You are on page 1of 12

Publicado por Aplicaciones Tecnológicas, S.A. 2018 . Rev.

0-3/2018

LOCAL STORM
DETECTION

AT-555 | REMOTE RELAY MODULE


Instruction Manual
Thank you for purchasing ATSTORM® Relay Remote Module. This handbook explains how to
correctly carry out the installation of ATSTORM® Relay Remote Module and how to use the
system with the operation console.
This manual refers to the following Aplicaciones Tecnológicas items:

• AT-555 Remote Relay Module

Symbol

Danger due to electric shock.

Device complying with the


Relayvant standards.

Device complying with current


recycling standards.

3
AT-555 | REMOTE RELAY MODULE Instruction Manual

Connection of the dry-contact relays

The connsole is provided with 4 dry-contact relays able to switch signals up to 250 V, 2 A.
These relays can be associated with different events and alarms using the alarm configuration
screen (see 7.1)

Connect the dry-contact relays for


configuring the alarms.

When an event activates an alarm, then the 1 2 3


connection switches from 2 & 3 to 2 & 1.

3 3

2 2
1 Normally open
2 Common
1 1
3 Normally closed

4
Front panel

Power indicator Relay status indicator

Network indicator

Use of CPU

Rear panel

1-4 Relay 1 connector 1,2 Digital input

Power Supply Sensor comm

On/OFF CAN-RS-485
Switch Communication

5
AT-555 | REMOTE RELAY MODULE Instruction Manual

MODBUS COMMUNICATION

The ATSTORM® REMOTE RELAY MODULE has implemented a Modbus Commnication over
RS-485 or TCP in order to get information from ATSTORM V3 sensors.

TCP:

The paremeters of the Modbus Configuration can be done by the settings webpage of the
system:

To configure the IP settings enter the new settings and press SAVE
To configure the Slave ID and the Local Port enter the new settings and press SEND

6
MODBUS COMMUNICATION
REGISTER MAP
The ATSTORM® REMOTE RELAY MODULE has implemented a Modbus Commnication over
RS-485 or TCP in order to get information from ATSTORM V3 sensors.

Address Type Cont Values


0 FIELD Electrostatic field 27000 to - 27000
1 TEMPERATURE Temperature inside the sensor in C
2 DISTANCE Lightning Distance 0 to 63 in Kilometers
3 ALARM STATUS Alarm Status from ATSA Same digital Inputs (Decimal)
0 1 2 3 -1 -2
4 RELAY STATUS Actual Relay and Flag Status Same digital Outputs (Decimal)
5 RESERVED Not defined Not defined
6 RESERVED Not defined Not defined
7 RESERVED Not defined Not defined
8 RESERVED Not defined Not defined
9 RESERVED Not defined Not defined
10 RESERVED Not defined Not defined
11 RESERVED Not defined Not defined
12 RESERVED Not defined Not defined
13 RESERVED Not defined Not defined
14 RESERVED Not defined Not defined
15 RESERVED Not defined Not defined

Alarm Status from ATSA

0 NORMAL
1 ALERT
2 EMERGENCY
3 MAX. RISK
-1 No server comm
-2 No sensor comm

7
AT-555 | REMOTE RELAY MODULE Instruction Manual

Modbus Map ¨Actual Relay Output Status¨


Digital Outputs Read & Write

Address Type Cont Values


0 No Comm Output Relay 1 Status No Comm 1 or 0
1 Alarm 1 Output Relay 2 Status "Alert" 1 or 0
2 Alarm 2 Output Relay 3 Status "Emergency" 1 or 0
3 Alarm 3 Output Relay 4 Status "Max Risk" 1 or 0
4 User Key Custom User Key 0 ATSA Relay Driver / 1 Custom
Relay Driver

RS-485

The module allows to communicate through Modbus RTU over RS-485.


The module does not include the end of line resistance (normally 100-120 Ohm)
The Baudrate configured is 9600
Minimum delay between polls: 500ms

8
9
Notas
Notas
Aplicaciones Tecnológicas S.A. - Parque Tecnológico de Valencia - Nicolás Copérnico, 4 - 46980 Paterna (Valencia), Spain
T +34 961 318 250 - F +34 961 318 206 - atsa@at3w.com - at3w.com

You might also like