2 381333-414 A
Functional Test Installation Manual
Functional Test
The functional test consists of three checks: manual maintenance
operation, voltage checks, and electrical operation. h dl
Emergency
contacts
window
indicators
Counterclockwise DOWN Clockwise DOWN CLOSES
OPENS the contacts the contacts
Pull out shaft to open Pull out shaft to close
OPEN or Emergency source contacts Emergency source contacts
CLOSED (upper) (upper)
Push in shaft to open Normal Push in shaft to close
source contacts (lower) Normal source contacts
(lower)
381333-414 A 3
Installation Manual Functional Test
○ White square means the light is off. Shut down the engine-
generator, if applicable. The
* If necessary, adjust the voltage regulator on the Emergency Source Accepted
generator according to the manufacturer’s light should go off. Then put
recommendations. The transfer switch will respond 6
the starting control selector
only to the rated voltage specified on the transfer switch switch (on the generator set)
nameplate. in the automatic position.
Close enclosure door.
4 381333-414 A
Functional Test Installation Manual
7ACTS buttons
7ADTS light is
on when load is
disconnected
observe
these
lights
operate
this
switch Figure 8. 7ACTS controls & lights Figure 9. 7ADTS light
The Transfer Switch Connected To
Normal and Normal Source Accepted
lights should be on.
1
381333-414 A 5
Installation Manual Testing & Service
6 381333-414 A
Troubleshooting Installation Manual
Troubleshooting
Check in Numerical Sequence
Problem
1 Operation 2 Generator 3 Voltage
The engine-generator set does Wait for the Feature 2E Starting control must
not stop after load retransfer to time delay to time out (if be in the automatic -
the normal source. used). position.
7ACTS Conditions of Normal or Emergency Sources not suitable for closed transition
Failure to Synchronize light transfer. Recheck voltage and frequency of both sources. Press Alarm Reset
comes on. pushbutton.
7ACTS
CN and CE contacts are closed longer than setting in the Group 5 controller.
Extended Parallel Time light
Open the disconnected source circuit breaker, then call ASI for assistance.
comes on.
7ADTS Delayed transition transfer operation. If load is disconnected longer than the
Load Disconnect Active light setting in Group 5 controller (see User’s Guide 381333-126), then contact
comes on. ASCO Power Services, Inc. for assistance.
381333-414 A 7
Installation Manual Index
INDEX
A H R
ASCO Power Services Inc. harness, 2 rating label, 1
800-800-2726(ASCO) HELP 800-800-2726(ASCO) replacement parts, 6
customercare@ascopower.com customercare@ascopower.com
automatic operation, 5 S
auxiliary circuits, 2 I source acceptable lights, 4, 5
inphase transfer feature, 7 starting contacts, 2
B inspection, 6 starting control, 5, 7
battery, 7 installation, 2 starting problem, 7
stopping problem, 7
C L
cables, power, 2 lights, 4, 5, 7 T
connections, 2 line connections, 2 terminals, 2
controller load on emergency light, 4, 5 testing power conductors, 2
see User’s Guide 381333- load on normal light, 4, 5 time delays, 5, 7
126 lubrication, 6 transfer button, 5, 7
controller ground, 2 transfer problem, 7
controls, 5 M troubleshooting, 7
cooldown, generator, 5, 7 maintenance, 6
maintenance handle, 3, 6 V
D WARNING, 3, 6 voltage checks, 4, 7
DANGER statements, 1, 2, 4, 6 manual load transfer, 6
WARNING, 3, 6 W
E mounting, 2 WARNING statements, 1, 3, 5, 6
electrical operation, 5
emergency source accepted N
light, normal source accepted light, 4,
4, 5 5
engine starting contacts, 2
O
F operation, electrical, 5
foundation, 1
frequency, 4, 7 P
functional test, 3, 4, 5 phase rotation, 4
preventive maintenance, 6
G problem, 7
generator, 2, 4, 5, 7
ground, controller, 2
8 381333-414 A