You are on page 1of 12

4

. F q a uf, drza 62, u s i 201309 (3010)


o 1960 CENTRAL POWER RESEARCH INSTITUTE
IA Government of India Society. Ministry of Power)
REGIONAL TESTING LABORATORY
3.A. Institutional Area, Sector. 62, Noida 201309 (U.P.)
t/Phone 0120-2402823, 2402058, FR/Fax. 0120-2402824, $ Ha/E-mail: rtinoida@cpri.in, rtinoida@gmail.com

HulRIT/4REUEITEdá 2020-21/ 1423 o (Date): 13.07 2022


F To,
M/s Safe and Sure
Engineeringg
16/1/3. Safe and Sure House, Road
no.-7, 1DA, Nacharam,
Medchal, Malkanjgiri, Hyderabad. Telangana-500076.
fa
(Sub):4RIGUI YAJ9a (Test Report): CPRINOAHV22TO251 Dt. 12.07.2022

HETG/Dear sir,

Please find attached the following documents in


respect of the test(s) conducted on your sample on
30.06.2022 at our laboratory.

Any discrepancies in the test report must be brought to our notice in writing
within 45 days of the date of issue of this test repot for
effecting
corrections for which all the original coples of the test report must be returned.
necessary
Please note that request received beyond this date will not be
entertained

Please acknowledge receipt of the documents.


HUNaIK, Thanking you,

4agTu (Yours sincerely)


EnclI :As above

Unit-Head
PRI

TEST REPORT

RESEAR

AMGALO

oESTD 190

CENTRAL POWER RESEARCH INSTITUTE


(A Govt. of India Society)
Regional Testing Laboratory
3A, Institutional Area, Sector 62
Noida 201 309
CENTRAL POWER RESEARCH INSTITUTE

TEST REPORT

CPRI
Test Report Number : CPRINOAHV22T0251 Date: 12 July 2022

Name and Address of the Customer M/s Safe and Sure


Engineering
16/1/3, Safe and Sure House, Road no.-7, IDA, Nacharam,
Name and Address of the
Medchal, Malkanjgiri, Hyderabad, Telangana-500076.
:M/s Safe and Sure Engineering
Manufacturer
16/1/3, Safe and Sure House, Road no.-7, IDA, Nacharam,
Medchal, Malkanjgiri, Hyderabad, Telangana-500076.
Particulars of sample tested :415V, 4000Amps, LT Panel
Type Main Distribution Panel
Description of test sample R e l e r sheet z or 6
Serial Number SASE2223092
Number of samples tested
Date(s) of Test(s)
One
:30 June 2022
CPRI Sample code Number(s). NOAHV22S0240
Particulars of tests :Refer sheet 3 of 6
conducted
Test in
accordance with IS/IEC 61439.1: 2011&IS/IEC 61439-2: 2011
Standard/Specification
Sampling Plan None
Temp. rise limit on busbar & busbar joints Is to be 7OK
Customer's Requirement
Deviations if any : Nil

Name of the witnessing persons


Customers representative Nil
Other than customer's Nil
representatives

Test subcontracted with address of


the laboratory
Documents constituting this report (in words)
Number of Sheets SIX

Number of Oscillogram(s
Number of Graph(s) NIil

Number of Photograph(s) One


Nil
Number of Test Circuit Diagram(s) Three
Number of Drawing(s)

(sndeep Singh) (M.K.Jaiswal)


Head of Division
Test Engineer
Reviewed and Authorized by

Sheet 1 of 6
ULR-TC5223220HVLT0251F
Discipline: Electrical Testing
Line Equipments
Group: Transmission
& ACcessories
CENTRAL POWER RESEARCH INSTITUTE
TEST REPORT

OLSTD19

CPRI
Test Report Number: CPRINOAHV22T0251 Date: 12 July 2022

DESCRIPTION OF SAMPLE TESTED


(As assigned by the manufacturer)

Sample : LT Panel
Rated voltage(Volts) 415
Rated current{Amps) 4000
Frequency (HZ)
No of Phase 3Ph +N
Insulation Level 690Volts
Pollution Degree 3
Material Group lla
Rated short time current : 7OkArms for a second with initial peak of 154kApeak

(Sandeep Singh)
Test Engineer

ULR-TC5223220HVLT0251F Sheet 2 of 6
Discipline: Electrical Testing 3A
Group: Transmission Line Equipments
UPIndia
& Accessories
CENTRAL POWER RESEARCH INSTITUTE

TEST REPORT

CPRI
Test Report Number: CPRINOAHv22T0251 Date: 12 July 2022

SUMMARY OF TESTS CONDUCTED

Tests conducted 1). Veriftication of Temperature Rise

2). Verification Di-electric Property

3). Verification of Clearance & Creepage Distance


2 Rating for which tested 1). 4000Amps, 50Hz, 2). 1.89kVrms,3). As per standard

3 Schedule of tests

Tests Conducted Clause Numbers Sheet

Verfication of Temperature Rise10.10 ofIS/IEC 61439-1:2011 &IS/EC61439-2 2011 4 of 6


Verification of Di-electric Property_|10.9.2 of IS/EC 61439-1:2011 &IS/IEC 61439-2: 2011 5 of 6
Verification of Clearance & 1 10.4 of IS/EC 61439-1: 2011& IS/IEC 61439-2: 2011 5 of 6

Creepage Distances
4 Oscillogram Numbers NA
Graph Numbers NA
6 Photograph Numbers CPRINOAHV22T0251PO01
7 Test Circuit Diagram Numbers. NIL

Drawing Numbers As given bellow

Drawing Numbers
The manufacturer has guaranteed that the sample submitted for the test(s) has been manufactured in accordance
with the following drawings

Drawing Number
SI. NNO.
Sheet Number
01 of 03
Revision Number
1
SASE2223092 00
SASE2223092

SASE2223092
02of 03 00

03 of 03 00
It is verified that these drawings adequately represent the sample tested. Verification of this drawing by CPRI is
limited to
dimensional check only wherever possible.

(Saideep Singh)
Test Engineer

ULR-TC5223220HVLT0251F Sheet 3 of 6
Discipline: Electrical Testing
Transmission Line Equipments
Group
ACcessories le a02523
CENTRAL POWER RESEARCH INSTITUTE

TEST REPORT

CPRI

Test Report Number: CPRINOAHV22T0251 Date: 12 July 2022


TEST RESULTS
Test conducted veritication of Temperature RIse
Date of test 30.06.2022
Starting time (Hrs) : 09 30

Shut down time (Hrs) 14:30


Test current (A) 4000
Al. bus bar size 150x10sqmm x 4nos./phase connection
S12e of the conductor used for temporary
Frequency (HZ)
03
Pnase
ambient temperature at shut down 2. 1°C
Avg.
Arrangement of thermocouple locations: As per Drg.No: SASE2223092, sheet 02 of 03
Maximum Temperature lemperature
Thermocouples
Locations NumberS (C) Rise (K)
R1-Phase Incoming Terminal T01 b9.8
69.0
7 7
36.9
Y1-Phase Incoming
lerminal 102
B1-Phase Incoming erminal 3.0
R2-Phase Incoming Terminal T04 77.2 45.1
Y2-Phase Incoming lerminal TOS 61.6 29.5
B2-Phase IncomingTerminal TO6 50.4 18.3
54.0 21.9
R1-Phase Vertical Busbar T07
4.2
Y1-Phase Vertical Busbar
B1-Phase Vertical Busbar T09 b8.4 36.3
| 10 b6.8 34.
R2-Phase Vertical Busbar
2-Phase Vertical Busbar J11 55.0 22.9
B2-PhaseVertical Busbar 56.8 24.7
R1-Phase VBB+HBB
Joint . 22.0
Y1-Phase VBB+HBB Joint b8. 26.0
B1-Phase VBB+HBB Joint_ br.b
35.5
R2-Phase VBB+HBB Joint 16 6 68.5 36.4
Y2-Phase VBB+HBB Joint T 61.2 29.1

B2-Phase VBB+HBB Joint T 54.1 22.0


R1-Phase Horizontal Busbar Joint 54.2 22.1
Y1-Phase Horizontal Busbar Joint 59.0 26.9
62.8
B1-Phase Horizontal Busbar Joint 1Z1
65.0
30./
R2-Phase Horizontal Busbar Joint 32.9
Y2-Phase Horizontal Busbar Join 9.7
B2-Phase Horizontal Busbar Joint 53.6 21.5
Cont.nexxt

(Sandeep Singh)
Test Engineer
ULR-TC5223220HVLT0251F Sheet 4 of 6
A
Discipline: Electrical Testing
Group: Transmission Line Equipments
& ACcessories 0282
CENTRAL POWER RESEARCH INSTITUTE
TEST REPORT

CPRI

Test Report Number: CPRINOAHV22T0251 Date: 12 July 2022


TEST RESULTS

R1-Phase Outgoing Terminal 25 53.1 21.0


-Phase Outgoing Terminal 126 50.5 18.4
B1-Phase Outgoing Terminal 55.6 23.5
R2-Phase Outgoing Terminal I28 J.0 21.5
Y2-Phase Outgoinglerminal 129 54.6
B2-Phase Outgoing Terminal T30 57.0
Enclosure 131 35.0 2.9
ODservation he maximum temperature rise obtained was within the limits as per the requirements of the
Standardand customer. After temperature rise test, sample subjected to the HV test to check the effect of
emperature rise on adjacent parts of sample. The sample withstood 1.89 kVrms for 60 seconds.

2. Test conducted Verification


Test Details:
of Dielectric Properties
SINo Voltage applied to Connected to earth Remarks
Voltage applied
KV{(rms)
R YBN & Frame 1.89 Withstood for 60 sec.
RBN& Frame 1.89
Withstood for 60 sec
RYN& Frame 1.89 Withstood for 60 sec
RYB& Frame 1.89 Withstood for 60 secC
RYBN 1.89
Frame Withstood for 60 sec
3). Verification of Clearance & Creepage Distance:
Clearance & Creepage Distances were measured as per standard and the value found for clearance was
21mm and for creepage distance was 25mm whicn are within the limits as specified in standard for pollution
degree-3 and material group-lla.

Conclusion: The sample tested complies with the requirements of Clause 10.10, 10.9.2, & 10.4 of
IS/IEC 61439-1: 2011 &of IS/IEC 61439-2: 2011.

(Sandeep Singh)
Test Engineer

ULR-TC5223220HVLT0251F Sheet 5 of 6
Discipline: Electrical Testing
Group: Transmission Line Equipments
d UPT ndia
& Accessories 1oie C 120-2402823
CENTRAL PoWER RESEARCH INSTITUTE
TEST REPORT

CPRI
Test Report Number: CPRINOAHV22T0251 Date: 12 July 2022

NOTE

a) The Test results relate only to the sample(s) tested.

b) Publication o r reproduction of this Test Report /Test Certificate in any form other than by complete set of
the whole Test Report /Test Certificate and in the language written is not permitted without the written
consent of CPRI

c) Any Corrections/erasure invalidates the Test ReportTest Certificate

d) Any anomaly/discrepancy in the Test Report/ Test Certficate should be brought to the notice of CPRI
within 45 days from the dale of issue.

e)NABL has Accredited this laboratory as per ISO/IEC17025:2017, vide certificate no.TC-5223 for the tests
carfied out

ilac=MRA
TG-5223

(Sandeep Singh)
Test Engineer

-- -**************************************
--End of Test Report

Sheet 6 of6
ULR-TC5223220HVLTO251F
Discipline: Electrical Testing
Group Transmission Line Equipments

& Accessories 0232


CENTRAL POWER RESEARCH INSTITUTE

TEST REPORT

CPRI
Test Report Number: CPRINOAHV22T0251 Date: 12 July 2022

Photograph Number: CPRINOAHV22T0251 P01

(Sahdeep Shgh)
Test Engineer
009

**

0004

0St 0S 00
L-------------
" *

OT 0S

0St 0SP
0S1
1824

SHORTIN
LINK
THERMOCOUPLES
s8AN FOR N.
INCOMING: TI.T2.T3,T4,TS,T6
VERTICAL BB: T7,T8.T9,T10,TI1,TI2

VBB-HBB JOINT TI3.T14,TIS,TI6,TI7,T18

HBB JOINT: T19,T20,T21,T22.T23,T24


INCOMING
FOR OUTGOIING: T25,T26,T27,T28,T29.T30
pi ENCLOSURE: T3I

1 2 0 0

1800
INTERNAL MEW SIDE INIERNAL VEW VERIFICATION OF THIS DRAWING
WITHOUI DOOR BY CPRI IS LIMITED TO
DIMENSIONAL CHECK ONLY
WHEREVER POSSIBLE

T26
JsBAR T6N
1
T281
THIS DRAWING
TEST PERTAINS TO CPRI
REPORT NUMBER CPREN
Date: 1 V MHV
L
NTO Si
0 350L40
RATING: 400OA AISV
BOITOM 1NTERNAL VIEW
Test Enginèers
RTL, CPRI,
NOIDA
SAFE AND SURE ENGINEERING PROTECT 0004 T1OATUE Rz TESTING AT CPRI
wAOW CDO-AGR, iDOiND, TDAEso007 DIETAIL
SAL CT16 AC, 4000A Lr PANEL

REV.
PEV DATE RESION BGALE N.TS pOAIEOD TPRAAO T0408 303 |00.
19 1110

VERIFICATION OF THIS DRAWING


BY CPRI IS LIMITED TO
DIMENSIONAL CHECK ONLY
WHEREVER POSSIBLE

FINGER TYPE SUPPORT


FOR PH & N THIS
DRAWING PERTAINS TO CPRI
TEST REPORT NUMBER: ePRTA OnV
MATERIAL POLYMIDE Date: :V -T0 S
TOLERANCE = t1MM

MAKE POWERMAT

RATING:4o00A 415V Test Engineers


RILCPRI,
NOIDA

FROJECT 4004 TEMPERATURE RI TETIG AT CP


SAFE AND SURE ENGINEERING
NACWRA Do-NADRL OONND, TLwC-3o0078

EASIE222002 REV.

SCALE N.T.S AN OAE OD oA