION TIME
voltage range
(AT NOMINAL LOAD)
Power connector:
Receptacle: Weidmüller SLA 2/90
Plug: Weidmüller BLA 2/180
CONNECTOR TYPE
Fault relay connector:
Receptacle: Weidmüller SLA 3/90
Plug: Weidmüller BLA 3/180
SIGNALLING CHARACTERISTICS
CHANNEL NUMBER 2
CONTINUOUS CARRY 8A
PSR2+
2101
DC
AC
DC
1 L/+
2 N/-
FAULT
RELAY
3
4
5
6
7
8
9
10
11
CHANNEL NUMBER 6 6
110 V / 220 V 24 V / 48 V
RATED VOLTAGE user selectable on channel basis user selectable on channel basis
by jumpers by jumpers
THERMAL WITHSTAND
320 V 72 V
VOLTAGE
CONTINUOUS CARRY 8A 8A
Thermal withstand voltage: continuous with 60 % of the input channels are energised
O6R5+ O6R5+
2101 4201
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
CHANNEL NUMBER 9 9
SYNCHRON 1
1
CHANNEL TYPE 850 nm multimode fiber with
isolated BNC connector
AND NUMBER ST connector
THERMAL
WITHSTAND 320 V 320 V
VOLTAGE
WITHSTAND
VOLTAGE 35 VPEAK -
FOR SYNC. INPUT
GROUNDING
9 (3 × 3 common ground) 9 (3 × 3 common ground)
GROUPS
Receptacle: Receptacle:
Weidmüller SLA 12/90, BNC Weidmüller SLA 12/90, ST
CONNECTOR TYPE
Plug: Plug:
Weidmüller BLA 12/180, BNC Weidmüller BLA 12/180, ST
*Special modules. For further information see our Product availability chapter.
O9S+ O9S+
2111 2121
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
BNC
MM/ST
Rx
SYNC
CHANNEL NUMBER 2
CONTINUOUS CARRY 8A
Receptacle:
Weidmüller SLA 13/90
CONNECTOR TYPE
Plug:
Weidmüller BLA 13/180
R4MC+
01
1
2
3
4
5
6
7
8
9
10
11
12
13
18 Special devices
18.1.1 SCPU/PS
The SCPU/PS module contains all the control, communication and the
power supply functions of the device.
Receptacle:
min. 140 ms @
Weidmüller SLA 2/90
PS+1101 65-180 V DC 9W 110 V DC input
Plug:
voltage
Weidmüller BLA 2/180
18.1.2 SO12/R2
The O12/R2 module contains 12 binary input channels in one grounding group, and 2 relay
outputs with dry contacts.
THERMAL
CHANNEL TIME RATED CLAMP CONNECTOR
BI TYPE WITHSTAND
NUMBER SYNC. VOLTAGE VOLTAGE TYPE
VOLTAGE
Receptacle:
Weidmüller
falling 0.7 UR SL 3.5/13/90
SO12+1101 12 - 110 V 250 V
rising 0.73 UR Plug:
Weidmüller
BL 3.5/13/180
Thermal withstand voltage: continuous with 60 % of the input channels are energised
Main features:
• Digitally filtered per channel
• Current drain approx.: 2 mA per channel
Receptacle:
Weidmüller
250 V SL 3.5/6/90
R2+0001 6A CO 2 independent
AC/DC Plug:
Weidmüller
BL 3.5/6/180
Main features:
• Breaking capacity, (L/R = 40 ms) at 110 V DC: 0.2 A
Figure 17-2 Front view and rear view with fastening for mounting rail
18.2 TRCS
TRCS is a special device, which encodes the 28 stage-state of the transformer voltage regulator
into 5-bit binary code.
Figure 17-3 Front view and rear view with fastening for mounting rail
NUMBER OF INPUTS 28
NOMINAL VOLTAGE OF
48V DC/110V DC/220V DC
THE INPUTS AND
(Ordering option)
OUTPUTS
NUMBER OF OUTPUTS 5
OUTPUT CONTINUES
6A
CARRY
Receptacle: Weidmüller
SL 3.5/18/90
CONNECTOR TYPE Plug:
Weidmüller
BL 3.5/18/180
Main features:
• Breaking capacity, (L/R = 40 ms) at 110 V DC: 0.2 A, at 220 V DC: 0.1 A
19 General data
▪ Storage temperature: - 40 ºC … + 70 ºC
▪ Operation temperature: - 20 ºC … + 55 ºC
▪ Humidity: 10 % ... 93 %
▪ Altitude: up to 2000 m
▪ Atmospheric pressure: 86 ... 106 kPa
▪ Standard conformance:
• Electrostatic discharge immunity (ESD), IEC 60255-26:2013, Level 4
o Test voltages: 15 kV air discharge, 8 kV contact discharge
• Radiated, radio-frequency, electromagnetic field immunity, IEC 60255-26:2013
Level 3
o Test field strength: 10 V/m
• Electrical fast transient/burst immunity (EFT/B), IEC 60255-26:2013, Level 4
o Test voltage: 4 kV
• Surge immunity test, IEC 60255-26:2013
o Test voltages: 4 kV line-to-earth, 2 kV line-to-line
• Immunity to conducted disturbances, induced by radio-frequency fields,
IEC 60255-26:2013, Level 3
o Test voltage: 10 V
• Damped oscillatory wave immunity test, IEC 60255-26:2013
o Test frequency: 1 MHz
o Test voltage: 2.5 kV in common mode, 1 kV in differential mode
• Voltage dips, short interruptions and voltage variations immunity,
IEC 60255-26:2013
o Voltage dips: 40 % (200 ms), 70 % (500 ms), 80 % (5000 ms)
• Ripple on d.c. input power port immunity, IEC 60255-26:2013
o Level 4, 15 % of rated d.c. value
• Power frequency magnetic field immunity test, IEC 60255-26:2013, Level 5
o Test field field strength: 100 A/m continuous,
1000 A/m for 3 s
• Power frequency immunity test on the binary inputs,
IEC 60255-26:2013, Class A
o Test voltages: 300 V in common mode, 150 V in differential mode
• Insulation tests, IEC 60255-27:2013
o Impulse voltage test
▪ Test levels: 5 kV (1 kV for transducer and temperature
measuring inputs)
o Dielectric test
▪ Test levels: 2 kV AC 50 Hz (0.705 kV DC for transducer inputs)
o Insulation resistance
▪ Insulation resistance > 15 GΩ
• Radiated emission, IEC 60255-26:2013
Limits:
o 30 MHz to 230 MHz: 50 dB(μV/m) quasi peak, 3 m
o 230 MHz to 1 000 MHz: 57 dB(μV/m) quasi peak, 3 m
o 1 GHz to 3 GHz: 76 dB(μV/m) peak,3 m
o 3 GHz to 6 GHz: 80 dB(μV/m) peak,3 m
• Conducted emmission, IEC 60255-26:2013
Limits:
o 0,15 MHz to 0,50 MHz: 79 dB(μV) quasi peak, 66 dB(μV)
average
o 0,5 MHz - 30 MHz: 73 dB(μV) quasi peak, 60 dB(μV)
average
• Vibration, shock, bump and seismic tests on measuring relays and protection
equipment
o Vibration tests (sinusoidal), Class I, IEC 60255-21-1:1988
o Shock and bump tests, Class I, IEC 60255-21-2:1988
o Seismic tests, Class I, IEC 60255-21-3:1993
20 Mechanical data
▪ Construction: chromate aluminium surface with built-in EMC accessories
◼ If the power consumption of a 84 HP or 42 HP device does not exceed 30 W
(84 HP) or 14 W (42 HP), the construction will be built with solid top and
bottom cover panels.
If the power consumption exceeds 30 W (84 HP) or 14 W (42 HP), the
construction will be built with (honeycomb) perforated top and bottom cover
panels.
▪ EMC rack protects against electromagnetic environmental influences and protects
the environment from radiation from the interior
▪ IP protection:
o 24 HP panel instrument case: IP4x
o 84 HP and 42 HP (including double) rack: IP4x from front side, IP2x from rear
side
▪ Size:
o 19” (84 HP), 3 U, single rack
o ½ 19” (42 HP), 3 U, single rack
o ½ 19” (42 HP), 6 U, double rack
o 24 HP, panel instrument case
▪ Weight:
o 84 HP: max. 8 kg
o 42 HP, 6 U: max. 8 kg
o 42 HP, 3 U: max. 4.5 kg
o 24 HP: max. 3 kg
CONDUCTOR
CONNECTOR STRIP LENGTH CONDUCTOR TIGHTENING MINIMUM BEND
DIAMETER
TYPE [MM] AREA [MM2] TORQUE [NM] RADIUS*
[MM]
tension clamp
B2L 3.5 7 0.2 – 1 0.5 – 1.1 3 × OD**
connection
STVS AND
9 0.5 – 4 0.8 – 2.3 0.5 – 0.6 3 × OD**
RING LUG
ST/FC/LC - - - - 30 mm
PE FASTON
7 min. 4 min. 2.3 - 3 × OD**
TERMINAL
* Bend radius is measured along the inside curve of the wire or wire bundles.
** OD is the outer diameter of the wire or cable, including insulation.
The tightening torque of the screw for protective earth connection and the wall mounting must be
approx. 5 Nm.
The tightening torque of the screw for fastening the STVS connector must be approx. 1 Nm.
The minimum distance between an EP+ device and its wire channel must be at least 3 cm.
The minimum distance between two EP+ devices must be at least 10 cm.
During the installation make sure that the shortest possible length for PE (Protective Earth) cable
routing is applied.
21 Mounting methods
▪ Flush mounting
o 84 HP single rack
o 42 HP single rack
o 42 HP double rack
o 24 HP panel instrument case
o Remote HMI
▪ Rack mounting
o 84 HP single rack
o 42 HP single rack
o Remote HMI
▪ Semi-flush mounting
o 84 HP single rack
o 42 HP single rack
o 24 HP panel instrument case
o Remote HMI
▪ Wall mounting (with terminals)
o 84 HP single rack
o 42 HP single rack
▪ Din rail mounting
o 24 HP panel instrument case
▪ IP54 rated mounting
o 84 HP single rack
o 42 HP single rack
▪ Console mounting
o 42 HP single rack
▪ No mounting
FLUSH MOUNTING x x x x x
RACK MOUNTING x x x
SEMI-FLUSH
x x x x
MOUNTING
WALL MOUNTING
x x
(WITH TERMINALS)
IP54 RATED
x x
MOUNTING
CONSOLE
x
MOUNTING
COM COM
I I
0 0
x x
PANEL CUT-OUT
DEVICE 1 DEVICE 1
DEVICE 2 DEVICE 2
PANEL CUT-OUT
COM
I
0
DEVICE 1
DEVICE 2
MOUNTING FRAME
PANEL CUT-OUT
MOUNTING FRAME
Figure 21-5 Dimensions for flush mounting of 24 HP panel instrument case with 3D
illustration
COM COM
I I
0 0
x x
Note that rack mounting type devices can also be mounted in a cut-out (e.g. on a switchgear
door). It is possible to mount them from the front or from the back of the cut-out. The dimensions
for rack mounting cut-outs are in the figure below. Dimensions in brackets are applicable in case
of mounting from the back.
PANEL CUT-OUTS
84 HP DEVICE 1 42 HP DEVICE 1
84 HP DEVICE 2 42 HP DEVICE 2
a b
a b
SPECIAL
MOUNTING
COLLAR
PANEL CUT-OUT
COM
SPECIAL
MOUNTING
COLLAR
PANEL CUT-OUT
COM
MOUNTING FRAME
BACKPLANE OF THE SWITCHGEAR/RACK
Figure 21-12 Dimensions for semi-flush mounting of 24 HP panel instrument case with 3D illustration
277
UPPER TERMINAL
85
194
137
~312
ϕ 6.5(4X)
LOWER TERMINAL
252.5 75
~320
~515
UPPER VIEW
(M1:2)
UPPER TERMINAL
LOWER TERMINAL
UPPER VIEW
(M1:2)
206
76,8
~150 141
Figure 21-15 Dimensions for din rail mounting of 24 HP panel instrument case
21.8 No mounting
“No mounting” means that the 84 HP and 42 HP devices do not have any mounting accessories
on them.
This mounting method is only applicable if the device is for demonstration application.
For more information about this topic please contact our Application Team.
(application@protecta.hu)
22 Product availability
In this chapter you can read a list of the modules that have not regular availability for any reasons.
For more information about these devices please contact our Application Team.
(application@protecta.hu)
Connector with flange is an ordering option.
Ring-lug connector for CTs is an ordering option.