Guideline No 7:2004

European
Guideline

Safety distances
between waste
containers and
buildings

CFPA-E® -Guidelines
Guideline No 7:2004

FOREWORD
The European fire protection associations have decided to produce common guidelines in
order to achieve similar interpretation in the European countries and to give examples of
acceptable solutions, concepts and models. The Confederation of Fire Protection Associations
in Europe (CFPA E) has the aim to facilitate and support fire protection work in the European
countries.

The market imposes new demands for quality and safety. Today fire protection forms an
integral part of a modern strategy for survival and competitiveness.

The guideline is primarily intended for those responsible for safety in companies and
organisations. It is also addressed to the rescue services, consultants, safety companies etc
so that, in the course of their work, they may be able to help companies and organisations to
increase the levels of fire safety.

The proposal of this guideline have been produced by SPEK - The Finnish National Rescue
Association and the author is Mr Matti Orrainen.

This guideline was compiled by the Guidelines Commission and has been adopted by all fire
protection associations in the Confederation of Fire Protection Associations Europe.

Zurich, 12 Mars 2004


CFPA Europe

Dr. Hubert Rüegg


Chairman

Stockholm, 12 Mars 2004


Guidelines Commission

Tommy Arvidsson
Chairman

CFPA-E® -Guidelines
Guideline No 7:2004

1. Introduction................................................................................................................4
2. The safety distance defined..........................................................................................4
3. Example of fire objects ................................................................................................5
4. Rate of heat release ....................................................................................................5
4.1 Quick estimation of the safety distance ....................................................................5
4.2 Horizontal safety distances......................................................................................5
4.3 Minimum horizontal safety distance .........................................................................6
4.4 The 4m safety distance group .................................................................................6
4.5 The 6m safety distance group .................................................................................6
4.6 The 8m safety distance group .................................................................................6
5. The alternative to the safety distance............................................................................6
6. Conclusion ..................................................................................................................6
Appendix: Essentials of the calculations ............................................................................7
The temperature and height of the flame.......................................................................7
The Acceptance Criteria of Heat Radiation Calculations ................................................. 16
Horizontal safety distances ......................................................................................... 16
References ................................................................................................................... 17
European guideline ....................................................................................................... 17

CFPA-E® -Guidelines
Guideline No 7:2004

1. Introduction

Many arson attacks target waste containers and other combustible objects located outside
buildings. These relatively innocuous fires too often develop into fires which can cause
significant personal injuries or property damage when they spread into buildings. For this
reason, it is necessary to give the owners and occupiers of premises some basic advice about
ways to prevent these.

This guidance is based upon (1) methods of calculation which have developed from an
analysis of fire investigations and (2) empirical knowledge gained in such investigations.

In the prevention of arson, however, particular attention must also be paid to practical
measures to thwart the arsonist, i.e. the fencing of the yard, the locking of areas and the
removal of all combustible materials from the yard.

2. The safety distance defined

A fire can spread from its place of ignition:

− by conduction through structures


− through heat radiation from a flame or
− through the hot gases and sparks the fire has created.

Figure 1. A fire can spread from its place of ignition through heat radiation from a flame (D)
or through the hot gases and sparks the fire has created (E).

In outside areas, the heat of a fire is transferred from combustible objects primarily through
the last two methods mentioned above. That is why it is vital that the horizontal safety

4 CFPA-E® -Guidelines
distance between the burning object and (from the technical fire perspective), the building’s
weakest point, must be determined.

The potential spread of fire along the eaves caused by the heat energy of a smoke column,
has also been addressed by the application of and reference to horizontal safety distances.

3. Example of fire objects

For the purposes of calculation, three fire objects have been taken as examples:

(a) a 600 litre waste container made of glass fibre or plastic;


(b) a group of three such waste containers, burning simultaneously;
(c) a 2m x 6m demountable platform (open bed), loaded with combustible material.

Using these three examples, it is possible to estimate fire safety distances for other objects or
structures in the yard.

4. Rate of heat release

The material (garbage) stored in waste containers is mostly like household waste, comprising
paper, wood, cardboard and plastics. In what follows, heat release rates are based on this
kind of fuel. For example the value of heat release of the single waste container (2MW) is
comparable the peak value of the heat release of wood pallet stacks, when the pile height is
about 1m. The heat release of a burning petrol barrel is about 1MW.

The Rate of Heat Release (RHR) of a fire is needed to determine the height and temperature
of the flame. This can be calculated as described in source (3). The test results of source (2)
can also be used. On the basis of these results, the following values of RHR of the chosen fire
objects were determined:

(a) waste container RHR = 2 MW


(b) 3 waste containers RHR = 6 MW
(c) demountable platform RHR = 10 MW

4.1 Quick estimation of the safety distance

It is possible to use the results of the fire technical calculations (1) to determine the
horizontal safety distances of objects and structures from buildings.

Equation (1) provides a quick approximation of the horizontal safety distance:

Safety distance ≈ width of object to be estimated + 2,5 m (1)

This equation provides a valid result if the height of the fire object is not greater than its
width.

4.2 Horizontal safety distances

A range of horizontal safety distances can be established for different categories of fire
objects and structures outside buildings.

5 CFPA-E® -Guidelines
4.3 Minimum horizontal safety distance

According to equation (1) the minimum horizontal safety distance between combustible
objects and buildings is 2,5m. This is the horizontal safety distance for, for example, point
sources of flames.

4.4 The 4m safety distance group

These objects should be located at least 4m away from buildings:


− a single 600 litre waste container made of glass fibre or plastic;
− a waste container made of steel;
− other combustible objects, structures and piles which are less than 1,5m high and wide.

4.5 The 6m safety distance group

These objects should be located at least 6m away from buildings:


− a group of waste containers made of glass fibre or plastic;
− a trolley for pasteboard packages;
− other combustible objects, structures and piles which are less than 4m high and wide.

4.6 The 8m safety distance group

These objects should be located at least 8m away from buildings:


− an interchangeable platform full of combustible material (dumpsters);
− a rubbish shelter;
− a wooden shed, a small building and similar combustible structures;
− a car shelter;
− a caravan and other mobile homes;
− pallet piles;
− other combustible objects, structures and piles which are less than 6m high and wide

5. The alternative to the safety distance

If it is not possible to achieve any of the safety distances cited, then it is necessary that the
adjacent structure is fire resistant. It must have fire resistance in the EI 30 – EI 120
(2000/367/EC) according to national building regulations. The abbreviation EI 30 refers to a
wall which has a resistance to fire of 30 minutes in terms of both integrity (E) and insulation
(I).

6. Conclusion

In addition to the safety distances included in the guidebook (1),it describes different
methods for preventing the spread of fire from structures in a yard into a building.

It is worth repeating that, to thwart the arsonist, it is vital to implement practical measures to
secure the perimeter of a yard and to reduce the accumulation of combustible materials in
yards.

6 CFPA-E® -Guidelines
Guideline No 7:2004

Appendix: Essentials of the calculations

The temperature and height of the flame

The temperature of the persistent flame was presumed, in each fire object, to be 800 0 C ((2)
and (3)) (see Figs 2-4). The temperature of the intermittent flame was presumed to be 600 0
C ((2) and (3)). These values have been checked using calculation method (2), which is
based on RHR.

The height of the flame and the temperature of the smoke column were calculated using
McCaffrey’s smoke column model (2). The flame was assumed to be an orthogonal radiator,
radial plate. The largest possible width of the flame was taken to be the width of the flame,
i.e. in the case of the demountable platform, the longest side of the platform faces the
building.

7 CFPA-E® -Guidelines
The results of the calculations are shown in Figs 2-4.

8 CFPA-E® -Guidelines
9 CFPA-E® -Guidelines
Figure 2. The values of height and temperature of the fire plume on the demountable
platform.

10 CFPA-E® -Guidelines
Guideline No 7:2004

Figure 3. The values of height and temperature of the fire plume when three waste
containers are burning.

11 CFPA-E® -Guidelines
Guideline No 7:2004

Figure 4. The values of height and temperature of the fire plume when a single waste
container is burning.

12 CFPA-E® -Guidelines
Guideline No 7:2004

Heat radiation calculations

The energy of the heat radiation transmitted by the fire plume was calculated from the
temperature of the flame, i.e. a persistent flame has an energy of 75kW/m2 and a
intermittent flame has 33kW/m2 . The calculation was carried out according to Stefan-
Boltzmann’s radiation heat estimation theory and was checked using calculation method (2),
which is based on fire energy.

The energy of heat radiation, which can impinge on different external elements of a building,
can be examined by adding a visibility coefficient to the values of the heat radiation
transmitted by the fire plume. See, for example, sourer (2) for information about visibility
coefficients. Figure 5 shows the variables which are involved in the heat radiation
calculations.

Figure 5. The variables in the heat radiation calculations. B is the heat radiation to the facade
of the building and C is the horizontal distance between the fire plume and the facade. Their
values are shown in Figs 6-8. (D is the intermittent flame and E is the persistent flame.)

Figures 6-8 are graphs which show the relationship between heat radiation and distance from
the building for the three chosen fires.

13 CFPA-E® -Guidelines
Guideline No 7:2004

60

50
Radiation kW/m²

40

30

20

10

0
0 2 4 6 8 10
Distance m
F
igure 6. Heat radiation v. distance when the demountable platform is burning.

60

50
Radiation kW/m²

40

30

20

10

0
0 2 4 6 8 10
Distance m

Figure 7. Heat radiation v. distance when the three waste containers are burning.

14 CFPA-E® -Guidelines
60

50
Radiation kW/m²

40

30

20

10

0
0 2 4 6 8 10
Distance m

Figure 8. Heat radiation v. distance when the one waste container is burning.

15 CFPA-E® -Guidelines
Guideline No 7:2004

The Acceptance Criteria of Heat Radiation Calculations

The results of the radiation calculations can be used to estimate the safety distances if it is
possible to determine the acceptance criteria for the maximum values of the heat radiation
onto the facade of the building at risk. It is possible to determine the building elements from
the external wall. The heat radiation resistance of the elements is critical when examining the
spread of fire into a building from outside. Such elements include the wooden and plastic
parts and the windows of the facades. In addition, features inside the windows, such as
curtains, must be taken into consideration.

In sources (3) and (4), the experimental and theoretical value of the heat radiation resistance
of glass is presented. On the basis of these values it is possible to estimate that the critical
long-term radiation flow for normal window glass is about 10 kW/m2 .
It can be presumed that when this value is exceeded the glass panes will break one by one
and then the heat radiation will strike with full force the movable property which is located
inside and the plume gases could flow in through the window openings. The critical heat
radiation flow value for wooden materials is about 12.5kW/m2 and for plastic materials about
10kW/m2 , see source (2) and (3).

When the critical heat radiation flow value onto the external facade is exceeded for a long
period the material in question will ignite, at which time the fire will spread into the building
itself. The critical heat radiation flow value of wooden material is the same as will ignite thin,
cellulose-based curtain material, which in fact will occur at this heat radiation flow level faster
than the ignition of a wooden structure.

Thus a value of 10kW/m2 is used in the calculations as the largest acceptable heat radiation
flow into the external wall surface of the building at risk.

Horizontal safety distances

After a safety examination has been carried out it is possible to use the results of the
foregoing calculations to determine the horizontal safety distances of objects and structures
which are located outside buildings. The values which have been obtained from the
calculations must take into account the inclination of the fire plume towards the building,
caused by wind. This is done by carrying out an inclination examination of the fire plume, on
the basis of which it is possible to estimate the actual safety distances by adding 1m to the
safety distances which have been obtained from the calculations. In respect of the fire
objects which have been presented in the calculations, the following values for the safety
distance in the horizontal places were obtained:

(a) waste container safety distance 4m


(b) 3 waste containers safety distance 6m
(c) demountable platform safety distance 8m

The spread of fire into and along the eaves, caused by the heat energy of a smoke column,
has also been addressed by the application of and reference to horizontal safety distances.

16 CFPA-E® -Guidelines
Guideline No 7:2004

References

(1) Pihan jäteastiat ja tuhopolttojen torjunta Tekniikka opastaa 17 Suomen Palastusalan


Keskusjärjestö 2002 (The Finnish National Rescue Association)

(2) Drysdale, Dougal. An Introduction to Fire Dynamics, John Wiley, 1985.

(3) Buchanan, A.H. (ed). Fire Engineering Design Guide,: Centre of Advanced Engineering,
Christchurch NZ, 1994.

(4) Keski-Rahkonen Olavi. Ikkunoitten rikkoutuminen tulipalossa Palontorjuntatekniikka-lehti


3/1990.

European guideline
Guideline No 1:2002 - Internal Fire Protection Control
Guideline No 2:2002 - Panic & emergency exit devices
Guideline No 3:2003 - Certification of thermographers
Guideline No 4:2003 - Introduction to Qualitative Fire Risk Assessment
Guideline No 5:2003 - Guidance signs, Emergency lighting and General lighting
Guideline No 6:2004 – Fire safety in residential homes for the elderly

17 CFPA-E® -Guidelines