Assembly a) Center line/ Parallel/ Gap/ Rotated b) Existing bolt condition (corroded, wear, etc.) c) Existing Gasket Condition d) Damage during opening (scratch, dent. Etc.) Internal Condition a) Sealing Surface Roughness and any corrosion b) Raised-face Thickness (min 0.8 mm – ASME PCC 2) c) Inside Spool condition opportune (Pipe/ Elbow/ Weld) Inspection Tools Camera, Pit Gauge, and Caliper (equipped with Dye Penetrant Test) Repair Recommendation Bolt/Gasket Replacement, Flange Replacement, Flange Buildup & Re-facing
Internal Inspection We are interested on:
a) Thickness of Raised face (t) = ….. mm b) Width of Seating Surface (w) = ….. mm c) Projected radial distance of damage (rd) = …. mm d) Defect depth (td) = …… mm (max)