You are on page 1of 2

TEST REPORT NO.

& DATE

1. Name & Address of Customer

2. Project / Site

3. Customer's Reference
4. Sample
i) Description Hllow Block
ii) Quantity 03Nos.
iii) Date of receipt 7/10/2022
iv) Condition Acceptable
5. Test method followed, if any ASTM C426 , C140 , IS. : 2185 ( part 3)-2008
6. Date of Testing 11/07/2022

TEST REPORT
II. COMPRESSIVE STRENGTH TEST
Sr. ID. Marks Size of bricks Area Crushing
No. Load
BLOCK WT (mm) (mm2) (KN)
1 KAKAN 12910 400 x 180 x 150 72000.00 21.50
2 " 12892 400 x 180 x 150 72000.00 18.96
3 " 12916 400 x 180 x 150 72000.00 16.85

III. AVERAGE DENSITY (Kg/m3) 1100


NOTE
-- This test report refers only to the sample submitted for testing.
-- This test report is valid at the time of and under the conditions specified herein.
-- This test reportmay not be reproduced in part, without the permission of this laboratory.
-- Any correction invalidates this test report.
-- 1 Kg/cm2 = 0.0981 N/mm2.
PAGE 1 OF 1

: 2185 ( part 3)-2008

Compressive Strength

(N/mm2) (Kg/cm2)
0.30 3.04
0.26 2.68
0.23 2.39
0.27 2.70

Authorised Signatory