Professional Documents
Culture Documents
PFR96
PFR96P
Features
• Microprocessor based intelligent auto
switching control
• Programmable sensitivity
• For single-phase system • For 3-phase system • Complies with IEC 61000-6-2 standard
Technical Data
RATINGS AUXILIARY POWER SUPPLY CURRENT INPUT Temperature : -5˚C to +55˚C
Model PFR96 : 110 ~ 120 V AC / Rated current ( In ) :5A Humidity : 56 days at 93% RH and
220 ~ 240 V AC Operating Limits : 0.15 A to 6.5 A 40˚C non-condensing
Model PFR96P : 380 ~ 415 V AC Rated frequency : 50 Hz or 60 Hz
Operating Limits : -15% + 10%
Consumption : 10 VA max MECHANICAL
Rated frequency : 50 Hz or 60 Hz CONTROL RANGE Mounting : Panel mounting
Power factor setting : 0.8 Ind - 0.8 Cap Dimension (mm) : 96(w) x 96(h) x 70(d)
C/K setting : 0.03 - 1.20 / Automatic Approximate weight : 0.6 kg
OUTPUT CONTACTS Switching sensitivity : 5 - 600 s/step
Numbers of outputs : 6 Reconnection time for
Rated voltage : 250 V AC same step : 5 - 240 s
Contact rating : 5A Switching Program : Automatic / Automatic
Expected electrical life : 100,000 operations at Rotate / 4-quadrant /
PFR 96 / 96P
ENVIRONMENTAL CONDITIONS
Power Factor Regulator
MAIN MAIN
N L3 L2 L1 N L3 L2 L1
8 16 8 16
6 6
FUSE 15 FUSE
7 7 VOLTAGE 15
Power Factor
Power Factor
VOLTAGE 5
380~415
Regulator
6 14
Regulator
220 V AC / 4 6 14
V AC 4
5 110 V AC 13 5 13
3 3
4 12 4 12
2 2
P1 3 11 P1 3 11
CURRENT 1 CURRENT 1
2 /5A 10 2 10
/5A
P2 9 P2
1 1 9
FUSE FUSE
K1 K5 K6 K1 K5 K6
LOAD LOAD
Front
PFR96 - 110 - 50 6 Steps, for 50 Hz system, auxiliary voltage 110~120 V AC
PFR96 - 110 - 60 6 Steps, for 60 Hz system, auxiliary voltage 110~120 V AC
PFR96P - 415 - 50 6 Steps, for 50 Hz system, auxiliary voltage 380~415 V AC
PFR96P - 415 - 60 6 Steps, for 60 Hz system, auxiliary voltage 380~415 V AC 90 mm
70 mm
Side
PFR 96 / 96P
91.0 ± 0.5 mm
91.0 ± 0.5 mm
Panel
Cutout