Professional Documents
Culture Documents
DESIGN HIGHLIGHTS
Minimized initial CapEx
High reliability
Reduced TTM
Optimized footprint in multi-story
building design
Flexible IT space
[Reference Design 104] 2
Facility Power
UTILITY CONNECTION
The data centre is designed for a maximum demand of 23 MVA, which requires a connection to the electric utility’s medium voltage
(MV) distribution network. Depending on the country and region, the supply voltage could vary from 6.6/22/66 kV (e.g. Singapore),
to 10/110 kV (e.g. China) and up to 11/33/132 kV (e.g. Hong Kong). In this design the supply voltage is considered to be below 24
kV. Depending on the country requirements, the substation may or may not be built, owned and operated by the utility or owner. For
example, in Singapore the building owner will be responsible for building the MV substation within the building premises based on
the requirements by the utility company, who will control and maintain the substation since it will provide MV gear, cables, metering
equipment for “A” and “B” sides, etc. Then, an additional space is required to house the building’s MV equipment for taking in the
supply from the utility and for further distribution.
Facility Power
GENERATOR BACKUP POWER AND MEDIUM VOLTAGE DISTRIBUTION
Downstream of the main MV distribution, there are twenty GMAe switchgear lineups rated at <24 kV and 25 kA (1s) with a 630 A
busbar. Eight pairs of GMAe lineups feed eight IT blocks in a 2N architecture, to provide A- and B-side power. Each pair is
connected by a “coupling cable” to maintain redundancy downstream of a failure. The rest of the lineups feed four cooling systems
shared across the eight IT load blocks. Other cooling and non-critical auxiliaries receive power directly from the main MV
distribution switchgear.
There are two diesel generator plants that can be built in stages as business scales, each one serving four blocks. There is an
automatic transfer capability between mains and backup power built into the design. A total of 15 generators with 2500 kVA
capacity, rated at 400 V with N+1 redundancy serve the entire data centre: eight units in the first plant serve blocks 1 to 4 plus
comfort cooling and non-critical auxiliary loads, and seven in the second plant serve blocks 5 to 8. Each unit is coupled to the MV
network through LV/MV step-up 2500 kVA Trihal cast-resin transformers with 6% short circuit impedance, and additional GMAe
switchgear lineups. This backup generator plant configuration provides high reliability and safety, while minimizing cost. For full
Uptime Tier III compliance, a set of redundant GMAe MV switchgear could be added to the design. In addition, fuel storage and
piping can also be added to the design in accordance with country habits and regulations. The generator plants are located in the
third and fourth floors of the data centre building, above the main MV distribution and office floors, with provisioned ventilation and
cooling.
Utility A
MV Distribution to Blocks Utility B DESIGN OPTIONS
Four Blocks (1-4)
This reference design can be
G G 8 x 2500 kVA units
(blocks 1-4) modified as follows without a
LV LV
MV MV significant effect on the design’s
Genset SWG 630A, performance attributes:
<24kV
ATS ATS
Redundant generator
MV Dist. SWG A1 MV Dist. SWG B1
GMAe switchgear set
630A, <24 kV 630A, <24kV
Provision for load bank
Add/change standby
generator options:
MV IT
A
MV IT
B
MV IT
A
MV IT
B
MV IT
A
MV IT
B
MV IT
A
MV IT
B
MV MV
Cool. A Cool. B Location
COOLING
Tank size
BLOCK BLOCK BLOCK BLOCK COOLING COOLING & AUX.
Fuel type
Per 4 blocks
Number of MV distribution switchgear lineups 2
MV distribution bus amps 630 A
MV distribution bus voltage 24 < Un kV
MV distribution switchgear short time withstand
25 (3) kA (s)
current
Generator redundancy N+1
Number of Generators 7 or 8
Generator size 2500 kVA
Generator voltage 400 V
Facility Power
LOW VOLTAGE DISTRIBUTION
Downstream from the MV distribution, the 2N redundant electric supply is separated into LV sections. 16 sections feed one IT block
each, four feed the cooling systems for all blocks, and two more feed additional cooling and non-critical auxiliaries. A and B-side
distribution is made with a total of 26 Trihal transformers (at 6% impedance), used to transform voltage from 22 kV to 400 V.
The LV distribution for all IT rooms is made up by 16 Trihal 2000 kVA transformers coupled with the same number of Okken LV
lineups, each rated at 400 V and 50 kA (1s) with a 3200 A bus to minimize cost and maximize the IT capacity per bus. Each Okken
lineup feeds 4 Galaxy 7000 UPSs in a 2N configuration, as an A and B-side distribution, which then feed the IT load through a
combination of 2N LV switchgear and iBusway systems, with built in intelligence.
Cooling systems and auxiliary loads for all blocks receive power from eight Okken lineups, each coupled with a MV/LV Trihal
transformer rated at 1600 kVA for blocks 1 and 2 and rated at 1250 kVA for blocks 3 to 8. They provide A and B-side distribution to
chillers, pumps, cooling towers, and auxiliaries. Additional cooling and auxiliary loads for the building are fed from the non-critical
path through two Trihal 2500 kVA transformers. They supply redundant power for comfort cooling and accessories in the building,
and for 2N Galaxy 7000 UPSs feeding secondary pumps and perimeter coolers in the critical spaces.
The facility power system is designed to also support integrated peripheral devices like fire panels, access control systems, and
environmental monitoring and control devices. Power meters in the electrical path monitor power quality and allow for predictive
maintenance & diagnostics of the system. These meters also integrate with StruxureWare Power Monitoring Expert.
Every component in this Reference Design is built and tested to the applicable IEC standards. Further design details and
schematics are available in the Engineering Package available upon request.
LV Distribution to final loads per Block
MV Dist. SWG A1 MV Dist. SWG B1 DESIGN OPTIONS
Blocks 1&2 (shown two of eight blocks) This reference design can
be modified as follows
MV IT A MV IT B MV IT A MV IT B MV Cool. A MV Cool. B without a significant effect
Trihal
MV 2MVA
MV
LV
MV 2MVA
MV
LV
MV
LV
1.6MVA
MV
LV
MV 2.5MVA MV on the design’s
LV LV LV LV
Cooling Cooling performance attributes:
LV Crit. A1 LV Crit. B1 LV Crit. A2 LV Crit. B2 LV Cool. A LV Cool. B
& aux. A & aux. B
3200A, 400V 3200A, 400V 2500A, 400V Change UPS
UPS UPS UPS UPS
Okken UPS UPS batteries
LV Dist. A LV Dist.B LV Dist. A LV Dist.B
Location
Block 1 Block 2 Cooling & Auxiliaries CRAHs & Non-crit. Type
IT Rooms 1&2: 1728 kW IT Rooms 1&2: 1728 kW Blocks 1&2 Pumps
Facility Power
POWER MONITORING
Facility Cooling
This facility cooling design is optimized for hot and humid climates in Cooling system for 2 Blocks
places like Singapore or Hong Kong. However, it can be easily
adapted to work in other climates. It is made up of five stand-alone MUWP MUWP
Make up Make up
systems with water-cooled chillers and cooling towers: four identical water tank water tank
systems serve the blocks and one serves the offices with comfort CWP CWP CWP
cooling.
Chiller Chiller Chiller Chiller Chiller
Each pair of blocks share one cooling system comprised of six water-
PCHWP PCHWP PCHWP PCHWP PCHWP
cooled Uniflair BRRC-4802A chillers, primary-secondary variable flow
pumps, and three cooling towers, all in an N+1 configuration. In Thermal Thermal
addition, thermal storage and make up water systems are offered to Storage Storage
VFD
VFD
VFD
VFD
VFD
SCHWP SCHWP SCHWP SCHWP SCHWP
for ramp-up time of the chillers and building topology.
DAS DAS
IT Space
Eight independent IT blocks can be built one by one to make up the IT DESIGN OPTIONS
space of this design. One block includes two IT rooms of 864 kW apiece This reference design can be modified
on each floor of the data center. Each room is split into two zones: a
as follows without a significant effect on
medium-density area with 72 NetShelter racks of 5 kW each, and a high-
the design’s performance attributes:
density area with 72 NetShelter racks of 7 kW each. Altogether, they
constitute 13.8 MW of IT capacity for the whole site.
Add environmental and security
In this design, each IT room is powered by redundant (2N) iBusway management
systems. Every rack has the capacity to accept dual power feeds, since Change rack options (tall, wide, deep)
each is configured with redundant (2N) metered rack-mount power Change power distribution options (rack
distribution units (PDUs) which offer remote monitoring for improved PDU type: basic, switched)
Add StruxureWare Data Centre Expert
efficiency and capacity management.
In lower-density zones, heat is removed by Uniflair chilled water room-
based CRAHs in an N+2 redundant configuration at the room level. In
higher-density zones, heat is removed by InRow RC-HT units in an N+2
redundant configuration for each pair of rows. Considerations can be
made with respect to return air ducting systems and/or raised floors, to
improve the coolers’ performance. Redundant valves and piping are also
added to ensure continuous cooling with high reliability.
The security of the room is maintained at multiple points. At the rack
level, access is controlled by a door lock and sensor. At the room level,
security cameras are utilized for monitoring.
IT SPACE ATTRIBUTES