Professional Documents
Culture Documents
com
Setup Instructions
106 Bradrock Dr. Des Plaines, IL 60018-19671 Instruction Drawing Number: P25-LOPT21S-A77-368S-4
Tel: 847 299 1188 Fax: 847 299 3061 CPN 143126 Revision A00 Rev. Date: 07/20 ECN: 20985-31
Default Settings
The LaMarche Communications Card is shipped with the following default settings;
To change the Address, Baud Rate and Parity you need to enter the Settings Menu and go to the
Communications Settings Menu. From there you can change the following settings;
Remote Disable (YES or NO). Defaults to NO. When set to YES the charger data is read only. Remote settings
changes are prohibited. Writes to Coils and Holding Registers will be ignored.
Modbus Type (Modbus Serial or Modbus TCP). Defaults to Modbus Serial. Chargers with Option 21S should not
set the Modbus Type to Modbus TCP.
2
RS232 & RS485 Serial Applications
D+ GND D-
RS232 RS485 PORT RS485 PORT
SELECTION JUMPERS RS232 PORT (DTE)
WIRED AS D
For RS232 (WIRED AS DTE CONNECTION): TT
For RS485
The shorting jumpers must be on positions JP13 and JP15. In addition for RS485 applications the following
should also be set as required;
3
LaMarche Modbus Implementation
RTU
TCP
Coils
Supported Functions: 01 – Read Coil Status (0X), 05 – Write Single Coil
Address Name/Description
4
Coils
Supported Functions: 01 – Read Coil Status (0X), 05 – Write Single Coil
Address Name/Description
5
Discrete Inputs
Supported Functions: 02 – Read Discrete Input Registers (1X)
Address Name/Description
6
Discrete Inputs
Supported Functions: 02 – Read Discrete Input Registers (1X)
Address Name/Description
Holding Registers
Supported Functions: 03 – Read Holding Registers (4X), 06 – Write Single Register
Address Description, Units, Valid Settings/Range Scale Factor
40000 Equalize Timer Mode (0,1 2,3,4) None
40001 Equalize Timer Setting (0 to 144) None
40002 Low Voltage Alarm Threshold, Volts, (0 to MAXAV) 0.1
40003 High Voltage Alarm Threshold, Volts, (0 to MAXAV) 0.1
40004 High Voltage Shutdown Alarm Threshold, Volts, (0 to MAXAV) 0.1
40005 Low DC Current Alarm Threshold, Amps, (0 to MAXAI) 0.1
40006 End of Discharge Alarm Threshold, Volts, (0 to MAXAV) 0.1
40007 Float Voltage, Volts, (MINFV to MAXFV) 0.1
40008 Equalize Voltage, Volts, (MINEV to MAXEV) 0.1
40009 Current Limit, Amps, (MINCL to MAXCL) 0.1
Temperature Compensation Rate, (0 to MAXTCR) V/Cell/C
40010 0.001
Note 0=OFF
40011 Automatic Logging Interval, Minutes, (1 to 60) None
40012 AC Alarm Delay, Seconds, (0 to 300) None
40013 Low Voltage Alarm Delay, Seconds, (0 to 300) None
40014 End of Discharge Alarm Delay, Seconds, (0 to 300) None
Equalize Timer Mode 4 (Auto Equalize on LV Alarm Recovery)
40015 None
Delay, Seconds (1 to 300)
40016 High Voltage Alarm Delay, Seconds, (1 to 300) None
40017 High Voltage Shutdown Alarm Delay, Seconds, (1 to 300) None
40018 Low Current Alarm Delay, Seconds, (1 to 300) None
40019 Low Voltage Alarm Recovery Threshold, Percent (0 to 20) None
40020 End of Discharge Alarm Recovery Threshold, Percent (0 to 20) None
40021 RTC Month, Month, (1 to 12) None
40022 RTC Day, Days, (1 to 31) None
40023 RTC Year, Years, (0 to 4095) None
7
Holding Registers
Supported Functions: 03 – Read Holding Registers (4X), 06 – Write Single Register
40024 RTC Hours, Hours, (0 to 23) None
40025 RTC Minutes, Minutes, (0 to 59) None
40026 RTC Seconds, Seconds, (0 to 59) None
40027 Ground Detection Alarm Delay, Seconds, (0 to 300) None
Ground Detection Alarm Threshold, Milliamps, (10 to 40),
10=1.0mA, 40=4.0mA
40028 Note: This point should only be monitored and written to when 0.1
the Charger is equipped with the optional 407/417S Ground
Detection Board and Binary Input Point 15 is enabled.
40029 Battery Over Temperature Alarm Threshold, C, (25 to 100) None
40030 Automatic Battery Continuity Test Interval, Days (7,14,21,30,60) None
AC Fail Alarm Threshold, Voltage. Note setting the threshold
below the value contained in Input Register 30042 will force the
40031 0.1
threshold to become one half of the AC Voltage Rating of the
Charger.
Input Registers
Supported Functions: 04 – Read Input Registers (3X)
8
Input Registers
Supported Functions: 04 – Read Input Registers (3X)
9
Input Registers
Supported Functions: 04 – Read Input Registers (3X)
10
Input Registers
Supported Functions: 04 – Read Input Registers (3X)
11
Document Control and Revision History
Part Number: 143126
Instruction Number: P25-LOPT21S-A77-368S-4
Issue ECN: 20985-31 – 07/20
20985-31 – 07/20
12