You are on page 1of 98

HARDWARE GUIDES

EuroProt+ Hardware description

DOCUMENT ID: PP-13-19958


LAST VERSION: 1.40
PROTECTION, AUTOMATION AND
2018-10-16, BUDAPEST CONTROL FOR POWER INDUSTRY
VERSION INFORMATION

VERSION INFORMATION

VERSION DATE MODIFICATION COMPILED BY


Preliminary version Peter
Preliminary 01.02.2010.
Budenszki
Peter
Preliminary 04.23.2010. Corrected preliminary version
Budenszki
1.0 11.11.2010. First edition Kornel Petri
Module description updated, some technical data Peter
1.1 15.06.2011.
added Budenszki
Binary output module (R4) drawings corrected, Peter
1.2 07.09.2011.
new modules added Budenszki
PS+2401 power supply added, some other Peter
1.3 prelim. 08.09.2011.
corrections added Budenszki
Peter
1.31 17.04.2012. New modules added
Budenszki
Peter
1.32 26.04.2012. Wall-mounting drawing update
Budenszki
Peter
1.34 28.08.2012. Minor corrections
Budenszki
10.09.2012. 24HP IP54 feature added,
09.10.2012. power supply naming clarification, PS+4401,
PS+2101 and PS+1602 added, O16+2401 and
10.10.2012. O16+4801 added
24 V DC PSTP+4201 and PS+4201 added
15.10.2012. Resolving Acronyms
31.10.2012 EMC/ESD conformance data updated Peter
1.35 RIO module added Budenszki
Device housing description updated Gabor Nagy
O8+2401 module added
VT+ and TRIP+ modules data updated
HMI+ module types added
07.11.2012. Device weight data added
ASIF-O transmitter and receiver data added
21.11.2012. TRIP+ wiring methods
CPU+9201 module type added
COM+8882, COM+1112 module types added
Long and short haul Ethernet transceiver types
added
ASIF-O POF, ASIF-O GLASS transmitter output
optical power data updated, ASIF-O GLASS
receiver data added
Slot numbers updated in backplane table
CT+ accuracy and power consumption data
updated, recommended applications added
VT+ selectable voltage range and power
Peter
consumption data updated, recommended
1.36 06.2013. Budenszki
applications added
Gabor Nagy
Binary input modules data updated
R4S+ modules data updated
TRIP+ module wiring chapter updated
RTD module data updated
AI modules data updated
PS+2101 input voltage interruption time updated
O6R5 modules added
Semi-flush mounting chapter updated
Product availability chapter added
Minor corrections

2 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
VERSION INFORMATION

New modules added:


CPU+0007, CPU+0291, CPU+1191, CPU+1391,
CPU+1291, CPU+9291,
COM+9901, COM+9902, COM+9992,
COM+1324,
HMI+2404, HMI+2504,
CT+5152, CT+5153, CT+2500,
VT+2212,
R8+01, R8+A1, R8+C0, R8+FF, R12+4400,
R16+0101, R16+0001, R16+A001,
RTD+0200,
AIC+0201.
CPU and COM module:
CPU+ module description updated.
Human-Machine Interface (HMI) module:
Remote HMI product added.
Voltage input module:
Voltage measuring ranges updated.
Binary input module:
Thermal withstand voltages updated.
Signaling module:
Rated voltages updated.
Main features updated.
Tripping module:
Thermal withstand voltages updated.
TRIP+ module wiring description and figures
Peter
updated.
1.37 10.2014. Budenszki
RTD input module:
Gabor Nagy
RTD module wiring figures updated.
Analog input module:
AIC+ module illustrations has been updated.
AI wiring figures added.
Power supply module:
Input voltage interruption times updated.
Input voltage ranges updated.
Internal fuses added.
Inrush current values added to main features.
PSTP+ module:
Input voltage interruption times updated, Input
voltage ranges updated.
Internal fuses added.
Inrush current values added to main features
O6R5+ module: Rated voltages updated, Relay
output main features updated
Binary input module with time
synchronization: Module description updated,
Withstand voltage for sync. input added
General data chapter: Altitude, atmospheric
pressure added
Mounting methods chapter: Rack types vs.
mounting methods table added, Illustrations
updated for all methods, 42 HP and 84 HP
remote HMI dimensions added
Product availability chapter: Modules added
Minor corrections:
SL/BL and SLA/BLA marking correction
HMI module: Peter
1.38 02.2015. LCD dot-defect handling policy chapter added Budenszki
Current input module: Gabor Nagy
CT+2500 became obsolete, replacement:
CT+1500

3 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
VERSION INFORMATION

Tripping module:
TRIP+2101 restricted to 110 V DC application,
TRIP+2201 became available and recommended
for new designs with rated voltage 220 V DC
PSTP+ module:
Card drawings updated, PE symbol added
Minor corrections
New modules added:
CPU+0281, CPU+0501, CPU+1401, CPU+1091
PSTP+2102, PSTP+4202
VS+0031
Mechanical data:
Notes on solid and perforated rack covers for 84
and 42 HP devices added. Peter
1.39 08.2015. Mounting methods: Budenszki
Semi-flush mounting of 24 HP panel instrument Gabor Nagy
case figure updated.
Wall mounting method figures updated.
IP54 rated mounting kit for 42 HP devices
chapter updated.
No mounting chapter added.
Minor corrections
New modules added:
ATO+0002, ATO+0004,
CPU+A001, CPU+A011, COM+1801,
CT+5111, CT+5154, CT+5155, CT+5253,
R1T+0001,
RTD+1200,
CVS+0001, CVSR+0001,
INJ+0005, INJ+0015,
RAI+01, RAI+11, RINJ+21,
PS3F+1001, PS+2303,
PSR2+2101,
RBOX+A201.
Current input module:
Thermal withstand data updated.
Accuracy data removed.
Max. measured current data updated.
Voltage input module:
Accuracy data removed. Peter
1.40 10.2018. Max. measured current data updated. Budenszki
Signaling module: Zoltan Bido
Main features updated.
Unused modules have been removed.
Tripping module:
TRIP+1101 restricted to 110 V DC.
RTD input module:
RTD module wiring figures updated.
Power supply module:
PS+4401 nominal 60 V DC input voltage range
added.
PSTP+ module:
PSTP+4201 nominal voltage and input voltage
range updated.
Special devices:
TRCS has been added.
Mounting methods:
IP54 rated mounting kit for 84 HP devices
Minor corrections

4 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CONTENTS

CONTENTS

1 System design ...................................................................................................................... 7


2 CPU and COM module ......................................................................................................... 8
2.1 CPU+ module.................................................................................................................. 8
2.1.1 Module handling ...................................................................................................... 8
2.1.2 Fast start-up ............................................................................................................. 9
2.1.3 HMI and communication tasks ................................................................................ 9
2.2 COM+ module ............................................................................................................... 14
2.3 Communication interface characteristics ...................................................................... 16
2.3.1 Ethernet multi-mode transmitter and receiver ....................................................... 16
2.3.1.1 MM/ST connector ........................................................................................... 16
2.3.1.2 MM/LC connector ........................................................................................... 17
2.3.2 Ethernet single mode transmitter and receiver ...................................................... 18
2.3.2.1 Long haul single mode transceiver................................................................. 18
2.3.2.2 Short haul single mode transceiver ................................................................ 19
2.3.3 ASIF-O transmitter and receiver ............................................................................ 20
2.3.3.1 ASIF-O POF ................................................................................................... 20
2.3.3.2 ASIF-O GLASS............................................................................................... 20
2.3.4 ASIF-G transmitter and receiver ............................................................................ 21
2.3.5 G.703 64 kbit/s co-directional interface (E0) ......................................................... 22
2.3.6 PRP/HSR redundant Ethernet communication interface ....................................... 23
2.3.6.1 Parallel Redundancy Protocol (PRP) ............................................................. 23
2.3.6.2 High-availability Seamless Redundancy (HSR) ............................................. 24
2.3.7 RBOX module ........................................................................................................ 25
3 Backplane module .............................................................................................................. 26
4 Human-Machine Interface (HMI) module ........................................................................... 28
5 Current input module .......................................................................................................... 32
6 Voltage input module .......................................................................................................... 38
7 Binary input module ............................................................................................................ 40
8 Signaling module ................................................................................................................ 43
9 Tripping module .................................................................................................................. 46
9.1 TRIP+ module wiring .................................................................................................... 47
9.1.1 3-wire TRIP+ wiring methods ................................................................................ 47
9.1.2 2-wire TRIP+ wiring methods ................................................................................ 48
10 RTD input module ............................................................................................................... 50
10.1 RTD module wiring .................................................................................................... 51
11 Analog input module (AI) .................................................................................................... 52
11.1 AI module wiring ........................................................................................................ 53
12 Analog output module (ATO) .............................................................................................. 54
12.1 ATO module wiring .................................................................................................... 55
13 Sensor input module ........................................................................................................... 56
14 INJ module .......................................................................................................................... 58

5 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CONTENTS

15 Generator protection modules ............................................................................................ 59


15.1 Auxiliary boxes for rotor earth fault protection .......................................................... 60
15.1.1 Use of auxiliary boxes ........................................................................................ 60
15.2 Wiring of the rotor earth fault protection modules ..................................................... 61
16 Power supply module ......................................................................................................... 62
17 Mixed function modules ...................................................................................................... 66
17.1 PSTP+ module .......................................................................................................... 66
17.1 PSR2+ module .......................................................................................................... 68
17.2 O6R5+ module .......................................................................................................... 70
17.3 Binary input module with time synchronization ......................................................... 72
17.4 Externally driven trip module ..................................................................................... 73
18 Special devices ................................................................................................................... 74
18.1 Remote I/O (RIO) server ........................................................................................... 74
18.1.1 SCPU/PS ........................................................................................................... 74
18.1.2 SO12/R2 ............................................................................................................ 74
18.2 TRCS ......................................................................................................................... 76
19 General data ....................................................................................................................... 78
20 Mechanical data .................................................................................................................. 79
21 Mounting methods .............................................................................................................. 80
21.1 Flush mounting .......................................................................................................... 81
21.1.1 Flush mounting of 84 HP and 42 HP single rack ............................................... 81
21.1.2 Flush mounting of 42 HP double rack ................................................................ 82
21.1.3 Flush mounting of 24 HP panel instrument case ............................................... 83
21.2 Rack mounting .......................................................................................................... 84
21.3 Semi-flush mounting.................................................................................................. 86
21.3.1 Semi-flush mounting of 84 HP single rack ......................................................... 86
21.3.2 Semi-flush mounting of 42 HP single rack ......................................................... 87
21.3.3 Semi-flush mounting of 24 HP panel instrument case ....................................... 88
21.4 Wall mounting of 42 HP and 84 HP devices ............................................................. 89
21.5 Din rail mounting of 24 HP panel instrument case .................................................... 90
21.6 IP54 rated mounting kit for 84 HP and 42 HP devices .............................................. 91
21.7 No mounting .............................................................................................................. 93
21.8 Remote HMI devices ................................................................................................. 95
22 Product availability .............................................................................................................. 96

6 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SYSTEM DESIGN

1 System design
The EuroProt+ protection device family is a scalable hardware platform to adapt to different
applications. Data exchange is performed via a 16-bit high-speed digital non-multiplexed parallel
bus with the help of a backplane module. Each module is identified by its location and there is no
difference between module slots in terms of functionality. The only restriction is the position of the
CPU module because it is limited to the “CPU” position. The built-in self-supervisory function
minimizes the risk of device malfunctions.

FLASH FLASH FLASH FLASH FLASH FRAM


8 MB 8 MB 8 MB 8 MB 8 MB 8 kB
REAR CONNECTORS P1 SRAM (64 kB), 7 ns

BACKPLANE CONNECTOR
STATION

SA0...15
BUS SDRAM (64 MB) SDRAM (64 MB)

RD0...15
FIBER P2

BUS CONTROL

BUS CONTROL

RD0...15
CD0...15

RA0...15
CA0...15
RJ45
SB REDU. CUART P3 125 MHz 125 MHz 12,5 MHz
FIBER FIB/PLA/G BACKPLANE
BUA0...13 BUA0...13
PROCESS
BUD0...15
P4 SPI SPI BUD0...15
PROCESS CUART RUART
DRIVER/
BUS
RA0...15 HIGH 12,5 MHz RECEIVER
BUS +
FIBER
DRIVER HIGH SPEED BUS RD0...15
SPEED PROTECTION
ETHERNET SWITCH

CIRCUITS

SPORT0

SPORT1
LOGIC BACK- BACK-
CUART TFT SIGNALS CCPU RCPU 125 MHz PLANE PLANE
PPI

CONTROL CONTROL
TOUCHSCREEN 500 MHz 500 MHz SLAVE CPU
GPIO

SIGNALS FUNCTIONS

MAC MAC

3,3 V 12 V
DC/DC
CMII JTAGs

CN1, CN2 CONNECTORS 25 MHz OSC

P5 RMII RTC, WDT,


SUPERCAP
CUART RUART 12 V 3,3 V (1,5 F/5,5 V) RESET
GENERATOR

Figure 1-1 CPU block diagram

7 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2 CPU and COM module

2.1 CPU+ module


The CPU module contains all the protection, control and communication functions of the
EuroProt+ device. Dual 500 MHz high-performance Analog Devices Blackfin processors separate
relay functions (RDSP) from communication and HMI functions (CDSP). Reliable communication
between processors is performed via high-speed synchronous serial internal bus (SPORT).
Each processor has its own operative memory such as SDRAM and flash memories for
configuration, parameter and firmware storage. The firmwares are stored in a dedicated flash
memory independent from the disturbance recorder and event storage. CDSP’s operating system
(uClinux) utilizes a robust JFFS flash file system, which enables fail-safe operation and the
storage of disturbance record files, configuration and parameters.

2.1.1 Module handling


The RDSP core runs at 500 MHz and its external bus speed is 125 MHz. The backplane data
speed is limited to approx. 20 MHz, which is more than enough for module data throughput. An
additional logic element (CPLD and SRAM) is used as a bridge between the RDSP and the
backplane. The CPLD collects analogue samples from CT/VT modules and also controls signaling
outputs and inputs.

8 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.1.2 Fast start-up


After power-up the RDSP processor starts up with the previously saved configuration and
parameters. Generally, the power-up procedure for the RDSP and relay functions takes only a
few seconds. That is to say, it is ready to trip within this time. CDSP’s start-up procedure is longer
because its operating system needs time to build its file system, initializing user applications such
as HMI functions and the IEC61850 software stack.

2.1.3 HMI and communication tasks


▪ Embedded WEB-server:
o Firmware upgrade possibility
o Modification of user parameters
o Events list and disturbance records
o Password management
o Online data measurement
o Commands
o Administrative tasks

▪ Front panel TFT display handling: the interactive menu set is available through the TFT
and the touchscreen interface

▪ User keys: capacitive touch keys on front panel

▪ The built-in 5-port Ethernet switch allows EuroProt+ to connect to IP/Ethernet-based


networks. The following Ethernet ports are available:
o Station bus (100Base-FX Ethernet) SBW
o Redundant station bus (100Base-FX Ethernet) SBR
o Process bus (100Base-FX Ethernet)
o EOB or EOB2 (Ethernet Over Board) or RJ-45 Ethernet user interface on front
panel
o Optional 10/100Base-T port via RJ-45 connector

▪ PRP/HSR seamless redundancy for Ethernet networking (100Base-FX Ethernet)

▪ Other communication:
o RS422/RS485 interfaces (galvanic interface to support legacy or other serial
protocols, ASIF)
o Plastic or glass fiber interfaces to support legacy protocols, ASIF
o Proprietary process bus communication controller on COM+ module
o Telecommunication interfaces: G.703, IEEE C37.94

9 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

SECONDARY STATION BUS SERVICE


PRIMARY
PROCESS PORT ON
STATION
CPU LEGACY BUS FRONT
BUS REDUNDANT
VERSION STATION BUS PORT/PROTOCOL (FIBER) PANEL
(FIBER) STATION BUS
(RJ-45) PB EOB/
SBW (FIBER) SBR
RJ45

CPU+0007 - - - - - +
CPU+0091 - - - - + SM SH +
CPU+0201 - + - - - +
CPU+0281 - + - - + SM LH +
CPU+0291 - + - - + SM SH +
CPU+0301 - - - + POF - +
CPU+0501 - - - + Galv. RS485/422 - +
CPU+1001 + MM - - - - +
CPU+1011 + MM - - - + MM +
CPU+1091 + MM - - - + SM SH +
CPU+1101 + MM - + MM - - +
CPU+1111 + MM - + MM - + MM +
CPU+1181 + MM - + MM - + SM LH +
CPU+1191 + MM - + MM - + SM SH +
CPU+1201 + MM + - - - +
CPU+1211 + MM + - - + MM +
CPU+1281 + MM + - - + SM LH +
CPU+1291 + MM + - - + SM SH +
CPU+1301 + MM - - + POF - +
CPU+1311 + MM - - + POF + MM +
CPU+1331 + MM - - + double POF - +
CPU+1381 + MM - - + POF + SM LH +
CPU+1391 + MM - - + POF + SM SH +
CPU+1401 + MM - - + GS - +
CPU+1411 + MM - - + GS + MM +
CPU+1481 + MM - - + GS + SM LH +
CPU+1491 + MM - - + GS + SM SH x
CPU+1501 + MM - - + Galv. RS485/422 - +
CPU+1511 + MM - - + Galv. RS485/422 + MM +
CPU+1581 + MM - - + Galv. RS485/422 + SM LH +
CPU+1611 + MM - - + Galvanic sync + MM +
CPU+1681 + MM - - + Galvanic sync + SM LH +
CPU+9201 + SM SH + - - - +

10 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

SECONDARY STATION BUS SERVICE


PRIMARY
PROCESS PORT ON
STATION
CPU LEGACY BUS FRONT
BUS REDUNDANT
VERSION STATION BUS PORT/PROTOCOL (FIBER) PANEL
(FIBER) STATION BUS
(RJ-45) PB EOB/
SBW (FIBER) SBR
RJ45

CPU+9291 + SM SH + - - + SM SH +
CPU+9501 + SM SH - - + Galv. RS485/422 - +
+ MM
CPU+A001 - - - - +
PRP/HSR
+ MM
CPU+A011 - - - + MM +
PRP/HSR
+ MM
CPU+A081 - - - + SM LH +
PRP/HSR
+ MM
CPU+A091 - - - + SM SH +
PRP/HSR

For legacy CPU cards (e.g. CPU+0001, ...) see Product availability chapter.

Legend for CPU version table:


MM: Multimode with ST connector,
SM: Single mode with FC/PC connector,
LH: Long Haul with FC/PC connector,
SH: Short Haul with FC/PC connector,
POF: Plastic Optical Fiber with 1 mm fiber connector,
GS: Glass with ST connector,
SB: Station Bus,
SBW: Station Bus Working,
SBR: Station Bus Redundant,
PB: Proprietary Process Bus,
PRP/HSR: PRP/HSR seamless redundancy port A and port B with MM/LC connector

11 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+
0007 0091 0201 0281 0291 0301 0501 1001 1011 1091 1101 1111

MM/ST MM/ST MM/ST MM/ST MM/ST


Tx Tx Tx Tx Tx
SB SB SB SBW SBW
Rx Rx Rx Rx Rx

Tx+ 1 MM/ST MM/ST


POF
RJ-45 RJ-45 RJ-45 Tx- 2
Tx Tx Tx
GND 3
Rx Rx- 4 SBR SBR
Rx+ 5 Rx Rx
SM SH SM LH SM SH SM SH
FCPC FCPC FCPC MM/ST FCPC MM/ST
Tx Tx Tx Tx Tx Tx
PB PB PB PB PB PB
Rx Rx Rx Rx Rx Rx

CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+
1181 1191 1201 1211 1281 1291 1301 1311 1331 1381 1391 1401

MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
SBW SBW SB SB SB SB SB SB SB SB SB SB
Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx

MM/ST MM/ST POF POF POF1 POF POF GS/ST


Tx Tx RJ-45 RJ-45 RJ-45 RJ-45 Tx Tx Tx Tx Tx Tx
SBR SBR Rx Rx Rx Rx Rx ASIF
Rx Rx Rx
SM LH SM SH SM LH SM SH POF2 SM LH SM SH
FCPC FCPC MM/ST FCPC FCPC MM/ST Tx FCPC FCPC
Tx Tx Tx Tx Tx Tx Tx Tx
Rx
PB PB PB PB PB PB PB PB
Rx Rx Rx Rx Rx Rx Rx Rx

CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+ CPU+
1411 1481 1491 1501 1511 1581 1611 1681 9201 9291 9501 A001
SM SH SM SH SM SH PRP/HSR
MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST MM/ST FCPC FCPC FCPC MM/LC
SB_LAN_A SB_LAN_B

Rx
Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx
Tx
SB SB SB SB SB SB SB SB SB SB SB
Rx
Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx
Tx

GS/ST GS/ST GS/ST Tx+ 1 Tx+ 1 Tx+ 1 - 1 - 1 Tx+ 1


A B I
Tx Tx- 2 Tx- 2 Tx- 2 - 2 - 2 RJ-45 RJ-45 Tx- 2 LINK/ACT
Tx Tx
GND 3 GND 3 GND 3 GND 3 GND 3 GND 3
ASIF ASIF ASIF Rx- 4 Rx- 4 Rx- 4 Sy- 4 Sy- 4 Rx- 4
Rx Rx Rx Rx+ 5 Rx+ 5 Rx+ 5 Sy+ Sy+ Rx+ 5
5 5
SM LH SM SH SM LH SM LH SM SH
MM/ST FCPC FCPC MM/ST FCPC MM/ST FCPC FCPC
Tx Tx Tx Tx Tx Tx Tx Tx
PB PB PB PB PB PB PB PB
Rx Rx Rx Rx Rx Rx Rx Rx

12 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

CPU+ CPU+ CPU+


A011 A081 A091
PRP/HSR PRP/HSR PRP/HSR
MM/LC MM/LC MM/LC

SB_LAN_A SB_LAN_B

SB_LAN_A SB_LAN_B

SB_LAN_A SB_LAN_B
Rx Rx Rx

Tx Tx Tx

Rx Rx Rx

Tx Tx Tx

A B I A B I A B I
LINK/ACT LINK/ACT LINK/ACT

SM LH SM SH
MM/ST
FCPC FCPC
Tx Tx Tx
PB PB PB
Rx Rx Rx

Figure 2-1 CPU versions

Interface types:
▪ 100Base-FX Ethernet:
o MM/ST 1300 nm, 50/62.5/125 μm connector, (up to 2 km) fiber
o SM/FC 1550 nm, 9/125 μm connector, (LH: long haul, up to 120 km)
o SM/FC 1550 nm, 9/125 μm connector, (SH: short haul, up to 50 km)
o MM/LC 1300 nm, 50/62.5/125 μm connector, (up to 2 km) fiber
▪ 10/100 Base-TX Ethernet: RJ-45-8/8
▪ Service port on HMI:
o 10/100 Base-T Ethernet: RJ-45-8/8
o EOB interface: attachable to the front panel by a proprietary magnetic connector;
the connector box ends in a RJ-45 8/8 plug. It is 10Base-T full duplex interface.
The EOB2 accessory enables 10/100Base TX communication with service
computers.
▪ ASIF: Asynchronous Serial Interface
o plastic optical fiber (ASIF-POF)
o glass with ST connector (ASIF-GS)
o galvanic RS485/422 (ASIF-G)

13 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.2 COM+ module


The COM+ family of EuroProt+ protection device is responsible for general communication tasks
such as line differential protection communication via Ethernet or telecommunication networks.
Other application is a general 5-port Ethernet switch.
The COM+1111 module is a 3 port 100Base-FX Ethernet-based communication module which
enables bus bar protection communication functionality or line differential protection
communication in T-branch applications.
The COM+1335 module is a not manageable 5-port Ethernet switch with 100Base-FX multi and/or
single mode fiber support. This module also the capability to communicate via MODBUS/TCP
protocol with Remote I/O (RIO) servers Protecta Ltd. also has an own RIO device product.
COM+1101 and COM+8801 additional communication modules added to EuroProt+ device
enables three terminal line differential communication between protections and redundant
communication too. Communication channel in this case is Ethernet 100Base-FX.

COM+ COM+ COM+ COM+ COM+


0091 1101 1111 1324 1335

MM/ST MM/ST
MM/LC MM/LC
Tx Tx
Tx Tx
LINE 1 LINE 1 LINE 1 LINE 1
Rx Rx
Rx Rx LINK 1 LINK 1
Tx Tx
LINE 2 LINE 2
MM/ST MM/ST Rx Rx
Tx Tx LINK 2 LINK 2
Tx Tx
LINE 2 LINE 2 LINE 3 LINE 3
Rx Rx
Rx Rx LINK 3 LINK 3
Tx Tx
LINE 4 LINE 4
Signal MM/ST Rx Rx
LINK 4 LINK 4
Tx
Syb Sya Tx
LINE 3 LINE 5
Rx
Rxb Rxa Rx LINK 5

Txb Txa

G.703 E0

COM+ COM+ COM+ COM+ COM+ COM+


1801 8801 8882 9901 9902 9992
SM LH SM LH SM SH SM SH SM SH
MM/ST FCPC FCPC FCPC FCPC FCPC
Tx Tx Tx Tx Tx Tx
LINE 1 LINE 1 LINE 1 LINE 1 LINE 1 LINE 1
Rx Rx Rx Rx Rx Rx
SM LH SM LH SM LH SM SH SM SH SM SH
FCPC FCPC FCPC FCPC FCPC FCPC
Tx Tx Tx Tx Tx Tx
LINE 2 LINE 2 LINE 2 LINE 2 LINE 2 LINE 2
Rx Rx Rx Rx Rx Rx
SM LH SM SH
FCPC FCPC
Tx Tx
LINE 3 LINE 3
Rx Rx

Figure 2-2 COM modules

14 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

NUMBER OF UNIT
MODULE TYPE INTERFACE TYPE APPLICATION
INTERFACES WIDTH

Line differential
COM+0091 G703.1 (64 kbit/s) 1 4 HP protection via telecom
network

MM/ST 1300 nm, 3 terminals / redundant


50/62.5/125 µm line differential
COM+1101 2 4 HP
connector, protection
100Base-FX Ethernet up to 2 km
MM/ST 1300 nm,
Busbar protection for 3
50/62.5/125 µm
COM+1111 3 4 HP bay units
connector,
up to 2 km
100Base-FX Ethernet
MM/LC 1300 nm,
50/62.5/125 µm 4-port Ethernet switch
COM+1324 4 8 HP
connector, for MODBUS via RIO
100Base-FX Ethernet
MM/LC 1300 nm,
50/62.5/125 µm 5-port Ethernet switch
COM+1335 5 8 HP
connector, for MODBUS via RIO
100Base-FX Ethernet
MM/ST 1300 nm,
50/62.5/125 µm and Line differential
SM/FC 1550 nm, protection,
COM+1801 2 4 HP
9/125 µm binary signal
connector, transmission
100Base-FX Ethernet
SM/FC 1550 nm, 3 terminals / redundant
9/125 µm line differential
COM+8801 2 4 HP
connector, protection
100Base-FX Ethernet up to 120 km
SM/FC 1550 nm, 3 direction
9/125 µm binary signal
COM+8882 3 4 HP
connector, transmission
100Base-FX Ethernet up to 120 km
SM/FC 1550 nm, 3 terminals / redundant
9/125 µm line differential
COM+9901 2 4 HP
connector, protection
100Base-FX Ethernet up to 50 km
SM/FC 1550 nm, 2 direction
9/125 µm binary signal
COM+9902 2 4 HP
connector, transmission
100Base-FX Ethernet up to 50 km
SM/FC 1550 nm, 3 direction
9/125 µm binary signal
COM+9992 3 4 HP
connector, transmission
100Base-FX Ethernet up to 50 km

15 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3 Communication interface characteristics

2.3.1 Ethernet multi-mode transmitter and receiver

2.3.1.1 MM/ST connector


Up to approximately 2 km.

Transmitter
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
OPTICAL OUTPUT POWER PO BOL*: -19
- -14 dBm avg.
62.5/125 μm, NA = 0.275 FIBER EOL*: -20
OUTPUT OPTICAL POWER PO BOL*: -22.5
- -14 dBm avg.
50/125 μm, NA = 0.20 FIBER EOL*: -23.5
10 %
OPTICAL EXTINCTION RATIO ER - -
-10 dB

CENTER WAVELENGTH λC 1270 1308 1380 nm

* BOL: Beginning of life, EOL: End of life

Receiver sensitivity is measured with 223 – 1 PRBS pattern within BER = 2.5 × 10-10
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

SIGNAL DETECT - ASSERTED PA PD + 1.5 dB - -33 dBm avg.

SIGNAL DETECT - DEASSERTED PD -45 - - dBm avg.

SIGNAL DETECT - HYSTERESIS PA – PD 1.5 - - dB

SIGNAL DETECT ASSERT TIME


AS_Max 0 2 100 µs
(OFF TO ON)
SIGNAL DETECT DEASSERT TIME (ON TO
ANS_Max 0 8 350 µs
OFF)

16 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.1.2 MM/LC connector


Up to approximately 2 km.

Transmitter
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

OPTICAL OUTPUT POWER PO BOL*: -19


-15.7 -14 dBm avg.
62.5/125 μm, NA = 0.275 FIBER EOL*: -20
OUTPUT OPTICAL POWER PO BOL*: -22.5
- -14 dBm avg.
50/125 μm, NA = 0.20 FIBER EOL*: -23.5
0.002 0.2 %
OPTICAL EXTINCTION RATIO ER -
-47 -27 dB

CENTER WAVELENGTH λC 1270 1308 1380 nm

* BOL: Beginning of life, EOL: End of life

Receiver sensitivity is measured with 223 – 1 PRBS pattern within BER = 2.5 × 10-10
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

SIGNAL DETECT - ASSERTED PA PD + 1.5 dB - -33 dBm avg.

SIGNAL DETECT - DEASSERTED PD -45 - - dBm avg.

SIGNAL DETECT - HYSTERESIS PA – PD 1.5 - - dB

SIGNAL DETECT ASSERT TIME


AS_Max 0 2 100 µs
(OFF TO ON)
SIGNAL DETECT DEASSERT TIME (ON TO
ANS_Max 0 5 100 µs
OFF)

17 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.2 Ethernet single mode transmitter and receiver

2.3.2.1 Long haul single mode transceiver


Up to approximately 120 km, with max. 32 dB link attenuation.

Transmitter
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

OPTICAL OUTPUT POWER PO -6 - 0 dBm avg.

OPTICAL EXTINCTION RATIO ER 8.3 - - dB

CENTER WAVELENGTH λC 1490 1550 1610 nm

Receiver sensitivity is measured with 223 – 1 PRBS pattern within BER = 2.5 × 10-10
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

OPTICAL INPUT SENSITIVITY PIN - -38 -35 dBm avg.

SATURATION PSAT -3 0 - dBm

CENTER WAVELENGTH λC 1100 - 1600 nm

SIGNAL DETECT - ASSERTED PA - - -35 dBm avg.

SIGNAL DETECT - DEASSERTED PD -45 - - dBm avg.

HYSTERESIS PHYS - 3 - dB

18 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.2.2 Short haul single mode transceiver


Up to approximately 50 km, with max. 27 dB link attenuation.

Transmitter
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

OPTICAL OUTPUT POWER PO -12 - -6 dBm avg.

OPTICAL EXTINCTION RATIO ER 8.3 - - dB

CENTER WAVELENGTH λC 1490 1550 1610 nm

Receiver sensitivity is measured with 223 – 1 PRBS pattern within BER = 2.5 × 10-10
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

OPTICAL INPUT SENSITIVITY PIN - -38 -35 dBm avg.

SATURATION PSAT -3 0 - dBm

CENTER WAVELENGTH λ 1100 - 1600 nm

SIGNAL DETECT - ASSERTED PA - - -35 dBm avg.

SIGNAL DETECT - DEASSERTED PD -45 - - dBm avg.

HYSTERESIS PHYS - 3 - dB

19 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.3 ASIF-O transmitter and receiver

2.3.3.1 ASIF-O POF

Transmitter
JUMPER
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
SETTINGS

TRANSMITTER -15.3 - -9 JP1 2-3


OUTPUT OPTICAL PT dBm
POWER -23.3 - -17 JP1 1-2

PEAK EMISSION
λPK - 660 - nm
WAVELENGTH

EFFECTIVE DIAMETER D - 1 - mm

NUMERICAL
NA - 0.5 -
APERTURE

Receiver
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

INPUT OPTICAL POWER


PR(L) -39 - -13.7 dBm
LEVEL LOGIC 0
INPUT OPTICAL POWER
PR(H) - - -53 dBm
LEVEL LOGIC 1

EFFECTIVE DIAMETER D - 1 - mm

NUMERICAL APERTURE NA - 0.5 -

These characteristics are valid for both POF interfaces in CPU+1331 module.

2.3.3.2 ASIF-O GLASS

Transmitter (Output measured out of 1 meter of cable)


JUMPER
PARAMETER SYMBOL MIN. TYP. M AX. UNIT
SETTINGS

50/125 μm -19.4 -16.4 -14.4 JP1 2-3


dBm
FIBER CABLE PO
peak
NA = 0.2 -28.9 -25.9 -23.9 JP1 1-2

62.5/125 μm -15.6 -12.6 -10.6 JP1 2-3


dBm
FIBER CABLE PO
peak
NA = 0.275 -22.9 -19.9 -17.9 JP1 1-2

Receiver
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

PEAK OPTICAL INPUT POWER dBm


PRH -25.4 - -9.2
LOGIC LEVEL HIGH (λP = 820 nm) peak
PEAK OPTICAL INPUT POWER dBm
PRL - - -40
LOGIC LEVEL LOW peak

20 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.4 ASIF-G transmitter and receiver


The RS422/RS485 interfaces of our CPU+1501, CPU+1511, CPU+1581, CPU+9501 modules
provide galvanic interface to support legacy or other serial protocols. For more details see our
RS485/422 application note, available on our homepage.

Driver
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

DIFFERENTIAL OUTPUT VOLTAGE


VOD2 2 - 3.6 V
(LOADED, RL = 100 Ω, RS422)
DIFFERENTIAL OUTPUT VOLTAGE
VOD2 1.5 - 3.6 V
(LOADED, RL = 54 Ω, RS485)

Receiver
PARAMETER SYMBOL MIN. TYP. M AX. UNIT

DIFFERENTIAL INPUT THRESHOLD


VTH -200 -125 -30 mV
VOLTAGE

INPUT VOLTAGE HYSTERESIS VHYS - 15 - mV

LINE INPUT RESISTANCE RIN 96 - - kΩ

21 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.5 G.703 64 kbit/s co-directional interface (E0)


The EuroProt+ device also supports line differential communication via telecom networks using
G.703.1 64 kbit/s co-directional interface type through COM+0091. This type of communication
is performed via 2 × 2 wire isolated galvanic type interface. The protection device is connected to
a multiplexer or gateway which is responsible for protocol/speed conversion.
▪ Connector type: Weidmüller: Receptacle: S2L 3.50/12/90 F
Plug: B2L 3.50/12/180 F
▪ Impedance: 120 Ω
▪ Cable length: 50 m
▪ Interface type: G.703.1 64 kbit/s (E0) co-directional, selectable grounding, with optional
external clock input
For further information about the cable assembly of this type of interface please see our
G.703 E0 cable assembly guide.

Receiver
± 1.5 dB difference between alarm-on and
LOSS OF SIGNAL ALARM LEVEL
alarm-off

DYNAMIC RANGE 10 dB maximum cable loss range

Transmitter

PAIR FOR EACH DIRECTION One symmetric pair

TEST LOAD IMPEDANCE 120 Ω resistive

NOMINAL PEAK VOLTAGE OF A “MARK” (PULSE) 1.0 V

PEAK VOLTAGE OF A “SPACE” (NO PULSE) 0 V ± 0.10 V

NOMINAL PULSE WIDTH 3.9 ms

RATIO OF THE AMPLITUDES OF POSITIVE AND NEGATIVE


0.95 to 1.05
PULSES AT THE CENTRE OF THE PULSES INTERVAL

RATIO OF THE WIDTHS OF POSITIVE AND NEGATIVE PULSES


0.95 to 1.05
AT THE NOMINAL HALF AMPLITUDE

M AXIMUM PEAK-TO-PEAK JITTER AT THE OUTPUT PORT Refer to clause 2/G.823

22 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.6 PRP/HSR redundant Ethernet communication interface


The PRP/HSR redundant Ethernet communication interface supports the two new IEC 62439-3
protocols which provide seamless redundancy for Ethernet networking in substations with zero-
time recovery in case of a single failure without frame loss:
▪ PRP – Parallel Redundancy Protocol (IEC 62439-3 Clause 4)
▪ HSR – High-availability Seamless Redundancy (IEC 62439-3 Clause 5)
This interface uses two MM/LC connectors for double connection to networks as these protocols
are based on the duplication of the sent frames.

CPU+
A001
PRP/HSR
MM/LC

SB_LAN_A SB_LAN_B
Rx

Tx

Rx

Tx

A B I
LINK/ACT

Figure 2-3 PRP/HSR connectors on a CPU+A001 module

2.3.6.1 Parallel Redundancy Protocol (PRP)


This redundancy protocol implements redundancy in the nodes as they are connected to two
independent networks (LAN_A and LAN_B) sending a copy of each frame to both directions. The
destination node receives and processes the first copy and discards the other copy of the sent
frame.
Source

DANP DANP
SAN

„A” frame

„B”
frame
LAN_A LAN_B
Bridge Bridge

Bridge Bridge Bridge Bridge

„A” frame
„B”
SAN frame SAN
RedBox
DANP

Destination

DANP SAN SAN

Figure 2-4 Example of a PRP redundant network

Single attached node (SAN): Network device that connects to a network with only one port.
Double attached node implementing PRP (DANP): Network device which connects to a network
with two ports implementing PRP redundancy.

23 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.6.2 High-availability Seamless Redundancy (HSR)


An HSR network provides redundancy with the same safety as PRP does with a lower cost. The
principle of this protocol is also based on the duplication of the sent frames but in this solution the
nodes are connected to a closed ring. A source node sends two copy of a frame to both direction
and the destination node accepts the first received copy and discards the other one. If a frame
returns to its source the node does not let it through itself prevent the possibility of an overload of
the ring.

„A” frame
SAN SAN SAN
„B” frame
Not HSR frame between host and ring

Source

DANH DANH
Bridge
CPU CPU

RedBox

CPU CPU CPU


DANH DANH DANH
Destination

Figure 2-5 Example of an HSR redundant network

Single attached node (SAN): Network device that connects to a network with only one port.
Double attached node implementing HSR (DANH): Network device which connects to a network
with two ports implementing HSR redundancy.

24 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CPU AND COM MODULE

2.3.7 RBOX module


The RBOX module connects to a PRP/HSR network with a Single Attachment Node. It does not
participate in the EP+ internal communication, it only receives the power supply and some device
management signals from the backplane module. It connects to the redundant network through
two MM/LC (Port A and Port B) interfaces, and the Interlink link connects to the device Ethernet
port.

RBOX+
A201
PRP/HSR
MM/LC
A

PRP/HSR
B

RJ-45

INTERLINK

Figure 2-6 RBOX module

25 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
BACKPLANE MODULE

3 Backplane module
The backplane board itself is a passive board but it provides a 16-bit bus, power supply
distribution, a two-wire interface (TWI) supporting module inventory management and module
identification. It is designed to meet the requirements for high speed digital buses and to comply
with electromagnetic emission standards.
Three versions are available: one is 84 HP wide with 21 module slots, the 42 HP wide, which
supports 10 module slots and the 24 HP, which supports 6 module slots. In case of applications
where more modules need to be supported or mounting space is critical, it is possible to
interconnect the racks (called double rack). The 24 HP case is not a modular system, and it has
fixed module layout.

MODULE
RACK CONFIGURATION
SLOTS

84 HP, SINGLE RACK (3 U) 20

42 HP, SINGLE RACK (3 U) 9

42 HP, DOUBLE RACK (6 U) 19

24 HP, PANEL INSTRUMENT CASE 5

All CPU modules require 1 slot.

26 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
BACKPLANE MODULE

The following illustrations only for showing the different types of rack/case configurations. For the
full scale of our available HMI modules please see the Human Machine Interface (HMI) module
chapter in the next pages.

84 HP single rack
(3 U)

42 HP single rack
(3 U)
[normal rack and with
cover profile]

42 HP double rack
with cover profile
(6 U)

24 HP panel
instrument case

Figure 3-1 Rack configuration illustrations

27 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
HUMAN-MACHINE INTERFACE
(HMI) MODULE

4 Human-Machine Interface (HMI) module


The EuroProt+ device HMI consists of the following two main parts:
• HMI module, which is the front panel of the device,
• HMI functionality is the embedded web server and the intuitive menu system that is
accessible through the HMI module. The web server is accessible via station bus, EOB
interface or RJ-45 Ethernet connector.

Remote HMI
Protecta provides an alternative solution in that
case if the IED can be only mounted in a non-
practical way for managing the device via usual
Human-Machine Interface.
By using a remote HMI (terminal HMI device)
customers are able to place the HMI at longest 3
meters far from the IED itself (host device) and
mount the IED in any possible way that is
applicable. The connection between the remote
HMI and the IED is provided by a custom
galvanic interface with DA-15 connector on the Figure 4-1 42 HP Remote HMI
remote side.
In such applications where remote display is used the HMI module can be only 42 or 84 HP wide
HMI+3502 or 84 HP wide HMI+5702.
Depending on the size of the HMI module you can use any applicable mounting methods that
described in the Mounting methods chapter (Flush mounting, Semi-flush mounting, Rack
mounting).

Figure 4–2 Remote HMI module with its host device

28 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
HUMAN-MACHINE INTERFACE
(HMI) MODULE

MODULE SERVICE
DISPLAY RACK SIZE ILLUSTRATION
TYPE PORT

42 HP

HMI+3501 3,5” TFT EOB

84 HP

42 HP

HMI+3502 3,5” TFT RJ-45

84 HP

HMI+5001 5,7” TFT EOB 42 HP

HMI+5002 5,7” TFT RJ-45 42 HP

HMI+5701 5,7” TFT EOB 84 HP

HMI+5702 5,7” TFT RJ-45 84 HP

HMI+2401* 3,5” TFT EOB 24 HP

HMI+2404** 3,5” TFT RJ-45 24 HP

HMI+2504** B&W LCD RJ-45 24 HP

*Obsolete module. These modules are not recommended for new designs! For the full list of
obsolete modules see our Product availability chapter.
**Smart Line S24 special selection modules. For further information please contact our sales
team: sales@protecta.hu

29 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
HUMAN-MACHINE INTERFACE
(HMI) MODULE

Function Description

16 PIECES USER LEDS Three-color, 3 mm circular LEDs

Yellow, 3 mm circular LED indicating EOB/RJ-45 (on the front


COM LED
panel) communication link and activity

CAPACITIVE TOUCH KEY


4 pcs yellow, 3 mm circular LEDs indicating touch key actions
LEDS

1 piece three-color, 3 mm circular LED


Green: normal device operation
DEVICE STATUS LED
Yellow: device is in warning state
Red: device is in error state

DEVICE KEYS Capacitive touch keys


(I, O, X, PAGE) Tactile push buttons (24 HP devices)

BUZZER Audible touch key pressure feedback

CHANGEABLE LED
Describes user LED functionality
DESCRIPTION LABEL

320 × 240 pixel TFT color display with resistive touchscreen


interface (3.5” or optional 5.7”)
DISPLAY
128 × 64 LCD black & white display

OPTICAL INTERFACE FOR For debugging and software development purposes


FACTORY USAGE Only for 42 and 84 HP devices.

Ethernet Over Board: communication interface accomplishes


isolated, non-galvanic Ethernet connection with the help of a
magnetically attached EOB device. The EOB device has an RJ-
45 type connector supporting Ethernet connection to the user
computer. This is a proprietary and patented solution from
Protecta Ltd.
EOB CONNECTOR
EOB1: Supporting 10Base-T Ethernet connection. Passive
device with one RJ45 type connector. Obsolete module.
EOB2: Supporting 10/100Base-Tx Ethernet connection. An
active device that has a USB port in addition to the RJ45
connector for powering up.

IP56 rated Ethernet 10/100-Base-T interface with RJ-45 type


ETHERNET SERVICE PORT
connector (IP56 only valid if the cap of the service port is closed.)

30 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
HUMAN-MACHINE INTERFACE
(HMI) MODULE

Device status LED Touch key LEDs

COM LED

Optical
interface
for factory
usage
Touch keys

Ethernet
service
port

Changeable LED User TFT display


description label LEDs

Figure 4–3 HMI signals and controls

LCD dot-defect handling policy


The definitions of dot-defect are as below:
▪ The defect area of the dot must be bigger than half of a dot.
▪ For bright dot-defect (sparkle mode), showing black pattern, the dot's brightness must be
over 30 % brighter than others at black raster.
▪ For dark dot-defect (black mode), showing white pattern, the dot's brightness must be
under 70 % darker than others at R.G.B. raster.

M AXIMUM NUMBER
ACCEPTABLE
DOT-DEFECT TYPE
3.5" 5.7"

1 dot 4 4

SPARKLE MODE 2 dots 2 (sets) 1

IN TOTAL 4 5

1 dot 4 5

BLACK MODE 2 dots 2 (sets) 2

IN TOTAL 4 5

SPARKLE MODE AND BLACK MODE 2 dots 2 (sets) n/a

IN TOTAL 6 10
For further information please contact our Application Team. (application@protecta.hu)

31 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CURRENT INPUT MODULE

5 Current input module


This is an input module with intermediate current transformers to input the phase currents and
the zero sequence current. The rated current for the phase current and for the zero sequence
current can be selectable by parameter.
For more detailed information about the application of our current input modules please see our
“CT application guide” on our webpage.
Main features:
• Rated frequency: 50 Hz, 60 Hz
• Electronic iron-core flux compensation
• Connector type:
o Receptacle: Weidmüller STVS8 SS
o Plug: Weidmüller STVS8 SB

Module type CT+5151(R**) CT+5152*

CHANNEL NUMBER 1–4 1–4

SELECTABLE RATED
1 5 1 5
CURRENT, IN [A]

M AX. MEASURED
50 × IR 50 × IR
CURRENT (± 10 %)

POWER CONSUMPTION
0.01 0.25 0.01 0.25
AT RATED CURRENT [VA]

THERMAL WITHSTAND
[A]

CONTINUOUSLY 20 20

10 s 175 175

1s 500 500

10 ms 1200 1200

RECOMMENDED General protection


BBP bay units.
APPLICATION applications.

*Special module. For further information see our Product availability chapter.
**Ring lug connector (CT+5151R)

32 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CURRENT INPUT MODULE

Module type CT+1155* CT+1500 CT+2500**

CHANNEL NUMBER 1–4 1–3 1–3

SELECTABLE RATED
1 5 1 5 1 5
CURRENT, IN [A]

M AX. MEASURED
12.5 × IR 2 × IR 2 × IR
CURRENT (± 10 %)

POWER CONSUMPTION
0.02 0.45 0.1 1.55 0.1 1.55
AT RATED CURRENT [VA]

THERMAL WITHSTAND
[A]

CONTINUOUSLY 20 7 7

10 s 120 50 50

1s 380 150 150

10 ms 850 330 330

Special protection
General 3Ph
applications where
RECOMMENDED measurement
the overcurrent in the DGBV applications.
APPLICATION applications.
secondary circuit can
DGBV applications.
not exceed 10 × In.
*Special module. For further information see our Product availability chapter.
**Obsolete module. For further information see our Product availability chapter.

33 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CURRENT INPUT MODULE

MODULE TYPE CT+5102 CT+5101

CHANNEL NUMBER 1–3 4 1–3 4

SELECTABLE RATED
1 5 0.2 1 1 5 0.2 1
CURRENT, IN [A]

M AX. MEASURED
50 × IR 50 × IR 50 × IR 12.5 × IR
CURRENT (± 10 %)

POWER CONSUMPTION
0.01 0.25 0.001 0.01 0.01 0.25 0.005 0.1
AT RATED CURRENT [VA]

THERMAL WITHSTAND
[A]

CONTINUOUSLY 20 20 20 7

10 s 175 120 175 50

1s 500 380 500 150

10 ms 1200 850 1200 330

RECOMMENDED Sensitive earth fault Extremely sensitive earth fault


APPLICATION protection applications. protection applications.

MODULE TYPE CT+0101* CT+5111**

CHANNEL NUMBER 1–4 1–3 4

SELECTABLE RATED
0.01 0.05 1 5 0.001 0.005
CURRENT, IN [A]

M AX. MEASURED CURRENT


50 × IR 50 × IR 50 × IR
(± 10 %)

POWER CONSUMPTION AT
0.005 0.1 0.01 0.25 0.005 0.1
RATED CURRENT [VA]

THERMAL WITHSTAND [A]

CONTINUOUSLY 7 20 7

10 s 50 175 50

1s 150 500 150

10 ms 330 1200 330

RECOMMENDED DEFL earth fault Sensitive earth fault


APPLICATION protection applications protection applications.
*Special module. For further information see our Product availability chapter.
**Obsolete module. For further information see our Product availability chapter.

34 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CURRENT INPUT MODULE

MODULE TYPE CT+5153 CT+5154

CHANNEL NUMBER 1–3 4 1–3 4

SELECTABLE RATED 0.2


1 5 1 0.2 1 5 5 1 0.2
CURRENT, IN [A] sens.
M AX. MEASURED CURRENT
50 × IR 10 × IR 50 × IR 10 × IR
(± 10 %)
POWER CONSUMPTION AT
0.06 1.3 0.6 0.004 0.0004 0.06 1.3 1.3 0.06 0.004
RATED CURRENT [VA]

THERMAL WITHSTAND [A]

CONTINUOUSLY 20 7 20

10 s 175 50 175

1s 500 150 500

10 ms 1200 330 1200

General protection application. General protection application.


RECOMMENDED
Transient earth fault protection Transient earth fault protection
APPLICATION
applications. applications.

35 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CURRENT INPUT MODULE

MODULE TYPE CT+5155* CT+5253*

CHANNEL NUMBER 1–3 4 1–3 4

SELECTABLE RATED 0.05 0.05


1 5 0.25 0.05 1 5 0.25 0.05
CURRENT, IN [A] sens. sens.
M AX. MEASURED
50 × IR 10 × IR 25 × IR
CURRENT (± 10 %)

POWER CONSUMPTION AT
0.06 1.3 0.6 0.004 0.0004 0.06 1.3 0.6 0.004 0.0004
RATED CURRENT [VA]

THERMAL WITHSTAND [A]

CONTINUOUSLY 20 7 20 7

10 s 165 50 165 50

1s 475 150 475 150

10 ms 1050 330 1050 330

DMD.
RECOMMENDED
Sensitive earth fault Circuit breaker diagnostics.
APPLICATION
protection applications.
*Special module. For further information see our Product availability chapter.

36 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
CURRENT INPUT MODULE

CT+ CT+ CT+ CT+ CT+ CT+ CT+ CT+


5151 5152 1155 1500 2500 5102 5101 0101

1 1 1 1 1 1 1 1

CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1

CT3 CT2 CT1

CT3 CT2 CT1

CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1


2 2 2 2 2 2 2 2
3 3 3 3 3 3 3 3
4 4 4 4 4 4 4 4
5 5 5 5 5 5 5 5
6 6 6 6 6 6 6 6
7 7 7 7 7 7 7 7
8 8 8 8 8 8 8 8

CT+ CT+ CT+ CT+ CT+ CT+ CT+


5111 1515 5110 5153 5154 5155 5253

1 1 1 1 1 1 1
CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1

CT4 CT3 CT2 CT1

2 2 2 2 2 2 2 CT4 CT3 CT2 CT1


3 3 3 3 3 3 3
4 4 4 4 4 4 4
5 5 5 5 5 5 5
6 6 6 6 6 6 6
7 7 7 7 7 7 7
8 8 8 8 8 8 8

Figure 5-1 CT modules

37 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
VOLTAGE INPUT MODULE

6 Voltage input module


If the device performs voltage related functions (over/undervoltage, directionality, distance
protection) or the voltage is to be sampled for the disturbance recorder, then this module is
needed. The module also has access to 3 frequency measurement lines on the backplane that
can be assigned during configuration.

MODULE TYPE VT+2211 (F**) VT+2215*

CHANNEL NUMBER 4 4

Type 100: Type 100:


100 100
, 100 V , 100 V
SELECTABLE VOLTAGE 3 3
RANGE Type 200: Type 200:
200 200
, 200 V , 200 V
3 3

CONTINUOUS VOLTAGE
250 V 250 V
WITHSTAND

SHORT TIME
275 V AC / 350 V DC 275 V AC / 350 V DC
OVERLOAD (1 S)

VOLTAGE MEASURING
0.05 UR – 1.3 UR 0.05 UR – 1.3 UR
RANGE (± 10 %)

ch. 1-3: 0.61 VA at 200 V


POWER CONSUMPTION 0.61 VA at 200 V
0.2 VA at 100 V
OF VOLTAGE INPUT 0.2 VA at 100 V
ch. 4: 50 mVA at 100 V

FREQUENCY
Ux ≥ 25 % of rated voltage
MEASUREMENT RANGE

Receptacle: Weidmüller SLA 8/90


CONNECTOR TYPE
Plug: Weidmüller BLA 8/180

Special protection
applications.
The 4th channel of VT+2215
RECOMMENDED General protection
is for special voltage
APPLICATION applications.
transformers where low
power consumption is
needed.
*Special module. For further information see our Product availability chapter.
**Screwed type connector. (VT+2211F)

38 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
VOLTAGE INPUT MODULE

MODULE TYPE VT+2245* VT+2246**

CHANNEL NUMBER 4 3

Type 200:
200
, 200 V
SELECTABLE VOLTAGE 3
RANGE Type 400:
400
3

CONTINUOUS VOLTAGE
400 V
WITHSTAND

SHORT TIME
420 V AC / 560 V DC
OVERLOAD (1 S)

VOLTAGE MEASURING
0.05 UR – 1.3 UR
RANGE (± 10 %)

POWER CONSUMPTION 0.21 VA at 200 V


OF VOLTAGE INPUT 0.28 VA at 230 V

FREQUENCY
Ux ≥ 25 % of rated voltage
MEASUREMENT RANGE

Receptacle: Weidmüller SLA 8/90 Receptacle: Weidmüller SLA 6/90


CONNECTOR TYPE
Plug: Weidmüller BLA 8/180 Plug: Weidmüller BLA 6/180

RECOMMENDED
Special protection applications for 400 V AC secondary voltage.
APPLICATION

*Special module. For further information see our Product availability chapter.
**Increased isolation to 6kV

VT+ VT+ VT+ VT+ VT+


2211 2215 2212 2245 2246

1 1 1 1 1
VT1
VT1

VT1

VT1

VT1

2 2 2 2 2
3 3 3 3 3
VT3 VT2
VT3 VT2

VT3 VT2

VT3 VT2

VT3 VT2

4 4 4 4 4
5 5 5 5 5
6 6 6 6 6
7 7 7 7
VT4
VT4

VT4

VT4

8 8 8 8

Figure 6-1 VT modules

39 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
BINARY INPUT MODULE

7 Binary input module


The inputs are galvanic isolated and the module converts high-voltage signals to the voltage level
and format of the internal circuits. This module is also used as an external IRIG-B synchronization
or PPM input. Dedicated synchronization input is used for this purpose.

MODULE TYPE O8+2401 O8+4801 O8+1101 O8+2201

CHANNEL NUMBER 8 8 8 8

TIME configured by configured by configured by configured by


SYNCHRONIZATION EuroCAP EuroCAP EuroCAP EuroCAP

RATED VOLTAGE 24 V 48 V 110 V 220 V

THERMAL WITHSTAND
72 V 100 V 250 V 320 V
VOLTAGE

falling 0.64 UR falling 0.64 UR falling 0.64 UR falling 0.64 UR


CLAMP VOLTAGE
rising 0.8 UR rising 0.8 UR rising 0.8 UR rising 0.8 UR

GROUNDING GROUPS independent independent independent independent

Receptacle: Weidmüller SLA 16/90


CONNECTOR TYPE
Plug: Weidmüller BLA 16/180

MODULE TYPE O12+2401 O12+4801 O12+1101 O12+2201

CHANNEL NUMBER 12 12 12 12

TIME configured by configured by configured by configured by


SYNCHRONIZATION EuroCAP EuroCAP EuroCAP EuroCAP

RATED VOLTAGE 24 V 48 V 110 V 220 V

THERMAL WITHSTAND
72 V 72 V 250 V 320 V
VOLTAGE

falling 0.64 UR falling 0.64 UR falling 0.64 UR falling 0.64 UR


CLAMP VOLTAGE
rising 0.8 UR rising 0.8 UR rising 0.8 UR rising 0.8 UR

4 × 3 common 4 × 3 common 4 × 3 common 4 × 3 common


GROUNDING GROUPS
ground ground ground ground

Receptacle: Weidmüller SLA 16/90


CONNECTOR TYPE
Plug: Weidmüller BLA 16/180

40 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
BINARY INPUT MODULE

MODULE TYPE O12+4201* O12+2101*

CHANNEL NUMBER 12 12

TIME
configured by EuroCAP configured by EuroCAP
SYNCHRONIZATION

24 V DC / 48 V DC 110 V DC / 220 V DC
RATED VOLTAGE user selectable on channel user selectable on channel
basis by jumpers basis by jumpers

THERMAL WITHSTAND
72 V 320 V
VOLTAGE

falling 0.64 UR falling 0.64 UR


CLAMP VOLTAGE
rising 0.8 UR rising 0.8 UR

GROUNDING GROUPS 4 × 3 common ground 4 × 3 common ground

Receptacle: Weidmüller SLA 16/90


CONNECTOR TYPE
Plug: Weidmüller BLA 16/180
* O12+2101 and O12+4201 modules can be used only in demonstration applications! For further
information see our Product availability chapter.

MODULE TYPE O16+2401 O16+4801 O16+1101 O16+2201

CHANNEL NUMBER 16 16 16 16

TIME
- - - -
SYNCHRONIZATION

RATED VOLTAGE 24 V 48 V 110 V 220 V

THERMAL WITHSTAND
72 V 100 V 250 V 320 V
VOLTAGE

falling 0.64 UR falling 0.64 UR falling 0.64 UR falling 0.64 UR


CLAMP VOLTAGE
rising 0.8 UR rising 0.8 UR rising 0.8 UR rising 0.8 UR

2 × 8 common 2 × 8 common 2 × 8 common 2 × 8 common


GROUNDING GROUPS
ground ground ground ground

Receptacle: 2 × Weidmüller SL 3,5/9/90


CONNECTOR TYPE
Plug: Weidmüller 2 × BL 3.5/9/180

Thermal withstand voltage: continuous with 60 % of the input channels are energized.

41 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
BINARY INPUT MODULE

Main features:
• Digitally filtered per channel
• Current drain:
o max. 1.6 mA per channel at 220 V DC
o max. 1.8 mA per channel at 110 V DC
o max. 2 mA per channel at 48 V DC
o max. 3 mA per channel at 24 V DC
• In such applications where the input voltage is 60 V the modules with 48 V rated
voltage can be used.
• Input voltage type can be either DC or AC voltage. If AC voltage is used make
sure that the type and the parameters of the binary inputs are configured properly
in EuroCap tool.

O8+ O8+ O8+ O8+ O12+ O12+ O12+ O12+


2401 4801 1101 2201 2401 4801 1101 2201

1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 2
3 3 3 3 3 3 3 3
4 4 4 4 4 4 4 4
5 5 5 5 5 5 5 5
6 6 6 6 6 6 6 6
7 7 7 7 7 7 7 7
8 8 8 8 8 8 8 8
9 9 9 9 9 9 9 9
10 10 10 10 10 10 10 10

11 11 11 11 11 11 11 11

12 12 12 12 12 12 12 12

13 13 13 13 13 13 13 13

14 14 14 14 14 14 14 14

15 15 15 15 15 15 15 15

16 16 16 16 16 16 16 16

O12+ O12+ O16+ O16+ O16+ O16+


4201 2101 2401 4801 1101 2201
1 1 1 1

1 1 2 2 2 2

2 2 3 3 3 3

3 3 4 4 4 4

4 4 5 5 5 5

5 5 6 6 6 6

6 6 7 7 7 7

7 7 8 8 8 8

8 8 9 9 9 9

9 9 10 10 10 10
10 10 11 11 11 11
11 11 12 12 12 12
12 12 13 13 13 13
13 13 14 14 14 14
14 14 15 15 15 15
15 15 16 16 16 16
16 16 17 17 17 17

18 18 18 18

Figure 7-1 Binary input modules

42 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SIGNALING MODULE

8 Signaling module
The signaling module has 4, 8, 12 or 16 relay outputs with dry contacts.

MODULE TYPE R4+01 R8+00 R8+80 R8+C0*

RATED VOLTAGE 250 V AC/DC 250 V AC/DC 250 V AC/DC 250 V AC/DC

CONTINUOUS
8A 8A 8A 8A
CARRY

CONTACT CH8 NC CH7 and CH8 NC


4 CO 8 NO
VERSIONS others NO others NO

GROUP ISOLATION 4 independent 8 independent 8 independent 8 independent

Receptacle:
Weidmüller
SLA 12/90 Receptacle: Weidmüller SLA 16/90
CONNECTOR TYPE
Plug: Plug: Weidmüller BLA 16/180
Weidmüller
BLA 12/180
*Special module. For further information see our Product availability chapter.

MODULE TYPE R8+FF* R12+0000 R12+4000

RATED VOLTAGE 250 V AC/DC 250 V AC/DC 250 V AC/DC

CONTINUOUS CARRY 8A 8A 8A

CH12 NC
CONTACT VERSIONS 8 NC 12 NO
others NO

GROUP ISOLATION 8 independent 4 × 3 common 4 × 3 common

Receptacle:
Weidmüller SLA 16/90
Receptacle: Weidmüller SLA 16/90
CONNECTOR TYPE Plug: Weidmüller BLA
Plug: Weidmüller BLA 16/180
16/180

*Special module. For further information see our Product availability chapter.

43 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SIGNALING MODULE

MODULE TYPE R16+0000 R16+8000 R16+8080

RATED VOLTAGE 250 V AC/DC 250 V AC/DC 250 V AC/DC

CONTINUOUS
8A 8A 8A
CARRY

CONTACT CH16 NC CH16 and CH8 NC


16 NO
VERSIONS others NO others NO

GROUP ISOLATION 2 × 8 common 2 × 8 common 2 × 8 common

Receptacle: 2 × Weidmüller SL 3.5/9/90


CONNECTOR TYPE
Plug: 2 × Weidmüller BL 3.5/9/180

MODULE TYPE R4S+01* R4S+16* R1T+0001***

RATED VOLTAGE 250 V AC/DC 250 V AC/DC 320 V AC/DC

CONTINUOUS
8A 8A 32 A
CARRY**

CONTACT
4 CO 4 CO 1 NO
VERSIONS

GROUP ISOLATION 4 independent 4 independent 1 independent

Receptacle: Weidmüller
Receptacle: Weidmüller SLA 12/90 STVS6 SS
CONNECTOR TYPE
Plug: Weidmüller BLA 12/180 Plug: Weidmüller
STVS6 SB
*Special module. For further information see our Product availability chapter.
**If the signaling is performed only via a solid state relay (SSR), the continuous carry value is
120 mA.
***Thyristor module. Can be used only unipolarly. For further information see our Product
availability chapter.

Main features (according to IEC 60255-26):


• Maximum switching voltage: 400 V AC
• Breaking capacity: (L/R=40 ms) at 220 V DC: 0.2 A, at 110 V DC: 0.3 A
• Breaking capacity max.: 2000 VA
• Short time carrying capacity: 1 s, 35 A
• Limiting making current, max. 4 s: 15 A (df = 10 %)
• Initial dielectric strength between open contacts, 1 min: 1000 VRMS
• Mechanical endurance: 10 × 106 cycles
• Circuit closing capability: typically 10 ms, maximally 22 ms,
with SSR 0.5 ms.
• Bounce time: typically 6,5 ms, maximally 10 ms, with SSR 0.5 ms.
• Minimal switching requirement: 5 V
• The signaling is also performed via a solid state relay (SSR) channel on
R4S+01 and R4S+16 module

44 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SIGNALING MODULE

R4+ R4S+ R4S+ R8+ R8+ R8+ R8+


01 01 16 00 80 C0 FF

1 1 1 1
2 2 2 2
1 1 1 3 3 3 3
2 2 2 4 4 4 4
3 3 3 5 5 5 5
4 4 4 6 6 6 6
5 5 5 7 7 7 7
6 6 6 8 8 8 8
7 7 7 9 9 9 9
8 8 8 10 10 10 10

9 9 9 11 11 11 11

10 10 10 12 12 12 12

11 11 11 13 13 13 13

12 12 12 14 14 14 14

15 15 15 15

16 16 16 16

R12+ R12+ R16+ R16+ R16+ R1T+


0000 4000 0000 8000 8080 0001
1 1 1

1 1 2 2 2

2 2 3 3 3

3 3 4 4 4

4 4 5 5 5

5 5 6 6 6

6 6 7 7 7 1
7 7 8 8 8 2
8 8 9 9 9 3
9 9 10 10 10 4
10 10 11 11 11 5
11 11 12 12 12 6
12 12 13 13 13
13 13 14 14 14
14 14 15 15 15
15 15 16 16 16
16 16 17 17 17

18 18 18

Figure 8-1 Signaling modules

45 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
TRIPPING MODULE

9 Tripping module
The tripping module is a proprietary and patented solution that facilitates direct control of a circuit
breaker.

MODULE TYPE TRIP+4201 TRIP+2101 TRIP+2201 TRIP+21F1** TRIP+1101*

CHANNEL NUMBER 4 4 4 4 4

24 V DC and
RATED VOLTAGE 110 V DC 220 V DC 110 V DC 110 V DC
48 V DC
THERMAL
WITHSTAND 72 V DC 132 V DC 242 V DC 132 V DC 242 V DC
VOLTAGE
CONTINUOUS
8A 8A 8A 8A 8A
CARRY

M AKING CAPACITY 0.5 s, 30 A 0.5 s, 30 A 0.5 s, 30 A 0.5 s, 30 A 0.5 s, 30 A

BREAKING L/R = 40 ms: L/R = 40 ms: L/R = 40 ms: L/R = 40 ms: L/R = 40 ms:
CAPACITY 4 A DC 4 A DC 4 A DC 4 A DC 4 A DC

Receptacle: Weidmüller SLA 12/90


CONNECTOR TYPE
Plug: Weidmüller BLA 12/180
*Obsolete module. These modules are not recommended for new designs! For the full list of
obsolete modules see our Product availability chapter.
**Without trip circuit supervision.
Thermal withstand voltage: continuous with 60 % of the input channels are energised
Main features:
• High-speed operation: with pre-trip 0.5 ms, without pre-trip typically 10 ms,
maximally 22 ms.
• Trip circuit supervision for each trip contact
• Tripping output can be dry contact type too (applies to TRIP+4201 and
TRIP+2101). For further information please contact our Application Team.
(application@protecta.hu)

TRIP+ TRIP+ TRIP+ TRIP+ TRIP+


1101 2201 4201 2101 21F1

1+ 1+ 1+ 1+ 1+
2 - 2 - 2 - 2 - 2 -
3 NO 3 NO 3 NO 3 NO 3 NO

4+ 4+ 4+ 4+ 4+
5 - 5 - 5 - 5 - 5 -
6 NO 6 NO 6 NO 6 NO 6 NO

7+ 7+ 7+ 7+ 7+
8 - 8 - 8 - 8 - 8 -
9 NO 9 NO 9 NO 9 NO 9 NO

10 + 10 + 10 + 10 + 10 +

11 - 11 - 11 - 11 - 11 -

12 NO 12 NO 12 NO 12 NO 12 NO

Figure 9-1 Tripping modules

46 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
TRIPPING MODULE

9.1 TRIP+ module wiring


The tripping module provides tripping circuit supervision function (TCS). The wiring of these
modules can be 2-wire or 3-wire. (TCS function is active for all wiring methods.)
The voltage of the "No" contact is maximized at 15 V by a zener-diode. Make sure that the voltage
caused by the resistance of the circuit breaker and the injected current from the TRIP+ module
does not reach 10 V.
Our TRIP+ modules are improved to switch DC circuits. Using reversed polarity or AC voltage
can cause the damage of the internal circuits.

9.1.1 3-wire TRIP+ wiring methods

TRIP+ module + +

Circuit breaker
TCS – –
(TRIP Circuit
Supervision)

No –

Figure 9-2 3-wire TRIP+ wiring

It is possible to use parallel connected TRIP+ modules. In this case the negative contacts must
be common.

+ A+
TRIP+ module

Circuit breaker
TCS –

(TRIP Circuit
Supervision)

No –

+ B+
TRIP+ module

TCS

(TRIP Circuit
Supervision)

No

Figure 9-3 3-wire TRIP+ wiring using parallel connected TRIP+ modules

47 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
TRIPPING MODULE

9.1.2 2-wire TRIP+ wiring methods


If it is necessary you can also wire the TRIP+ modules using only the “+” and the “No” contacts.
+ +
TRIP+ module

Circuit breaker
TCS
(TRIP Circuit
Supervision)

No –

Figure 9-4 2-wire TRIP+ wiring

It is possible to use parallel connected TRIP+ modules.

+ A+
TRIP+ module

Circuit breaker
TCS
(TRIP Circuit
Supervision)

No –

+ B+
TRIP+ module

TCS
(TRIP Circuit
Supervision)

No

Figure 9-5 2-wire TRIP+ wiring using parallel connected TRIP+ modules

48 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
TRIPPING MODULE

If the circuit breaker needs two-pole switching TRIP+ modules can be connected series as you
can see in Figure 9–6.
+ +
TRIP+ module

Circuit breaker
TCS
(TRIP Circuit
Supervision)

No

TRIP+ module +

TCS
(TRIP Circuit
Supervision)

No –

Figure 9-6 2-wire TRIP+ wiring using series connected TRIP+ modules

MODULE TYPE TRIP+4201 TRIP+2101 TRIP+2201 TRIP+1101


VALUE OF R
RESISTOR (± 10 10 kΩ 73 kΩ 130 kΩ 60 kΩ
%)
INJECTED
2.4 mA @ 24 V DC 1.8 mA @ 110 V DC
CURRENT AT "NO" 1.5 mA @ 110 V DC 1.7 mA @ 220 V DC
4.8 mA @ 48 V DC 3.6 mA @ 220 V DC
CONTACT

49 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
RTD INPUT MODULE

10 RTD input module


The RTD+1100 module is used to measure the temperature through the variation of resistance
of temperature detectors. RTD+0200 and RTD+1200 are special modules for Petersen coil
controllers (DRL) measuring the resistance of the potentiometer.

MODULE TYPE RTD+0200 RTD+1100 RTD+1200

CHANNEL NUMBER 1 4 1

MEASUREMENT METHOD 3 wire configuration 2, 3 or 4 wire configuration 3 wire configuration

RELATIVE ACCURACY ± 0.5 % ± 1 digit ± 0.5 % ± 1 digit ± 0.5 % ± 1 digit

Pt100/Ni100
Ni120/Ni120US
Pt250/Ni250
SENSOR TYPE Service-Ohm Pt1000/Ni1000 Service-Ohm
Cu10
Service-Ohm
(60 Ω … 1.6 kΩ)

MEASUREMENT RANGES 2 Ω … 200 Ω - 50 °C – +150 °C 10 Ω … 1000 Ω

Receptacle: Weidmüller Receptacle: Weidmüller Receptacle: Weidmüller


SLA 4/90 SLA 16/90 SLA 4/90
CONNECTOR TYPE
Plug: Weidmüller Plug: Weidmüller Plug: Weidmüller
BLA 4/180 BLA 16/180 BLA 4/180

Resistance-based
RECOMMENDED
DRL. temperature DRL.
APPLICATION
measurement.

RTD+ RTD+ RTD+


0200 1100 1200
WIRE
4 3 2
1
2
3
WIRE WIRE
4 3 2 4 4 3 2
1 5 1
2 6 2
3 7 3
4 8 4
9
10

11

12

13

14

15

16

Figure 10-1 RTD input modules

50 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
RTD INPUT MODULE

10.1 RTD module wiring


If 2-wire wiring is used you have to make sure that the value of RA and RD resistors are set
correctly in the “parameters” menu of the web server.
[RTDInput >>> Ohm bias (2 wire)].

A
1 RA

B
2
RTD+
RTD
module C
3
D
4 RD

A
5

Figure 10-2 2-wire RTD wiring

A
1 RA

B
2 RB
RTD+
RTD
module C
3 RA ≈ RD

D
4 RD

A
5

Figure 10-3 3-wire RTD wiring

A
1 RA

B
2 RB
RTD+
RTD
module C
3 RC

D
4 RD

A
5

Figure 10-4 4-wire RTD wiring

A
1 RA

B
2 RB
RTD+
Potentiometer
module C
3 RC

D
4 RD

A
5

Figure 10-5 4-wire RTD wiring of potentiometer

51 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
ANALOG INPUT MODULE (AI)

11 Analog input module (AI)


The analog input module accepts transducers current or voltage outputs. The AIC module can
measure unipolar and bipolar current values in wide ranges.

MODULE TYPE AIC+0200 AIC+0201*

CHANNEL NUMBER 4 4

2 wire inputs with


MEASUREMENT METHOD 2 wire inputs optional
12 V excitation

RELATIVE ACCURACY ± 0.5 % ± 1 digit ± 0.5 % ± 1 digit

± 20 mA ± 20 mA
MEASUREMENT RANGES (typical 0-20, 4-20 mA) (typical 0-20, 4-20 mA)
RLOAD = 56 Ω RLOAD = 56 Ω

Receptacle: Weidmüller SLA 12/90


CONNECTOR TYPE
Plug: Weidmüller BLA 12/180

*Obsolete module. These modules are not recommended for new designs! For the full list of
obsolete modules see our Product availability chapter.

AIC+ AIC+
0200 0201

1 1 12 Vout

2 2
3 3
4 4 12 Vout

5 5
6 6
7 7 12 Vout

8 8
9 9
10 10 12 V
out

11 11

12 12

Figure 11-1 Analog input modules

52 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
ANALOG INPUT MODULE (AI)

11.1 AI module wiring


Depending on which module type is used the following wiring methods can be applied.

External
source

1
+ PS -
+ 2
Analog input
Transmitter mA / Vout
module
- 3

4
Figure 11-2 2-wire AI wiring without 12 V excitation

+ 1 12 V excitation
Transmitter mA / Vout

- 2
Analog input
module
3

4
Figure 11-3 2-wire AI wiring with 12 V excitation

1 12 V excitation
+ PS -
+ 2
Analog input
Transmitter mA / Vout
module
- 3

4
Figure 11-4 3-wire AI wiring with 12 V excitation

53 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
ANALOG OUTPUT MODULE
(ATO)

12 Analog output module (ATO)


The analog output module is able to transmit current or voltage signals. The ATO module can be
used in wide ranges in unipolar and bipolar mode.

MODULE TYPE ATO+0002 ATO+0004

CHANNEL NUMBER 2 4

OUTPUT MODE 2 wire output 2 wire output

M AXIMUM LOAD
500 Ω 500 Ω
(RCABLE + RRECEIVER)

± 20 mA ± 20 mA
OUTPUT RANGES 0 - 20 mA 0 - 20 mA
4 - 20 mA 4 - 20 mA

Receptacle: Weidmüller SLA 12/90


CONNECTOR TYPE
Plug: Weidmüller BLA 12/180

ATO+ ATO+
0002 0004

1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10

11 11

12 12

Figure 12-1 Analog output modules

54 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
ANALOG OUTPUT MODULE
(ATO)

12.1 ATO module wiring


The analog output module should be connected according to the following wiring diagram.

Shield

1 +
mA Receiver
Analog output
module
2 -

Figure 12-2 Analog output module wiring diagram

55 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SENSOR INPUT MODULE

13 Sensor input module


The sensor modules are able to receive low-level signals of current and voltage sensors (low-
power instrument transformers).

MODULE TYPE VS+0031* CVS+0001 CVSR+0001

CHANNEL NUMBER 4U 4U 4I 4U 4I

NOMINAL VALUES 3.25 V 3.25 V 0.225 V** 1.27 V 0.150 V***

CONTINUOUS VOLTAGE
35 V DC 35 V DC 35 V DC
WITHSTAND

SHORT TIME OVERLOAD


40 V AC / 56 V DC 40 V AC / 56 V DC 40 V AC / 56 V DC
(1 S)

M AX. MEASURED
1.6 UR 1.8 UR 50 IR 2.1 UR 50 IR
CURRENT (± 10 %)

RELATIVE ACCURACY ≤ 0.5 % (0.1 UR – 1.2 UR) ≤ 0.5 % (0.1 UR – 1.2 UR) ≤ 0.5 % (0.1 UN – 1.2 UR)

FREQUENCY RANGE DC – 1 kHz DC – 1 kHz DC – 1 kHz

200 kΩ 200 kΩ 21 kΩ 10 MΩ 1.1 MΩ


INPUT RESISTANCE
± 1% ± 1% ± 1% ± 1% ± 1%

300 pF 300 pF 300 pF 300 pF


INPUT CAPACITANCE 300 pF (1 kHz)
(1 kHz) (1 kHz) (1 kHz) (1 kHz)
M8 3-pin connector
Receptacle:
RJ45 – 8 pole, RJ45 – 8 pole,
Hirschmann ELST
CONNECTOR TYPE shielded connector, shielded connector,
3308 RV FM 8 05
isolated shielding grounded shielding
Plug: Binder 768 99-
3360-00-03
*Obsolete module. These modules are not recommended for new designs! For the full list of
obsolete modules see our Product availability chapter.
**Voltage proportional to current
***Voltage proportional to current change (Rogowski coil)

For more information about more available nominal values please contact our Application Team.
(application@protecta.hu)

56 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SENSOR INPUT MODULE

VS+ CVS+ CVSR+


0031 0001 0001

RJ45_1 RJ45_1
4 1 dI 4
I 2 5
1 3 dt
U 6 7
3 U 8

RJ45_2 RJ45_2
4 1 dI 4
I 2
1 3 dt 5
U 6 7
3 U 8

RJ45_3 RJ45_3
4 1 dI 4
I 2 5
1 3 dt
U 6 7
3 U 8

RJ45_4 RJ45_4
4 1 dI 4
1 3 I 2 5
dt
U 6 7
3 U 8

Figure 13-1 Voltage sensor modules

(4) „n”
(1) „a” (3) not connected

( FRONT VIEW)

Figure 13-2 M8 connector pinout

1.: S1
2.: S2
3.: “a”
6.: “n”
Figure 13-3 CVS module connector pinout

4.: S1
5.: S2
8.: “n”
7.: “a”
Figure 13-4 CVSR module connector pinout

57 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
INJ MODULE

14 INJ module
Complex module for controlling the Petersen coil, which contains an injector function for the
measurements, an enabling and a blocking input, and a fault relay what signs if there is any
fault in the injection circuit.

MODULE TYPE INJ+0005* INJ+0015*

INJECTED CURRENT 2A 4A

ENABLING INPUT CLAMP


85 V AC Not available function
VOLTAGE

BLOCKING INPUT CLAMP


200 V AC 200 V AC
VOLTAGE

ADDITIONAL RESISTANCE
Not available function 265 kΩ ± 1%
FOR VOLTAGE INPUT

Receptacle: Weidmüller SLA 10/90


Weidmüller STVS6 SS
CONNECTOR TYPE
Plug: Weidmüller BLA 10/180
Weidmüller STVS6 SB

RECOMMENDED
DRL. DMD.
APPLICATION

*Special module. For further information see our Product availability chapter.

INJ+ INJ+
0005 0015

1 11 1 11

2 12 2 12

3 13 3 13

4 14 4 14

5 15 5 15

6 16 6 16

7 7
8 8
9 9
10 10

Figure 14-1 INJ modules

58 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
GENERATOR PROTECTION
MODULES

15 Generator protection modules


Special generator protection modules whose system measures and produces the necessary
analog signals.

MODULE TYPE RAI+01 RAI+11 RINJ+21

NOMINAL VOLTAGE N/A N/A 110 V / 220 V

88 - 264 V DC
INPUT VOLTAGE RANGE N/A N/A
80 - 250 V AC

OUTPUT VOLTAGE N/A N/A 100V DC ± 2 %

MEASUREMENT RAGE ± 20 mA ± 20 mA N/A

THERMAL WITHSTAND
CONTINUOUS: 15 mA 10 mA 20 mA
30 SEC: 20 mA 20 mA
Receptacle: Weidmüller STVS8 SB
CONNECTOR TYPE
Plug: Weidmüller STVS8 SS

RECOMMENDED Ungrounded (isolated) Ungrounded (isolated)


Middle-grounded rotors
APPLICATION rotors rotors

RAI+ RAI+ RINJ+


01 11 21

1 1 1
2 2 2
3 3 3
4 4 4
5 5 5
6 6 6
7 7 7
8 8 8
DC
DC

Figure 15-1 Generator protection modules

59 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
GENERATOR PROTECTION
MODULES

15.1 Auxiliary boxes for rotor earth fault protection

MODULE TYPE RAI+01-AUX_01 RAI+01-AUX_02 RAI+11-AUX_11 RAI+11-AUX_12*

M AXIMUM INPUT
250 V 350 V 600 V 1200 V
VOLTAGE

SERIES RESISTANCE ON
12.6 kΩ 18 kΩ 35 kΩ 30 kΩ
SIDES

FILTER CAPACITORS 4x10 µF 4x10 µF 2x1 µF 0 µF

Receptacle: Weidmüller STVS6 SB


CONNECTOR TYPE
Plug: Weidmüller STVS6 SS

RECOMMENDED Middle-grounded Middle-grounded Ungrounded Ungrounded


APPLICATION rotors rotors (isolated) rotors (isolated) rotors

* This module can only be used together with RAI+11-AUX_11 module.

15.1.1 Use of auxiliary boxes


• Ungrounded (isolated) rotors:
If the excitation voltage is lower than 600 V, then it is enough to use the RAI+11-AUX_11 auxiliary
box. If the excitation voltage is higher than 600 V, the RAI+11-AUX_12 auxiliary box shall be used
additionally. With both auxiliary boxes the protection shall be used up to 1200 V excitation voltage.

• Middle-grounded rotors
If the excitation voltage is lower than 250 V, then it is enough to use the RAI+01-AUX_01 auxiliary
box. If the excitation voltage is higher than 250 V, than the RAI+01-AUX_02 auxiliary box shall be
used. With this auxiliary box the protection shall be used up to 350 V excitation voltage.

P
R
O
T RAIXX+AUX_XX
E
C
T
A

Figure 15-2 Size of the auxiliary boxes

60 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
GENERATOR PROTECTION
MODULES

15.2 Wiring of the rotor earth fault protection modules

RAI+ RINJ+
11 21

RAI+11-AUX_12 RAI+11-AUX_11
1 3 1 3
Ug+
1 1
Ug-
6 4 6 4 2 2
3 3
4 4
5 5
6 6
7 UPS
+7
8 -8
DC
DC

Figure 15-3 Wiring for ungrounded (isolated) rotors

RAI+
01
RAI+01-AUX_01
CON. A
1 3
Ug+
4
1
2
3
3
6 4
4
Ug- 5
CON. B
6
7
8

Figure 15-4 Wiring for middle-grounded rotors

61 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
POWER SUPPLY MODULE

16 Power supply module


The power supply module converts primary AC and/or DC voltage to required system voltages.
In most applications, one power supply module is sufficient to provide the required power to the
system. Redundant power supply modules extend system availability in case of the outage of any
power source.

IMPORTANT
Depending on the hardware configuration, the power consumption of the devices can be different.
We reserve the right to make the decision about which PS+ module must be used.
For most applications where the power consumption does not reach 30 W we use one of our 4
HP wide PS+ modules.

PS+4201 PS+2101
MODULE TYPE
(4 HP wide) (4 HP wide)

24 V DC / 110 V DC /
NOMINAL VOLTAGE
48 V DC / 60 V DC 220 V DC

INPUT VOLTAGE 88 - 264 V DC


19.2 - 72 V DC
RANGE 80 - 250 V AC

NOMINAL POWER 20 W 20 W

50 ms at nominal input
INPUT VOLTAGE min. 100 ms in the
voltages
INTERRUPTION TIME specified input voltage
min. 40 ms in the specified
(AT NOMINAL LOAD) range
input voltage range

INTERNAL FUSE 3.15A/250V 3.15A/250V

Power connector:
Receptacle: Weidmüller SLA 2/90
Plug: Weidmüller BLA 2/180
CONNECTOR TYPE
Fault relay connector:
Receptacle: Weidmüller SLA 3/90
Plug: Weidmüller BLA 3/180

62 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
POWER SUPPLY MODULE

IMPORTANT
In case of the power consumption of the device reach or exceed 20 W we select from the following
8 HP wide modules.

MODULE TYPE PS+1301 PS+2301 PS+2303** PS+1030* PS+1060*

NOMINAL 110 V DC / 110 V DC /


110 V DC 220 V DC 220 V DC
VOLTAGE 220 V DC 220 V DC
INPUT
88 - 132 V DC 176 - 264 V DC 176 - 264 V DC 100 - 242 V DC
VOLTAGE 88 - 242 V DC
85 - 130 V AC 160 - 250 V AC 160 - 250 V AC 85 - 250 V AC
RANGE
NOMINAL
30 W 30 W 30 W 25 W 60 W
POWER
INPUT 100 ms at
100 ms at nominal 100 ms at nominal
VOLTAGE nominal input
input voltages input voltages min. 50 ms in the min. 50 ms in the
INTERRUPTION voltages
min. 50 ms in the min. 50 ms in the specified input specified input
TIME min. 50 ms in the
specified input specified input voltage range voltage range
(AT NOMINAL specified input
voltage range voltage range
LOAD) voltage range
INTERNAL
2.5A/250V 2.5A/250V 2.5A/250V 2.5A/250V 3.15A/250V
FUSE

Power connector: Fault relay connector:


CONNECTOR
Receptacle: Weidmüller SLA 2/90 Receptacle: Weidmüller SLA 3/90
TYPE
Plug: Weidmüller BLA 2/180 Plug: Weidmüller BLA 3/180

*Special module. For further information see our Product availability chapter.
**Can be connected in parallel.

MODULE TYPE PS+1601 PS+1602* PS+2601 PS+4301 PS+4401**

NOMINAL 48 V DC /
110 V DC 110 V DC 220 V DC 48 V DC
VOLTAGE 60 V DC
INPUT
88 - 132 V DC 88 - 132 V DC 176 - 264 V DC
VOLTAGE 38.4 - 57.6 V DC 38.4 - 72 V DC
95 - 130 V AC 95 - 130 V AC 160 - 250 V AC
RANGE
NOMINAL
60 W 60 W 60 W 25 W 30 W
POWER

INPUT 100 ms at 100 ms at 100 ms at


40 ms at nominal 40 ms at nominal
VOLTAGE nominal input nominal input nominal input
input voltages input voltages
INTERRUPTION voltages voltages voltages
min. 20 ms in the min. 20 ms in the
TIME min. 50 ms in the min. 50 ms in the min. 50 ms in the
specified input specified input
(AT NOMINAL specified input specified input specified input
voltage range voltage range
LOAD) voltage range voltage range voltage range

INTERNAL FUSE 2.5A/250V 2.5A/250V 2.5A/250V 3.15A/250V 3.15A/250V

Power connector: Fault relay connector:


CONNECTOR
Receptacle: Weidmüller SLA 2/90 Receptacle: Weidmüller SLA 3/90
TYPE
Plug: Weidmüller BLA 2/180 Plug: Weidmüller BLA 3/180

*Special module. PS+1602 supports auxiliary voltage measurement. The module is calibrated
to DC voltage measurement. For further information see our Product availability chapter.
**Can be connected in parallel.

63 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
POWER SUPPLY MODULE

MODULE TYPE PS3F+1001*

NOMINAL VOLTAGE 3x100 V AC (line voltage)

INPUT VOLTAGE RANGE 80 - 120 V AC

NOMINAL POWER 20 W

INPUT VOLTAGE INTERRUPTION TIME 100 ms at nominal input voltages


(AT NOMINAL LOAD) min. 50 ms in the specified input voltage range

INTERNAL FUSE 2.5A/250V

Power connector: Fault relay connector:


Receptacle: Weidmüller SLA Receptacle: Weidmüller SLA
CONNECTOR TYPE
4/90 3/90
Plug: Weidmüller BLA 4/180 Plug: Weidmüller BLA 3/180
*Special module. At least 2 healthy phase voltage needed for the operation of the PS3F+1001
module. LEDs on the front of the module indicates the presence of healthy phase voltages. For
further information see our Product availability chapter.

Main features:
• Fault relay contacts (NC and NO): device fault contact and also assignable to
user functions. All the three relay contact points are accessible to users.
• Redundant applications (nominal power and reliability can be increased by using
parallel power supplies)
• On-board self-supervisory circuits: temperature and voltage monitors
• Short-circuit-protected outputs
• Efficiency: > 70 %, power consumption = nominal power / efficiency
• Passive heatsink
• Early power failure indication signals to the CPU the possibility of power outage,
thus the CPU has enough time to save the necessary data to non-volatile memory
• Inrush current (until 0.1 s): < 10 A for all types excluding PS+4401 which has <
21 A inrush current.
• Common features for internal fuses:
o 5 mm x 20 mm (0.20" x 0.79")
o TT characteristics (very inverse time-lag)
o 35 A @ 250 V AC rated breaking capacity
• Recommended external protection: miniature circuit breaker, 6 A (C char.)

64 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
POWER SUPPLY MODULE

PS+ PS+ PS+ PS+ PS+ PS+


1301 2301 1030 1060 1601 1602

L/+ L/+ L/+ L/+ L/+ L/+


1 AC
DC
1 AC
DC
1 AC
DC
1 AC
DC
1 AC
DC
1 AC
DC
2 N/-
DC 2 N/-
DC 2 N/-
DC 2 N/-
DC 2 N/-
DC 2 N/-
DC

3 3 3 3 3 3
4 FAULT 4 FAULT 4 FAULT 4 FAULT 4 FAULT 4 FAULT
5 RELAY 5 RELAY 5 RELAY 5 RELAY 5 RELAY 5 RELAY

PS+ PS+ PS+ PS+ PS+ PS+ PS3F+


2303 2601 4301 4401 2101 4201 1001

DC DC DC
AC
DC DC AC

L/+ L/+ + +
+
1 AC
DC
1 AC
DC
1 DC 1 DC 1 L/+ 1 1 L1
L2
2 N/-
DC 2 N/-
DC 2 -
DC 2 -
DC 2 N/- 2 - 2
FAULT FAULT 3 L3
RELAY RELAY
3 3 3 3 3 3 4
4 4 FAULT
FAULT 4 FAULT 4 FAULT 4 4 FAULT
RELAY RELAY RELAY RELAY
5 5 RELAY 5 5 5 5 5
6
7

Figure 16-1 Power supply modules

65 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MIXED FUNCTION MODULES

17 Mixed function modules

17.1 PSTP+ module


IMPORTANT
PSTP+ modules can be used only if the power consumption of the device does not reach 20 W
and maximum 2 TRIP contacts are needed. If the application does not meet any of these two
requirements it is not allowed to use these cards. In this case separate PS+ and TRIP+ modules
must be used.

PSTP+2101 PSTP+4201
MODULE TYPE PSTP+2131**
(PSTP+2102*) (PSTP+4202*)

POWER SUPPLY CHARACTERISTICS

NOMINAL VOLTAGE 110 V / 220 V 110 V / 220 V 24 V / 48 V / 60 V

88 - 264 V DC 88 - 264 V DC
INPUT VOLTAGE RANGE 19.2 - 72 V DC
80 - 250 V AC 80 - 250 V AC

NOMINAL POWER 20 W 20 W 20 W

50 ms at nominal input
INPUT VOLTAGE min. 100 ms in the min. 100 ms in the voltages
INTERRUPTION TIME specified input voltage specified input voltage min. 40 ms in the
(AT NOMINAL LOAD) range range specified input voltage
range

INTERNAL FUSE 3.15A/250V 3.15A/250V 3.15A/250V

Power connector: Fault relay connector:


CONNECTOR TYPE Receptacle: Weidmüller SLA 2/90 Receptacle: Weidmüller SLA 3/90
Plug: Weidmüller BLA 2/180 Plug: Weidmüller BLA 3/180

TRIPPING CHARACTERISTICS

CHANNEL NUMBER 2 2 2

110 V DC and 220 V DC 110 V DC and 220 V DC 24 V DC and 48 V DC


RATED VOLTAGE
or dry contacts or dry contacts or dry contacts

THERMAL WITHSTAND
242 V DC 242 V DC 72 V DC
VOLTAGE

CONTINUOUS CARRY 8A 8A 8A

M AKING CAPACITY 0.5 s, 30 A 0.5 s, 30 A 0.5 s, 30 A

BREAKING CAPACITY L/R = 40 ms: 4 A DC L/R = 40 ms: 4 A DC L/R = 40 ms: 4 A DC

Receptacle: Weidmüller SLA 6/90


CONNECTOR TYPE
Plug: Weidmüller BLA 6/180
Thermal withstand voltage: continuous with 60 % of the input channels are energised
* Special module. PSTP+2102 and PSTP+4202 support auxiliary voltage measurement. The
module is calibrated to DC voltage measurement. For further information see our
Product availability chapter.
**Without trip circuit supervision.

66 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MIXED FUNCTION MODULES

Main features:
• High-speed operation: with pre-trip 0.5 ms, without pre-trip typically 10 ms,
maximally 22 ms.
• Trip circuit supervision for each trip contact
• 1 unit wide (4 HP) modules
• Inrush current (until 0.1 s): < 10 A
• Common features for internal fuses:
o 5 mm x 20 mm (0.20" x 0.79")
o TT characteristics (very inverse time-lag)
o 35 A @ 250 V AC rated breaking capacity
• Recommended external protection: miniature circuit breaker, 6 A (C char.)

PSTP+ PSTP+ PSTP+ PSTP+ PSTP+


2101 4201 2102 4202 2131
DC DC DC DC DC
AC AC AC
DC DC DC DC DC

1 L/+
1 + 1 L/+
1 + 1 L/+

2 N/-
2 - 2 N/-
2 - 2 N/-
FAULT FAULT FAULT FAULT FAULT
RELAY RELAY RELAY RELAY RELAY
3 3 3 3 3
4 4 4 4 4
5 5 5 5 5

6+ 6+ 6+ 6+ 6+
7- 7- 7- 7- 7-
8 NO 8 NO 8 NO 8 NO 8 NO
9+ 9+ 9+ 9+ 9+
10 - 10 - 10 - 10 - 10 -
11 NO 11 NO 11 NO 11 NO 11 NO

Figure 17-1 Power supply with 2 Ch. TRIP modules

67 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MIXED FUNCTION MODULES

17.1 PSR2+ module


IMPORTANT
PSR2+ modules can be used only if the power consumption of the device does not reach 20 W
and maximum 2 contacts are needed. If the application does not meet any of these two
requirements it is not allowed to use these cards. In this case separate PS+ and TRIP+ modules
must be used.

MODULE TYPE PSR2+2101 (PSTP+2102*)

POWER SUPPLY CHARACTERISTICS

NOMINAL VOLTAGE 110 V / 220 V

88 - 264 V DC
INPUT VOLTAGE RANGE
80 - 250 V AC

NOMINAL POWER 20 W

INPUT VOLTAGE
min. 100 ms in the specified input
INTERRUPTION TIME
voltage range
(AT NOMINAL LOAD)

INTERNAL FUSE 3.15A/250V

Power connector:
Receptacle: Weidmüller SLA 2/90
Plug: Weidmüller BLA 2/180
CONNECTOR TYPE
Fault relay connector:
Receptacle: Weidmüller SLA 3/90
Plug: Weidmüller BLA 3/180

SIGNALLING CHARACTERISTICS

CHANNEL NUMBER 2

RATED VOLTAGE 250 V AC/DC

CONTINUOUS CARRY 8A

M AKING CAPACITY 0.5 s, 30 A

Receptacle: Weidmüller SLA 6/90


CONNECTOR TYPE
Plug: Weidmüller BLA 6/180

68 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MIXED FUNCTION MODULES

Main features (according to IEC 60255-26):


• Maximum switching voltage: 400 V AC
• Breaking capacity: (L/R=40 ms) at 220 V DC: 0.2 A, at 110 V DC: 0.3 A
• Breaking capacity max.: 2000 VA
• Short time carrying capacity: 1 s, 35 A
• Limiting making current, max. 4 s: 15 A (df = 10 %)
• Initial dielectric strength between open contacts, 1 min: 1000 VRMS
• Mechanical endurance: 10 × 106 cycles
• Circuit closing capability: typically 10 ms, maximally 22 ms.
• Bounce time: typically 6,5 ms, maximally 10 ms.
• Minimal switching requirement: 5 V

PSR2+
2101
DC
AC
DC

1 L/+

2 N/-
FAULT
RELAY
3
4
5

6
7
8
9
10
11

Figure 17-2 Power supply with 2 Ch. signaling modules

69 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MIXED FUNCTION MODULES

17.2 O6R5+ module


The O6R5+ module contains 6 binary input channels in one grounding group, and 5 relay outputs
with 2 × 2 NO contacts and one CO contact.

MODULE TYPE O6R5+2101 O6R5+4201

BINARY INPUT CHARACTERISTICS

CHANNEL NUMBER 6 6

110 V / 220 V 24 V / 48 V
RATED VOLTAGE user selectable on channel basis user selectable on channel basis
by jumpers by jumpers

TIME SYNCHRONIZATION configured by EuroCAP configured by EuroCAP

THERMAL WITHSTAND
320 V 72 V
VOLTAGE

falling 0.64 UR falling 0.64 UR


CLAMP VOLTAGE
rising 0.8 UR rising 0.8 UR

GROUNDING GROUPS 1 × 6 common ground 1 × 6 common ground

RELAY OUTPUT CHARACTERISTICS

RATED VOLTAGE 250 V AC/DC 250 V AC/DC

CONTINUOUS CARRY 8A 8A

CONTACT VERSIONS 4 NO, 1 CO 4 NO, 1 CO

GROUP ISOLATION 2 × 2 common, 1 independent 2 × 2 common, 1 independent

CONNECTOR TYPE FOR


Receptacle: Plug:
BOTH BINARY INPUT AND
Weidmüller SLA 16/90 Weidmüller BLA 16/180
RELAY OUTPUT

Thermal withstand voltage: continuous with 60 % of the input channels are energised

70 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MIXED FUNCTION MODULES

Main features for binary inputs:


• Digitally filtered per channel
• Current drain:
o max. 1.6 mA per channel at 220 V DC
o max. 1.8 mA per channel at 110 V DC
o max. 2 mA per channel at 48 V DC
o max. 3 mA per channel at 24 V DC
• In such applications where the input voltage is 60 V the modules with 48 V rated
voltage can be used.
• Input voltage type can be either DC or AC voltage. If AC voltage is used make
sure that the type and the parameters of the binary inputs are configured properly
in EuroCap tool.

Main features for signaling outputs:


• Maximum switching voltage: 400 V AC
• Breaking capacity, (L/R=40 ms) at 220 V DC: 0.1 A, at 110 V DC: 0.2 A
• Breaking capacity max.: 2000 VA
• Short time carrying capacity: 1 s, 35 A
• Limiting making current, max. 4 s: 15 A (df = 10 %)
• Initial dielectric strength between open contacts, 1 min: 1000 VRMS
• Circuit closing capability: typically 10 ms, maximally 22 ms.
• Bounce time: typically 6,5 ms, maximally 10 ms.
• Mechanical endurance: 10 × 106 cycles
• Circuit closing capability

O6R5+ O6R5+
2101 4201

1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10

11 11

12 12

13 13

14 14

15 15

16 16

Figure 17-3 Binary input/output modules

71 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MIXED FUNCTION MODULES

17.3 Binary input module with time synchronization


The inputs are galvanic isolated and the module converts high-voltage signals to the voltage level
and format of the internal circuits. This module is also used as an external IRIG-B synchronization
(IRIG-B000, unmodulated), PPM or PPS input. Dedicated synchronization input is used for this
purpose.

MODULE TYPE O9S+2111* O9S+2121*

CHANNEL NUMBER 9 9

SYNCHRON 1
1
CHANNEL TYPE 850 nm multimode fiber with
isolated BNC connector
AND NUMBER ST connector

110 V DC / 220 V DC 110 V DC / 220 V DC


RATED VOLTAGE
user selectable by jumpers user selectable by jumpers

THERMAL
WITHSTAND 320 V 320 V
VOLTAGE

WITHSTAND
VOLTAGE 35 VPEAK -
FOR SYNC. INPUT

falling 0.64 UR falling 0.64 UR


CLAMP VOLTAGE
rising 0.8 UR rising 0.8 UR

GROUNDING
9 (3 × 3 common ground) 9 (3 × 3 common ground)
GROUPS

Receptacle: Receptacle:
Weidmüller SLA 12/90, BNC Weidmüller SLA 12/90, ST
CONNECTOR TYPE
Plug: Plug:
Weidmüller BLA 12/180, BNC Weidmüller BLA 12/180, ST
*Special modules. For further information see our Product availability chapter.

O9S+ O9S+
2111 2121

1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10

11 11

12 12

BNC
MM/ST
Rx
SYNC

Figure 17-4 Binary input modules with time synchronization

72 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MIXED FUNCTION MODULES

17.4 Externally driven trip module


The R4MC+01 is a special TRIP module, which can be operated from the connector side. It also
has two diode inputs with cathodes which are connected and led to the connector side.

Module type R4MC+01(F*)

CHANNEL NUMBER 2

RATED VOLTAGE 110 V DC

THERMAL WITHSTAND VOLTAGE 132 V DC

CONTINUOUS CARRY 8A

M AKING CAPACITY 0.5 s, 30 A

BREAKING CAPACITY L/R = 40 ms: 4 A DC

DIODE PROPERTIES 1 A, 1000 V DC

Receptacle:
Weidmüller SLA 13/90
CONNECTOR TYPE
Plug:
Weidmüller BLA 13/180

*Screwed type connector. (R4MC+01F)

R4MC+
01

1
2
3
4
5
6
7
8
9
10

11

12

13

Figure 17-5 Externally driven TRIP module

73 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SPECIAL DEVICES

18 Special devices

18.1 Remote I/O (RIO) server


Remote I/O (RIO) server is an IED, which provides remote binary
inputs and outputs far from an EuroProt+ protection device. It
communicates with the EP+ device via COM+1335 module,
MODBUS/TCP protocol.
RIO server consists of two mixed function modules:
• SCPU+0011/PS+1101
• SO12+1101/R2+0001

18.1.1 SCPU/PS
The SCPU/PS module contains all the control, communication and the
power supply functions of the device.

Figure 17-1 Remote I/O

CPU VERSION ETHERNET INTERFACE SERVICE PORT

MM/LC 1300 nm,


SCPU+0011 50/62,5/125 µm connector, RS232
100Base-FX

INPUT NOMINAL INPUT VOLTAGE


PS TYPE CONNECTOR TYPE
VOLTAGE POWER INTERRUPTION TIME

Receptacle:
min. 140 ms @
Weidmüller SLA 2/90
PS+1101 65-180 V DC 9W 110 V DC input
Plug:
voltage
Weidmüller BLA 2/180

18.1.2 SO12/R2
The O12/R2 module contains 12 binary input channels in one grounding group, and 2 relay
outputs with dry contacts.

THERMAL
CHANNEL TIME RATED CLAMP CONNECTOR
BI TYPE WITHSTAND
NUMBER SYNC. VOLTAGE VOLTAGE TYPE
VOLTAGE
Receptacle:
Weidmüller
falling 0.7 UR SL 3.5/13/90
SO12+1101 12 - 110 V 250 V
rising 0.73 UR Plug:
Weidmüller
BL 3.5/13/180
Thermal withstand voltage: continuous with 60 % of the input channels are energised
Main features:
• Digitally filtered per channel
• Current drain approx.: 2 mA per channel

74 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SPECIAL DEVICES

RATED CONTINUOUS CONTACT GROUP


BO TYPE CONNECTOR TYPE
VOLTAGE CARRY VERSIONS ISOLATION

Receptacle:
Weidmüller
250 V SL 3.5/6/90
R2+0001 6A CO 2 independent
AC/DC Plug:
Weidmüller
BL 3.5/6/180
Main features:
• Breaking capacity, (L/R = 40 ms) at 110 V DC: 0.2 A

Figure 17-2 Front view and rear view with fastening for mounting rail

75 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SPECIAL DEVICES

18.2 TRCS
TRCS is a special device, which encodes the 28 stage-state of the transformer voltage regulator
into 5-bit binary code.

Figure 17-3 Front view and rear view with fastening for mounting rail

Figure 17-4 – Connector arrangement

76 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
SPECIAL DEVICES

DEVICE TYPE TRCS

NUMBER OF INPUTS 28

NOMINAL VOLTAGE OF
48V DC/110V DC/220V DC
THE INPUTS AND
(Ordering option)
OUTPUTS

NUMBER OF OUTPUTS 5

OUTPUT CONTINUES
6A
CARRY

Receptacle: Weidmüller
SL 3.5/18/90
CONNECTOR TYPE Plug:
Weidmüller
BL 3.5/18/180

Main features:
• Breaking capacity, (L/R = 40 ms) at 110 V DC: 0.2 A, at 220 V DC: 0.1 A

77 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
GENERAL DATA

19 General data
▪ Storage temperature: - 40 ºC … + 70 ºC
▪ Operation temperature: - 20 ºC … + 55 ºC
▪ Humidity: 10 % ... 93 %
▪ Altitude: up to 2000 m
▪ Atmospheric pressure: 86 ... 106 kPa
▪ Standard conformance:
• Electrostatic discharge immunity (ESD), IEC 60255-26:2013, Level 4
o Test voltages: 15 kV air discharge, 8 kV contact discharge
• Radiated, radio-frequency, electromagnetic field immunity, IEC 60255-26:2013
Level 3
o Test field strength: 10 V/m
• Electrical fast transient/burst immunity (EFT/B), IEC 60255-26:2013, Level 4
o Test voltage: 4 kV
• Surge immunity test, IEC 60255-26:2013
o Test voltages: 4 kV line-to-earth, 2 kV line-to-line
• Immunity to conducted disturbances, induced by radio-frequency fields,
IEC 60255-26:2013, Level 3
o Test voltage: 10 V
• Damped oscillatory wave immunity test, IEC 60255-26:2013
o Test frequency: 1 MHz
o Test voltage: 2.5 kV in common mode, 1 kV in differential mode
• Voltage dips, short interruptions and voltage variations immunity,
IEC 60255-26:2013
o Voltage dips: 40 % (200 ms), 70 % (500 ms), 80 % (5000 ms)
• Ripple on d.c. input power port immunity, IEC 60255-26:2013
o Level 4, 15 % of rated d.c. value
• Power frequency magnetic field immunity test, IEC 60255-26:2013, Level 5
o Test field field strength: 100 A/m continuous,
1000 A/m for 3 s
• Power frequency immunity test on the binary inputs,
IEC 60255-26:2013, Class A
o Test voltages: 300 V in common mode, 150 V in differential mode
• Insulation tests, IEC 60255-27:2013
o Impulse voltage test
▪ Test levels: 5 kV (1 kV for transducer and temperature
measuring inputs)
o Dielectric test
▪ Test levels: 2 kV AC 50 Hz (0.705 kV DC for transducer inputs)
o Insulation resistance
▪ Insulation resistance > 15 GΩ
• Radiated emission, IEC 60255-26:2013
Limits:
o 30 MHz to 230 MHz: 50 dB(μV/m) quasi peak, 3 m
o 230 MHz to 1 000 MHz: 57 dB(μV/m) quasi peak, 3 m
o 1 GHz to 3 GHz: 76 dB(μV/m) peak,3 m
o 3 GHz to 6 GHz: 80 dB(μV/m) peak,3 m
• Conducted emmission, IEC 60255-26:2013
Limits:
o 0,15 MHz to 0,50 MHz: 79 dB(μV) quasi peak, 66 dB(μV)
average
o 0,5 MHz - 30 MHz: 73 dB(μV) quasi peak, 60 dB(μV)
average
• Vibration, shock, bump and seismic tests on measuring relays and protection
equipment
o Vibration tests (sinusoidal), Class I, IEC 60255-21-1:1988
o Shock and bump tests, Class I, IEC 60255-21-2:1988
o Seismic tests, Class I, IEC 60255-21-3:1993

78 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MECHANICAL DATA

20 Mechanical data
▪ Construction: chromate aluminium surface with built-in EMC accessories
◼ If the power consumption of a 84 HP or 42 HP device does not exceed 30 W
(84 HP) or 14 W (42 HP), the construction will be built with solid top and
bottom cover panels.
 If the power consumption exceeds 30 W (84 HP) or 14 W (42 HP), the
construction will be built with (honeycomb) perforated top and bottom cover
panels.
▪ EMC rack protects against electromagnetic environmental influences and protects
the environment from radiation from the interior
▪ IP protection:
o 24 HP panel instrument case: IP4x
o 84 HP and 42 HP (including double) rack: IP4x from front side, IP2x from rear
side
▪ Size:
o 19” (84 HP), 3 U, single rack
o ½ 19” (42 HP), 3 U, single rack
o ½ 19” (42 HP), 6 U, double rack
o 24 HP, panel instrument case
▪ Weight:
o 84 HP: max. 8 kg
o 42 HP, 6 U: max. 8 kg
o 42 HP, 3 U: max. 4.5 kg
o 24 HP: max. 3 kg

CONDUCTOR
CONNECTOR STRIP LENGTH CONDUCTOR TIGHTENING MINIMUM BEND
DIAMETER
TYPE [MM] AREA [MM2] TORQUE [NM] RADIUS*
[MM]

0.2 – 1.5 0.5 – 1.4


BLA 7 0.4 – 0.5 3 × OD**
solid: 0.2 – 2.5 solid: 0.5 – 1.8

BL 3.5 6 0.2 – 1.5 0.5 – 1.4 0.2 – 0.25 3 × OD**

tension clamp
B2L 3.5 7 0.2 – 1 0.5 – 1.1 3 × OD**
connection

STVS AND
9 0.5 – 4 0.8 – 2.3 0.5 – 0.6 3 × OD**
RING LUG

ST/FC/LC - - - - 30 mm

PE FASTON
7 min. 4 min. 2.3 - 3 × OD**
TERMINAL

* Bend radius is measured along the inside curve of the wire or wire bundles.
** OD is the outer diameter of the wire or cable, including insulation.
The tightening torque of the screw for protective earth connection and the wall mounting must be
approx. 5 Nm.
The tightening torque of the screw for fastening the STVS connector must be approx. 1 Nm.
The minimum distance between an EP+ device and its wire channel must be at least 3 cm.
The minimum distance between two EP+ devices must be at least 10 cm.
During the installation make sure that the shortest possible length for PE (Protective Earth) cable
routing is applied.

79 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21 Mounting methods
▪ Flush mounting
o 84 HP single rack
o 42 HP single rack
o 42 HP double rack
o 24 HP panel instrument case
o Remote HMI
▪ Rack mounting
o 84 HP single rack
o 42 HP single rack
o Remote HMI
▪ Semi-flush mounting
o 84 HP single rack
o 42 HP single rack
o 24 HP panel instrument case
o Remote HMI
▪ Wall mounting (with terminals)
o 84 HP single rack
o 42 HP single rack
▪ Din rail mounting
o 24 HP panel instrument case
▪ IP54 rated mounting
o 84 HP single rack
o 42 HP single rack
▪ Console mounting
o 42 HP single rack
▪ No mounting

84 HP SINGLE 42 HP SINGLE 42 HP DOUBLE 24 HP PANEL REMOTE


MOUNTING METHOD
RACK RACK RACK INSTRUMENT CASE HMI

FLUSH MOUNTING x x x x x

RACK MOUNTING x x x

SEMI-FLUSH
x x x x
MOUNTING
WALL MOUNTING
x x
(WITH TERMINALS)

DIN RAIL MOUNTING x

IP54 RATED
x x
MOUNTING

CONSOLE
x
MOUNTING

80 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.1 Flush mounting


Flush mounting can be used for all size of racks (84 HP, 42 HP, double 42 HP) including the 24
HP panel instrument case and the remote HMI devices. When this type of mounting alternative is
used the 84 HP, 42 HP, double 42 HP and remote HMI devices have got a cover profile fit on and
the 24 HP devices have got a mounting frame fit on.
The dimensions of the cut-outs for the 84 HP and 42 HP devices are also applicable for the same
sized remote HMI devices.

21.1.1 Flush mounting of 84 HP and 42 HP single rack

COM COM

I I

0 0

x x

PANEL CUT-OUT

DEVICE 1 DEVICE 1

DEVICE 2 DEVICE 2

Figure 21-1 Dimensions for flush mounting of 84 HP and 42 HP single rack

81 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

Figure 21-2 3D illustration for flush mounting of 84 HP and 42 HP devices

21.1.2 Flush mounting of 42 HP double rack

PANEL CUT-OUT

COM

I
0

DEVICE 1

DEVICE 2

Figure 21-3 Dimensions for flush mounting of 42 HP double rack

Figure 21-4 42 HP wide cover profile

82 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.1.3 Flush mounting of 24 HP panel instrument case

MOUNTING FRAME

PANEL CUT-OUT

MOUNTING FRAME

Figure 21-5 Dimensions for flush mounting of 24 HP panel instrument case with 3D
illustration

83 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.2 Rack mounting


When rack mounting is used the devices do not have a cover profile fit on. So it is possible to
mount them in a 19" rack.

COM COM

I I

0 0

x x

Figure 21-6 Dimensions for rack mounting of 84 HP and 42 HP single rack

Note that rack mounting type devices can also be mounted in a cut-out (e.g. on a switchgear
door). It is possible to mount them from the front or from the back of the cut-out. The dimensions
for rack mounting cut-outs are in the figure below. Dimensions in brackets are applicable in case
of mounting from the back.

PANEL CUT-OUTS

84 HP DEVICE 1 42 HP DEVICE 1

84 HP DEVICE 2 42 HP DEVICE 2

Figure 21-7 Dimensions of rack mounting cut-outs

84 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

a b

Figure 21-8 3D illustration for rack mounting of 42 HP device


(a - from the front; b - from the back)

a b

Figure 21-9 3D illustration for rack mounting of 84 HP device


(a - from the front; b - from the back)

85 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.3 Semi-flush mounting


Semi-flush mounting can be used for 84 HP and 42 HP single racks, for 24 HP panel instrument
cases and for remote HMI devices. The purpose of this type of mounting alternative is to reduce
the depth of the devices in the switchgear/rack if there is not enough space in that direction. To
achieve this, a special mounting collar must be fit on the rack type devices. The default colour of
the mounting collar is grey (RAL 7035).
The dimensions of the special mounting collars and the cut-outs for the 84 HP and 42 HP devices
are also applicable for the same sized remote HMI devices.

21.3.1 Semi-flush mounting of 84 HP single rack

SPECIAL
MOUNTING
COLLAR

PANEL CUT-OUT

COM

Figure 21-10 Dimensions for semi-flush mounting of 84 HP single rack with 3D


illustration

86 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.3.2 Semi-flush mounting of 42 HP single rack

SPECIAL
MOUNTING
COLLAR

PANEL CUT-OUT

COM

Figure 21-11 Dimensions for semi-flush mounting of 42 HP single rack with 3D


illustration

87 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.3.3 Semi-flush mounting of 24 HP panel instrument case


The dimensions of the panel cut-out for this type of mounting method are the same as in case of
flush mounting (138 mm × 138 mm). For semi flush mounting you only have to cut in two the fixing
elements (with green colour in the 3D illustration below) and make the assembly as you can see
in the pictures below.

MOUNTING FRAME
BACKPLANE OF THE SWITCHGEAR/RACK

Figure 21-12 Dimensions for semi-flush mounting of 24 HP panel instrument case with 3D illustration

88 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.4 Wall mounting of 42 HP and 84 HP devices


Depending on the amount of the terminal contacts it is possible to use both upper and lower
terminals.

277

UPPER TERMINAL

85
194

137
~312

ϕ 6.5(4X)

LOWER TERMINAL

252.5 75

~320
~515
UPPER VIEW
(M1:2)

IT IS POSSIBLE TO OPEN THE RACK


~330

FROM LEFT TO RIGHT AND ALSO


FROM RIGHT TO LEFT.

Figure 21-13 Dimensions for wall mounting of 42 HP devices

UPPER TERMINAL

LOWER TERMINAL

UPPER VIEW
(M1:2)

IT IS POSSIBLE TO OPEN THE RACK


FROM LEFT TO RIGHT AND ALSO
FROM RIGHT TO LEFT.

Figure 21-14 Dimensions for wall mounting of 84 HP devices

89 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.5 Din rail mounting of 24 HP panel instrument case

FRONT VIEW SIDE VIEW BACK VIEW


135

206

76,8
~150 141

Figure 21-15 Dimensions for din rail mounting of 24 HP panel instrument case

90 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.6 IP54 rated mounting kit for 84 HP and 42 HP devices


The IP frame seen below provides IP54 protection from front side.

Figure 21-16 84 HP IP frame front view

Figure 21-17 42 HP IP frame front view

91 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

Figure 21-18: 84 HP IP frame dimensions

Figure 21-19 42 HP IP frame dimensions

92 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.7 Console mounting

Figure 21-20 42 HP console mounting

93 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.8 No mounting
“No mounting” means that the 84 HP and 42 HP devices do not have any mounting accessories
on them.

This mounting method is only applicable if the device is for demonstration application.

For more information about this topic please contact our Application Team.
(application@protecta.hu)

94 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
MOUNTING METHODS

21.9 Remote HMI devices


IMPORTANT
The dimensions of the cut-outs applicable for the remote HMI are depending on which previously
mentioned mounting method is used (flush mounting, semi-flush mounting or rack mounting).

Figure 21-21 Dimensions for 42 HP wide remote HMI

Figure 21-22 Dimensions for 84 HP wide remote HMI

95 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
PRODUCT AVAILABILITY

22 Product availability
In this chapter you can read a list of the modules that have not regular availability for any reasons.
For more information about these devices please contact our Application Team.
(application@protecta.hu)
Connector with flange is an ordering option.
Ring-lug connector for CTs is an ordering option.

MODULE TYPE COMMENT DATE

Legacy CPU card, not recommended for new configurations.


CPU+0001 12.06.2013.
Replacement: CPU+1211

Legacy CPU card, not recommended for new configurations.


CPU+0002 12.06.2013.
Replacement: CPU+1111

Legacy CPU card, not recommended for new configurations.


CPU+0003 12.06.2013.
Replacement: CPU+1101

Legacy CPU card, not recommended for new configurations.


CPU+0004 12.06.2013.
Replacement: CPU+1201

Legacy CPU card, not recommended for new configurations.


CPU+0005 12.06.2013.
Replacement: CPU+1281

Legacy CPU card, not recommended for new configurations.


CPU+0006 12.06.2013.
Replacement: CPU+1381

CT+1155 Available only for special configurations. 12.06.2013.

CT+5152 Available only for OGYD bay unit configurations. 14.06.2013.

VT+2215 Available only for special configurations. 12.06.2013.

VT+2245 Available only for special configurations. 12.06.2013.

O12+2101 Available only for demonstration applications. 12.06.2013.

O12+4201 Available only for demonstration applications. 12.06.2013.

R4S+01 Available only for special configurations. 12.06.2013.

R4S+16 Available only for special configurations. 12.06.2013.

TRIP+1101 Obsolete module. Not recommended for new designs. 12.06.2013.

PS+1030 Obsolete module. Not recommended for new designs. 12.06.2013.

PS+1060 Obsolete module. Not recommended for new designs. 12.06.2013.

PS+1602 Available only for special configurations. 12.06.2013.

O9S+2111 Available only for special configurations. 12.06.2013.

O9S+2121 Available only for special configurations. 12.06.2013.

HMI+2401 Obsolete module. Not recommended for new designs. 06.10.2014.

HMI+2404 Smart Line S24 special selection modules. 06.10.2014.

96 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
PRODUCT AVAILABILITY

HMI+2504 Smart Line S24 special selection modules. 06.10.2014.

COM+8882 Available only for special configurations. 06.10.2014.

CT+1111 Available only for special configurations. 06.10.2014.

CT+2500 Available only for special configurations. 06.10.2014.

CT+5153 Available only for special configurations. 06.10.2014.

VT+2212 Available only for special configurations. 06.10.2014.

R8+01 Available only for special configurations. 06.10.2014.

R8+A1 Available only for special configurations. 06.10.2014.

R8+C0 Available only for special configurations. 06.10.2014.

R8+FF Available only for special configurations. 06.10.2014.

R12+4400 Available only for special configurations. 06.10.2014.

R16+0101 Available only for special configurations. 06.10.2014.

R16+0001 Available only for special configurations. 06.10.2014.

R16+A001 Available only for special configurations. 06.10.2014.

PS+4401 Available only for special configurations. 06.10.2014.

Obsolete module. Not recommended for new designs.


CT+2500 13.02.2015.
Replacement: CT+1500.

PSTP+2102 Available only for special configurations. 23.06.2015.

PSTP+4202 Available only for special configurations. 23.06.2015.

CT+5111 Available only for special configurations. 08.12.2015.

Available only for special configurations. DEFL earth fault


CT+0101 19.03.2018.
protection only.

INJ+0005 Available only for special configurations. 19.03.2018.

INJ+0015 Available only for special configurations. 19.03.2018.

CT+5155 Available only for special configurations. 26.03.2018.

VT+2245 Available only for special configurations. 26.03.2018.

VT+2246 Available only for special configurations. 26.03.2018.

AIC+0201 Obsolete module. Not recommended for new designs. 26.03.2018.

CT+5111 Obsolete module. Not recommended for new designs. 27.03.2018.

97 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu
PRODUCT AVAILABILITY

VS+0031 Obsolete module. Not recommended for new designs. 25.05.2018.

R1T+0001 Available only for special configurations. DMD. 2018.10.05.

CT+5253 Available only for special configurations. 2018.10.05.

98 EUROPROT+ HARDWARE DESCRIPTION


www.protecta.hu

You might also like