IEC61850 SCADA Interface


for A77 Chargers with S2A-368S
Option 21J

Setup Instructions

This manual is only valid for A77 Chargers


equipped with the S2A-383S-1X4X communications card
and 368S software version P368S0114

106 Bradrock Dr. Des Plaines, IL 60018-1967 Instruction Drawing Number: P25-LOPT21J-A77-368S-3
Tel: 847 299 1188 Fax: 847 299 3061 CPN 137417 Revision A02 Rev. Date: 01/20 ECN:22485
Default Settings
The LaMarche Communications Card is shipped with the following default settings:

Ethernet/TCP/Configuration Port Settings


Protocol: IEC61850
IP Address: 192.168.0.6
Subnet: 255.255.255.0
Gateway: 192.168.0.1

Required Equipment/Software
PC/Laptop.

CAT 5/Ethernet Null-Modem/Crossover cable to connect PC/Laptop to Ethernet Port on Communications Card.

To change settings it is necessary to load and install the EasyConnect Software provided by Kalki
Communications from the following URL onto your PC/Laptop:

http://www.web.lamarchemfg.com/files/ftp/EasyConnect_V4.6.0_Setup/

Setting changes are made through the Ethernet connector on the 383S card.

EasyConnect Software Operation


EasyConnect is the software that will be used to accomplish the following setting changes.

TCPIP Setting (IP, Subnet, Gateway)

Setting the Modbus Address of the Chargers Control Card


The 383S communications board utilizes Modbus RTU to read and write settings from the Chargers 368S control
board. The settings are polled every 5 seconds. By default they are set as follows:

Modbus Address: 1
Modbus Baud Rate: 9600
Modbus Parity Type: None
Modbus Port Type: RS232

These settings are required for the two cards to communicate properly. If for some reason the Communications
Card is unable to obtain readings from the Control Card it is suggested to review the Modbus settings to confirm
they match the above. The Modbus Settings may be accessed from the Settings Menu.

2
Changing the IP, Subnet & Gateway Settings

Step 1: Select IP Configuration from the Settings menu as shown below.

3
Step 2: In the Lan Settings dialog shown below you enter the present IP address in the box just below the
SYNCS2R1OEM drop down box. In this case the card is at IP 192.168.0.6. In the IP Address, Subnet and
Gateway under the eth0 label you enter the settings you would like the card to take on. In this case the
module is presently at 192.168.0.6 and will be changed to an IP of 192.168.0.121 with a Subnet of
255.255.255.0 and a Gateway of 192.168.0.1. Press the OK button when you are done making changes.

Step 3: The card is now at the new IP settings. Press the OK button and the board will be restarted
automatically and will now be at the new settings. Note: If you have changed them to a different subnet you
will have to modify your network adapter card settings to reconnect to the card.

4
IEC61850 Point List
Name Description
ATBE_GGIO102 Automatic Battery Continuity Test Enable (ENABLED=TRUE)
ACAP1_MMXN4 PHASE 1, ACA
Note: This point should only be monitored when OACE_GGIO81 indicates
enabled and the charger is equipped with the optional 411S AC Sensing Board.
OACSS_GGIO84 should also be monitored to verify validity of this reading.
ACAP2_MMXN5 PHASE 2, ACA
Note: This point should only be monitored when OACE_GGIO81 indicates
enabled and the charger is equipped with the optional 411S AC Sensing Board.
OACSS_GGIO84 should also be monitored to verify validity of this reading.
ACAP3_MMXN6 PHASE 3, ACA
Note: This point should only be monitored when OACE_GGIO81 indicates
enabled and the charger is equipped with the optional 411S Sensing Board.
OACSS_GGIO84 should also be monitored to verify validity of this reading.
ACBAD_GGIO78 Disable Open AC Breaker Open Alarm (DISABLED=TRUE)
ACBO_GGIO86 Open AC Breaker Alarm Status (FAILURE=TRUE).
ACBOE_GGIO112 AC Breaker Open Alarm Monitoring Option Enabled (ENABLED=1)
ACBSM_GGIO75 Include AC Breaker Open Alarm in Summary Alarm (INCLUDED=TRUE)
ACDLY_GGIO58 AC Alarm Delay, Seconds, (0 to 300)
ACF_GGIO119 AC Fail Alarm Threshold, Voltage. Note setting the threshold below the value
contained in MINAC_GGIO120 will force the threshold to become one half of
the AC Voltage Rating of the Charger.
ACF_TFRQ1 AC Line Frequency, Hertz
ACSUM_GGIO50 Include AC Fail Alarm in Summary Alarm (INCLUDED=TRUE)
ACVP1_MMXN1 PHASE 1, ACV
Note: This point should only be monitored when OACE_GGIO81 indicates
enabled and the charger is equipped with the optional 411S AC Sensing Board.
OACSS_GGIO84 should also be monitored to verify validity of this reading.
ACVP2_MMXN2 PHASE 2, ACV
Note: This point should only be monitored when OACE_GGIO81 indicates
enabled and the charger is equipped with the optional 411S AC Sensing Board.
OACSS_GGIO84 should also be monitored to verify validity of this reading.
ACVP3_MMXN3 PHASE 3, ACV
Note: This point should only be monitored when OACE_GGIO81 indicates
enabled and the charger is equipped with the optional 411S AC Sensing Board.
OACSS_GGIO84 should also be monitored to verify validity of this reading.
ACV_MMXN7 AC Line Voltage, Volts
AC_GGIO5 AC Fail Alarm Status (FAILURE=TRUE)
AEQT1_GGIO20 Auto Equalize Timer, Days
AEQT2_GGIO21 Auto Equalize Timer, Hours, Minutes
Note: The last two digits are the minutes.
ATDAY_GGIO106 Automatic Battery Continuity Test Days Timer, Days to next test

5
ATHM_GGIO107 Automatic Battery Continuity Test Hours & Minutes Timer, Hours and Minutes
to next test. Note first two digits are hours last two digits are minutes.
BOARD_GGIO17 Board Number. Will read 368 for 368S card.
BOTAC_GGIO93 Battery Over-Temperature Alarm Threshold, C
BOTAD_GGIO77 Disable Battery Over Temperature Alarm (DISABLED=TRUE)
BOTSM_GGIO30 Include Battery Over Temperature Alarm in Summary Alarm
(INCLUDED=TRUE)
BOT_GGIO85 Battery Over Temperature Alarm Status (FAILURE=TRUE).
BSVE_GGIO121 Optional 417/407S Remote Battery Voltage Sensing Enable (ENABLED=1)
BSV_MMDC3 Optional 417/407S Remote Battery Voltage
BTFAS_GGIO103 Include Battery Continuity Test Fail Alarm in Summary Alarm
(INCLUDED=TRUE).
BTINT_GGIO111 Automatic Battery Continuity Test Interval, Days (7, 14, 21, 30, 60)
BTRES_GGIO110 Battery Continuity Test Result,0=NOT TESTED,1=TESTING BATTERY,2=TEST
PASSED,3=CHECK BATTERY,4=TEST FAILED,5=TEST NOT STARTED,
CHARGER IN EQUALIZE,6=TEST NOT STARTED, CHARGER LOAD >
50%,7=TEST NOT STARTED, ALARM CONDITION PRESENT
BTSTS_GGIO109 Battery Continuity Test Status
0=IDLE,1=TEST IN PROCESS,2=TEST FINISHED
BTYPE_GGIO94 Battery Type (LEAD ACID=0, NICAD=1)
CBAS_GGIO104 Include Battery Continuity Test Check Battery Alarm in Summary Alarm
(INCLUDED=TRUE).
CELLS_GGIO95 Battery Cells
CF_GGIO15 Charger Failure Alarm Status (FAILURE=TRUE).
CL_GGIO48 Current Limit, Amps, (MINCL_GGIO44 to MAXCL_GGIO43)
COMMS_GGIO16 Communications Alarm Status (OK=TRUE, FAILURE=FALSE). This indicates that
communications between the 368s control card and the 383s communications
card have failed.
DCA_MMDC2 DC Output Current, Amps
DCBAD_GGIO79 Disable Open DC Breaker Alarm (DISABLED=TRUE)
DCBO_GGIO87 Open DC Breaker Alarm Status (FAILURE=TRUE).
DCBOE_GGIO113 DC Breaker Open Alarm Monitoring Option Enabled (ENABLED=1)
DCBSM_GGIO76 Include DC Breaker Open Alarm in Summary Alarm (INCLUDED=TRUE)
DCV_MMDC1 DC Output Voltage, Volts
EDDLY_GGIO60 End of Discharge Alarm Delay, Seconds, (1 to 300)
EDRST_GGIO67 End of Discharge Alarm Recovery Threshold, Percent (0 to 20)
EOD_GGIO13 End of Discharge Alarm Status (FAILURE=TRUE).
EOD_GGIO29 End of Discharge Alarm Threshold, Volts, (0 to MAXAV_GGIO37)
EQTMR_GGIO19 Equalize Cycle Time Hours Remaining, Hours, Minutes
Note: The last two digits are the minutes.

6
EQTM_GGIO23 Equalize Timer Mode (0,1 2,3,4)
EQTS_GGIO24 Equalize Timer Setting (0 to 144)
EQV_GGIO47 Equalize Voltage, Volts, (MINEV_GGIO42 to MAXEV_GGIO41)
EVLOG_GGIO56 Event logging Enabled (ENABLED=TRUE)
F417S_GGIO99 Optional 417S Board Failure (FAILURE=TRUE). The 417S handles optional
ground detection, hydrogen gas sensor inputs, low electrolyte level sensor
inputs and low voltage battery disconnect inputs. Should this board fail the
previously listed inputs are no longer working reliably.
FCAD_GGIO116 Float Monitor Alarm Disable
FCAS_GGIO122 Include Float Monitor Alarm#1 in Summary Alarm
FLV_GGIO46 Float Voltage, Volts, (MINFV_GGIO40 to MAXFV_GGIO39)
FM1AF_GGIO143 Float Monitor #1 Current Reading, Fractional Portion

FM1AI_GGIO142 Float Monitor #1 Current Reading, Integer Portion

FM1AS_GGIO138 Float Monitor #1 Status


FM1C_GGIO145 Float Monitor #1 Temperature Reading

FM1V_GGIO144 Float Monitor #1 Voltage Reading


FM2AF_GGIO147 Float Monitor #2 Current Reading, Fractional Portion

FM2AI_GGIO146 Float Monitor #2 Current Reading, Integer Portion

FM2AS_GGIO139 Float Monitor #2 Status


FM2C_GGIO149 Float Monitor #2 Temperature Reading
FM2V_GGIO148 Float Monitor #2 Voltage Reading
FM3AF_GGIO151 Float Monitor #3 Current Reading, Fractional Portion

FM3AI_GGIO150 Float Monitor #3 Current Reading, Integer Portion

FM3AS_GGIO140 Float Monitor #3 Status


FM3C_GGIO153 Float Monitor #3 Temperature Reading
FM3V_GGIO152 Float Monitor #3 Voltage Reading
FM4AF_GGIO155 Float Monitor #4 Current Reading, Fractional Portion

FM4AI_GGIO154 Float Monitor #4 Current Reading, Integer Portion

FM4AS_GGIO141 Float Monitor #4 Status


FM4C_GGIO157 Float Monitor #4 Temperature Reading
FM4V_GGIO156 Float Monitor #4 Voltage Reading
H2GA_GGIO101 Hydrogen Gas Alarm Indicator (0-0%,1=1%,2=2%,3=SENSOR
FAILURE,4=OPTION N/A)
HV_GGIO7 High Voltage Alarm Indicator (FAILURE=TRUE)
HVSD_GGIO8 High Voltage Shutdown Alarm Indicator (FAILURE=TRUE)

7
LAC_GGIO88 Low AC Voltage Alarm Status (FAILURE=TRUE).
LCDBL_GGIO55 LCD Backlight Timeout Enable (ENABLED=TRUE)
This has no effect on Chargers equipped with VFD Displays.
LCDLY_GGIO64 Low Current Alarm Delay, Seconds, (1 to 300)
LCLL_GGIO4 Low DC Current Alarm Low Limit, Amps. Setting the Low DC Current Alarm
below this will result in disabling the Low DC Current Alarm Status Indicator.
LCSUM_GGIO51 Include Low Current Alarm in Summary Alarm (INCLUDED=TRUE)
LC_GGIO28 Low DC Current Alarm Threshold, Amps, (LCLL_GGIO4 to MAXAI_GGIO38)
LC_GGIO9 Low Current Alarm Status (FAILURE=TRUE)
LELAD_GGIO2 Low Electrolyte Level Alarm Disable (DISABLED=TRUE)
LEL_GGIO97 Low Electrolyte Level Alarm Status (FAILURE=TRUE)
LELOE_GGIO114 Low Electrolyte Alarm Monitoring Option Enabled (ENABLED=1)
LOGI_GGIO57 Automatic Logging Interval, Minutes, (1 to 60)
LVBDD_GGIO32 Low Voltage Battery Disconnect Alarm Disable (DISABLED=TRUE)
LVBDO_GGIO98 Low Voltage Battery Disconnect Alarm Option Enabled (ENABLED=TRUE). Point
indicates whether or not the charger is equipped with the optional Low Voltage
Battery Disconnect Alarm Input.
LVBDS_GGIO3 Low Voltage Battery Disconnect Alarm Included in Summary
(INCLUDED=TRUE)
LVBD_GGIO96 Low Voltage Battery Disconnect Alarm Status (FAILURE=TRUE)
LVDLY_GGIO59 Low Voltage Alarm Delay, Seconds, (0 to 300)
LVRST_GGIO66 Low Voltage Alarm Recovery Threshold, Percent (0 to 20)
LV_GGIO25 Low Voltage Alarm Threshold, Volts, (0 to MAXAV_GGIO37)
LV_GGIO6 Low Voltage Alarm Status (0=NO ALARM,1=LOW VOLTAGE,2=LOW BATTERY
VOLTAGE)
MINAC_GGIO120 Minimum AC Fail Alarm Voltage Setting, Settings below the minimum are
allowed however they will force the alarm voltage to be set to one half of the
AC Voltage Rating of the Charger.
MAXAI_GGIO38 Maximum Allowable Alarm Current Threshold, Amps
MAXAV_GGIO37 Maximum Allowable Alarm Voltage Threshold, Volts
MAXCL_GGIO43 Maximum Allowable Current Limit, Amps
MAXEV_GGIO41 Maximum Allowable Equalize Voltage, Volts
MAXFV_GGIO39 Maximum Allowable Float Voltage, Volts
MBH_GGIO90 Modbus Heartbeat. Increments continuously to indicate communications
between Controller board and communications board are working.
MINCL_GGIO44 Minimum Allowable Current Limit, Amps
MINEV_GGIO42 Minimum Allowable Equalize Voltage, Volts
MINFV_GGIO40 Minimum Allowable Float Voltage, Volts
MODE_GGIO31 Float/EQ Mode Indicator (FLOAT=FALSE, EQUALIZE=TRUE)

8
MTCR_GGIO108 Maximum Temperature Compensation Rate, V/Cell/C
NFM_GGIO137 Number of Float Monitors in System
NGMA_MMDC6 Negative Ground Amps
Note: This point should only be monitored when OGDE_GGIO80 indicates
enabled and the charger is equipped with the optional 407S Sensing Board.
OGDSS_GGIO89 should also be monitored to verify validity of this reading.
NG_GGIO11 Negative Ground Alarm Status (FAILURE=1).
Point will always read 0 when Ground Detection Enabled (GDE_GGIO22) is
FALSE.
OACE_GGIO81 Optional AC Sensing using 411S board Enabled (ENABLED=TRUE)
OACSS_GGIO84 411S Board Status (FAILURE=TRUE). A hardware problem exists with the 411S
board. AC Sensing is not functioning properly.
Note: This point should only be monitored when the Charger is equipped with
the optional 411S AC Sensing Board.
OGDE_GGIO80 Optional Ground Detection Method using 407S board Enabled
(ENABLED=TRUE)
OLSUM_GGIO74 Include Overload Alarm in Summary Alarm (INCLUDED=TRUE)
OL_GGIO14 Overload/Over Current Alarm Status (FAILURE=TRUE).
OTALM_GGIO92 Over Temperature Alarm Threshold, C
OTA_GGIO100 Over Temperature Alarm (0=OK,1=FAIL,2=DERATE,4=SHUTDOWN)
OTP_GGIO35 Over Temperature Probe Status (probe not connected, open or shorted=TRUE,
Probe OK=FALSE).
OTP_TTMP1 Over Temperature Probe Reading, Degrees C
OT_GGIO33 Over Temperature Alarm Status (FAILURE=TRUE).
PG_GGIO010 Positive Ground Alarm Status (FAILURE=1).
Point will always read 0 when Ground Detection Enabled (GDE_GGIO22) is
FALSE.
PGMA_MMDC5 Positive Ground Amps
Note: This point should only be monitored when OGDE_GGIO80 indicates
enabled and the charger is equipped with the optional 407S Sensing Board.
OGDSS_GGIO89 should also be monitored to verify validity of this reading.
PLFU_GGIO45 Percent of log drive space used.
RCDAY_GGIO69 RTC Day, Days, (1 to 31)
RCHR_GGIO71 RTC Hours, Hours, (0 to 23)
RCMIN_GGIO72 RTC Minutes, Minutes, (0 to 59)
RCMON_GGIO68 RTC Month, Month, (1 to 12)
RCP_GGIO82 Remote Setting Change Inhibit. When this point is read as 1 remote setting
changes via are not allowed. This will occur when an operator is in the Settings
Menu.
RCSEC_GGIO73 RTC Seconds, Seconds, (0 to 59)
RCYR_GGIO70 RTC Year, Years, (0 to 4095)
RSDS_GGIO118 Remote Shutdown Alarm Status (OK=0, FAILURE=1,DISABLED=2)

9
RSTA_GGIO136 Reset All Alarms (1=RESET ALL)
SCR_GGIO34 SCR Failure Alarm Status (FAILURE=TRUE).
SUM_GGIO12 Summary Alarm Status (FAILURE=TRUE)
SWVER_GGIO18 Software Version, Version of software on 368S card.
TBATT_GGIO105 Start Battery Continuity Test (START TEST=TRUE).
TCP_GGIO36 Temperature Compensation Probe Status (probe not connected, open or
shorted=1, Probe OK=FALSE).
TCP_TTMP2 Temperature Compensation Probe Reading, Degrees C
TCR_GGIO49 Temperature Compensation Rate, (0 to MTCR_GGIO108) V/Cell/C
Note 0=OFF
TM4DLY_GGIO61 Equalize Timer Mode 4 (Auto Equalize on LV Alarm Recovery)
Delay, Seconds (1 to 300)
TPC_GGIO83 Three Phase Charger (3PHASE=TRUE, 1 PHASE=FALSE)
VGTON_MMDC7 DC Voltage between Ground and Negative, Volts
Note: This point should only be monitored when OGDE_GGIO80 indicates
enabled and the charger is equipped with the optional 417S Sensing Board.
OGDSS_GGIO89 should also be monitored to verify validity of this reading.

VPTOG_MMDC8 DC Voltage between Positive and Ground, Volts Note: This point should only be
monitored when OGDE_GGIO80 indicates enabled and the charger is equipped
with the optional 417S Sensing Board. OGDSS_GGIO89 should also be
monitored to verify validity of this reading.

Goose Control Blocks

GCB_ACV

ACV_MMXN7 AC Line Voltage, Volts

ACF_TFRQ1 AC Line Frequency, Hertz

GCB_CHARGER_OUTPUT

DCA_MMDC2 DC Output Current, Amps

DCV_MMDC1 DC Output Voltage, Volts

MODE_GGIO31 Float/EQ Mode Indicator (FLOAT=FALSE, EQUALIZE=TRUE)

GCB_OPT_AC_AMPS

ACAP1_MMXN4 PHASE 1, ACA

10
ACAP2_MMXN5 PHASE 2, ACA

ACAP3_MMXN6 PHASE 3, ACA

GCB_OPT_AC_VOLTS

ACVP1_MMXN1 PHASE 1, ACV

ACVP2_MMXN2 PHASE 2, ACV

ACVP3_MMXN3 PHASE 3, ACV

GCB_TEMPERATURES

OTP_TTMP1 Over Temperature Probe Status (probe not connected, open or shorted=TRUE,
Probe OK=FALSE).

TCP_TTMP2 Temperature Compensation Probe Status (probe not connected, open or


shorted=1, Probe OK=FALSE).

GCB_OPT_GND_DET

PGMA_MMDC5 Positive Ground Amps


NGMA_MMDC6 Negative Ground Amps
VGTON_MMDC7 DC Voltage between Ground and Negative, Volts
VPTOG_MMDC8 DC Voltage between Positive and Ground, Volts

GCB_RMT_SHUTDOWN_ALARM

RSDS_GGIO118 Remote Shutdown Alarm Status (OK=0,FAILURE=1,DISABLED=2)

GCB_TEMPERRATURE_ALARMS

OT_GGIO33 Over Temperature Alarm (0=OK,1=FAIL,2=DERATE,4=SHUTDOWN)

BOT_GGIO85 Battery Over Temperature Alarm Status (FAILURE=TRUE).

GCB_TEMP_PROBE_ALARMS

OTP_GGIO35 Over Temperature Probe Status (probe not connected, open or shorted=TRUE,
Probe OK=FALSE).

11
TCP_GGIO36 Temperature Compensation Probe Status (probe not connected, open or
shorted=1, Probe OK=FALSE).

GCB_SUMMARY_ALARM

SUM_GGIO12 Summary Alarm Status (FAILURE=TRUE)

GCB_OVER_CURRENT_ALARM

OL_GGIO14 Overload/Over Current Alarm Status (FAILURE=TRUE).

GCB_LOW_VOLTAGE_ALARMS

LV_GGIO6 Low Voltage Alarm Status (0=NO ALARM,1=LOW VOLTAGE,2=LOW BATTERY


VOLTAGE)

EOD_GGIO13 End of Discharge Alarm Status (FAILURE=TRUE).

GCB_LOW_ELECTROLYTE_ALARM

LEL_GGIO97 Low Electrolyte Level Alarm Status (FAILURE=TRUE)

GCB_LOW_CURRENT_ALARM

LC_GGIO9 Low Current Alarm Status (FAILURE=TRUE)

GCB_HYDROGEN_GAS_ALARM

H2GA_GGIO101 Hydrogen Gas Alarm Indicator (0-0%,1=1%,2=2%,3=SENSOR


FAILURE,4=OPTION N/A)

GCB_HIGH_VOLTAGE_ALARMS

HV_GGIO7 High Voltage Alarm Indicator (FAILURE=TRUE)

HVSD_GGIO8 High Voltage Shutdown Alarm Indicator (FAILURE=TRUE)

GCB_GND_DETECTION_ALARMS

PG_GGIO010 Positive Ground Alarm Status (FAILURE=1).

12
NG_GGIO11 Negative Ground Alarm Status (FAILURE=1).

GCB_CHARGER_FAILURE_ALARM

CF_GGIO15 Charger Failure Alarm Status (FAILURE=TRUE).

GCB_BREAKER_ALARMS

DCBO_GGIO87 Open DC Breaker Alarm Status (FAILURE=TRUE).

ACBO_GGIO86 Open AC Breaker Alarm Status (FAILURE=TRUE).

GCB_BATTERY_TEST_STATUS

BTRES_GGIO110 Battery Continuity Test Result,0=NOT TESTED,1=TESTING BATTERY,2=TEST


PASSED,3=CHECK BATTERY,4=TEST FAILED,5=TEST NOT STARTED,
CHARGER IN EQUALIZE,6=TEST NOT STARTED, CHARGER LOAD >
50%,7=TEST NOT STARTED, ALARM CONDITION PRESENT

BTSTS_GGIO109 Battery Continuity Test Status


0=IDLE,1=TEST IN PROCESS,2=TEST FINISHED

GCB_AC_ALARMS

AC_GGIO5 AC Fail Alarm Status (FAILURE=TRUE)

LAC_GGIO88 Low AC Voltage Alarm Status (FAILURE=TRUE).

GCB_CHARGER_OUTPUT_SETTINGS

FLV_GGIO46 Float Voltage, Volts

EQV_GGIO47 Equalize Voltage, Volts

CL_GGIO48 Current Limit, Amps

Document Control and Revision History


Part Number: 137417
Instruction Number: P25-LOPT21J-A77-368S-3
Issue ECN: 22485 - 01/20
22485 - 01/20 20985-18 – 06/19 20985-12 – 03/18