Professional Documents
Culture Documents
Why would anyone want in-rack sprinklers? The development of Early Suppression
Fast Response (ESFR) sprinklers by Factory Mutual Research Corporation, now FM
Global, more than 30 years ago1,2,3 revolutionized storage fire protection. Various
ESFR and Control Mode ceiling level sprinklers introduced since then have led to
ceiling-only protection dominating the storage sprinkler market. But as storage
buildings have evolved, the limitations of ceiling-only sprinkler protection have
become apparent.
Currently, NFPA 13 limits K14.0 ESFR sprinklers to ceiling heights of 35 ft. when
protecting rack storage, unless in-rack sprinklers are provided. Ceiling-only design
criteria to protect rack storage under ceilings up to 45 ft. tall are available with larger
orifice K22.4 and K25.2 ESFR sprinklers. Specific application criteria are also
available for certain ESFR sprinklers under ceiling heights up to 48 ft. Those are the
current limits of ceiling-only storage sprinkler protection. Eventually the challenges
associated with activating and delivering water to fires under taller ceiling heights
catches up to the ceiling sprinkler.
Particularly in areas of the world where fresh water is not plentiful, the use of large
amounts of potable water for inspection, testing, and maintenance (ITM) of fire
protection systems is increasingly scrutinized. Sprinkler systems with high water
demands and design pressures can result in increased pipe sizes and the need for a fire
pump. Large pipes, which must be drained for service, and the use of a fire pump,
which requires periodic testing, both typically increase the quantity of water needed
for ITM. Thus, limiting the demand of a sprinkler system typically limits the amount
of water needed for ITM.
For example, NFPA 13 limits storage of rubber tires on racks to 35 ft. of storage under
a 40 ft. ceiling with ESFR sprinkler protection at the ceiling. The criterion requires
more than 2,600 gpm of basic sprinkler water demand from K25.2 ESFR sprinklers.
A new design criterion, based on a project conducted by the Fire Protection Research
Foundation, is designed to protect Exposed Expanded Group A plastics stored in racks
up to 35 ft. tall under a 40 ft. ceiling. The criterion uses approximately 2,350 gpm of
basic sprinkler water demand from K25.2 ESFR sprinklers and requires the
installation of vertical barriers in the racks to assist the ceiling sprinkler system. This
new criterion is currently proposed to be included in the next edition of NFPA 13.
NFPA 30B provides a clear illustration of the enhanced protection that in-rack
sprinklers can provide. Rack storage of the most hazardous category of aerosols,
Uncartoned Level 3, requires in-rack sprinklers. Rack storage of Cartoned Level 2 and
Level 3 aerosols are limited to maximum storage heights of 20 ft. and 15 ft.,
respectively, with ceiling-only sprinkler protection, while unlimited storage heights
are permitted where in-rack sprinklers are provided.
Thus, while ceiling-only criteria are available for storage of Cartoned Unexpanded
Group A plastics under ceilings up to 48 ft. tall, other commodities have lower ceiling
height limits for ceiling-only protection. Even when ceiling-only protection options
are available, the water demand or other required features may make the installation
of in-rack sprinklers preferable.
WHY IN-RACKS
Location matters. Being located closer to a rack storage fire gives in-rack sprinklers
an advantage over ceiling sprinklers in terms of both activation and delivering water
to the burning commodity. Thus, in-rack sprinklers have the potential to activate when
a fire is smaller and requires less water to control.
A key feature of in-rack sprinklers is that they do not depend on the configuration of
the building enclosure. The tallest current listing for an ESFR sprinkler without in-
rack sprinklers is 48 ft. There are typically no limits on building height with in-rack
sprinklers.
Two of the biggest challenges with ESFR sprinklers do not affect in-rack sprinklers:
(1) sloped ceilings and (2) complicated ESFR obstruction rules. These issues have
been identified by the Fire Protection Research Foundation 6,7 and in Fire Protection
Engineering8 as requiring further research to develop improved guidance for ceiling
sprinklers. These are, however, not issues for in-rack sprinklers.
The ceiling configuration does not impact in-rack sprinklers. For years, sprinkler
designers have been challenged with roofs having slopes greater than 2 in 12, where
ESFR sprinklers are not permitted. A sloped ceiling changes the dynamics of the fire
gases traveling along the ceiling, impacting both the operation of ceiling sprinklers
and their spray pattern. In-rack sprinklers are not impacted by ceiling slope.
NFPA 13’s obstruction rules for ceiling sprinklers, including more complicated rules
for ESFR sprinklers, do not apply to in-rack sprinklers. In-rack sprinklers are intended
specifically for areas that have obstructions. While there are specific rules for the
placement of in-rack sprinklers, such as having the deflector at or below the load
beam, the rules are typically simpler than for ceiling sprinklers.
The new NFPA 13 design criterion uses K8.0 or K11.2 quick-response sprinklers in
the rack. The in-rack sprinklers are located directly below a horizontal barrier
constructed of nominal 3/8 in. plywood or 22 gauge metal. In-rack sprinklers and
horizontal barriers are required to be located at maximum intervals of 12 ft. vertically
in the rack. If solid shelving is provided, the in-rack sprinklers must be provided
below every level of solid shelving.
The in-rack sprinklers are located between each pallet load in a single-row rack. In
double-row racks, the in-rack sprinklers are located between each pallet load at the
face and between every other pallet load in the longitudinal flue. Multiple-row racks
require in-rack sprinklers between each pallet load at the face, and alternating rows of
in-rack sprinklers between every other pallet load and between every pallet load
provided within the rack.
The new in-rack protection scheme can be a useful option for existing storage
buildings where the ceiling protection is not adequate. The new in-rack system has a
basic sprinkler water demand of less than 500 gpm. Because the in-rack system
demand is separate from the ceiling sprinkler demand, the in-rack sprinkler system
can be used in many existing storage buildings where the ceiling sprinkler system is
not adequate, often without upgrading the water supply infrastructure.
The protection scheme can be used throughout a storage area, but it can also be used
where a higher hazard commodity is stored only in designated racks. In that
configuration, the in-rack sprinkler system and horizontal barriers must be extended
one pallet position beyond the higher hazard commodity or a vertical barrier must be
provided between the lower and higher hazard commodity.
While providing a potentially useful sprinkler protection option, the new in-rack
design criterion has at least two significant drawbacks:
The installation can be costly due to the number of in-rack sprinklers and the
amount of piping required; and
For double- and multiple-row racks, in-rack sprinklers are located between
each pallet load at the face of the aisle where they can be vulnerable to damage.
These two concerns are common with conventional in-rack sprinkler technology. The
next generation of in-rack sprinklers offers substantial improvements in both areas.
The extended coverage in-rack sprinkler system uses a sprinkler with a nominal k-
factor of 25.2 gpm/ psi1/2coupled with a pendent deflector that is designed to spray
within the relatively shallow space available in a rack. The sprinklers are designed to
allow an increased spacing, both horizontally and vertically, compared with
conventional in-rack sprinklers.
Conventional in-rack sprinklers are designed to surround a fire and typically have a
maximum k-factor of 11.2 gpm/psi1/2. This results in conventional in-rack sprinklers
being closely spaced, typically approximately 5 ft. or 10 ft. apart horizontally. In
addition, the relatively small k-factor of conventional in-rack sprinklers results in
droplet distributions, which are not ideal for penetrating through a fire plume over a
significant height. This limits the distance between levels of conventional in-rack
sprinklers.
A series of full-scale fire tests has been conducted to investigate the extended
coverage in-rack sprinkler system. Tests have included the following commodities:
Protection criteria are not currently provided in NFPA 13 for Exposed Expanded
Group A plastics stored in racks. Two criteria discussed above are likely to be
included in the next edition of NFPA 13, which would protect Exposed Expanded
Group A plastics as follows for a double-row rack:
The extended coverage in-rack sprinkler configuration eliminates the face sprinklers
that are required for the conventional system and significantly reduces the potential
for damage to the in-rack sprinkler system. The spray pattern from the extended
coverage sprinkler located in the longitudinal flue is adequate to wet not only the face
of the commodity at the aisle, but also to spray water into the aisle to protect adjacent
racks of commodity.
The first fire test was ignited at the base of the commodity at the aisle, which was the
most remote location between the in-rack sprinklers. Test criteria were as follows
based on requirements in UL 199 for storage sprinklers: 9
The results of the first fire test demonstrated the performance of the extended
coverage in-rack sprinklers. The fire was contained within the two initial rack bays
that were ignited. Two in-rack sprinklers activated and, in part because the fire was
ignited at the face of the aisle, one ceiling sprinkler activated. No ignition of the target
array occurred and the maximum one-minute average steel temperature above the fire
was limited to 102°F. The success of the first test showed the performance and
potential advantages of extended coverage in-rack sprinklers.
Further fire testing has investigated not only additional commodities, but additional
storage configurations. For example, protection for 15 1/2 ft. deep multiple-row racks
of Exposed Expanded Group A plastics was investigated where in-rack sprinklers
were provided in the longitudinal flue and in the rack uprights nominally 18 in. from
the face. The sprinklers were able to contain the spread of the fire within the main
storage array through the activation of five in-rack sprinklers at an operating pressure
of 30 psi. Further fire testing is planned for additional commodities and storage
configurations.
Lower cost by reducing the amount of piping and number of sprinklers needed.
Less piping and fewer sprinklers to coordinate with racking.
Less piping and fewer sprinklers to interfere with loading and unloading of
commodity.
The fire sprinkler industry must continue to evolve to address new storage fire
challenges. While many storage and distribution buildings could be protected with
ceiling-only sprinkler protection, an increase in the height of these buildings has led to
renewed research into more efficient in-rack sprinkler systems.
References:
Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers