Professional Documents
Culture Documents
Facility Power
UTILITY CONNECTION
The data centre is designed for 42 MVA maximum demand, which requires a connection to the electrical utility high voltage (HV) sub-
transmission network. Depending on the country, the supply voltage could vary from 90 kV (e.g. France), 110 kV (e.g. Finland) up to
132 kV (e.g. UK). The utility company will be responsible for building the HV substation which provides metered supplies A and B.
Therefore, the change of ownership occurs after the metering point, which means that the data centre owner will specify and procure
the HV/MV transformer.
HV/MV Substation
Utility A Utility B
KWh KWh
HV HV
42MVA 42MVA
MV MV
2500A, 10kV 2500A, 10kV
MV Primary Dist. MV Primary Dist.
SWG A SWG B PiX
BLOCK 1
BLOCK 2
BLOCK 3
BLOCK 4
BLOCK 5
BLOCK 6
Facility Power
SECONDARY MEDIUM VOLTAGE DISTRIBUTION
To reduce initial investment and ensure a good scalability approach, each block is independent in terms of primary and secondary
MV distribution. However, to reduce the total cost a MV back up diesel generator power plant is shared across two blocks.
Automatic transfer between main power and backup generators is built into the design
A total of 56 Premset switchboards make up the secondary set of medium voltage distribution for all blocks, each rated at 17.5 kV,
1250 A and 25 kA (3s). Six of the Premset switchboards feed Type 1 blocks, ten feed Type 2 blocks, and twelve feed Type 3
blocks. All in a 2N architecture, where half of the units provide A-side power and the other B-side power and both sides are
connected by a “coupling cable” to maintain redundancy downstream of the failure on all blocks. The diesel generator backup
power is connected to the MV distribution network via a Premset switchoard. Seven 2500 kVA generators for each pair of blocks
type 1 and nine 2500 kVA generators for each pair of blocks type 2, provide N+1 LV power, while eleven 2500 kVA generators
provide N+2 power for the two type 3 blocks. Each generator is coupled to the MV network with a LV/MV step-up 2500 kVA Trihal
cast resin transformer with a 6% short circuit impedance. This choice of backup generator plant configuration provides high
reliability and safety, while minimizing cost. For full Tier III compliance, a set of redundant Premset MV switchgear could be added
to the design. Fuel storage and piping can also be added to the design in accordance with country habits and regulations.
Facility Power
LOW VOLTAGE DISTRIBUTION
Downstream from the MV secondary distribution, each block is separated into three with MV/LV transformers and LV switchboards.
Two of these groups are dedicated to two IT rooms and the other group to the cooling system and auxiliaries that serve the whole
block.
A total of 56 Trihal transformers, ranging from 1250 to 2500 kVA, are used in this design to transform power from 17.5 kV to 400 V
with 6% impedance, in a close-coupling installation. The same number of LV Okken switchboards makes up the LV distribution,
each rated at 400V, distributed as follows: for each type 1 block there are six switchboards rated at 50 kA (1s) with a 3200 A bus
(four for IT and two for cooling); for type 2 blocks there are eight units rated at 50 kA (1s) with a 2000 A bus for IT and two more at
80 kA (1s) with a 4000 A bus for cooling; and, finally, for each type 3 block there are eight switchboards rated at 50 kA (1s) with
2500 A bus for IT, and four for cooling rated at 50 kA (1s) (two with a 2500 A bus and two with a 3200 A bus).
On each IT power train the Okken switchboards feed 2N Symmetra PX arranged for an A and B-side distribution. Downstream from
the electrical rooms to the IT space there is a combination of LV switchgear and iBusway systems with built-in intelligence for 2N
power distribution. In the mean time, the Okken units that make up the cooling power train provide A- and B-side distribution to
chillers, pumps, lighting, monitoring, security and automation systems, etc., while providing fault protection to cooling units in the IT
and electrical rooms.
The facility power system is designed to also support integrated peripheral devices like fire panels, access control systems, and
environmental monitoring and control devices. Power meters in the electrical path monitor power quality and allow for predictive
maintenance & diagnostics of the system. These meters also integrate with StruxureWare Power Monitoring Expert.
Every component in this Reference Design is built and tested to the applicable IEC standards. Further design details and
schematics are available in the engineering package, which can be requested at the end of this document.
UPS UPS
batteries
UPS UPS
Location
LV Dist. A LV Dist.B LV Dist. A LV Dist. B
© 2015 Schneider Electric. All rights reserved.
Type
IT Room: 1.6MW IT Room: 1.6MW Cooling
MV Secondary
LV Distribution to final loads per Block Type 2 MV Secondary
Dist. SWG A Dist. SWG B
LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit.
Okken SWB A SWB B SWB A SWB B SWB A SWB B SWB A SWB B SWB A SWB B
2000A, 400V 2000A, 400V 2000A, 400V 2000A, 400V 4000A, 400V
UPS UPS UPS UPS UPS UPS UPS UPS
MV Secondary
LV Distribution to final loads per Block Type 3 MV Secondary
Dist. SWG A Dist. SWG B
LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit. LV Crit.
Okken SWB A SWB B SWB A SWB B SWB A SWB B SWB A SWB B SWB A SWB B SWB B
SWB A
2500A, 400V 2500A, 400V 2500A, 400V 2500A, 400V 3200A, 400V 3200A, 400V
UPS UPS UPS UPS UPS UPS UPS UPS
Facility Power
POWER MONITORING
Historic and archive building for data analysis and Block2 Block 2 Block 2 Block 4 Block 4 Block 4 Block 4 Block 4 Block 4
IT room 1 IT room 2 Mechanical IT room 1 IT room 2 Mechanical IT room 1 IT room 2 Mechanical
capacity planning.
Facility Cooling
Cooling system for Type 1 Blocks (shown as example)
This facility cooling system is meant for climates in places like
CHWR CHWS CHWS CHWR
Boston or Malmö, with warm summers and cold, snowy winters, IT & ER
IT & ER IT & ER IT & ER
though it can be easily adapted to work in other climates.
The facility cooling design is made up of six stand-alone cooling DAS GF GF DAS
VFD
VFD
VFD
VFD
VFD
VFD
systems sized specifically to serve each type of block. Every ET ET
chilled water system is comprised of a dual-path piping system
with N+1 redundant Uniflair air-cooled packaged chillers with Thermal Thermal
Storage Storage
free cooling, accompanied by a primary-secondary pumping
scheme, with variable speed secondary pumps, all in an N+1
configuration. Also, a redundant piping system across all the IT
and electrical distribution rooms in the block provide an alternate
Chiller Chiller Chiller Chiller Chiller
path for chilled water, in case of equipment failure.
In this cooling system design, economization is achieved with
dry coolers integrated within each chiller, to save energy during
favorable outdoor conditions. In addition, thermal storage
systems are offered to provide continuous cooling after a power Piping in electrical and IT rooms
outage or chiller restart. These tanks would be sized accordingly
CHWR
for the ramp-up time of the chillers and building topology.
ER A
CHWS CHWS
The redundant piping architecture of the mechanical system
feeds InRow RC units in the IT rooms and Uniflair chilled water IT Room IT Room
room-based computer room air handlers (CRAHs) in the LV 1 2
electrical rooms. Additional air handling units are added to
CHWR
ER B
supply fresh air in the building and direct expansion (DX) units
are provisioned for the rooms containing the generator
switchgear, MV switchgear and UPS batteries.
This design is instrumented to work with StruxureWare Building DESIGN OPTIONS
Operation for cooling control and monitoring. Further design This reference design can be modified as follows without a
details such as dimensions, equipment placement, temperature significant effect on the design’s performance attributes:
set points, pipe sizing, flow rates, and pressure drops are Add StruxureWare Building Operation
available in the engineering package.
IT Space
Six IT blocks are built one by one to make up the IT space of this design. DESIGN OPTIONS
One block includes two IT rooms with 196 NetShelter racks each, so all This reference design can be modified
rooms have a similar footprint even though they have different IT
as follows without a significant effect on
capacities. In type 1 blocks, each IT room houses racks of 8kW each, in
the design’s performance attributes:
type 2 blocks density is 10kW, and in type 3 blocks the rack density is
12kW. Altogether they provide 23.52 MW of IT capacity for the whole site.
Add environmental and security
In this design, each IT room is powered by redundant (2N) iBusway management
systems. Every rack has the capacity to accept dual power feed, since Change rack options (tall, wide, deep)
each is configured with redundant (2N) metered rack-mount power Change power distribution options (rack
distribution units (PDUs) to enable remote monitoring of the units for PDU type: basic, switched)
Add StruxureWare Data Centre Expert
efficiency and capacity management.
In all rooms, heat is removed by InRow RC-HT units in an in an N+2
redundant configuration for each pair of rows. Considerations can be
made with respect to return air ducting systems and/or raised floors, to
improve the coolers’ performance. Redundant valves and piping are also
added to ensure continuous cooling with high reliability.
The security of the room is maintained at multiple points. At the rack level,
access is controlled by a door lock and sensor. At the room level, security
cameras are utilized for monitoring.
IT SPACE ATTRIBUTES
Get more information on this design © 2015 Schneider Electric. All rights reserved.
Contact your Schneider Electric Account Manager to receive the Engineering Package for
this design which contains the electrical one line diagrams, piping diagrams, dimensioned
floor layouts, and equipment lists.