You are on page 1of 9

Correct application

of monitors

Marcus Wildschuetz
March 2017

1
Content

 Application for Monitor


 Military and Premixed fuels
 Proper nameplate
 Rumors about SAP problems

2
Application

 Monitors are really a fuse which is showing


the presence of water and/or dirt

 According ATA103 they should only be used


in into plane operations (JIG is different)
 They must be changed out after one year or
on high differential pressure (22psi(1,5 bar))

3
Military and premixed fuels

 Monitors must not be used with Military and


premixed fuels

 They have been proven to be disarmed

 The chemistry of the super absorbent


polymer does not work with FSII

 Cases were military fuels generated SAP


migration

4
Nameplate acc. EI 1596

Not to be removed!!! To be replaced!!!

5
IATA-SAP working group
Conclusion

• Monitors are in good use at a lot of into


plane locations globally
• They must not be used with premixed or
military fuels
• Even without premixed or military fuels
there have been indications of SAP
shedding of monitors

7
Questions?

8
Final Slide

Thank you for attention