Pressure Monitoring | Differential Air Pressure Switches

PASXX SERIES Easy cable lead-in Integrated cable


Monitor Air Ducts, Filters and Fans Case geometry allows easy cable strain relief
lead-in
Cable strain relief integrated in
PG11 (DIN 40430)

High accuracy Snap cover


High adjustment accuracy through User-friendly snap cover
individual laser etched scale

PASxx
Stable switching
points
PASxx differential air flow switches are intended for use in air handling Long-term stability of switching
systems for the monitoring of air ducts, filters and fans. points through trapezoidal bead
The enclosure is plastic with a rating of IP54. A set-point adjustment is diaphragm
provided under the clip-on clear plastic cover.
Supplied complete with mounting adaptor ring, two straight duct APPLICATIONS
probes and a 6-foot length of clear tubing. •  High pressure monitoring •  Filter monitoring

SPECIFICATIONS •  Vacuum pressure monitoring •  Fan monitoring

Medium Air and neutral gases


Pressure range See Ordering Information table
Set-point scale Inches WC
Tolerable overload on one side 20 in. WC at -22 to +185 °F Tests/admissions EU Conformity, Electromagnetic
Repeatability PAS01 ±2.5 (0.01 in. WC) Compatibility:
CE1 conformity according to
PAS02 ±5 (0.02 in. WC) EN 60730-2-6:2008
PAS03 ±5 (0.02 in. WC) Low Voltage Directive: 2014/35/EU
Gas Appliance Directive: 2009/142/EC
PAS04 ±5 (0.02 in. WC) Pressure Sensing Devices for Gas Burners
Switching load Resistive load 5 A at 250 Vac and Gas Burning Appliances: EN 1854:2010
4 A at 30 Vdc EU Directive on RoHS: 2011/65/EU
Inductive 0.8 A at 250 Vac WARRANTY
0.7 A at 30 Vdc Limited Warranty 5 years
Materials in contact with the Case: PC 10% GF AGENCY APPROVALS
medium Cover: PC
Diaphragm: Silicone LSR tempered 200 °C,
free of gas emissions
Operating Medium/ -22 to +185 °F (-30 to +85 °C)
temperature ambient
Storage -40 to +185 °F (-40 to +85 °C)
Service life Mechanical > 106 = 1,000,000 switching
cycles
Electrical connection Screw terminals
Cable gland type PG11 (DIN 40430)
complete with cable strain relief
Switch contact type SPDT (change-over)
Protection Without IP00
standard cover
With cover IP54
Pressure connections Pipe Ø 6.2 mm

800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | veris.com HQ0006606.E 0321


Pressure Monitoring | PASxx Series

DIMENSIONAL DRAWING INSTALLATION


91.4 (3.60) Mounting:
22 (0.87) 51 (2.01)
6 (0.24) •  Vertical with pressure
connections facing downward
6.2 (0.24) 3.4 (0.13) (factory recommended)

78.5 (3.09)
52 (2.05)

P2 16 (0.63)
•  Horizontal with cover facing

60 (2.36)
44.4 (1.75)

downward
25 (0.98)

18 (0.71)
P1
6.5 (0.26) 8 (0.32)
(switching setpoint 0.4” WC
9.1 (0.36)
3.4 (0.13) lower than scale)
16 (0.63) •  Horizontal with cover facing
upward
(switching setpoint 0.4” WC
2.2 (0.09) higher than scale)
*

WIRING
49.7

2
(1.96

*Hole for PT screws KA25


)

)
1
0.18
4.5 (

3
80.8 (3.18)

4.
5

53.7 (2.11)
88 (3.46)

(0

56 (2.20)
65 (2.56)
.1
8) 1 = COM (Common)
2 = NC Contact (Normally Closed)
15.5º

3 = NO Contact (Normally Open)

)
(2.11
53.7

4 x hole PT - screw d1 = 3.0 mm (0.12 in.)

FUNCTIONALITY
The pressure switch has two separate pressure chambers, each with
its own connection. The switch operates when the setpoint is either
exceeded or not reached.
Vacuum Monitoring
Connect the pressure switch via P2. Do not connect P1. Leave P1 open.
Make sure that debris cannot get into P1.
High Pressure Monitoring
Connect the pressure switch via Pa. Do not Connect P2. Leave P2 open.
Make sure that debris cannot get into P2.
Filter Monitoring
Connect P1 before the filter and P2 after it.
Fan Monitoring
Connect P1 after the fan (in blowing direction) and P2 before the fan.

ORDERING INFORMATION
PART NUMBER DESCRIPTION PRESSURE RANGE ACCESSORIES
PAS01 0.08 to 1.2 in. WC (20 to 300 Pa) Static-04 Pick-up - 4” Duct Static
PAS02 Differential Air 0.2 to 2.0 in. WC (50 to 500 Pa) Pickup Probe (AA06)
Pressure Switch AA06 AA07
PAS03 0.4 to 4.0 in. WC (100 to 1000 Pa) Static-08 Pick up - 8” Duct Static
PAS04 2.0 to 8.0 in. WC (500 to 2000 Pa) Pickup Probe) (AA07)

HQ0006606.E 0321 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | veris.com