TRANSFORMER
Nanda Hucharaddi1, Mohsin Mulla2, Swapnil Ghatage3
1
Student,EEE, 2Asst. Professor, EEE, 3Student, EEE, HIT Nidasoshi.
ISSN (PRINT):2394-3408,(ONLINE):2394-3416,VOLUME-4,ISSUE-2,2017
24
INTERNATIONAL JOURNAL OF ADVANCED COMPUTING AND ELECTRONICS TECHNOLOGY (IJACET)
ISSN (PRINT):2394-3408,(ONLINE):2394-3416,VOLUME-4,ISSUE-2,2017
25
INTERNATIONAL JOURNAL OF ADVANCED COMPUTING AND ELECTRONICS TECHNOLOGY (IJACET)
should be smaller; for smaller cross sectional (3). Stacking factor (Ks) is defined by the ratio
area the chosen flux density is high and between the cross-sectional area of
therefore, the core loss increases. If large rating ferromagnetic material and total cross-sectional
power transformers are designed for low flux area of the core. With sheets of CRGO steel it is
density then cross sectional area of core becomes 0.9 or higher. For amorphous alloy it is in
large; for larger cross-sectional area of a core, between 0.8 and 0.9 (Bendito et al 1999). With
costs of the core and winding are higher, reduced stacking factor the gross cross-sectional
therefore the cost of the transformer becomes area of core becomes larger, resulting overall
higher (Dasgupta 2011, Sawhney 2006, Say size to be big. The disadvantage with bigger size
M.G. 1977). Therefore, amorphous alloy is not a is the higher cost, but the advantage is better
suitable choice for large rating power cooling.
transformers, if economy is an issue. Amorphous (4). Cost of a transformer is also assessed as
core transformers are energy efficient Total owning cost (TOC) (Amoiralis 2009).
transformers with increased costs (Kennedy B TOC is sum of initial cost of a transformer and
1998); the cost of amorphous core transformers cost of energy losses during operation. TOC =
is 20 to 30 percent higher than that of (Purchase Price) + (A x Core Loss) + (B x
conventional CRGO core transformers (Puneet Winding Loss). where, The core loss factor (A)
K Singh 2010). Cost of a transformer depends on and the winding loss factor (B) can be calculated.
cost of core, cost of winding and manufacturing For low TOC, the losses in a transformer should
cost. Costs of core and winding are affected by be low. As the time passes, the TOC increases.
shape and size of cross-sectional area of core. A Amorphous metal cores are particularly valuable
core having square or rectangular crosssection is for transformer users with relatively high “A”
called 1-step core. For square or rectangular factors, because the lower core loss of AMDTs
cross-section of a core, cost of core is lower but results in substantially reduced cost of
the cost of winding is higher, than that of circular ownership, with only a moderate increase in
multi-stepped cross-section of core. Selection of purchase price.
number of steps in a core depends on KVA rating (5). For medium and large rating transformers
of transformer. As the rating of transformer electromagnetic forces on the windings must also
increases, the number of steps in a core increases. be considered as they are very high (Martin J.
For more number of steps, the diameter of Heathcote 1988). Radial electromagnetic forces
circumscribing circle reduces for an iron area of on the winding are proportional to square of the
the core, so cost of copper winding reduces, and current (Fr α I2). Under short circuit condition
copper losses are also reduced. However; with the current in a transformer may be 20 times of
the increase in number of steps, the assembly rated current, so the electromagnetic force may
cost of the core increases. Therefore for low be 400 times higher than that of normal
rating transformers the square section of the core condition. For square section of core, the shape
is economical and for medium and large rating of the coil is also square, for which radial
transformers multi-stepped CRGO core is electromagnetic forces are not uniform around
economical. On the other hand, for the the periphery of the coil. Non uniform radial
amorphouscore transformers of medium and electromagnetic forces may distort the shape of a
large ratings, the square or rectangular section of coil in a transformer. Therefore square or
core is adopted by manufacturers (Lee Ji-Kwang rectangular section of core is not advisable for
1999, Nicols DeCristofaro 1998, Schulz R.N. medium and large rating transformers. For a
1998), the reason is the higher cost of multi-stepped core, the shape of the coil is
amorphous-core assembly, as compared to circular, and the radial electromagnetic forces
CRGO-core assembly. are uniform around periphery of the coil.
ISSN (PRINT):2394-3408,(ONLINE):2394-3416,VOLUME-4,ISSUE-2,2017
26
INTERNATIONAL JOURNAL OF ADVANCED COMPUTING AND ELECTRONICS TECHNOLOGY (IJACET)
(6). Low voltage and high voltage windings are total number of Mitred joints in core assembly is
accommodated in the window area (Aw). The six. However, in Ccore assembly of a 3-phase 3-
ratio between height (Hw) and width of the limb transformer, nonmitred joints are used, and
window (Ww) is chosen 2 or above; for low the total number of joints is only three.
leakage reactance this ratio should be high Therefore, the magnetising force required for C-
(Dasgupta 2011,Sawhney 2006, Say M.G. core assembly is less as compared to
1977). The window space factor (Kw) is defined conventional CRGO core assembly, which
by the ratio between the conductor cross section reduces the magnetising current.
area and the window area. Insulation and (9). When a transformer is switched in, the core
clearance reduce the available area for actual is driven into saturation; therefore current inrush
conductor cross section to kw.Aw. Window comes in picture (Kulkarni S.V., Khaparde S.A.
design considerations for conventional CRGO 2005). Because of low saturation limit of
core transformers and amorphous core amorphous alloy, the magnitude of inrush
transformers are same. current is higher in case of amorphous core
(7). In case of 3-phase 3-limb transformer transformers compared to conventional CRGO
magnetic asymmetry exists, because length of core transformers. The inrush current is not
magnetic path are unequal for three fluxes (ΦA , harmful for a transformer but may result in the
ΦB , and ΦC ); here flux ΦB is produced by the inadvertent operation of overload relays.
winding of central limb, and fluxes ΦA and ΦC (10).In transformers, because of increase in
are for side limbs (KulkarniS.V., Khaparde S.A. supply voltage, flux density in core increases
2005). The length of magnetic path followed by beyond the designed value, which may result
the flux ΦB is less than the length of magnetic saturation of core. Therefore, the problem of
path followed by fluxes ΦA and ΦC.; therefore, third harmonic comes inpicture because of
the reluctance offered by the magnetic path saturation of core. To reduce this problem, a
for flux ΦB is less than that of reluctances for ΦA transformer should be designed for a low value
and ΦC. It causes difference in magnetising of flux density, which increases the cost of a
currents of three phases, which results zero transformer. In amorphous core transformers the
sequence current. In case of amorphous core problem of third harmonic is more because of
transformers, the reluctance offered by magnetic low saturation limit. The problem of third
path is much less (about 1/4 of reluctance offered harmonic may be eliminated by adopting zig-zag
in conventional CRGO core transformer), which connection in place of star connection.
reduces the magnetic asymmetry, resulting (11). Magnetostriction is less in amorphous
reduction in zero sequence current. alloy, compared to CRGO steel (Bendito et al
(8). For a convention CRGO core transformers, 1999). Therefore, amorphous core transformers
the magnetising current is 1% to 2% of rated have low noise level, so they are friendlier to
current. The magnetising current drawn by a environment .
transformer depends on two factors; one is the (12) Average life of an amorphous core
nature of B-H curve, and other is number of transformer is 30 years; however it is 25 years in
joints in the core assembly. Comparing between case of conventional transformers. Therefore, the
B-H characterics of amorphous alloy and average life of amorphous core transformer is
conventional CRGO steel, magnetizing current more than the average life of conventional
for amorphous alloy is about one third than that transformer.
of CRGO steel (BHEL 2009). During
construction of conventional CRGO core
assembly for a transformer, Mitred joints are
used in corners. For 3-phase 3-limb transformer
ISSN (PRINT):2394-3408,(ONLINE):2394-3416,VOLUME-4,ISSUE-2,2017
27
INTERNATIONAL JOURNAL OF ADVANCED COMPUTING AND ELECTRONICS TECHNOLOGY (IJACET)
4. Conclusions References
Compared to conventional transformers, [1]Amoiralis, Marina and Antonios, 2009:
amorphous core transformers have- low core Transformer design and optimization: A
losses, low magnetising current, less zero literature survey, IEEE trans. on Power delivery
sequence current, less noise, higher inrush vol. 24 No. 4, pp. 1999-2024.
current, more harmonic problem, bigger size, [2]Bendito Antonio, Misael Elias and Claudio
higher initial cost, higher efficiency, and longer Shyinti Kiminami, 1999: Single phase 1-KVA
life. Advantages with amorphous core Amorphous core Transformer, IEEE trans. on
transformer are more, compared to magnetics, vol- 35,No.4, July. BHEL, 2009:
disadvantages. At present, initial cost of [3]Transformers Tata Mc-Graw Hill publication,
amorphous core transformer is comparatively India.
higher; it becomes economical after a certain [4]Boyd E.L. and Borst J.D. 1984: Design
period of time. In future, as the manufacturing concepts for an amorphous metal distribution
will increase, the initial cost will be reduced transformer, IEEE Trans. Power Apparatus and
because of reduction in manufacturing cost. Systems, vol.103,no.11,pp.3365-3372.
Amorphous core transformers are energy [5]Dasgupta I. 2011: Design of transformers,
efficient transformers; If all conventional Tata McGraw Hill publishers.
transformers are replaced by amorphous core [6]Kennedy B. 1998: Energy Efficient
transformers, a considerable amount of energy Transformers, McGraw-Hill.
will be saved for a nation. [7]Kulkarni S.V.,Khaparde S.A. 2005:
Transformer Engineering: Design and Practice,
Marcel Dekker, Inc. New York, USA
ISSN (PRINT):2394-3408,(ONLINE):2394-3416,VOLUME-4,ISSUE-2,2017
28