Table of Contents
Page
©2017-2020 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
8-34 Protection for Automatic Storage
Page 2 FM Global Property Loss Prevention Data Sheets
List of Figures
Fig. 1. Summarized guidance on how to navigate Data Sheet 8-34 ............................................................. 7
Fig. 2. Example of mini-load ASRS storage arrangement ........................................................................... 13
Fig. 3. Example of a mini-load ASRS having angle irons that support the trays and/or containers ........... 14
Fig. 4. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths up to
3 ft (0.9 m) ......................................................................................................................................... 52
Fig. 5. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over
3 ft (0.9 m) and up to 6 ft (1.8 m) ..................................................................................................... 53
Fig. 6. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over
3 ft (0.9 m) and up to 6 ft (1.8 m) .................................................................................................... 54
Fig. 7. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over
6 ft (1.8 m) ........................................................................................................................................ 54
Fig. 8. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over
6 ft (1.8 m) ......................................................................................................................................... 55
Fig. 9. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths up to
3 ft (0.9 m) ......................................................................................................................................... 56
Fig. 10. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over
3 ft (0.9 m) and up to 6 ft (1.8 m) ................................................................................................... 56
Fig. 11. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over
3 ft (0.9 m) and up to 6 ft (1.8 m) .................................................................................................. 57
Fig. 12. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over
6 ft (1.8 m) ...................................................................................................................................... 58
Fig. 13. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over
6 ft (1.8 m) ....................................................................................................................................... 59
Fig. 14. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths up to
3 ft (0.9 m) ....................................................................................................................................... 59
Fig. 15. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over
3 ft (0.9 m) and up to 6 ft (1.8 m) ................................................................................................... 60
Fig. 16. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over
3 ft (0.9 m) and up to 6 ft (1.8 m) ................................................................................................... 61
Fig. 17. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over
6 ft (1.8 m) ....................................................................................................................................... 61
Fig. 18. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over
6 ft (1.8 m) ....................................................................................................................................... 62
Fig. 19. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths up to
3 ft (0.9 m) ....................................................................................................................................... 63
Fig. 20. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over
3 ft (0.9 m) and up to 6 ft (1.8 m) ................................................................................................... 63
Fig. 21. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over
3 ft (0.9 m) and up to 6 ft (1.8 m) .................................................................................................. 64
Fig. 22. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over
6 ft (1.8 m) ...................................................................................................................................... 65
Fig. 23. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over
6 ft (1.8 m) ....................................................................................................................................... 65
Fig. 24. Examples of Potential Robot Holding Areas .................................................................................. 67
Fig. 25. Example of a TL-ASRS arrangement showing maximum 100 ft (30 m) depth in one direction ... 74
Fig. 26. TL-ASRS arrangements where the maximum ceiling height is 25 ft (7.6 m) ................................ 75
Fig. 27. Example of solid-floored elevated mezzanine levels when span of TL-ASRS exceeds 100 ft
(30 m) in each direction ................................................................................................................... 75
Fig. 28. Example showing the use of vertical barriers within a TL-ASRS arrangement ............................ 76
Fig. 29. Example of TL-ASRS arrangement protected by fixed-in-place monitor nozzles .......................... 77
Fig. 30. Establishing storage subdivisions within TL-ASRS ........................................................................ 80
Fig. 31. Positioning of void spaces under ceiling sprinklers ........................................................................ 80
Fig. 32. Example of a TL-ASRS arrangement showing maximum 100 ft (30 m) depth in one direction .... 82
Fig. 33. Example of solid-floored elevated mezzanine levels when span of TL-ASRS exceeds 100 ft
(30 m) in each direction ................................................................................................................... 83
Fig. 34. Example of a vertically enclosed ASRS storage unit ...................................................................... 84
Fig. 35. Example of open-top plastic containers in mini-load ASRS storage arrangementi ....................... 87
Fig. 36. Example of an empty mini-load ASRS storage arrangement where rack uprights are about
2 to 3 in. (50 to 75 mm) wide and about 2 ft (0.6 m) horizontally apart ....................................... 88
Fig. 37. Example of rack-supported ASRS storage arrangement ............................................................... 89
Fig. 38. Example of motorized automated picking robot in a mini-load ASRS storage arrangement
with open-top unexpanded plastic containers ................................................................................ 89
Fig. A-1. ASRS rack row depth .................................................................................................................... 92
List of Tables
Table 1. Spacing of Ceiling-Level Storage Sprinklers Under Unobstructed Ceiling Construction ............... 10
Table 2. Ceiling-Level Protection Guidelines for Mini-Load ASRS Storage Arrangements Using
Open-Top Noncombustible Solid-Walled Containers .................................................................... 18
Table 3. In-Rack Sprinkler Discharge Rates for Open-Top Noncombustible Solid-Walled
Containers in Mini-Load ASRS Storage Arrangements .................................................................. 19
Table 4. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers for Mini-Load
ASRS Storage Arrangements Using Open-Top Noncombustible Solid-Walled Containers .......... 20
Table 6. Ceiling-Level Protection Guidelines for Mini-Load ASRS Storage Arrangements with (1)
Closed-Top Cellulosic Containers Having a Commodity Classification of CEP, or (2) UEP
Materials Stored on Trays ............................................................................................................... 23
Table 7. Ceiling-Level Sprinkler System Hose Demand and Water Supply Duration .................................. 24
Table 8. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Storage on Trays
or in Closed-Top Cellulosic Containers ........................................................................................... 25
Table 9. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on a Wet
System for Mini-Load ASRS Storage Arrangements with (1) Closed-Top Cellulosic Containers
Having Commodity Classification up to CUP, or (2) Materials with Commodity Classification
up to UUP Stored on Trays ............................................................................................................ 27
Table 10. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on
a Wet System for Mini-Load ASRS Storage Arrangements with (1) Closed-Top CEP
Containers, or (2) UEP Materials Stored on Trays ....................................................................... 28
Table 11. Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration ..................... 29
Table 12. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Storage on Trays
or in Closed-Top Cellulosic Containers ......................................................................................... 31
Table 12. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Storage on Trays
or in Closed-Top Cellulosic Containers (continued) ..................................................................... 32
Table 13. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on a
Dry-Pipe Sprinkler System for Mini-Load ASRS Storage Arrangements with (1)
Closed-Top Cellulosic Containers Having Commodity Classification up to CUP, or (2) Materials
with Commodity Classification up to UUP Stored on Trays ......................................................... 33
Table 14. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on a
Dry-Pipe System for Mini-Load ASRS Storage Arrangements with (1) Closed-Top
Cellulosic Containers Having a CEP Commodity Classification, or (2) UEP Materials
Stored on Trays ............................................................................................................................ 33
Table 15. Combined Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration ... 34
Table 16. Ceiling-Level Protection Guidelines for Mini-Load ASRS Storage Arrangements
Using (1) Noncombustible Containers with Non-Solid Walls, (2) Closed-Top Unexpanded
Plastic Containers, and (3) Adequately Vented Open-Top Unexpanded Plastic
Containers; Maximum Storage Height of 10 ft (3.0 m) ................................................................ 35
Table 17. Ceiling-Level Sprinkler System Hose Demand and Water Supply Duration ................................ 36
Table 18. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with
Noncombustible Containers with Non-Solid Walls, Closed-Top Unexpanded Plastic Containers,
and Adequately Vented Open-Top Unexpanded Plastic Containers ............................................ 37
Table 19. Ceiling-Level Protection Guidelines, in Combination with In-Rack Sprinklers, for Mini-Load
ASRS Storage Arrangements with (1) Noncombustible Containers with Non-Solid Walls,
(2) Closed-Top Unexpanded Plastic Containers, and (3) Adequately Vented Open-Top
Unexpanded Plastic Containers on a Wet-Pipe Sprinkler System ............................................... 38
Table 20. Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration ..................... 39
Table 21. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements Using
Noncombustible Containers with Non-Solid Walls, Closed-Top Unexpanded Plastic Containers,
and Adequately Vented Open-Top Unexpanded Plastic Containers ............................................ 40
Table 22. Ceiling-Level Protection Guidelines, in Combination with In-Rack Sprinklers, Installed on a
Dry-Pipe Sprinkler Systems for Mini-Load ASRS Storage Arrangements Using (1)
Noncombustible Containers with Non-Solid Walls, (2) Closed-Top Unexpanded Plastic
Containers, and (3) Adequately Vented Open-Top Unexpanded Plastic Containers ................... 41
Table 23. Combined Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration ... 41
Table 24. Ceiling-Level Protection Guidelines for Mini-Load ASRS Storage Arrangements Using
Non-Adequately Vented Open-Top Cellulosic and Unexpanded Plastic Containers;
Maximum Storage Height of 10 ft (3.0 m) .................................................................................... 43
Table 25. Ceiling-Level Protection Guidelines for Mini-Load ASRS Storage Arrangements Using
Adequately Vented Open-Top Cellulosic Containers; Maximum Storage Height of 10 ft (3.0 m) . 43
Table 26. Ceiling-Level Sprinkler System Hose Demand and Water Supply Duration ................................ 44
Table 27. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Non-Adequately
Vented Cellulosic and Unexpanded Plastic Open-Top Containers and Adequately Vented
Open-Top Cellulosic Containers ................................................................................................... 45
Table 28. Ceiling-Level Protection Guidelines, in Combination with In-Rack Sprinklers, Installed on a
Wet-Pipe System for Mini-Load ASRS Storage Arrangements with Non-Adequately
Vented Cellulosic and Unexpanded Plastic Open-Top Containers .............................................. 47
Table 29. Ceiling-Level Protection Guidelines, in Combination with In-Rack Sprinklers, for Mini-Load
ASRS Storage Arrangements with Adequately Vented Open-Top Cellulosic Containers
on a Wet-Pipe Sprinkler System ................................................................................................... 48
Table 30. Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration ..................... 49
Table 31. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Non-Adequately
Vented Cellulosic and Unexpanded Plastic Open-Top Containers and Adequately Vented
Open-Top Cellulosic Containers ................................................................................................... 50
Table 32. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on a
Dry-Pipe Sprinkler Systems for Mini-Load ASRS Storage Arrangements with
Non-Adequately Vented Cellulosic and Unexpanded Plastic Open-Top Containers ................... 51
Table 33. Ceiling-Level Protection Guidelines, in Combination with In-Rack Sprinklers, Installed on a
Dry-Pipe Sprinkler Systems for Mini-Load ASRS Storage Arrangements Using Adequately
Vented Open-Top Cellulosic Containers ....................................................................................... 51
Table 34. Combined Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration ... 52
Table 35. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top
Solid-Walled Noncombustible Containers ..................................................................................... 69
Table 36. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top
Solid-Walled Unexpanded Plastic Containers; Storage Height up to and including 20 ft (6.1 m) . 71
Table 37. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top
Solid-Walled Unexpanded Plastic Containers; Storage Height in Excess of 20 ft (6.1 m) .......... 72
Table 38. Sprinkler Pressure Requirements for the Protection of Vertically Enclosed ASRS Storage Units
Over 25 ft (7.6 m) and up to 55 ft (16.8 m) Tall ........................................................................... 85
1.0 SCOPE
This data sheet provides loss prevention guidelines specific to Class 1, 2, 3, 4, and plastic commodities for
the following:
A. Mini-load and shuttle-type automatic storage and retrieval systems (ASRS)
B. Top-loading automatic storage and retrieval systems (TL-ASRS)
C. Vertically enclosed automatic storage and retrieval systems (ASRS) (see Appendix A for definitions
of these ASRS storage arrangements)
See Data Sheet 8-9, Storage of Class 1, 2, 3, 4, and Plastic Commodities, when:
1. a rack-structure type of ASRS is being installed. Use the protection guidelines indicated in Data Sheet
8-9 for multiple-row rack storage.
2. a shuttle-type ASRS storage arrangement is being installed. In addition to the protection guidelines in
Data Sheet 8-9, adhere to the recommendations in Section 2.1 of this data sheet.
Note that the following automatic storage and retrieval system (ASRS) conditions are outside the scope of
this data sheet and currently do not have any known protection options:
• ASRS arrangements that use expanded plastic trays and/or containers
• ASRS arrangements that use non-solid (gridded) bottom, open-top containers
• Commodity hazards higher than plastics, such as Level 2 and 3 aerosols, ignitable liquids, flammable
gasses, and other special hazards
1.1 Changes
October 2020. Interim revision. Significant changes include the following:
A. The following changes were made to the entire document:
1. Reformatted the sections so Section 2.2 is specific to mini-load ASRS storage arrangements, Section
2.3 is specific to TL-ASRS storage arrangements, and Section 2.4 is specific to vertically enclosed
storage arrangements.
2. Added instructions for users to see Data Sheet 8-9 for the protection of rack structure ASRS storage
arrangements.
3. Noted that protection options for open-top, gridded-bottom containers are outside the scope of this
data sheet.
B. The following changes were made specific to mini-load ASRS storage arrangements:
1. Moved all the protection options specific to mini-load ASRS storage arrangements to this document
(i.e., users no longer referred to Data Sheet 8-9 for certain storage arrangements)
2. Added new guidelines for solid-walled noncombustible containers.
3. Added dry-pipe sprinkler protection options.
4. Noted that protection options for expanded plastic trays and containers are outside the scope of
this data sheet.
5. Added information on shuttle-type ASRS storage arrangements in Section 2.1 and Appendix A.
C. The following changes were made specific to top-loading ASRS storage arrangements:
1. Noted that protection options for open-top, gridded-bottom containers are outside the scope of this
data sheet.
2. Added protection options for open-top, non-solid walled containers to this data sheet.
3. Added protection options for noncombustible open-top, solid-walled containers to this data sheet.
D. Clarified TL-ASRS storage arrangements regarding what is needed for sprinkler protection (suppression
or control) and what is needed for final extinguishment. Added new sections for each ASRS storage
arrangement specific to final extinguishment.
E. Added definitions to Appendix A to clarify guidance for the various types of containers described in
this data sheet.
No
No
Is the ASRS a
Mini-Load,Top-Loading, or No Data Sheet 8-34 does not currently
Vertically Enclosed system have protection options for this ASRS
as defined in arrangement
Appendix A?
Yes
Will the trays and/or Data Sheet 8-34 does not currently
containers used within the Yes have protection options for an ASRS
ASRS be expanded plastic or storage array using containers with
have gridded bottoms? gridded bottoms or trays/containers
made of expanded plastic
No
Yes
2.1 General Recommendations for All Automatic Storage and Retrieval Systems
Coordinate the facility’s construction, occupancy, and protection details in the planning stages so they are
all compatible.
2.1.2.6.9 If open-top, non-solid-walled combustible containers are present within a rack storage array, assume
one-third of the containers stored vertically within the footprint of the in-rack sprinkler design will be filled
with water up to the point of the container’s openings.
2.1.3 Occupancy
2.1.4 Protection
2.1.4.1 In addition to the recommendations in this data sheet, follow the sprinkler, ceiling and in-rack,
installation guidelines indicated for Storage sprinklers in DS 2-0, Installation Guidelines for Automatic
Sprinklers.
2.1.4.2 For facilities located in earthquake-prone regions, refer to DS 2-8, Earthquake Protection for
Water-Based Fire Protection Systems.
2.1.4.3.4 Mixing Different Ceiling-Level Storage Sprinklers Within the Same ASRS Protected Area
2.1.4.3.4.1 For a ceiling-level sprinkler system protecting an ASRS storage arrangement, install Storage
sprinklers having the same K-factor, coverage listing (i.e., standard or extended), orientation, response time
index (RTI) rating, and temperature rating throughout the protected ASRS area, whenever possible. See
Sections 2.1.4.3.4.2 through 2.1.4.3.4.6 for possible exceptions.
2.1.4.3.4.2 Sprinkler K-Factor. Mixing sprinklers that have different K-factors on the same ceiling-level
sprinkler system within the same ASRS protected area is acceptable when there is a change in the ceiling
height in the same area that requires a different ceiling-level sprinkler design. When this occurs, extend the
higher sprinkler system design a minimum of one branchline or sprinkler, depending on how the sprinkler
piping is arranged, into the area requiring the lower sprinkler system design.
2.1.4.3.4.3 Sprinkler Coverage Listing. Mixing sprinklers that have different coverage listings (i.e., standard-
coverage and extended-coverage) on the same ceiling-level sprinkler system within the same ASRS
protected area is acceptable when there is a change in the ceiling height in the same area that requires a
different ceiling-level sprinkler design. When this occurs, extend the higher sprinkler system design a minimum
of one branchline or sprinkler, depending on how the sprinkler piping is arranged, into the area requiring
the lower sprinkler system design.
2.1.4.3.4.4 Sprinkler Orientation. Mixing sprinklers that have different orientations (i.e., pendent and upright)
on the same ceiling-level sprinkler system within the same ASRS protected area is acceptable when it is
for the purpose of eliminating obstructions to sprinkler discharge in accordance with DS 2-0.
2.1.4.3.4.5 Sprinkler RTI Rating. Mixing sprinklers that have different RTI ratings (i.e., standard-response
and quick-response) on the same ceiling-level sprinkler system within the same ASRS protected area is
acceptable when there is a change in the ceiling height in the same area that requires a different ceiling-level
sprinkler design. When this occurs, extend the higher sprinkler system design a minimum of one branchline
or sprinkler, depending on how the sprinkler piping is arranged, into the area requiring the lower sprinkler
system design and provide a minimum 2 ft (0.6 m) deep draft curtain that separates the two different RTI rated
sprinklers.
2.1.4.3.4.6 Temperature Rating. Mixing sprinklers that have different nominal temperature ratings (e.g., 160°F
[70°C], 212°F [100°C], and 280°F [140°C]) on the same ceiling-level sprinkler system within the same ASRS
protected area is acceptable when ambient conditions, such as the immediate area around unit heaters,
require a higher temperature-rated sprinkler to avoid the potential for premature operation.
(E) identifying and providing operational guidance on the specialized firefighting equipment, such as hose
station connections, fixed-in-place monitors, visible or infrared cameras, remote monitor nozzle steering
mechanisms, etc., installed at the facility for protection of the ASRS storage array
2.2.1.1.2 What differentiates this storage arrangement from traditional pallet load storage rack arrangements
is:
1. Rack uprights that are typically only about 2 ft (0.6 m) apart horizontally as opposed to about
8 ft (2.4 m),
2. Tiers that are only about 12 to 18 in. (300 to 450 mm) high as opposed to about 5 ft (1.5 m),
3. Product handling that consists of 18 in. x 24 in. (450 mm x 600 mm) trays or open-top containers as
opposed to 4 ft x 4 ft (1.2 m x 1.2 m) pallets,
4. Material handling support accomplished by angle irons as opposed to horizontal supports
While bullet points 1 through 3 create a unique storage arrangement for the mini-load ASRS, it is the presence
of the angle irons within the mini-load ASRS rack structure that has a major impact on the protection
requirements for them. This is because the angle irons divert most of the sprinkler discharge out to the face
of the rack, thus limiting the amount of sprinkler discharge that can be distributed into the flue spaces of
the storage rack.
See Figure 3 for an example of angle irons being used for material handling support within a mini-load ASRS
storage arrangement.
Fig. 3. Example of a mini-load ASRS having angle irons that support the trays and/or containers
2.2.1.1.3 To determine the recommendations for the protection of products being stored within a mini-load
ASRS storage array, use the following generic procedure:
1. See Section 2.1 for general recommendations that apply to all ASRS storage arrangements, including
construction, occupancy, protection, and final extinguishment.
2. See Section 2.2.1 for additional general recommendations that apply to just mini-load ASRS storage
arrangements.
3. Obtain the specific protection guidelines from the applicable section for the type of storage being
maintained within the mini-load ASRS. The applicable sections are as follows:
A. Section 2.2.2 for open-top noncombustible solid-walled containers,
B. Section 2.2.3 for (1) products stored on trays, or (2) products storage in closed-top cellulosic containers
stored directly on the rails of the mini-load ASRS storage array,
C. Section 2.2.4 for (1) noncombustible, non-solid walled containers, (2) closed-top unexpanded plastic
containers, and (3) adequately vented, open-top cellulosic or unexpanded plastic containers,
D. Section 2.2.5 for non-adequately vented open-top cellulosic or unexpanded plastic containers
2.2.1.1.4 The protection of expanded plastic trays or expanded plastic containers in a mini-load ASRS storage
array is outside the scope of this data sheet.
A. Maximum commodity hazard to be protected (see FM Global Property Loss Prevention Data Sheet
[Data Sheet] 8-1, Commodity Classification)
B. Depth of the ASRS unit (rack row depth)
C. Material composition (i.e., chemical construction) of the trays and/or containers used for material
handling
D. Type of containers (open-top, closed-top, non-solid walled, adequately vented solid-walled, and
non-adequately vented solid-walled)
E. Transverse flue space width
F. Horizontal distance between transverse flue spaces
G. Longitudinal flue space width (if provided)
H. Tier height
I. Maximum storage height
J. Maximum ceiling height over the storage area
2.2.1.3 Properly anchor all mini-load ASRS rack structures to prevent them from falling over and causing
nearby racks to fall over (i.e., a “domino” effect). Take into consideration the effects of rack loads, the additional
load created by the collection of fire protection water by the stored commodity and its container (see Section
2.1.2.6), the weight of water-filled, in-rack sprinkler piping (if provided), and any seismic conditions (see FM
Global Property Loss Prevention Data Sheet [Data Sheet] 1-2, Earthquakes).
2.2.1.4 Design mini-load ASRS rack-supported structures taking into consideration the effects of weather
(wind, snow, rain, hail, etc.), rack loads, seismic conditions (see Data Sheet 1-2), and the additional load
created by the stored commodity and/or its container collecting or absorbing fire protection water (see Section
2.1.2.6), the weight of water-filled sprinkler piping (from ceiling or in-rack sprinklers), and any other loads
to which the rack or structure may be exposed.
3. When installing a preaction or refrigerated area sprinkler system, see Data Sheet 5-48, Automatic
Fire Detection, for recommendations pertaining to the sprinkler system’s activating detection system.
4. Ceiling sprinkler designs for single-interlocked preaction sprinkler systems can be either classified as
“wet-pipe” or “dry-pipe,” depending on the installation of the activating detection system. See Data
Sheet 5-48 to determine the installation requirements needed for the detection system to achieve a
sprinkler system design classification of wet pipe. Design the single-interlocked preaction system using
the dry-pipe sprinkler system designs in Table 2 when the detection installation is not in compliance
with the recommendations provided in Data Sheet 5-48 for a wet-pipe sprinkler system design.
5. A ceiling-level sprinkler system consisting of 20% to 30% concentration of propylene glycol in water
is acceptable for ambient temperatures between 32ºF (0ºC) and 40ºF (4ºC).
6. When installing an antifreeze sprinkler system consisting of a 20% to 30% concentration of propylene
glycol in water, the ceiling designs indicated for a wet-pipe sprinkler system can be used.
7. See FM Global Property Loss Prevention Data Sheet (Data Sheet) 2-0, Installation Guidelines for
Automatic Sprinklers, for additional recommendations related to the installation of all sprinkler system
types. See FM Global Property Loss Prevention Data Sheet 8-29, Refrigerated Storage, when a
refrigerated area sprinkler system is installed.
B. In-Rack Sprinkler System Types
1. Depending on the ambient temperature of the ASRS area being protected, in-rack sprinkler systems
can be:
a. Wet-pipe sprinkler systems
b. Dry-pipe sprinkler systems
c. Non-interlocked or single-interlocked preaction sprinkler systems
d. Refrigerated area sprinkler systems
e. Antifreeze solution sprinkler system consisting of a 20% to 30% propylene glycol concentration
in water
2. The maximum water delivery time for all in-rack sprinkler dry-pipe and similar sprinkler systems is
40 seconds upon the operation of the hydraulically most remote in-rack sprinkler.
3. When installing a preaction or refrigerated area sprinkler system, see Data Sheet 5-48 for
recommendations pertaining to the sprinkler system’s activating detection system.
4. An in-rack sprinkler system consisting of 20% to 30% concentration of propylene glycol in water is
acceptable for ambient temperatures between 32ºF (0ºC) and 40ºF (4ºC).
5. When installing an antifreeze sprinkler system consisting of a 20% to 30% concentration of propylene
glycol in water, the ceiling designs indicated for a wet-pipe sprinkler system can be used.
6. See Data Sheet 2-0 for additional recommendations related to the installation of all sprinkler system
types. See FM Global Property Loss Prevention Data Sheet 8-29, Refrigerated Storage, when a
refrigerated area sprinkler system is installed.
2.2.1.5.4 Sprinklers
A. Ceiling-Level Sprinklers
Install FM Approved, Storage ceiling-level sprinklers having the attributes indicated in the applicable mini-load
ASRS protection tables.
B. In-Rack Sprinklers
When in-rack sprinklers are required, install FM Approved, quick-response, 160ºF (70ºC) nominally rated,
Storage sprinklers having the appropriate K-factor value indicated in the applicable mini-load ASRS in-rack
sprinkler protection tables. Note that if not specifically indicated, in-rack sprinklers can be either pendent
or upright.
2.2.1.6 Detection
2.2.1.6.1 Install a FM Approved ceiling-level fire detection system over the mini-load ASRS storage area in
accordance with Data Sheet 5-48.
2.2.1.6.2 When the ceiling construction over the storage area is considered obstructed per Data Sheet 2-0,
install the detectors on the same maximum spacing indicated for the ceiling-level sprinklers using an
obscuration rate that is in accordance with the detection system manufacturer’s guidelines.
2.2.1.6.3 Arrange the detection system upon activation to:
(1) send an alarm to a constantly attended location, and
(2) automatically shut-down the operations of the ASRS robots, and
(3) send an alarm to a constantly attended location.
2.2.1.6.4 A ceiling-level fire detection system over the mini-load ASRS storage area is not needed when
noncombustible solid-walled containers are used throughout the ASRS storage array.
2.2.2 Protection of Mini-Load ASRS Storage Arrangements Using Open-Top Noncombustible Solid-
Walled Containers
2.2.2.1 Ceiling-Only Sprinkler System Design Criteria for Open-Top Noncombustible Solid-Walled
Containers
2.2.2.1.1 In-rack sprinklers are recommended in combination with ceiling-level sprinklers when:
A. the ceiling height over the mini-load ASRS storage array exceeds 55 ft (16.8 m), or
B. a ceiling-only protection option is not provided in Table 2 for the specific sprinkler being installed at
ceiling level, or
C. the water supply cannot provide the flow and pressure requirements for any of the protection options
offered in Table 2.
When in-rack sprinklers are recommended, see Section 2.2.2.2 for recommendations regarding ceiling and
in-rack sprinkler systems.
2.2.2.1.2 Use Table 2 to determine the ceiling-only sprinkler system designs for open-top, solid-walled
noncombustible containers.
Page 18
8-34
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @ psi (bar)
Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC) Dry System, Upright Storage Sprinklers,
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2 K11.2 K16.8 K25.2 K33.6
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360) (K160) (K240) (K360) (K480)
20 12 @ 12 @ 7 12 @ 7 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 12 @ 12 @ 7 9 @ 16 9@7 12 @ 12 @ 7 12 @ 7 6 @ 20 12 @ 12 @ 7 9@7 16 @ 16 @ 7 16 @ 7 12 @
(6.1) 10 (0.7) (0.5) (0.5) (1.4) (1.4) (1.4) (2.8) (3.8) 10 (0.7) (0.5) (1.1) (0.5) 10 (0.7) (0.5) (0.5) (1.4) 10 (0.7) (0.5) (0.5) 10 (0.7) (0.5) (0.5) 50 (3.5)
25 10 @ 10 @ 10 @ 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 10 @ 10 @ 9 @ 16 10 @ 7 10 @ 10 @ 10 @ 6 @ 20 10 @ 10 @ 10 @ 7 20 @ 20 @ 7 20 @ 7 12 @
©2017-2020 Factory Mutual Insurance Company. All rights reserved.
(7.6) 30 (2.1) 20 (1.4) 13 (0.9) (1.4) (1.4) (1.4) (2.8) (3.8) 30 (2.1) 20 (1.4) (1.1) (0.5) 30 (2.1) 20 (1.4) 13 (0.9) (1.4) 30 (2.1) 13 (0.9) (0.5) 16 (1.1) (0.5) (0.5) 50 (3.5)
30 18 @ 12 @ 12 @ 9 @ 20 9 @ 20 6 @ 25 9 @ 40 9 @ 55 18 @ 18 @ 9 @ 16 9 @ 10 18 @ 12 @ 12 @ 6 @ 25 18 @ 18 @ 12 @ 20 @ 20 @ 20 @ 7 12 @
(9.1) 50 (3.5) 50 (3.5) 35 (2.4) (1.4) (1.4) (1.7) (2.8) (3.8) 50 (3.5) 32 (2.2) (1.1) (0.7) 50 (3.5) 50 (3.5) 35 (2.4) (1.7) 50 (3.5) 22 (1.5) 20 (1.4) 25 (1.7) 10 (0.7) (0.5) 50 (3.5)
35 9 @ 75 9 @ 52 9 @ 28 9 @ 22 6 @ 60 9 @ 40 9 @ 55 15 @ 9 @ 30 9 @ 75 9 @ 52 8 @ 40 20 @ 20 @ 20 @ 7 12 @
(10.7) (5.2) (3.6) (1.9) (1.5) (4.1) (2.8) (3.8) 25 (1.7) (2.1) (5.2) (3.6) (2.8) 25 (1.7) 10 (0.7) (0.5) 50 (3.5)
40 9 @ 75 9 @ 52 9 @ 28 9 @ 22 9 @ 40 9 @ 55 9 @ 30 36 @ 36 @ 12 @ 12 @
(12.2) (5.2) (3.6) (1.9) (1.5) (2.8) (3.8) (2.1) 55 (3.8) 22 ((1.5) 50 (3.5) 50 (3.5)
50 10 @ 10 @ 10 @ 9 @ 55 15 @
(15.2) 63 (4.3) 50 (3.5) 40 (2.8) (3.8) 50 (3.5)
Table 3. In-Rack Sprinkler Discharge Rates for Open-Top Noncombustible Solid-Walled Containers in Mini-Load ASRS
Storage Arrangements
Maximum Vertical Distance Between Minimum K-factor Value for In-Rack Minimum Flow from Most Remote
In-Rack Sprinklers, ft (m) Sprinkler In-Rack Sprinkler, gpm (L/min)
20 (6.1) K5.6 (K80) 30 (115)
25 (7.6) K8.0 (K115) 45 (175)
30 (9.1) K8.0 (K115) 60 (230)
35 (10.7) K11.2 (K160) 90 (340)
40 (12.2) K14.0 (K200) 120 (455)
45 (13.7) K16.8 (K240) 150 (570)
50 (15.2) K22.4 (K320) 180 (680)
2.2.2.2.4 Ceiling-Level Sprinkler System Designs in Combination with In-Rack Sprinklers for Open-Top
Noncombustible Solid-Walled Containers
A. When open-top noncombustible solid-walled containers are located throughout the storage array, Table
4 is used to determine the ceiling-level sprinkler design, when supplemented with in-rack sprinklers, using
a maximum ceiling height value that is equal to the vertical distance between the top in-rack sprinkler
level and the maximum ceiling height above the in-rack sprinklers.
B. If the vertical distance between the top in-rack sprinkler level and the maximum ceiling height over
the storage array exceeds the maximum ceiling height indicated for the sprinkler installed at ceiling level,
install a flat, continuous noncombustible false ceiling over the ASRS storage area and for a minimum
of 15 ft (4.6 m) beyond it in all directions. Design the false ceiling to be capable of withstanding a minimum
uplift pressure of 3 lb/ft2 (14.4 kg/m2). Provide sprinkler protection under this false ceiling in accordance
with Section 2.2.2.2.4(A).
C. Hydraulically balance the ceiling and in-rack sprinkler demands at their point of connection.
Page 20
8-34
Max.
Vertical Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @ psi (bar)
Distance Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC) Dry System, Upright Storage Sprinklers,
Between 280ºF (140ºC)
Top
IRAS Quick-Response Standard-Response Quick-Response Standard-Response Standard-Response
Level
and K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2 K11.2 K16.8 K25.2 K33.6
Ceiling, (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360) (K160) (K240) (K360) (K480)
ft (m)
©2017-2020 Factory Mutual Insurance Company. All rights reserved.
20 (6.1) 12 @ 12 @ 7 12 @ 7 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 12 @ 12 @ 7 9 @ 16 9 @ 7 12 @ 12 @ 7 12 @ 7 6 @ 20 12 @ 12 @ 7 9 @ 7 16 @ 16 @ 7 16 @ 7 12 @
10 (0.7) (0.5) (0.5) (1.4) (1.4) (1.4) (2.8) (3.8) 10 (0.7) (0.5) (1.1) (0.5) 10 (0.7) (0.5) (0.5) (1.4) 10 (0.7) (0.5) (0.5) 10 (0.7) (0.5) (0.5) 50 (3.5)
25 (7.6) 10 @ 10 @ 10 @ 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 10 @ 10 @ 9 @ 16 10 @ 7 10 @ 10 @ 10 @ 6 @ 20 10 @ 10 @ 10 @ 7 20 @ 20 @ 7 20 @ 7 12 @
30 (2.1) 20 (1.4) 13 (0.9) (1.4) (1.4) (1.4) (2.8) (3.8) 30 (2.1) 20 (1.4) (1.1) (0.5) 30 (2.1) 20 (1.4) 13 (0.9) (1.4) 30 (2.1) 13 (0.9) (0.5) 16 (1.1) (0.5) (0.5) 50 (3.5)
30 (9.1) 18 @ 12 @ 12 @ 9 @ 20 9 @ 20 6 @ 25 9 @ 40 9 @ 55 18 @ 18 @ 9 @ 16 9 @ 10 18 @ 12 @ 12 @ 6 @ 25 18 @ 18 @ 12 @ 20 @ 20 @ 20 @ 7 12 @
50 (3.5) 50 (3.5) 35 (2.4) (1.4) (1.4) (1.7) (2.8) (3.8) 50 (3.5) 32 (2.2) (1.1) (0.7) 50 (3.5) 50 (3.5) 35 (2.4) (1.7) 50 (3.5) 22 (1.5) 20 (1.4) 25 (1.7) 10 (0.7) (0.5) 50 (3.5)
35 (10.7) 9 @ 75 9 @ 52 9 @ 28 9 @ 22 6 @ 60 9 @ 40 9 @ 55 15 @ 9 @ 30 9 @ 75 9 @ 52 8 @ 40 20 @ 20 @ 20 @ 7 12 @
2.2.3 Protection of Mini-Load ASRS Storage Arrangements with Storage on Trays or in Closed-Top
Cellulosic Containers
Note the protection of materials being stored on expanded plastic trays is outside the scope of the data sheet.
2.2.3.1 Ceiling-Only Sprinkler System Design Criteria for Storage on Trays or in Closed-Top Cellulosic
Containers
2.2.3.1.1 In-rack sprinklers are needed in combination with ceiling-level sprinklers when:
A. For the given material handling scenario outlined in this section, a ceiling-only protection is not provided
in Tables 5 or 6 for the specific sprinkler being installed at ceiling level, or
B. The water supply cannot provide the flow and pressure requirements for any of the protection options
offered in the applicable protection table
When in-rack sprinklers are recommended, see Section 2.2.3.2 for ceiling and in-rack sprinkler systems
installed on a wet-pipe sprinkler system, or Section 2.2.3.3 for ceiling and in-rack sprinkler systems installed
on a dry-pipe sprinkler system.
2.2.3.1.2 When in-rack sprinklers are not required, use Table 5 to determine the ceiling-only sprinkler system
designs when storage throughout the mini-load ASRS storage array consists of:
A. Closed-top cellulosic containers having a maximum commodity classification of cartoned unexpanded
plastic (CUP) are being stored directly on the rails of the mini-load ASRS array, or
B. Materials having a maximum commodity classification of uncartoned unexpanded plastics (UUP) are
being stored on trays.
2.2.3.1.3 When in-rack sprinklers are not required, use Table 6 to determine the ceiling-only sprinkler system
designs when the mini-load ASRS storage array consists of:
A. Closed-top cellulosic containers having a commodity classification of cartoned expanded plastics (CEP)
are being stored directly on the rails of the mini-load ASRS array, or
B. Uncartoned expanded plastic (UEP) materials are being stored on trays.
Page 22
8-34
Classification of CUP, or (2) Materials with Maximum Commodity Classification of UUP Stored on Trays
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @ psi (bar)
Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC)
Dry System, Upright Storage Sprinklers,
Max. 280ºF (140ºC)
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2 K11.2 K16.8 K25.2 K33.6
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360) (K160) (K240) (K360) (K480)
10 (3.0) 15 @ 10 15 @ 7 15 @ 7 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 15 @ 10 15 @ 7 12 @ 16 15 @ 7 15 @ 10 15 @ 7 15 @ 7 6 @ 20 15 @ 10 15 @ 7 15 @ 7 20 @ 10 20 @ 7 20 @ 7 20 @ 50
(0.7) (0.5) (0.5) (1.4) (1.4) (1.4) (2.8) (3.8) (0.7) (0.5) (1.1) (0.5) (0.7) (0.5) (0.5) (1.4) (0.7) (0.5) (0.5) (0.7) (0.5) (0.5) (3.5)
©2017-2020 Factory Mutual Insurance Company. All rights reserved.
15 (4.6) 15 @ 50 12 @ 32 12 @ 22 9 @ 25 9 @ 20 6 @ 60 9 @ 40 9 @ 55 15 @ 50 12 @ 50 12 @ 25 12 @ 15 15 @ 50 15 @ 32 15 @ 22 8 @ 35 15 @ 50 15 @ 22 15 @ 10 20 @ 50 20 @ 22 20 @ 10 20 @ 50
(3.5) (2.2) (1.5) (1.7) (1.4) (4.1) (2.8) (3.8) (3.5) (3.5) (1.7) (1.0) (3.5) (2.2) (1.5) (2.4) (3.5) (1.5) (0.7) (3.5) (1.5) (0.7) (3.5)
20 (6.1) 9 @ 50 9 @ 35 9 @ 25 9 @ 20 6 @ 60 9 @ 40 9 @ 55 12 @ 50 12 @ 25 12 @ 15
(3.5) (2.4) (1.7) (1.4) (4.1) (2.8) (3.8) (3.5) (1.7) (1.0)
25 (7.6) 10 @ 50 10 @ 35 10 @ 25 10 @ 20 10 @ 40 10 @ 55
(3.5) (2.4) (1.7) (1.4) (2.8) (3.8)
30 (9.1) 15 @ 50 15 @ 35 10 @ 50 10 @ 40 10 @ 40 10 @ 55
(3.5) (2.2) (1.5) (1.7) (1.4) (2.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (2.4) (3.5) (1.5) (0.7) (3.5) (1.5) (0.7) (3.5)
25 (7.6) 12 @ 75 12 @ 52 9 @ 32 9 @ 25 9 @ 40 9 @ 55
(5.2) (3.6) (2.2) (1.7) (2.8) (3.8)
30 (9.1) 12 @ 12 @ 70 12 @ 50 12 @ 40 12 @ 40 12 @ 55
100 (6.9) (4.8) (3.5) (2.8) (2.8) (3.8)
40 (12.2) 20 @ 75 20 @ 61 20 @ 42
(5.2) (4.2) (2.9)
Page 23
8-34
8-34 Protection for Automatic Storage
Page 24 FM Global Property Loss Prevention Data Sheets
Table 7. Ceiling-Level Sprinkler System Hose Demand and Water Supply Duration
Ceiling Sprinkler Spacing Number of Sprinklers in the Water Supple Duration,
Type Ceiling Design Hose Demand, gpm (L/min) minutes
Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
2.2.3.2 Ceiling and In-Rack Sprinkler Systems Installed on a Wet-Pipe Sprinkler System for Storage
on Trays or in Closed-Top Cellulosic Containers
2.2.3.2.1 Ceiling and In-Rack Sprinkler Systems
The ceiling and in-rack sprinkler systems for this section can be either wet-pipe or consist of a 20% to 30%
propylene glycol antifreeze solution.
2.2.3.2.2 Horizontal Location of In-Rack Sprinklers
A. See Section 2.2.6.2 for the recommended horizontal in-rack sprinkler arrangements protecting storage
maintained on trays when the in-rack sprinklers are on a wet system.
B. See Section 2.2.6.3 for the recommended horizontal in-rack sprinkler arrangements protecting
closed-top cellulosic containers when the in-rack sprinklers are on a wet system.
2.2.3.2.3 Vertical Location of In-Rack Sprinklers
A. The maximum vertical distance between in-rack sprinklers is 10 ft (3.0 m) for:
1. UEP commodities stored on trays, or
2. CEP commodities stored directly on the rails of the mini-load ASRS array
B. The maximum vertical distance between in-rack sprinklers is 15 ft (4.6 m) for:
1. Commodity hazards up to and including UUP stored on trays, or
2. Commodity hazards up to CUP stored directly on the rails of the mini-load ASRS array
2.2.3.2.4 In-Rack Sprinkler Design for Storage on Trays or in Closed-Top Cellulosic Containers
A. When vertical barriers are not needed within the mini-load ASRS, design the in-rack sprinkler system
in accordance with Table 8.
Table 8. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Storage on Trays or in Closed-Top
Cellulosic Containers
In-Rack Sprinkler Design
Flow from Most Remote
Maximum In-Rack Sprinkler, gpm
Vertical (L/min)
Distance Vertical Vertical
Between Minimum No. of Distances Distances
Depth of Tray or In-Rack In-Rack In-Rack Between Tier Between Tier
ASRS Rack Cellulosic Commodity Sprinklers, ft Sprinkler Sprinklers in Levels ≥ 9 Levels <9 in.
Row, ft (m) Container Classification (m) K-Factor Design in. (225 mm) (225 mm)
Up to 3 (0.9) Tray Up to UUP 10 (3.0) K11.2 (K160) 4 60 (230) 80 (300)
15 (4.6) K14.0 (K200) 6 100 (380) 120 (455)
UEP 10 (3.0) K11.2 (K160) 6 60 (230) 80 (300)
Cellulosic Up to CUP 10 (3.0) K11.2 (K160) 4 60 (230) 80 (300)
Container 15 (4.6) K14.0 (K200) 6 100 (380) 120 (455)
CEP 10 (3.0) K11.2 (K160) 6 60 (230) 80 (300)
Over 3 (0.9) Tray Up to UUP 10 (3.0) K11.2 (K160) 6 60 (230) 80 (300)
and up to 6 15 (4.6) K14.0 (K200) 9 100 (380) 120 (455)
(1.8) UEP 10 (3.0) K11.2 (K160) 8 60 (230) 80 (300)
Cellulosic Up to CUP 10 (3.0) K11.2 (K160) 6 60 (230) 80 (300)
Container 15 (4.6) K14.0 (K200) 9 100 (380) 120 (455)
CEP 10 (3.0) K11.2 (K160) 8 60 (230) 80 (300)
Over 6 (1.8) Tray Up to UUP 10 (3.0) K11.2 (K160) 8 60 (230) 80 (300)
15 (4.6) K14.0 (K200) 12 100 (380) 120 (455)
UEP 10 (3.0) K11.2 (K160) 10 60 (230) 80 (300)
Cellulosic Up to CUP 10 (3.0) K11.2 (K160) 8 60 (230) 80 (300)
Container 15 (4.6) K14.0 (K200) 12 100 (380) 120 (455)
CEP 10 (3.0) K11.2 (K160) 10 60 (230) 80 (300)
B. When vertical barriers are recommended per Section 2.2.1.5.2, instead of using Table 8 to determine
the number of in-rack sprinklers in the in-rack sprinkler design, account for the number of in-rack sprinklers
in the design as follows:
1. Include all the in-rack sprinklers within the footprint created by the vertical barriers, and
2. Include all the in-rack sprinklers within 2 ft (0.6 m) horizontally that are located on the opposite side
of the vertical barriers.
C. In addition to the minimum in-rack sprinkler design flow obtained from Table 8, maintain a minimum
in-rack sprinkler design pressure of 7 psi (0.5 bar).
D. The design obtained from Table 8 applies to the single hydraulically most remote in-rack sprinkler level.
2.2.3.2.5 Ceiling-Level Sprinkler System Designs in Combination with In-Rack Sprinklers for Storage on Trays
or in Closed-Top Cellulosic Containers
A. Use Table 9 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers
when the mini-load ASRS storage array consists of:
1. Closed-top cellulosic containers having a maximum commodity classification of CUP are being stored
directly on the rails of the mini-load ASRS array, or
2. Materials having a maximum commodity classification of UUP are being stored on trays.
B. Use Table 10 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers
when the mini-load ASRS storage array consists of:
1. CEP containers are being stored directly on the rails of the mini-load ASRS array, or
2. UEP materials are being stored on trays
C. The ceiling-level sprinkler system designs in Tables 9 and 10 are determined based on the vertical distance
between the top in-rack sprinkler level and the maximum ceiling height of the ASRS protected area.
D. If the vertical distance between the top in-rack sprinkler level and the maximum ceiling height over the
storage array exceeds the maximum ceiling height indicated for the sprinkler installed at ceiling level, install
a flat, continuous noncombustible false ceiling over the ASRS storage area and for a minimum of 15 ft
(4.6 m) beyond it in all directions. Design the false ceiling to be capable of withstanding a minimum uplift
pressure of 3 lb/ft2 (14.4 kg/m2). Provide sprinkler protection under this false ceiling in accordance with either
Section 2.2.3.2.5(A) or 2.2.3.2.5(B), depending on the type of product being stored within the mini-load ASRS
storage array.
(3.5) (2.2) (1.5) (1.7) (1.4) (4.1) (2.8) (3.8) (3.5) (3.5) (1.7) (1.0) (3.5) (2.2) (1.5) (2.4) (3.5) (1.5) (0.7)
20 (6.1) 9 @ 50 9 @ 35 9 @ 25 9 @ 20 6 @ 60 9 @ 40 9 @ 55 12 @ 50 12 @ 25 12 @ 15
(3.5) (2.4) (1.7) (1.4) (4.1) (2.8) (3.8) (3.5) (1.7) (1.0)
25 (7.6) 10 @ 50 10 @ 35 10 @ 25 10 @ 20 10 @ 40 10 @ 55
(3.5) (2.4) (1.7) (1.4) (2.8) (3.8)
30 (9.1) 15 @ 50 15 @ 35 10 @ 50 10 @ 40 10 @ 40 10 @ 55
(3.5) (2.4) (3.5) (2.8) (2.8) (3.8)
40 (12.2) 12 @ 75 12 @ 60 12 @ 49 12 @ 55
(5.2) (4.1) (3.4) (3.8)
Page 27
8-34
Table 10. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on a Wet System for Mini-Load ASRS Storage Arrangements with (1) Closed-Top CEP
Page 28
8-34
Containers, or (2) UEP Materials Stored on Trays
Max.
Vertical Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @ psi (bar)
Distance Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC)
Between
Top
Quick-Response Standard-Response Quick-Response Standard-Response
IRAS
Level
and K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
Ceiling, (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
©2017-2020 Factory Mutual Insurance Company. All rights reserved.
ft (m)
10 (3.0) 15 @ 10 15 @ 7 15 @ 7 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 15 @ 10 15 @ 7 12 @ 16 15 @ 7 15 @ 10 15 @ 7 15 @ 7 6 @ 20 15 @ 10 15 @ 7 15 @ 7
(0.7) (0.5) (0.5) (1.4) (1.4) (1.4) (2.8) (3.8) (0.7) (0.5) (1.1) (0.5) (0.7) (0.5) (0.5) (1.4) (0.7) (0.5) (0.5)
15 (4.6) 15 @ 50 12 @ 32 12 @ 22 9 @ 25 9 @ 20 8 @ 35 9 @ 40 9 @ 55 15 @ 50 15 @ 32 15 @ 16 15 @ 10 15 @ 50 15 @ 32 15 @ 22 8 @ 35 15 @ 50 15 @ 22 15 @ 10
(3.5) (2.2) (1.5) (1.7) (1.4) (2.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (2.4) (3.5) (1.5) (0.7)
25 (7.6) 12 @ 75 12 @ 52 9 @ 32 9 @ 25 9 @ 40 9 @ 55
(5.2) (3.6) (2.2) (1.7) (2.8) (3.8)
E. When the ceiling and in-rack sprinkler systems have been installed in accordance with Section 2.2.3.2:
1. The ceiling and in-rack sprinkler systems do not need to be hydraulically balanced, and
2. The ceiling and in-rack sprinkler systems do not need to be treated as operating concurrently
2.2.3.2.6 Hose Demand Design and Water Supply Duration
A. See Table 11 to determine the hose demand design and the water supply duration for the ceiling sprinkler
system as well as the in-rack sprinkler system.
Table 11. Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration
Sprinkler Spacing Number of Sprinklers Hose Demand, gpm Water Supply
Sprinkler System Type in the Design (L/min) Duration, minutes
Ceiling Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
In-Rack Standard- or Any 250 (950) 60
Extended-Coverage
B. The hose demand and water supply duration values obtained from Table 11 apply to each sprinkler system
separately and are not required concurrently.
2.2.3.3 Ceiling and In-Rack Sprinkler Systems Installed on a Dry-Pipe or Similar Sprinkler System
for Storage on Trays or in Closed-Top Cellulosic Containers
2.2.3.3.1 Ceiling and In-Rack Sprinkler Systems
Dry-pipe or similar sprinkler systems include the following:
A. Dry-pipe sprinkler systems
B. Non-interlocked or single-interlocked preaction sprinkler systems
C. Refrigerated area sprinkler systems
2.2.3.3.2 Sprinklers
A. Ceiling-Level Sprinklers
Install FM Approved, standard-response, 280ºF (140ºC) nominally rated, standard-coverage upright Storage
ceiling-level sprinklers having the K-factor values indicated in Tables 13 and 14.
B. In-Rack Sprinklers
Install FM Approved, quick-response, 160ºF (70ºC) nominally rated, upright Storage sprinklers having the
appropriate K-factor value indicated in Table 12.
2.2.3.3.3 Horizontal Location of In-Rack Sprinklers
See Section 2.2.6.4 for the recommended horizontal in-rack sprinkler arrangements protecting storage on
trays and closed-top cellulosic containers when the in-rack sprinklers are on a dry sprinkler system.
2.2.3.3.4 Vertical Location of In-Rack Sprinklers
A. The maximum vertical distance between in-rack sprinklers is 10 ft (3.0 m) for:
1. UEP commodities stored on trays, or
2. CEP commodities stored directly on the rails of the mini-load ASRS array.
B. The maximum vertical distance between in-rack sprinklers is 15 ft (4.6 m) for:
1. commodity hazards up to and including UUP stored on trays, or
2. commodity hazards up to CUP stored directly on the rails of the mini-load ASRS
array.
2.2.3.3.5 In-Rack Sprinkler Design for Storage on Trays or in Closed-Top Cellulosic Containers
A. When vertical barriers are not needed within the mini-load ASRS, design the in-rack sprinkler system in
accordance with Table 12.
Table 12. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Storage on Trays or in Closed-Top
Cellulosic Containers
In-Rack Sprinkler Design
Flow from Most Remote
In-Rack Sprinkler, gpm
Maximum (L/min)
Vertical Vertical Vertical
Distance Distances Distances
Depth of Between Minimum Number of No. of Between Between
ASRS Tray or In-Rack In-Rack IRAS In-Rack Tier Levels Tier Levels
Rack Row, Cellulosic Commodity Sprinklers, Sprinkler Levels Sprinklers ≥ 9 in. (225 <9 in. (225
ft (m) Container Classification ft (m) K-Factor Installed in Design mm) mm)
Up to 3 Tray Up to UUP 10 (3.0) K11.2 1 4 60 (230) 80 (300)
(0.9) (K160) More than 8 (4 on top
1 2 levels)
15 (4.6) K14.0 1 6 100 (380) 120 (455)
(K200) More than 12 (6 on
1 top 2
levels)
UEP 10 (3.0) K11.2 1 6 60 (230) 80 (300)
(K160) More than 12 (6 on
1 top 2
levels)
Cellulosic Up to CUP 10 (3.0) K11.2 1 4 60 (230) 80 (300)
Container (K160) More than 8 (4 on top
1 2 levels)
15 (4.6) K14.0 1 6 100 (380) 120 (455)
(K200) More than 12 (6 on
1 top 2
levels)
CEP 10 (3.0) K11.2 1 6 60 (230) 80 (300)
(K160) More than 12 (6 on
1 top 2
levels)
Over 3 Tray Up to UUP 10 (3.0) 11.2 (K160) 1 6 60 (230) 80 (300)
(0.9) and More than 12 (6 on
up to 6 1 the 2
(1.8) levels)
15 (4.6) K14.0 1 9 100 (380) 120 (455)
(K200) More than 18 (9 on
1 top 2
levels)
UEP 10 (3.0) K11.2 1 8 60 (230) 80 (300)
(K160) More than 16 (8 on
1 top 2
levels)
Cellulosic Up to CUP 10 (3.0) K11.2 1 6 60 (230) 80 (300)
Container (K160) More than 12 (6 on
1 the 2
levels)
15 (4.6) K14.0 1 9 100 (380) 120 (455)
(K200) More than 18 (9 on
1 top 2
levels)
CEP 10 (3.0) K11.2 1 8 60 (230) 80 (300)
(K160) More than 16 (8 on
1 top 2
levels)
Table 12. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Storage on Trays or in Closed-Top
Cellulosic Containers (continued)
In-Rack Sprinkler Design
Flow from Most Remote
In-Rack Sprinkler, gpm
Maximum (L/min)
Vertical Vertical Vertical
Distance Distances Distances
Depth of Between Minimum Number of No. of Between Between
ASRS Tray or In-Rack In-Rack IRAS In-Rack Tier Levels Tier Levels
Rack Row, Cellulosic Commodity Sprinklers, Sprinkler Levels Sprinklers ≥ 9 in. (225 <9 in. (225
ft (m) Container Classification ft (m) K-Factor Installed in Design mm) mm)
Over 6 Tray Up to UUP 10 (3.0) K11.2 1 8 60 (230) 80 (300)
(1.8) (K160) More than 16 (8 on
1 top 2
levels)
15 (4.6) K14.0 1 12 100 (380) 120 (455)
(K200) More than 24 (12 on
1 top 2
levels)
UEP 10 (3.0) K11.2 1 10 60 (230) 80 (300)
(K160) More than 20 (10 on
1 top 2
levels)
Cellulosic Up to CUP 10 (3.0) K11.2 1 8 60 (230) 80 (300)
Container (K160) More than 16 (8 on
1 top 2
levels)
15 (4.6) K14.0 1 12 100 (380) 120 (455)
(K200) More than 24 (12 on
1 top 2
levels)
CEP 10 (3.0) K11.2 1 10 60 (230) 80 (300)
(K160) More than 20 (10 on
1 top 2
levels)
B. When vertical barriers are recommended per Section 2.2.1.5.2, instead of using Table 12 to determine
the number of in-rack sprinklers in the in-rack sprinkler design, account for the number of in-rack sprinklers
in the design as follows:
1. Include all the in-rack sprinklers within the footprint created by the vertical barriers, and
2. Include all the in-rack sprinklers within 2 ft (0.6 m) horizontally that are located on the opposite side
of the vertical barriers.
C. In addition to the minimum in-rack sprinkler design flow obtained from Table 12, maintain a minimum in-rack
sprinkler design pressure of 7 psi (0.5 bar).
D. The design obtained from Table 12 applies to the single hydraulically most remote in-rack sprinkler level.
2.2.3.3.6 Ceiling-Level Sprinkler System Designs in Combination with In-Rack Sprinklers for Storage on
Trays or in Closed-Top Cellulosic Containers
A. Use Table 13 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers
when the mini-load ASRS storage array consists of:
1. closed-top cellulosic containers having a maximum commodity classification of CUP stored directly
on the rails of the mini-load ASRS array, or
2. materials having a maximum commodity classification of UUP are being stored on trays.
B. Use Table 14 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers
when the mini-load ASRS storage array consists of:
1. closed-top cellulosic containers having a commodity classification of CEP are being stored directly on
the rails of the mini-load ASRS array, or
2. UEP materials are being stored on trays.
C. The ceiling-level sprinkler system designs in Tables 13 and 14 are determined based on the vertical
distance between the top in-rack sprinkler level and the maximum ceiling height of the ASRS protected area.
Table 13. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on a Dry-Pipe Sprinkler
System for Mini-Load ASRS Storage Arrangements with (1) Closed-Top Cellulosic Containers Having Commodity
Classification up to CUP, or (2) Materials with Commodity Classification up to UUP Stored on Trays
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @
Max. Vertical Distance psi (bar)
Between Top IRAS Dry System, Upright Storage Sprinklers, 280ºF (140ºC)
Level and Ceiling, ft Standard-Response
(m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 20 @ 10 (0.7) 20 @ 7 (0.5) 20 @ 7 (0.5) 20 @ 50 (3.5)
15 (4.6) 20 @ 50 (3.5) 20 @ 22 (1.5) 20 @ 10 (0.7) 20 @ 50 (3.5)
Table 14. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on a Dry-Pipe System for
Mini-Load ASRS Storage Arrangements with (1) Closed-Top Cellulosic Containers Having a CEP Commodity Classification,
or (2) UEP Materials Stored on Trays
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @
Max. Vertical Distance psi (bar)
Between Top IRAS Dry System, Upright Storage Sprinklers, 280ºF (140ºC)
Level and Ceiling, ft Standard-Response
(m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 25 @ 10 (0.7) 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 50 (3.5)
15 (4.6) 25 @ 50 (3.5) 25 @ 22 (1.5) 25 @ 10 (0.7) 25 @ 50 (3.5)
D. When the ceiling and in-rack sprinkler systems have been installed in accordance with Section 2.2.3.3:
1. the ceiling and in-rack sprinkler systems need to be hydraulically balanced at their point of connection,
and
2. the ceiling and in-rack sprinkler systems need to be treated as operating concurrently.
2.2.3.3.7 Hose Demand Design and Water Supply Duration
A. See Table 15 to determine the hose demand design and the water supply duration for the combined ceiling
and in-rack sprinkler system.
Table 15. Combined Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration
Ceiling Sprinkler Spacing Number of Sprinklers in the Water Supply Duration,
Type Ceiling Design Hose Demand, gpm (L/min) minutes
Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
B. The hose demand and water supply duration values obtained from Table 15 apply to the combined ceiling
and in-rack sprinkler system.
2.2.4 Protection of Mini-Load ASRS Storage Arrangements Using Noncombustible Containers with
Non-Solid Walls, Closed-Top Unexpanded Plastic Containers, and Adequately Vented Open-Top
Unexpanded Plastic Containers
Note that the protection of expanded plastic containers is outside the scope of this data sheet.See Appendix
A for the definition of an adequately vented container.
2.2.4.1 Ceiling-Only Sprinkler System Design Criteria for Noncombustible Containers with Non-Solid
Walls, Closed-Top Unexpanded Plastic Containers, and Adequately Vented Open-Top Unexpanded
Plastic Containers
2.2.4.1.1 In-rack sprinklers are recommended in combination with ceiling-level sprinklers when:
A. The storage height of the mini-load ASRS storage arrangement exceeds 10 ft (3.0 m), or
B. The ceiling height over the mini-load ASRS storage array exceeds 20 ft (6.1 m), or
C. A ceiling-only protection is not provided in Table 16 for the specific sprinkler being installed at ceiling
level, or
D. The water supply cannot provide the flow and pressure requirements for any of the protection options
offered in Table 16
When in-rack sprinklers are recommended, see Section 2.2.4.2 for ceiling and in-rack sprinkler systems
installed on a wet-pipe sprinkler system, or Section 2.2.4.3 for ceiling and in-rack sprinkler systems installed
on a dry-pipe sprinkler system.
2.2.4.1.2 Use Table 16 to determine the ceiling-only sprinkler system designs.
(3.5) (2.4) (1.7) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (2.6) (3.5) (1.5) (0.7) (3.5) (1.5) (0.7) (3.5)
20 (6.1) 12 @ 50 12 @ 35 12 @ 20 12 @ 20 9 @ 40 9 @ 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
Page 35
8-34
8-34 Protection for Automatic Storage
Page 36 FM Global Property Loss Prevention Data Sheets
Table 17. Ceiling-Level Sprinkler System Hose Demand and Water Supply Duration
Ceiling Sprinkler Spacing Number of Sprinklers in the Water Supply Duration,
Type Ceiling Design Hose Demand, gpm (L/min) minutes
Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
2.2.4.2 Ceiling and In-Rack Sprinkler Systems Installed on a Wet-Pipe Sprinkler System for
Noncombustible Containers with Non-Solid Walls, Closed-Top Unexpanded Plastic Containers, and
Adequately Vented Open-Top Unexpanded Plastic Containers
2.2.4.2.1 Ceiling and In-Rack Sprinkler Systems
The ceiling and in-rack sprinkler systems for this section can be either wet-pipe or consist of a 20% to 30%
propylene glycol antifreeze solution.
2.2.4.2.2 Horizontal Location of In-Rack Sprinklers
See Section 2.2.6.2 for the recommended horizontal in-rack sprinkler arrangements protecting
noncombustible containers with non-solid walls, closed-top unexpanded plastic containers, and adequately
vented open-top unexpanded plastic containers, when the in-rack sprinklers are on a wet system.
2.2.4.2.3 Vertical Location of In-Rack Sprinklers
The maximum vertical distance between in-rack sprinklers is 15 ft (4.6 m).
2.2.4.2.4 In-Rack Sprinkler Design for Noncombustible Containers with Non-Solid Walls, Closed-Top
Unexpanded Plastic Containers, or Adequately Vented Open-Top Unexpanded Plastic Containers
A. When vertical barriers are not needed within the mini-load ASRS, design the in-rack sprinkler system in
accordance with Table 18.
Table 18. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Noncombustible Containers with
Non-Solid Walls, Closed-Top Unexpanded Plastic Containers, and Adequately Vented Open-Top Unexpanded Plastic
Containers
In-Rack Sprinkler Design Flow
Maximum from Most Remote In-Rack
Vertical Sprinkler, gpm (L/min)
Distance Vertical Vertical
Between Minimum Distances Distances
Depth of ASRS In-Rack In-Rack No. of In-Rack Between Tier Between Tier
Rack Row, ft Container Sprinklers, ft Sprinkler Sprinklers in Levels ≥ 9 in. Levels <9 in.
(m) Composition (m) K-Factor Design (225 mm) (225 mm)
Up to 3 (0.9) Noncombustible 10 (3.0) K11.2 (K160) 4 60 (230) 80 (300)
with Non-Solid 15 (4.6) K14.0 (K200) 6 100 (380) 120 (455)
Walls or
Unexpanded
Plastic
Over 3 (0.9) Noncombustible 10 (3.0) K11.2 (K160) 6 60 (230) 80 (300)
and up to 6 with Non-Solid 15 (4.6) K14.0 (K200) 9 100 (380) 120 (455)
(1.8) Walls or
Unexpanded
Plastic
Over 6 (1.8) Noncombustible 10 (3.0) K11.2 (K160) 8 60 (230) 80 (300)
with Non-Solid 15 (4.6) K14.0 (K200) 12 100 (380) 120 (455)
Walls or
Unexpanded
Plastic
B. When vertical barriers are recommended per Section 2.2.1.5.2, instead of using Table 18 to determine
the number of in-rack sprinklers in the in-rack sprinkler design, account for the number of in-rack sprinklers
in the design as follows:
1. Include all the in-rack sprinklers within the footprint created by the vertical barriers, and
2. Include all the in-rack sprinklers within 2 ft (0.6 m) horizontally that are located on the opposite side
of the vertical barriers.
C. In addition to the minimum in-rack sprinkler design flow obtained from Table 18, maintain a minimum in-rack
sprinkler design pressure of 7 psi (0.5 bar).
D. The design obtained from Table 18 applies to the single hydraulically most remote in-rack sprinkler level.
2.2.4.2.5 Ceiling-Level Sprinkler System Designs in Combination with In-Rack Sprinklers for Noncombustible
Containers with Non-Solid Walls, Closed-Top Unexpanded Plastic Containers, and Adequately Vented
Open-Top Unexpanded Plastic Containers
A. Use Table 19 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers.
B. The ceiling-level sprinkler system designs in Table 19 are determined based on the vertical distance
between the top in-rack sprinkler level and the maximum ceiling height of the ASRS protected area.
Page 38
8-34
Walls, (2) Closed-Top Unexpanded Plastic Containers, and (3) Adequately Vented Open-Top Unexpanded Plastic Containers on a Wet-Pipe Sprinkler System
Max.
Max. Vertical Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @ psi (bar)
Storage Distance Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC)
Height Between
Quick-Response Standard-Response Quick-Response Standard-Response
Above Top Top IRAS
IRAS Level and K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
Level, Ceiling, ft (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
ft (m) (m)
0 (0) Any 20 @ 7 9 @ 20 9 @ 20 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 20 @ 7 9 @ 20 9 @ 16 9@7 20 @ 7 9 @ 20 9 @ 20 6 @ 20 20 @ 7 9 @ 20 9@7
©2017-2020 Factory Mutual Insurance Company. All rights reserved.
(0.5) (1.4) (1.4) (1.4) (1.4) (1.4) (2.8) (3.8) (0.5) (1.4) (1.1) (0.5) (0.5) (1.4) (1.4) (1.4) (0.5) (1.4) (0.5)
5 (1.5) 10 (3.0) 20 @ 30 12 @ 25 12 @ 18 9 @ 20 9 @ 20 10 @ 22 9 @ 40 9 @ 55 20 @ 30 20 @ 18 20 @ 16 20 @ 7 20 @ 30 20 @ 18 20 @ 13 10 @ 22 20 @ 30 20 @ 13 20 @ 7
(2.1) (1.7) (1.2) (1.4) (1.4) (1.0) (2.8) (3.8) (2.1) (1.2) (1.1) (0.5) (2.1) (1.2) (0.9) (1.0) (2.1) (0.9) (0.5)
15 (4.6) 25 @ 50 10 @ 35 10 @ 25 9 @ 20 9 @ 20 12 @ 38 9 @ 40 9 @ 55 25 @ 50 25 @ 32 25 @ 16 25 @ 10 25 @ 50 25 @ 32 25 @ 22 12 @ 38 25 @ 50 25 @ 22 25 @ 10
(3.5) (2.4) (1.7) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (2.6) (3.5) (1.5) (0.7)
20 (6.1) 12 @ 50 12 @ 35 12 @ 20 12 @ 20 9 @ 40 9 @ 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
C. When the ceiling and in-rack sprinkler systems have been installed in accordance with Section 2.2.4.2:
1. The ceiling and in-rack sprinkler systems do not need to be hydraulically balanced, and
2. The ceiling and in-rack sprinkler systems do not need to be treated as operating concurrently
2.2.4.2.6 Hose Demand Design and Water Supply Duration
A. See Table 20 to determine the hose demand design and the water supply duration for the ceiling sprinkler
system as well as the in-rack sprinkler system.
Table 20. Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration
Sprinkler Spacing Number of Sprinklers Hose Demand, gpm Water Supply
Sprinkler System Type in the Design (L/min) Duration, minutes
Ceiling Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
In-Rack Standard-Coverage Any 250 (950) 60
B. The hose demand and water supply duration values obtained from Table 20 apply to each sprinkler system
separately and are not required concurrently.
2.2.4.3 Ceiling and In-Rack Sprinkler Systems Installed on a Dry-Pipe or Similar Sprinkler System
for (1) Noncombustible Containers with Non-Solid Walls, (2) Closed-Top Unexpanded Plastic
Containers, and (3) Adequately Vented Open-Top Unexpanded Plastic Containers
2.2.4.3.1 Ceiling and In-Rack Sprinkler Systems
Dry-pipe and similar sprinkler systems include:
A. Dry-pipe sprinkler systems
B. Non-interlocked or single-interlocked preaction sprinkler systems
C. Refrigerated area sprinkler systems
2.2.4.3.2 Sprinklers
A. Ceiling-Level Sprinklers
Install FM Approved, standard-response, 280ºF (140ºC) nominally rated, standard-coverage upright Storage
ceiling-level sprinklers having the K-factor values indicated in Table 22.
B. In-Rack Sprinklers
Install FM Approved, quick-response, 160ºF (70ºC) nominally rated, upright Storage sprinklers having the
appropriate K-factor value indicated in Table 21.
2.2.4.3.3 Horizontal Location of In-Rack Sprinklers
See Section 2.2.6.4 for the recommended horizontal in-rack sprinkler arrangements protecting
noncombustible containers with non-solid walls, closed-top unexpanded plastic containers, and adequately
vented open-top unexpanded plastic containers, when the in-rack sprinklers are on a dry sprinkler system.
2.2.4.3.4 Vertical Location of In-Rack Sprinklers
The maximum vertical distance between in-rack sprinklers is 15 ft (4.6 m).
2.2.4.3.5 In-Rack Sprinkler Design for Noncombustible Containers with Non-Solid Walls, Closed-Top
Unexpanded Plastic Containers, or Adequately Vented Open-Top Unexpanded Plastic Containers
A. When vertical barriers are not needed within the mini-load ASRS, design the in-rack sprinkler system in
accordance with Table 21.
Table 21. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements Using Noncombustible Containers with
Non-Solid Walls, Closed-Top Unexpanded Plastic Containers, and Adequately Vented Open-Top Unexpanded Plastic
Containers
In-Rack Sprinkler Design Flow
Maximum from Most Remote In-Rack
Vertical Sprinkler, gpm (L/min)
Distance Vertical Vertical
Between Minimum Number of Distances Distances
Depth of ASRS In-Rack In-Rack In-Rack No. of In-Rack Between Tier Between Tier
Rack Row, ft Sprinklers, ft Sprinkler Sprinkler Sprinklers in Levels ≥ 9 in. Levels <9 in.
(m) (m) K-Factor Levels Needed Design (225 mm) (225 mm)
Up to 3 (0.9) 10 (3.0) Upright K11.2 1 4 60 (230) 80 (300)
(K160) More than 1 8 (4 on top 2
levels)
15 (4.6) Upright K14.0 1 6 100 (380) 120 (455)
(K200) More than 1 12 (6 on top 2
levels)
Over 3 (0.9) 10 (3.0) Upright K11.2 1 6 60 (230) 80 (300)
and up to 6 (K160) More than 1 12 (6 on top 2
(1.8) levels)
15 (4.6) Upright K14.0 1 9 100 (380) 120 (455)
(K200) More than 1 18 (9 on top 2
levels)
Over 6 (1.8) 10 (3.0) Upright K11.2 1 8 60 (230) 80 (300)
(K160) More than 1 16 (8 on top 2
levels)
15 (4.6) Upright K14.0 1 12 100 (380) 120 (455)
(K200) More than 1 24 (12 on top 2
levels)
B. When vertical barriers are recommended per Section 2.2.1.5.2, instead of using Table 21 to determine
the number of in-rack sprinklers in the in-rack sprinkler design, account for the number of in-rack sprinklers
in the design as follows:
1. Include all the in-rack sprinklers within the footprint created by the vertical barriers, and
2. Include all the in-rack sprinklers within 2 ft (0.6 m) horizontally that are located on the opposite side
of the vertical barriers.onf
C. In addition to the minimum in-rack sprinkler design flow obtained from Table 21, maintain a minimum in-rack
sprinkler design pressure of 7 psi (0.5 bar).
2.2.4.3.6 Ceiling-Level Sprinkler System Designs in Combination with In-Rack Sprinklers for Noncombustible
Containers with Non-Solid Walls, Closed-Top Unexpanded Plastic Containers, and Adequately Vented
Open-Top Unexpanded Plastic Containers
A. Use Table 22 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers.
B. The ceiling-level sprinkler system designs in Table 22 are determined based on the vertical distance
between the top in-rack sprinkler level and the maximum ceiling height of the ASRS protected area.
Table 22. Ceiling-Level Protection Guidelines, in Combination with In-Rack Sprinklers, Installed on a Dry-Pipe Sprinkler
Systems for Mini-Load ASRS Storage Arrangements Using (1) Noncombustible Containers with Non-Solid Walls, (2)
Closed-Top Unexpanded Plastic Containers, and (3) Adequately Vented Open-Top Unexpanded Plastic Containers
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements;
Max. Vertical No. of AS @ psi (bar)
Max. Storage Distance Between Dry System, Upright Storage Sprinklers, 280ºF (140ºC)
Height Above Top Top IRAS Level Standard-Response
IRAS Level, ft (m) and Ceiling, ft (m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
0 (0) Any 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 50 (3.5)
5 (1.5) 10 (3.0) 25 @ 30 (2.1) 25 @ 13 (0.9) 25 @ 7 (0.5) 25 @ 50 (3.5)
15 (4.6) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)
10 (3.0) 15 (4.6) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)
C. When the ceiling and in-rack sprinkler systems have been installed in accordance with Section 2.2.4.3:
1. The ceiling and in-rack sprinkler systems need to be hydraulically balanced at their point of connection,
and
2. The ceiling and in-rack sprinkler systems need to be treated as operating concurrently.
2.2.4.3.7 Hose Demand Design and Water Supply Duration
A. See Table 23 to determine the hose demand design and the water supply duration for the combined
ceiling and in-rack sprinkler system.
Table 23. Combined Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration
Ceiling Sprinkler Spacing Number of Sprinklers in the Water Supply Duration,
Type Ceiling Design Hose Demand, gpm (L/min) minutes
Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
B. The hose demand and water supply duration values obtained from Table 23 apply to the combined ceiling
and in-rack sprinkler system.
2.2.5 Protection of Mini-Load ASRS Storage Arrangements Using Non-Adequately Vented Open-Top
Cellulosic and Unexpanded Plastic Containers and Adequately Vented Open-Top Cellulosic
Containers
Note that the protection of expanded plastic containers is outside the scope of this data sheet.
See Appendix A for the definition of an adequately vented container.
2.2.5.1 Ceiling-Only Sprinkler System Design Criteria for Non-Adequately Vented Open-Top Cellulosic
and Unexpanded Plastic Containers and Adequately Vented Open-Top Cellulosic Containers
2.2.5.1.1 In-rack sprinklers are recommended in combination with ceiling-level sprinklers when:
A. The storage height of the mini-load ASRS storage arrangement exceeds 10 ft (3.0 m), or
B. The ceiling height over the mini-load ASRS storage array exceeds 20 ft (6.1 m), or
C. A ceiling-only protection is not provided in Table 24 for the specific sprinkler being installed at ceiling
level, or
D. The water supply cannot provide the flow and pressure requirements for any of the protection options
offered in Table 24
When in-rack sprinklers are recommended, see Section 2.2.5.2 for ceiling and in-rack sprinkler systems
installed on a wet-pipe sprinkler system, or Section 2.2.5.3 for ceiling and in-rack sprinkler systems installed
on a dry-pipe sprinkler system.
2.2.5.1.2 Use Table 24 to determine the ceiling-only sprinkler system designs for non-adequately vented
cellulosic and unexpanded plastic containers.
2.2.5.1.3 Use Table 25 to determine the ceiling-only sprinkler system designs for adequately vented open-top
cellulosic containers.
Table 25. Ceiling-Level Protection Guidelines for Mini-Load ASRS Storage Arrangements Using Adequately Vented Open-Top Cellulosic Containers; Maximum Storage Height of 10
ft (3.0 m)
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @ psi (bar)
Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC) Dry System, Upright Storage Sprinklers,
Max. 280ºF (140ºC)
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response Standard-Response
Height, ft K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2 K11.2 K16.8 K25.2 K33.6
(m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360) (K160) (K240) (K360) (K480)
10 (3.0) 20 @ 30 12 @ 25 12 @ 18 9 @ 20 9 @ 20 10 @ 22 9 @ 40 9 @ 55 20 @ 30 20 @ 18 20 @ 16 20 @ 7 20 @ 30 20 @ 18 20 @ 13 10 @ 22 20 @ 30 20 @ 13 20 @ 7 25 @ 30 25 @ 13 25 @ 7 25 @ 50
(2.1) (1.7) (1.2) (1.4) (1.4) (1.0) (2.8) (3.8) (2.1) (1.2) (1.1) (0.5) (2.1) (1.2) (0.9) (1.0) (2.1) (0.9) (0.5) (2.1) (0.9) (0.5) (3.5)
15 (4.6) 25 @ 50 10 @ 35 10 @ 25 9 @ 20 9 @ 20 12 @ 38 9 @ 40 9 @ 55 25 @ 50 25 @ 32 25 @ 16 25 @ 10 25 @ 50 25 @ 32 25 @ 22 12 @ 38 25 @ 50 25 @ 22 25 @ 10 30 @ 50 30 @ 22 30 @ 10 30 @ 50
(3.5) (2.4) (1.7) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (2.6) (3.5) (1.5) (0.7) (3.5) (1.5) (0.7) (3.5)
20 (6.1) 12 @ 50 12 @ 35 12 @ 20 12 @ 20 9 @ 40 9 @ 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
Page 43
8-34
8-34 Protection for Automatic Storage
Page 44 FM Global Property Loss Prevention Data Sheets
Table 26. Ceiling-Level Sprinkler System Hose Demand and Water Supply Duration
Ceiling Sprinkler Spacing Number of Sprinklers in the Water Supply Duration,
Type Ceiling Design Hose Demand, gpm (L/min) minutes
Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
2.2.5.2 Ceiling and In-Rack Sprinkler Systems Installed on a Wet-Pipe Sprinkler System for Non-
Adequately Vented Cellulosic and Unexpanded Plastic Open-Top Containers and Adequately Vented
Open-Top Cellulosic Containers
2.2.5.2.1 Ceiling and In-Rack Sprinkler Systems
The ceiling and in-rack sprinkler systems for this section can be either wet-pipe or consist of a 20% to 30%
propylene glycol antifreeze solution.
2.2.5.2.2 Horizontal Location of In-Rack Sprinklers
See Section 2.2.6.3 for the recommended horizontal in-rack sprinkler arrangements protecting non-
adequately vented cellulosic and unexpanded plastic open-top containers and adequately vented open-top
cellulosic containers, when the in-rack sprinklers are on a wet system.
2.2.5.2.3 Vertical Location of In-Rack Sprinklers
The maximum vertical distance between in-rack sprinklers is as follows:
A. Non-adequately vented cellulosic and unexpanded plastic open-top containers: 10 ft (3.0 m)
B. Adequately vented open-top cellulosic containers: 15 ft (4.6 m)
2.2.5.2.4 In-Rack Sprinkler Design for Non-Adequately Vented Cellulosic and Unexpanded Plastic Open-Top
Containers and Adequately Vented Open-Top Cellulosic Containers
A. When vertical barriers are not needed within the mini-load ASRS, design the in-rack sprinkler system in
accordance with Table 27.
Table 27. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Non-Adequately Vented Cellulosic
and Unexpanded Plastic Open-Top Containers and Adequately Vented Open-Top Cellulosic Containers
In-Rack Sprinkler Design Flow
Maximum from Most Remote In-Rack
Vertical Sprinkler, gpm (L/min)
Distance Vertical Vertical
Between Minimum Distances Distances
Depth of ASRS In-Rack In-Rack No. of In-Rack Between Tier Between Tier
Rack Row, ft Container Sprinklers, ft Sprinkler Sprinklers in Levels ≥ 9 in. Levels <9 in.
(m) Composition (m) K-Factor Design (225 mm) (225 mm)
Up to 3 (0.9) Non- 10 (3.0) K11.2 (K160) 4 100 (380) 120 (455)
Adequately
Vented
Cellulosic and
Unexpanded
Plastic Open-
Top
Adequately 10 (3.0) K11.2 (K160) 4 60 (230) 80 (300)
Vented Open- 15 (4.6) K14.0 (K200) 6 100 (380) 120 (455)
Top Cellulosic
Over 3 (0.9) Non- 10 (3.0) K11.2 (K160) 6 100 (380) 120 (455)
and up to 6 Adequately
(1.8) Vented
Cellulosic and
Unexpanded
Plastic Open-
Top
Adequately 10 (3.0) K11.2 (K160) 6 60 (230) 80 (300)
Vented Open- 15 (4.6) K14.0 (K200) 9 100 (380) 120 (455)
Top Cellulosic
Over 6 (1.8) Non- 10 (3.0) K11.2 (K160) 8 100 (380) 120 (455)
Adequately
Vented
Cellulosic and
Unexpanded
Plastic Open-
Top
Adequately 10 (3.0) K11.2 (K160) 8 60 (230) 80 (300)
Vented Open- 15 (4.6) K14.0 (K200) 12 100 (380) 120 (455)
Top Cellulosic
B. When vertical barriers are recommended per Section 2.2.1.5.2, instead of using Table 27 to determine
the number of in-rack sprinklers in the in-rack sprinkler design, account for the number of in-rack sprinklers
in the design as follows:
1. Include all the in-rack sprinklers within the footprint created by the vertical barriers, and
2. Include all the in-rack sprinklers within 2 ft (0.6 m) horizontally that are located on the opposite side
of the vertical barriers.
C. In addition to the minimum in-rack sprinkler design flow obtained from Table 27, maintain a minimum in-rack
sprinkler design pressure of 7 psi (0.5 bar).
D. The design obtained from Table 27 applies to the single hydraulically most remote in-rack sprinkler level.
2.2.5.2.5 Ceiling-Level Sprinkler System Designs in Combination with In-Rack Sprinklers for Non-Adequately
Vented Cellulosic and Unexpanded Plastic Open-Top Containers and Adequately Vented Open-Top Cellulosic
Containers
A. Use Table 28 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers
for non-adequately vented cellulosic and unexpanded plastic open-top containers.
B. Use Table 29 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers
for adequately vented open-top cellulosic containers.
C. The ceiling-level sprinkler system designs in Tables 28 and 29 are determined based on the vertical
distance between the top in-rack sprinkler level and the maximum ceiling height of the ASRS protected area.
(0.5) (1.4) (1.4) (1.4) (1.4) (1.4) (2.8) (3.8) (0.5) (1.4) (1.1) (0.5) (0.5) (1.4) (1.4) (1.4) (0.5) (1.4) (0.5)
5 (1.5) 10 (3.0) 25 @ 50 12 @ 25 12 @ 18 9 @ 20 9 @ 20 12 @ 38 9 @ 40 9 @ 55 25 @ 50 25 @ 32 25 @ 16 25 @ 10 25 @ 50 25 @ 32 25 @ 18 12 @ 38 25 @ 50 25 @ 18 25 @ 10
(3.5) (1.7) (1.2) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.2) (2.6) (3.5) (1.2) (0.7)
15 (4.6) 12 @ 50 12 @ 35 12 @ 20 10 @ 20 9 @ 40 9 @ 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
20 (6.1) 12 @ 75 12 @ 52 12 @ 29 12 @ 23 9 @ 40 9 @ 55
(5.2) (3.6) (2.0) (1.6) (2.8) (3.8)
10 (3.0) 15 (4.6) 12 @ 50 12 @ 35 12 @ 20 10 @ 20 9 @ 40 9 @ 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
20 (6.1) 12 @ 75 12 @ 52 12 @ 29 12 @ 23 9 @ 40 9 @ 55
(5.2) (3.6) (2.0) (1.6) (2.8) (3.8)
Page 47
8-34
Table 29. Ceiling-Level Protection Guidelines, in Combination with In-Rack Sprinklers, for Mini-Load ASRS Storage Arrangements with Adequately Vented Open-Top Cellulosic
Page 48
8-34
Containers on a Wet-Pipe Sprinkler System
Max.
Max. Vertical Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements; No. of AS @ psi (bar)
Storage Distance Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC)
Height Between
Quick-Response Standard-Response Quick-Response Standard-Response
Above Top Top IRAS
IRAS Level and K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
Level, Ceiling, (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
ft (m) ft (m)
0 (0) Any 20 @ 7 9 @ 20 9 @ 20 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 20 @ 7 9 @ 20 9 @ 16 9@7 20 @ 7 9 @ 20 9 @ 20 6 @ 20 20 @ 7 9 @ 20 9@7
©2017-2020 Factory Mutual Insurance Company. All rights reserved.
(0.5) (1.4) (1.4) (1.4) (1.4) (1.4) (2.8) (3.8) (0.5) (1.4) (1.1) (0.5) (0.5) (1.4) (1.4) (1.4) (0.5) (1.4) (0.5)
5 (1.5) 10 (3.0) 20 @ 30 12 @ 25 12 @ 18 9 @ 20 9 @ 20 10 @ 22 9 @ 40 9 @ 55 20 @ 30 20 @ 18 20 @ 16 20 @ 7 20 @ 30 20 @ 18 20 @ 13 10 @ 22 20 @ 30 20 @ 13 20 @ 7
(2.1) (1.7) (1.2) (1.4) (1.4) (1.0) (2.8) (3.8) (2.1) (1.2) (1.1) (0.5) (2.1) (1.2) (0.9) (1.0) (2.1) (0.9) (0.5)
15 (4.6) 25 @ 50 10 @ 35 10 @ 25 9 @ 20 9 @ 20 12 @ 38 9 @ 40 9 @ 55 25 @ 50 25 @ 32 25 @ 16 25 @ 10 25 @ 50 25 @ 32 25 @ 22 12 @ 38 25 @ 50 25 @ 22 25 @ 10
(3.5) (2.4) (1.7) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (2.6) (3.5) (1.5) (0.7)
20 (6.1) 12 @ 50 12 @ 35 12 @ 20 12 @ 20 9 @ 40 9 @ 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
D. When the ceiling and in-rack sprinkler systems have been installed in accordance with Section 2.2.5.2:
1. The ceiling and in-rack sprinkler systems do not need to be hydraulically balanced, and
2. The ceiling and in-rack sprinkler systems do not need to be treated as operating concurrently
2.2.5.2.6 Hose Demand Design and Water Supply Duration
A. See Table 30 to determine the hose demand design and the water supply duration for the ceiling sprinkler
system as well as the in-rack sprinkler system.
Table 30. Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration
Sprinkler Spacing Number of Sprinklers Hose Demand, gpm Water Supply
Sprinkler System Type in the Design (L/min) Duration, minutes
Ceiling Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
In-Rack Standard-Coverage Any 250 (950) 60
B. The hose demand and water supply duration values obtained from Table 30 apply to each sprinkler system
separately and are not required concurrently.
2.2.5.3 Ceiling and In-Rack Sprinkler Systems Installed on a Dry-Pipe Sprinkler System for Non-
Adequately Vented Cellulosic and Unexpanded Plastic Open-Top Containers and Adequately Vented
Open-Top Cellulosic Containers
2.2.5.3.1 Ceiling and In-Rack Sprinkler Systems
Dry-pipe or similar sprinkler systems include:
A. Dry-pipe sprinkler systems
B. Non-interlocked or single-interlocked preaction sprinkler systems
C. Refrigerated area sprinkler systems
2.2.5.3.2 Sprinklers
A. Ceiling-Level Sprinklers
Install FM Approved, standard-response, 280ºF (140ºC) nominally rated, standard-coverage upright Storage
ceiling-level sprinklers having the K-factor values indicated in Table 30.
B. In-Rack Sprinklers
Install FM Approved, quick-response, 160ºF (70ºC) nominally rated, upright Storage sprinklers having the
appropriate K-factor value indicated in Table 29.
2.2.5.3.3 Horizontal Location of In-Rack Sprinklers
See Section 2.2.6.4 for the recommended horizontal in-rack sprinkler arrangements protecting non-
adequately vented cellulosic and unexpanded plastic open-top containers and adequately vented open-top
cellulosic containers, when the in-rack sprinklers are on a dry sprinkler system.
2.2.5.3.4 Vertical Location of In-Rack Sprinklers
The maximum vertical distance between in-rack sprinklers is as follows:
A. Non-adequately vented cellulosic and unexpanded plastic open-top containers: 10 ft (3.0 m)
B. Adequately vented open-top cellulosic containers: 15 ft (4.6 m)
2.2.5.3.5 In-Rack Sprinkler Design for Non-Adequately Vented Cellulosic and Unexpanded Plastic Open-Top
Containers and Adequately Vented Open-Top Cellulosic Containers
Table 31. In-Rack Sprinkler Designs for Mini-Load ASRS Storage Arrangements with Non-Adequately Vented Cellulosic
and Unexpanded Plastic Open-Top Containers and Adequately Vented Open-Top Cellulosic Containers
In-Rack Sprinkler Design
Flow from Most Remote
Maximum In-Rack Sprinkler, gpm
Vertical (L/min)
Distance Number of Vertical Vertical
Between Minimum In-Rack No. of Distances Distances
Depth of In-Rack In-Rack Sprinkler In-Rack Between Tier Between Tier
ASRS Rack Container Sprinklers, ft Sprinkler Levels Sprinklers in Levels ≥ 9 Levels <9 in.
Row, ft (m) Type (m) K-Factor Needed Design in. (225 mm) (225 mm)
Up to 3 (0.9) Non- 10 (3.0) Upright 1 4 100 (380) 120 (455)
Adequately K11.2 (K160) More than 1 8 (4 on top 2
Vented levels)
Cellulosic
and
Unexpanded
Plastic Open-
Top
Adequately 10 (3.0) Upright 1 4 60 (230) 80 (300)
Vented K11.2 (K160) More than 1 8 (4 on top 2
Open-Top levels)
Cellulosic 15 (4.6) Upright 1 6 100 (380) 120 (455)
K14.0 (K200) More than 1 12 (6 on top
2 levels)
Over 3 (0.9) Non- 10 (3.0) Upright 1 6 100 (380) 120 (455)
and up to 6 Adequately K11.2 (K160) More than 1 12 (6 on top
(1.8) Vented 2 levels)
Cellulosic
and
Unexpanded
Plastic Open-
Top
Adequately 10 (3.0) Upright 1 6 60 (230) 80 (300)
Vented K11.2 (K160) More than 1 12 (6 on top
Open-Top 2 levels)
Cellulosic 15 (4.6) Upright 1 9 100 (380) 120 (455)
K14.0 (K200) More than 1 18 (9 on top
2 levels)
Over 6 (1.8) Non- 10 (3.0) Upright 1 8 100 (380) 120 (455)
Adequately K11.2 (K160) More than 1 16 (8 on top
Vented 2 levels)
Cellulosic
and
Unexpanded
Plastic Open-
Top
Adequately 10 (3.0) Upright 1 8 60 (230) 80 (300)
Vented K11.2 (K160) More than 1 16 (8 on top
Open-Top 2 levels)
Cellulosic 15 (4.6) Upright 1 12 100 (380) 120 (455)
K14.0 (K200) More than 1 24 (12 on
top 2 levels)
B. In addition to the minimum in-rack sprinkler design flow obtained from Table 31, maintain a minimum in-rack
sprinkler design pressure of 7 psi (0.5 bar).
2.2.5.3.6 Ceiling-Level Sprinkler System Designs in Combination with In-Rack Sprinklers for Non-Adequately
Vented Cellulosic and Unexpanded Plastic Open-Top Containers and Adequately Vented Open-Top Cellulosic
Containers
A. Use Table 32 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers
for non-adequately vented cellulosic and unexpanded plastic open-top containers.
B. Use Table 33 to determine the ceiling-level sprinkler system designs in combination with in-rack sprinklers
for adequately vented open-top cellulosic containers.
C. The ceiling-level sprinkler system designs in Tables 32 and 33 are determined based on the vertical
distance between the top in-rack sprinkler level and the maximum ceiling height of the ASRS protected area.
Table 32. Ceiling-Level Protection Guidelines in Combination with In-Rack Sprinklers Installed on a Dry-Pipe Sprinkler
Systems for Mini-Load ASRS Storage Arrangements with Non-Adequately Vented Cellulosic and Unexpanded Plastic
Open-Top Containers
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements;
Max. Vertical No. of AS @ psi (bar)
Max. Storage Distance Between Dry System, Upright Storage Sprinklers, 280ºF (140ºC)
Height Above Top Top IRAS Level Standard-Response
IRAS Level, ft (m) and Ceiling, ft (m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
0 (0) Any 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 50 (3.5)
5 (1.5) 10 (3.0) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)
Table 33. Ceiling-Level Protection Guidelines, in Combination with In-Rack Sprinklers, Installed on a Dry-Pipe Sprinkler
Systems for Mini-Load ASRS Storage Arrangements Using Adequately Vented Open-Top Cellulosic Containers
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements;
Max. Vertical No. of AS @ psi (bar)
Max. Storage Distance Between Dry System, Upright Storage Sprinklers, 280ºF (140ºC)
Height Above Top Top IRAS Level Standard-Response
IRAS Level, ft (m) and Ceiling, ft (m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
0 (0) Any 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 50 (3.5)
5 (1.5) 10 (3.0) 25 @ 30 (2.1) 25 @ 13 (0.9) 25 @ 7 (0.5) 25 @ 50 (3.5)
15 (4.6) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)
10 (3.0) 15 (4.6) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)
D. When the ceiling and in-rack sprinkler systems have been installed in accordance with Section 2.2.5.3:
1. the ceiling and in-rack sprinkler systems need to be hydraulically balanced at their point of connection,
and
2. the ceiling and in-rack sprinkler systems need to be treated as operating concurrently.
2.2.5.3.7 Hose Demand Design and Water Supply Duration
A. See Table 34 to determine the hose demand design and the water supply duration for the combined ceiling
and in-rack sprinkler system.
B. The hose demand and water supply duration values obtained from Table 34 apply to the combined ceiling
and in-rack sprinkler system.
Table 34. Combined Ceiling and In-Rack Sprinkler System Hose Demand and Water Supply Duration
Ceiling Sprinkler Spacing Number of Sprinklers in the Water Supply Duration,
Type Ceiling Design Hose Demand, gpm (L/min) minutes
Standard-Coverage Up to 12 250 (950) 60
13 to 19 500 (1900) 90
20 or More 500 (1900) 120
Extended-Coverage Up to 6 250 (950) 60
7 to 9 500 (1900) 90
10 or More 500 (1900) 120
2.2.6 Horizontal In-Rack Sprinkler Arrangements for Mini-Load ASRS Storage Arrangements
Noncombustible
Solid-Walled
Containers Max. 10 ft
Max. 2 ft
(3.0 m)
(0.6 m)
Max. 3 ft
(0.9 m)
IRAS
Fig. 4. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths up to 3 ft (0.9 m)
B. Individual Rack Rows with Rack Row Depths Over 3 ft (0.9 m) and Up to 6 ft (1.8 m)
Install face in-rack sprinklers using a horizontal arrangement as follows:
1. At transverse flue spaces on maximum 10 ft (3.0 m) linear spacing, and
2. Located no more than 2 ft (0.6 m) horizontally from the face of the storage array, and
3. Located no more than 2 ft (0.6 m) horizontally from the ends of the rack rows.
See Figure 5 for an example of this guidance.
Noncombustible
Solid-Walled
Containers Max. 10 ft
Max. 2 ft
(3.0 m)
(0.6 m)
Max. 2 ft
(0.6 m)
Max. 6 ft
(1.8 m)
IRAS
Fig. 5. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over 3 ft (0.9 m) and up
to 6 ft (1.8 m)
C. Back-to-Back Rack Rows with Rack Row Depths Over 3 ft (0.9 m) and Up to 6 ft (1.8 m)
Install face and longitudinal in-rack sprinklers using a horizontal arrangement as follows:
1. Install face in-rack sprinklers at transverse flue spaces on maximum 10 ft (3.0 m) linear spacing, and
2. Locate the face in-rack sprinklers no more than 2 ft (0.6 m) horizontally from the face of the storage
array, and
3. Install longitudinal in-rack sprinklers on maximum 10 ft (3.0 m) linear spacing within a maximum 2 ft
(0.6 m) wide longitudinal flue, and
4. Provide face and longitudinal in-rack sprinklers within 2 ft (0.6 m) horizontally from the ends of the rack
rows
See Figure 6 for an example of this guidance.
D. Individual Rack Rows with Rack Row Depths Over 6 ft (1.8 m)
Install face and transverse in-rack sprinklers using a horizontal arrangement as follows:
1. Install face in-rack sprinklers at transverse flue spaces on maximum 10 ft (3.0 m) linear spacing, and
2. Locate the face in-rack sprinklers no more than 2 ft (0.6 m) horizontally from the face of the storage
array, and
3. Install in-rack sprinklers within the transverse flue spaces on maximum 10 ft (3.0 m) spacing, and
4. Provide face and transverse in-rack sprinklers no more than 2 ft (0.6 m) horizontally from the ends of
the rack rows
See Figure 7 for an example of this guidance.
E. Back-to-Back Rack Rows with Rack Row Depths over 6 ft (1.8 m)
Install face, transverse and longitudinal in-rack sprinklers using a horizontal arrangement as follows:
1. Install face in-rack sprinklers at transverse flue spaces on maximum 10 ft (3.0 m) linear spacing, and
2. Locate the face in-rack sprinklers no more than 2 ft (0.6 m) horizontally from the face of the storage
array, and
Noncombustible
Solid-Walled
Containers Max. 10 ft
Max. 2 ft
(3.0 m)
(0.6 m)
Max. 2 ft
(0.6 m)
Max. 6 ft
(1.8 m)
Max. 2 ft
(0.6 m)
IRAS
Fig. 6. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over 3 ft (0.9 m) and
up to 6 ft (1.8 m)
Noncombustible
Solid-Walled Max. 10 ft
Max. 2 ft Containers (3.0 m)
(0.6 m) IRAS
Max. 2 ft
(0.6 m)
Max. 10 ft
(3.0 m)
Over 6 ft
(1.8 m)
Max. 10 ft
(3.0 m)
Max. 2 ft
(0.6 m)
Fig. 7. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over 6 ft (1.8 m)
3. Install longitudinal in-rack sprinklers on maximum 10 ft (3.0 m) linear spacing within a maximum 2 ft
(0.6 m) wide longitudinal flue, and
4. Install in-rack sprinklers within the transverse flue spaces on maximum 10 ft (3.0 m) spacing, and
5. Provide face and longitudinal in-rack sprinklers no more than 2 ft (0.6 m) horizontally from the ends
of the rack rows.
Max. 10 ft
Max. 2 ft (3.0 m)
(0.6 m)
Max. 2 ft
(0.6 m)
Max. 10 ft
(3.0 m)
Over 6 ft
(1.8 m)
Max. 10 ft
(3.0 m)
Max. 2 ft
(0.6 m)
IRAS
Noncombustible
Solid-Walled
Containers
Fig. 8. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over 6 ft (1.8 m)
2.2.6.2 Horizontal In-Rack Sprinkler Arrangements Using a Maximum 4 ft (1.2 m) or Every Other Transverse
Flue Space In-Rack Sprinkler Arrangement on a Wet In-Rack Sprinkler System
2.2.6.2.1 The horizontal in-rack sprinkler arrangements in Section 2.2.6.2 apply to the following:
A. Storage maintained on trays
B. Noncombustible containers with non-solid walls
C. Closed-top unexpanded plastic containers
D. Adequately vented open-top unexpanded plastic containers
2.2.6.2.2 The horizontal in-rack sprinkler arrangements for the material handling trays and containers
indicated in Section 2.2.6.2.1 are as follows:
A. Individual Rack Rows with Rack Row Depths up to 3 ft (0.9 m)
Install the in-rack sprinklers using a horizontal arrangement as follows:
1. At transverse flue spaces on maximum 4 ft (1.2 m) linear spacing or every other transverse flue space,
whichever is shorter, and
2. Located no more than 18 in. (450 mm) horizontally from the face of the storage array, and
3. Located at each end of the rack row
See Figure 9 for an example of this guidance.
B. Individual Rack Rows with Rack Row Depths over 3 ft (0.9 m) and up to 6 ft (1.8 m)
Install face in-rack sprinklers using a horizontal arrangement as follows:
Containers
Max. 4 ft
or Trays
(1.2 m)
Max. 18 in.
(450 mm) Max. 3 ft
(0.9 m)
Fig. 9. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths up to 3 ft (0.9 m)
1. At transverse flue spaces on maximum 4 ft (1.2 m) linear spacing or every other transverse flue space,
whichever is shorter, and
2. Located no more than 18 in. (450 mm) horizontally from the face of the storage array, and
3. Staggered on either side of the rack row, and
4. Provided at each corner of the rack row
See Figure 10 for an example of this guidance.
Containers
or Trays Max. 4 ft
(1.2 m)
Max. 18 in.
(450 mm)
Max. 6 ft
(1.8 m)
C. Back-to-Back Rack Rows with Rack Row Depths over 3 ft (0.9 m) and up to 6 ft (1.8 m)
Install face and longitudinal in-rack sprinklers using a horizontal arrangement as follows:
1. Install face in-rack sprinklers at transverse flue spaces on maximum 4 ft (1.2 m) linear spacing or every
other transverse flue space, whichever is shorter, and
2. Locate the face in-rack sprinklers no more than 18 in. (450 mm) horizontally from the face of the storage
array, and
3. Install longitudinal in-rack sprinklers on maximum 2 ft (0.6 m) linear spacing within a maximum 2 ft
(0.6 m) wide longitudinal flue, and
4. Provide face and longitudinal in-rack sprinklers at the ends of the rack rows
See Figure 11 for an example of this guidance.
Containers
or Trays Max. 2 ft Max. 4 ft
(0.6 m) (1.2 m)
Max. 18 in.
(450 mm)
Max. 6 ft
(1.8 m)
Max. 2 ft
(0.6 m)
IRAS @ End of
Rack Rows
IRAS
Fig. 11. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over 3 ft (0.9 m) and
up to 6 ft (1.8 m)
Max.
Face IRAS @ 18 in.
Each Corner (450 mm)
Max. 3 ft
(0.9 m)
Fig. 12. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over 6 ft (1.8 m)
5. Install in-rack sprinklers within the transverse flue spaces on maximum 6 ft (1.8 m) spacing, and
6. Limit the horizontal distance between a transverse flue space in-rack sprinkler and the face of the
storage array, that is not protected with a face sprinkler, to 3 ft (0.9 m), and
7. Provide face and longitudinal in-rack sprinklers at the ends of the rack rows
See Figure 13 for an example of this guidance.
2.2.6.3 Horizontal In-Rack Sprinkler Arrangements Using a Maximum 2 ft (0.6 m) Horizontal Face
In-Rack Sprinkler Arrangement on a Wet In-Rack Sprinkler System
2.2.6.3.1 The horizontal in-rack sprinkler arrangements in Section 2.2.6.3 apply to the following:
A. Closed-top cellulosic containers
B. Non-adequately vented open-top cellulosic and unexpanded plastic containers
C. Adequately vented open-top cellulosic containers
2.2.6.3.2 The horizontal in-rack sprinkler arrangements for the material handling containers indicated in
Section 2.2.6.3.1 are as follows:
A. Individual Rack Rows with Rack Row Depths up to 3 ft (0.9 m)
Install the in-rack sprinklers using a horizontal arrangement as follows:
1. At transverse flue spaces on maximum 2 ft (0.6 m) linear spacing, and
2. Located no more than 18 in. (450 mm) horizontally from the face of the storage array, and
3. Located at each end of the rack row
See Figure 14 for an example of this guidance.
B. Individual Rack Rows with Rack Row Depths over 3 ft (0.9 m) and up to 6 ft (1.8 m)
Install face in-rack sprinklers using a horizontal arrangement as follows:
1. At transverse flue spaces on maximum 2 ft (0.6 m) linear spacing, and
2. Located no more than 18 in. (450 mm) horizontally from the face of the storage array, and
3. Provided at the ends of each rack row
See Figure 15 for an example of this guidance.
Max. 2 ft Max. 4 ft
(0.6 m) (1.2 m)
Max. 18 in.
(450 mm)
Max. 3 ft
(0.9 m)
Max. 6 ft
(1.8 m)
Over 6 ft
(1.8 m)
Max. 6 ft
(1.8 m)
Max. 6 ft
(1.8 m)
Max. 2 ft
(0.6 m)
IRAS
Trays or
Containers
Face IRAS @
Each Corner
Max. 18 in.
(450 mm)
Fig. 13. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over 6 ft (1.8 m)
Containers Max. 2 ft
or Trays (0.6 m)
Max. 18 in.
(450 mm) Max. 3 ft
(0.9 m)
Fig. 14. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths up to 3 ft (0.9 m)
C. Back-to-Back Rack Rows with Rack Row Depths over 3 ft (0.9 m) and up to 6 ft (1.8 m)
Install face and longitudinal in-rack sprinklers using a horizontal arrangement as follows:
1. Install face in-rack sprinklers at transverse flue spaces on maximum 2 ft (0.6 m) linear spacing, and
Containers
or Trays
Max. 2 ft
(0.6 m)
Max. 18 in.
(450 mm)
Max. 6 ft
(1.8 m)
IRAS @ End of
IRAS
Each Storage
Array
Fig. 15. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over 3 ft (0.9 m) and up
to 6 ft (1.8 m)
2. Locate the face in-rack sprinklers no more than 18 in. (450 mm) horizontally from the face of the storage
array, and
3. Install longitudinal in-rack sprinklers on maximum 2 ft (0.6 m) linear spacing within a maximum 2 ft
(0.6 m) wide longitudinal flue, and
4. Provide face and longitudinal in-rack sprinklers at the ends of the rack rows
See Figure 16 for an example of this guidance.
D. Individual Rack Rows with Rack Row Depths over 6 ft (1.8 m)
Install face and transverse in-rack sprinklers using a horizontal arrangement as follows:
1. Install face in-rack sprinklers at transverse flue spaces on maximum 2 ft (0.6 m) linear spacing, and
2. Locate the face in-rack sprinklers no more than 18 in. (450 mm) horizontally from the face of the storage
array, and
3. Install in-rack sprinklers within the transverse flue spaces on maximum 6 ft (1.8 m) spacing, and
4. Provide in-rack sprinklers at the ends of each rack row
See Figure 17 for an example of this guidance.
E. Back-to-Back Rack Rows with Rack Row Depths over 6 ft (1.8 m)
Install face, transverse and longitudinal in-rack sprinklers using a horizontal arrangement as follows:
1. Install face in-rack sprinklers at transverse flue spaces on maximum 2 ft (0.6 m) linear spacing, and
2. Locate the face in-rack sprinklers no more than 18 in. (450 mm) horizontally from the face of the storage
array, and
3. Install longitudinal in-rack sprinklers on maximum 2 ft (0.6 m) linear spacing within a maximum 2 ft
(0.6 m) wide longitudinal flue, and
4. Install in-rack sprinklers within the transverse flue spaces on maximum 6 ft (1.8 m) spacing, and
5. Provide in-rack sprinklers at the ends of each rack row
Containers
or Trays Max. 2 ft
(0.6 m) IRAS
Max. 18 in.
(450 mm)
Max. 6 ft
(1.8 m)
Max. 2 ft
(0.6 m)
IRAS @ End of
Each Storage
Array
Fig. 16. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over 3 ft (0.9 m) and
up to 6 ft (1.8 m)
Trays or Max. 2 ft
Containers (0.6 m)
IRAS
Max.
18 in.
(450 mm)
Max. 6 ft
(1.8 m)
Over 6 ft
(1.8 m)
Max. 6 ft
(1.8 m)
Max.
18 in.
(450 mm)
IRAS @ End
of Each Storage
Array
Fig. 17. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over 6 ft (1.8 m)
2.2.6.4 Horizontal In-Rack Sprinkler Arrangements for Dry In-Rack Sprinkler Systems
2.2.6.4.1 See Section 2.2.6.1 for the horizontal in-rack sprinkler arrangements installed on a dry system for
open-top noncombustible containers with solid walls.
Max. 2 ft
(0.6 m)
Max. 18 in.
(450 mm)
Max. 6 ft
(1.8 m)
Over 6 ft
(1.8 m)
Max. 6 ft
(1.8 m)
Max. 2 ft
(0.6 m)
IRAS
IRAS @ End of
Each Storage
Array Trays or
Containers
Fig. 18. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over 6 ft (1.8 m)
2.2.6.4.2 The horizontal in-rack sprinkler arrangements in Section 2.2.6.4 apply to the following:
• Storage maintained on trays
• Noncombustible containers with non-solid walls
• Closed-top unexpanded plastic containers
• Adequately vented open-top unexpanded plastic containers
• Closed-top cellulosic containers
• Non-adequately vented cellulosic and unexpanded plastic open-top containers
• Adequately vented open-top cellulosic containers
2.2.6.4.3 The horizontal in-rack sprinkler arrangements for the material handling trays and containers
indicated in Section 2.2.6.4.1 are as follows:
A. Individual Rack Rows with Rack Row Depths up to 3 ft (0.9 m)
Install the in-rack sprinklers using a horizontal arrangement as follows:
1. At transverse flue spaces on maximum 4 ft (1.2 m) linear spacing or every other transverse flue space,
whichever is shorter, and
2. Located no more than 18 in. (450 mm) horizontally from the face of the storage array, and
3. Located at each end of the rack row.
See Figure 19 for an example of this guidance.
B. Individual Rack Rows with Rack Row Depths over 3 ft (0.9 m) and up to 6 ft (1.8 m)
Install face in-rack sprinklers using a horizontal arrangement as follows:
1. At transverse flue spaces on maximum 4 ft (1.2 m) linear spacing or every other transverse flue space,
whichever is shorter, and
Containers Max. 4 ft
or Trays (1.2 m)
Max. 18 in.
(450 mm) Max. 3 ft
(0.9 m)
Fig. 19. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths up to 3 ft (0.9 m)
2. Located no more than 18 in. (450 mm) horizontally from the face of the storage array, and
3. Staggered on either side of the rack row
See Figure 20 for an example of this guidance.
Containers
or Trays Max. 4 ft
(1.2 m)
Max. 18 in.
(450 mm)
Max. 6 ft
(1.8 m)
Max. 2 ft IRAS
(0.6 m)
Fig. 20. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over 3 ft (0.9 m) and up
to 6 ft (1.8 m)
C. Back-to-Back Rack Rows with Rack Row Depths over 3 ft (0.9 m) and up to 6 ft (1.8 m)
Install face and longitudinal in-rack sprinklers using a horizontal arrangement as follows:
1. Install face in-rack sprinklers at transverse flue spaces on maximum 4 ft (1.2 m) linear spacing or every
other transverse flue space, whichever is shorter, and
2. Locate the face in-rack sprinklers no more than 18 in. (450 mm) horizontally from the face of the storage
array, and
3. Install longitudinal in-rack sprinklers on maximum 4 ft (1.2 m) linear spacing or every other transverse
flue space, whichever is shorter, within a maximum 2 ft (0.6 m) wide longitudinal flue, and
4. Stagger the face and longitudinal in-rack sprinklers horizontally.
Containers
or Trays Max. 4 ft
(1.2 m)
Max. 18 in.
(450 mm)
Max. 6 ft
(1.8 m)
Max. 2 ft
(0.6 m)
IRAS
Fig. 21. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over 3 ft (0.9 m) and
up to 6 ft (1.8 m)
Max.
18 in.
(450 mm)
Max. 3 ft
(0.9 m)
Fig. 22. Horizontal in-rack sprinkler arrangements for individual rack rows with rack row depths over 6 ft (1.8 m)
5. Install in-rack sprinklers within the transverse flue spaces on maximum 6 ft (1.8 m) spacing, and
6. Limit the horizontal distance between a transverse flue space in-rack sprinkler and the face of the
storage array, that is not protected with a face sprinkler, to 3 ft (0.9 m), and
7. Provide in-rack sprinklers at the ends of the rack rows.
See Figure 23 for an example of this guidance.
Max. 2 ft Max. 4 ft
(0.6 m) (1.2 m)
Max. 18 in.
(450 mm)
Max. 3 ft
(0.9 m)
Max. 6 ft
(1.8 m)
Over 6 ft
(1.8 m)
Max. 6 ft
(1.8 m)
Max. 6 ft
(1.8 m)
Max. 2 ft
(0.6 m)
IRAS
Trays or
Containers
Max. 18 in.
(450 mm)
Fig. 23. Horizontal in-rack sprinkler arrangements for back-to-back rack rows with rack row depths over 6 ft (1.8 m)
2.3.2 Drainage
2.3.2.1 Due to the expected water application duration during a fire event, when possible provide minimum
4 in. (100 mm) high curbing at the perimeter of the storage array in combination with properly designed floor
drainage (account for both ceiling sprinkler discharge and an additional 500 gpm [1900 L/min] for manual
firefighting efforts).
2.3.2.2 The guidelines for drainage in Section 2.3.2.1 are not required when noncombustible solid-walled
containers are used throughout the ASRS storage array.
2.3.3.1 Robots
Arrange the robots so they are void of as much exterior combustible materials as possible. Use
noncombustible materials whenever decorative covers, sidings or other similar identification methods are
needed for the robots.
2.3.4 Detection
Top-Loading Robot
ASRS Grid Area Holding
Areas
Yellow Areas Void
of Storage
Egress to
Mezzanine Level
2.3.5.1.3 When installing a preaction or refrigerated area sprinkler system, see Data Sheet 5-48, Automatic
Fire Detection, for recommendations pertaining to the sprinkler system’s activating detection system.
2.3.5.1.4 Ceiling sprinkler designs for single-interlocked preaction sprinkler systems can be either classified
as “wet-pipe” or “dry-pipe,” depending on the installation of the activating detection system. See Data Sheet
5-48 to determine the installation requirements needed for the detection system to achieve a sprinkler system
design classification of wet pipe. Design the single-interlocked preaction system using the dry-pipe sprinkler
system designs in Table 35 when the detection installation is not in compliance with the recommendations
provided in Data Sheet 5-48 for a wet-pipe sprinkler system design.
2.3.5.1.5 A ceiling-level sprinkler system consisting of 20% to 30% concentration of propylene glycol in water
is acceptable for ambient temperatures between 32ºF (0ºC) and 40ºF (4ºC).
2.3.5.1.6 When installing an antifreeze sprinkler system consisting of a 20% to 30% concentration of
propylene glycol in water, the ceiling designs indicated for a wet-pipe sprinkler system can be used.
2.3.5.1.7 See Data Sheet 2-0 for additional recommendations related to the installation of all sprinkler system
types. See Sheet 8-29, Refrigerated Storage, when a refrigerated area sprinkler system is installed.
30 (9.1) 18 @ 50 12 @ 50 12 @ 35 9 @ 20 9 @ 20 6 @ 25 9 @ 40 9 @ 55 18 @ 50 18 @ 32 9 @ 16 9 @ 10 18 @ 50 12 @ 50 12 @ 35 6 @ 25 18 @ 50 18 @ 22 12 @ 20 20 @ 25 20 @ 10 20 @ 7 12 @ 50
(3.5) (3.5) (2.4) (1.4) (1.4) (1.7) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (1.7) (3.5) (1.5) (1.4) (1.7) (0.7) (0.5) (3.5)
35 (10.7) 9 @ 75 9 @ 52 9 @ 28 9 @ 22 6 @ 60 9 @ 40 9 @ 55 15 @ 25 9 @ 30 9 @ 75 9 @ 52 8 @ 40 20 @ 25 20 @ 10 20 @ 7 12 @ 50
(5.2) (3.6) (1.9) (1.5) (4.1) (2.8) (3.8) (1.7) (2.1) (5.2) (3.6) (2.8) (1.7) (0.7) (0.5) (3.5)
40 (12.2) 9 @ 75 9 @ 52 9 @ 28 9 @ 22 9 @ 40 9 @ 55 9 @ 30 36 @ 55 36 @ 22 12 @ 50 12 @ 50
(5.2) (3.6) (1.9) (1.5) (2.8) (3.8) (2.1) (3.8) ((1.5) (3.5) (3.5)
45 (13.7) 10 @ 63 10 @ 50 10 @ 40 9 @ 55 12 @ 50 12 @ 50
(4.3) (3.5) (2.8) (3.8) (3.5) (3.5)
50 (15.2) 10 @ 63 10 @ 50 10 @ 40 9 @ 55 15 @ 50
(4.3) (3.5) (2.8) (3.8) (3.5)
55 (16.8) 9 @ 80 9 @ 55 16 @ 50
(5.5) (3.8) (3.5)
Page 69
8-34
8-34 Protection for Automatic Storage
Page 70 FM Global Property Loss Prevention Data Sheets
30 (9.1) 20 @ 50 9@ 50 9@ 35 9@ 20 9@ 20 10@ 38 9@ 40 9@ 55 20@ 50 20@ 20@ 20@ 20@ 10@ 10@ 10@ 20 @ 20@ 20 @
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) 32(2.2) 16(1.1) 10(0.7) 50(3.5) 50(3.5) 35(2.4) 38(2.6) 50(3.5) 22(1.5) 10(0.7)
35 (10.7) 9 @ 75 9@ 52 9@ 29 9@ 23 9@ 40 9@ 55
(5.2) (3.6) (2.0) (1.6) (2.8) (3.8)
40 (12.2) 9 @ 75 9@ 52 9@ 29 9@ 23 9@ 40 9@ 55
(5.2) (3.6) (2.0) (1.6) (2.8) (3.8)
45 (13.7) 9 @ 75 9@ 60 9@ 50 9@ 55
(5.2) (4.1) (3.5) (3.8)
Page 71
8-34
Table 37. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top Solid-Walled Unexpanded Plastic Containers; Storage Height in Excess of 20 ft
Page 72
8-34
(6.1 m)
Ceiling-Level Sprinkler Protection Options for Top-Loading ASRS Arrangements; No. of AS @ psi (bar)
Max. Wet System, Pendent Storage Sprinklers, 160ºF (70ºC) Wet System, Upright Storage Sprinklers, 160ºF (70ºC)
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, ft K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
(m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
25 (7.6) 15 @ 50 10@ 50 10@ 35 10@ 20 10@ 20 7 @ 38 10 @ 40 10 @ 55 15@ 50 15@ 32 15@ 16 15@ 10 15@ 50 12@ 50 12@ 35 7 @ 38 15 @ 50 15@ 22 15 @ 10
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (2.6) (3.5) (1.5) (0.7)
30 (9.1) 20 @ 50 12@ 50 12@ 35 12@ 20 12@ 20 10@ 38 12@ 40 12@ 55 20@ 50 20@ 32 20@ 16 20@ 10 20@ 50 12@ 50 12@ 35 10@ 38 20@ 50 20@ 22 20 @ 10
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (2.6) (3.5) (1.5) (0.7)
©2017-2020 Factory Mutual Insurance Company. All rights reserved.
Egress to
Mezzanine Level
Fig. 25. Example of a TL-ASRS arrangement showing maximum 100 ft (30 m) depth in one direction
Top of Grid
Perimeter Perimeter
Mezzanine Mezzanine
Level Level
Top-Loading ASRS
Storage Area
Floor
Fig. 26. TL-ASRS arrangements where the maximum ceiling height is 25 ft (7.6 m)
Top-Loading Top-Loading
ASRS Grid Area ASRS Grid Area > 100 ft
(30 m)
Egress to
Mezzanine Level
Fig. 27. Example of solid-floored elevated mezzanine levels when span of TL-ASRS exceeds 100 ft (30 m) in each direction
2. Install the barriers from floor level to the top of the storage array
3. Attach the vertical barriers to each of the storage columns with a minimum of 3 tech screws per column
(near the top, middle, and bottom)
4. Provide a minimum 3 in. (75 mm) overlap, sealed with fire-rated silicone, of the barriers with the floor
and all sheet metal joints
5. Where the vertical barriers are required at corners, bend the sheet metal around the corner to avoid
any seams at these locations
B. Arrange the vertical barriers to limit the segregated storage area to a maximum size of 1,000 ft2 (93 m2).
C. Maintain one row of storage on one side and adjacent to each of the vertical barriers free of combustibles
as shown in Figure 28.
D. To aid with access to the fire area, limit the number of vertical barriers for each segregated area to 3 or
less as demonstrated in Figure 28.
Top-Loading
ASRS Grid Area
One Row on One
Side of Barrier
Void of Storage
> 100 ft
(30 m)
Vertical
Barrier
Monitor Nozzle
Plan View
Ceiling
< 10 ft
(3.0 m)
Monitor < 7 ft Monitor
Nozzle (2.1 m) Nozzle
Top of Grid
Perimeter Perimeter
Mezzanine Mezzanine
Level Level
Floor
Elevation View
D. Arrange the monitor nozzles to be manually controlled and operated from a dedicated location that will
not be affected by a fire involving the ASRS storage area.
E. Design the monitor nozzle system to provide a minimum flow of 200 gpm (760 L/min) from each of the
two most hydraulically remote monitor nozzles (400 gpm [1,520 L/min] total).
F. Water supplies for the monitor nozzles can be arranged in one of the following methods:
1. A piping system dedicated solely for the monitor nozzles, or
2. From sprinkler systems that are different than the one protecting the ASRS storage area
G. The installation of fixed-in-place monitor nozzles can be avoided when:
1. The recommendations outlined in Section 2.3.6.4.1(B) are met, or
2. Vertical barriers are installed throughout the storage area in accordance with Section 2.3.6.4.2, or
3. At the written discretion of the local authority having jurisdiction.
2.3.6.4.4 Visible or Infrared Camera Installation for Fixed-In-Place Monitor Nozzle Operation
A. To allow for guided discharge of the monitor nozzles to the point of fire origin, install infrared (IR) cameras
over the entire storage grid, in accordance with this section, using dedicated feeds to the remote location
designated for monitor nozzle operation.
B. Arrange the IR cameras as follows:
1. Install longwave infrared (LWIR) cameras, capable of panning and tilting, that have a spectral range
of 8-12 µm, a minimum spatial resolution of 15 pixels/ft (45 pixels/m), measured at the farthest position from
the camera along the top surface of the storage array, and a field of view (FOV) that does not exceed
25°. Avoid the use of IR cameras that use charge-coupled device (CCD) sensors.
2. Locate the cameras vertically as high as possible over the storage grid while also avoiding obstruction
to the camera’s view. Position the cameras horizontally as close as possible to the halfway mark
in-between the locations of the fixed-in-place monitor nozzles. Maintain a minimum horizontal distance
of 10 ft (3.0 m) from any camera to the nearest fixed-in-place monitor nozzle.
3. Install the cameras so that every column of the storage array can be viewed by a minimum of two
cameras.
4. When possible, incorporate data into the camera view that can communicate to the remote location
operator the specific location of the storage grid the camera is viewing.
C. The installation of visible imaging cameras can be used in lieu of infrared cameras when:
1. The space between the top of the storage grid and the ceiling will be (1) unconfined so that smoke
can readily escape the ASRS storage area, and (2) the ceiling-level sprinklers will be quick-response,
minimum K14.0 (K200) standard-coverage pendent Storage sprinklers, or
2. The space between the top of the storage grid and the ceiling will be (1) confined so that smoke cannot
readily escape the ASRS storage area, and (2) manually-operated ceiling-level ventilation will be provided
that can be turned on upon fire service arrival to clear the storage grid area of visible smoke.
D. When permitted by Section 2.3.6.4.4(C), install visible imaging cameras over the entire storage grid, using
dedicated feeds to the remote location designated for monitor nozzle operation, as follows:
1. Install cameras, capable of panning and tilting, that have a minimum spatial resolution of 15 pixels/ft
(45 pixels/m), measured at the farthest position from the camera along the top surface of the storage array.
2. Locate the cameras vertically as high as possible over the storage grid while also avoiding obstruction
to the camera’s view. Position the cameras horizontally as close as possible to the halfway mark
in-between the locations of the fixed-in-place monitor nozzles. Maintain a minimum horizontal distance
of 10 ft (3.0 m) from any camera to the nearest fixed-in-place monitor nozzle.
3. Install the cameras so that every column of the storage array can be viewed by a minimum of two
cameras.
4. When possible, incorporate data into the camera view that can communicate to the remote location
operator the specific location of the storage grid the camera is viewing.
5. Arrange the recording equipment so that review of the video is possible to help identify where flames
have been visually observed.
E. The installation of IR or visible cameras can be avoided, at the written discretion of the local authority
having jurisdiction, when all the fixed-in-place monitor nozzles are readily accessible during a fire event.
2.3.6.4.5 Small Hose Connection Stations
A. To aid in manual fire fighting efforts and after-extinguishment mop-up operations, install small hose
connection stations near the floor-level access points established for the local fire service and on the
mezzanine levels (perimeter and elevated). Consult with the local fire service or authority having jurisdiction
to determine their recommendations regarding:
(1) The use of wet- or dry-barrel stations,
(2) The size of the hose connections, and
(3) The horizontal distance between stations
B. Design the small hose connection station system to provide a minimum flow of 50 gpm (190 L/min) from
each of the two most hydraulically remote stations (100 gpm [380 L/min] total).
C. Arrange the water supplies feeding these stations in one of the following ways:
1. A piping system dedicated solely for the small hose connection stations, or
2. Piping that connects the stations to a sprinkler system that is different than the one protecting the ASRS
storage area
D. The installation of small hose connection stations can be avoided at the documented discretion of the
local authority having jurisdiction.
2.3.6.4.6 Pre-Incident Plan
For TL-ASRS storage arrangements that use solid-walled containers, establish a pre-incident plan with the
local fire service that takes into consideration how the local fire service will gain access to any point of the
ASRS storage grid for final extinguishment purposes. Items to consider, at a minimum, are:
A. Access to the storage grid itself (i.e., removal of any separating walls or fences),
B. A plan to remove storage containers along with a place to put them, and
C. A means of preventing robots from falling from the grid into the storage area.
See Section 2.1.5 for additional guidance on pre-incident planning.
Wall
Subdivided Subdivided
Storage Area Storage Area
Wall
One Container
Min. 4 ft (1.2 m)
High Storage Area Wide Void Space
Min. 4 ft (1.2 m)
Wide Void Space
Subdivided
Storage Area
Ceiling Sprinklers
Centered Over Void Spaces
Egress to
Mezzanine Level
Fig. 32. Example of a TL-ASRS arrangement showing maximum 100 ft (30 m) depth in one direction
B. If the horizontal distances between the ends of the storage array will exceed 100 ft (30 m) in both directions,
install solid-floored elevated mezzanine levels that will limit the horizontal distances between mezzanines
to 100 ft (30 m) and the maximum horizontal distances for hose stream application to 50 ft (15 m). Arrange
the elevated mezzanines to allow robots the ability to pass underneath them. See Figure 33 for an example
of this arrangement.
C. The installation of elevated mezzanines, as outlined in Section 2.3.7.7.1(B), can be avoided at the written
discretion of the local authority having jurisdiction.
Egress to
Mezzanine Level
Fig. 33. Example of solid-floored elevated mezzanine levels when span of TL-ASRS exceeds 100 ft (30 m) in each direction
2.4 Vertically Enclosed Automatic Storage and Retrieval System Storage Arrangements
2.4.1 General
2.4.1.1 Section 2.4 provides protection guidelines for vertically enclosed automatic storage and retrieval
systems (ASRS) storage arrangements. See Figure 34 for an example of this type of storage arrangement.
2.4.1.2 The protection options in this section for a vertically enclosed ASRS storage unit focus solely on the
protection provided within the unit itself. See the applicable FM Global Data Sheet for the surrounding
occupancy hazard to determine recommendations pertaining to the construction, occupancy, and protection
of the area in which the vertically enclosed ASRS storage unit is located.
2.4.3.1 General
2.4.3.1.1 Arrange the vertically enclosed ASRS storage unit for automatic shutdown upon fire/smoke detection
or sprinkler activation.
2.4.3.1.2 If the materials being maintained within the vertically enclosed ASRS storage unit are (a) of high
value, and/or (b) could result in a major interruption to business if damaged, consider the installation of an FM
Approved total flooding gaseous suppression system in accordance with the applicable FM Global 4-Series
Data Sheet to supplement the sprinkler protection recommended in Section 2.4.3.3.
Table 38. Sprinkler Pressure Requirements for the Protection of Vertically Enclosed ASRS Storage Units Over 25 ft (7.6
m) and up to 55 ft (16.8 m) Tall
Maximum
Ceiling Height
of Vertically Wet System, Quick Response, 160ºF (70ºC), Pendent Storage Sprinklers; Pressure, psi (bar)
Enclosed K14.0 (K200) K16.8 (K240) K22.4 (K320) K25.2 (K360) K28.0 (K400) K33.6 (K480)
ASRS Unit, ft
(m)
30 (9.1) 50 (3.4) 35 (2.4) 20 (1.4) 20 (1.4) 40 (2.8) 55 (3.8)
35 (10.7) 75 (5.2) 52 (3.6) 30 (2.1) 30 (2.1) 40 (2.8) 55 (3.8)
40 (12.2) 75 (5.2) 52 (3.6) 40 (2.8) 40 (2.8) 40 (2.8) 55 (3.8)
45 (13.7) 50 (3.4) 50 (3.4) 40 (2.8) 55 (3.8)
50 (15.2) 63 (4.3) 50 (3.4) 40 (2.8) 55 (3.8)
55 (16.8) 80 (5.5) 55 (3.8)
b. Install intermediate levels of quick response, 160°F (7°C) nominally rated, minimum K8.0 (K115)
Nonstorage sidewall or extended-coverage sidewall sprinklers installed at both ends of the ASRS unit.
Locate the intermediate levels of sprinklers on a maximum vertical spacing of 10 ft (3.0 m) while leaving
no more than 15 ft (4.6 m) of storage above the top level of intermediate sprinklers.
c. Design the sprinkler system to account for all sprinklers (ceiling and intermediate) within the vertically
enclosed ASRS storage unit operating at a minimum flow of 30 gpm (115 L/min) from the most remote
sprinkler.
2. If the top of the ASRS unit is open to the surrounding area, reduce the sprinkler spacing indicated in Section
2.4.3.3.2(B)(1)(a) to a maximum 4 ft (1.2 m) linear spacing and a maximum 16 ft2 (1.5 m2) area spacing.
2.4.3.4 Hose Demand and System Duration
2.4.3.4.1 Hose Demand Design
As part of the overall sprinkler system design, include a hose demand allowance of 250 gpm (950 L/min)
for manual intervention.
2.4.3.4.2 System Duration
Size the water supply for the sprinkler system and the hose demand design, when taken from the same
water supply source, for a minimum duration of 60 minutes.
Fig. 35. Example of open-top plastic containers in mini-load ASRS storage arrangementi
terminal. The robot can move in three directions: back and forth in the aisle, up and down the height of the
rack, and in and out of the rack when removing or returning a container to its location. Depending on the
size of the system, more than one robot may be used. Aisles are usually a minimum of about 3 ft (0.9 m) wide.
There are various types of containers in which parts may be stored within the retrieval system. For purposes
of providing protection guidelines they have been divided into the following three groups: noncombustible
containers, cellulosic containers, and plastic containers.
Fig. 36. Example of an empty mini-load ASRS storage arrangement where rack uprights are about 2 to 3 in. (50 to 75
mm) wide and about 2 ft (0.6 m) horizontally apart
Unexpanded plastic containers are typically either solid throughout or collapsible where the hinge is located
near the bottom of container. This hinge does allow for water to vent from the container in a timely fashion
provided that the hinge is located close enough to the bottom of the container and the product inside the
container will not block the water from escaping.
Fig. 38. Example of motorized automated picking robot in a mini-load ASRS storage arrangement with open-top
unexpanded plastic containers
3.1.2.1 General
A top-loading ASRS (TL-ASRS) storage arrangement consists of an open metal grid structure that is
supported by metal columns located at the corner of each of the grid openings. Under each grid opening is
a solid-piled column of storage containers that are vertically aligned due to the angle irons provided on the
metal support columns. The containers used in TL-ASRS storage arrangements are almost always open-top
and made from various plastics, such as polyethylene (HDPE) or polypropylene. The top of the grid acts
as a track across which remotely operated robots transverse; the robots are used to either remove containers
from the storage grid for picking operations, or are used to return containers to their designated storage
location. The track that the robots operate on is about the same width as the flue spaces surrounding each
container.
3.1.2.3 Batteries
In general, the batteries in use are one of two types: lead-acid or lithium-ion with the latter gaining more
popularity in recent times. For designs with Li-ion batteries, charging rates could be substantially higher than
for the lead acid counterparts. This can put additional stress on the current carrying parts of the battery pack
and charger in addition to the batteries themselves, which tend to heat at higher current levels. A Battery
Management System (BMS) is provided for the safe operation of the Li-ion battery pack.
Batteries use different chemistries. As indicated above, the chemistries typically observed in top-loading ASRS
robots are lead-acid and lithium-ion batteries. Lead-acid batteries are typically of the sealed type. Li-ion
batteries consist of several Li-ion cells (cylindrical or prismatic) connected in series/parallel combination to
meet the voltage, power, and capacity requirements of the application. The battery pack also consist of the
BMS and instrumentation to continuously monitor the battery state of charge, state of health. The BMS also
provides safety operation limits on charge/discharge voltage and currents. The chargers for these Li-ion
batteries follow specific charging profiles depending on the Li-ion chemistry used in the cells.
on July 13, 2002. Reportedly due to deficient welding and design aspects of the rack framing, a portion of
a rack-structure ASRS storage unit collapsed starting a domino effect with the remaining rack framing in the
warehouse area. Storage in the racking consisted of paper goods, which were then ignited by the building’s
lighting system. The building, which was reportedly 10 stories high and 115,000 ft2 (10,685 m2) in size, was
completely lost.
4.0 REFERENCES
4.1 FM Global
Data Sheet 1-2, Earthquakes
Data Sheet 1-10, Smoke and Heat Venting in One-story Sprinklered Buildings
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers
Data Sheet 2-1, Corrosion in Automatic Sprinkler Systems
Data Sheet 2-8, Earthquake Protection for Water-Based Fire Protection Systems
Data Sheet 5-48, Automatic Fire Detection
Data Sheet 7-43, Process Safety
Data Sheet 7-110, Industrial Control Systems
Data Sheet 8-1, Commodity Classification
Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities
Data Sheet 8-29, Refrigerated Storage
Data Sheet 10-1, Pre-Incident Planning
Data Sheet 10-8, Operators
4.2 Other
International Electrotechnical Commission (IEC). IEC 60950-1, Information Technology Equipment - Safety
- Part 1: General Requirements.
International Electrotechnical Commission (IEC). IEC 62619, Secondary Cells and Batteries Containing
Alkaline or Other Non-acid Electrolytes - Safety Requirements for Secondary Lithium Cells and Batteries,
for Use in Industrial Applications.
Local fire service: The responding personnel, paid or volunteer, whose assigned task would be to provide
final extinguishment of a fire that originates within an ASRS storage array.
Longitudinal flue space: A flue space that is parallel to the loading aisle having a minimum width of 3 in.
(75 mm) and a maximum width of 24 in. (600 mm). Note that any flue space that is parallel to the loading aisle
having a minimum width over 24 in. (600 mm) as an aisle for in-rack sprinkler location purposes.
Mini-load ASRS storage arrangement: An automatic storage and retrieval system that uses trays or small
totes/containers for material handling as opposed to traditional pallet loads. They are differentiated from other
storage racks due to the presence of angle irons, which result in the diversion of sprinkler discharge toward
the face of the rack and away from both the longitudinal and transverse flue spaces. Mini-load ASRS rack
structures typically use rack uprights that are about 18 to 24 in. (450 to 600 mm) horizontally apart and are
about 2 to 3 in. (50 to 75 mm) in size (both width and depth). Tier heights are roughly 1 ft (0.3 m) and product
handling is typically supported on angle irons (see Figure 3).
Modular in-rack sprinkler protection arrangement: An in-rack sprinkler protection arrangement that is
designed to prevent the vertical spread of fire beyond the first level of in-rack sprinklers that the fire
encounters. This in-rack sprinkler arrangement therefore allows the in-rack design to be based on the
operation of a given number of sprinklers at only one level and does not need to account for ceiling sprinkler
operation as part of its design.
Monitor nozzle: A nozzle used for water discharge to a fire area that can turn 360º in a horizontal plane
while also having a limited play in a vertical plane.
Non-adequately vented open-top container (mini-load or shuttle-type ASRS): See the definition for
“adequately vented open-top container.” Any container that does not meet the definition of an adequately
vented open-top container is considered a non-adequately vented open-top container for design purposes.
The protection requirements for these types of containers differ from those for adequately vented open-top
containers when maintained in a mini-load or shuttle-type ASRS storage arrangement.
Non-solid-walled container (top-loading ASRS): A container that has openings on any of its side walls.
The protection requirements for these types of containers differ from those for solid-walled containers when
maintained in a TL-ASRS storage arrangement.
Open-top container: A container with walls higher than 1 in. (25 mm) that either does not have a top cover
or is not equipped with a cover capable of preventing water from entering the container. Note that this includes
open-top containers filled with product to any height within the container.
Rack structure ASRS storage arrangement: An automatic storage and retrieval system that is similar to
traditional open-frame storage racks except that (1) the horizontal distance between rack uprights is sized for
only one pallet load, and (2) the support within the rack for the pallet loads tends to be either roller-type
conveyors or horizontal supports that are oriented perpendicular to the loading aisle as opposed to parallel
to it. Protection guidelines for these storage arrangements are provided in FM Global Property Loss
Prevention Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities.
Shuttle-type ASRS storage arrangement: An automatic storage and retrieval system that uses trays or
small totes/containers (as opposed to traditional pallet loads) for material handling. What differentiates these
ASRS storage arrangements from mini-load ASRS storage arrangements is the storage racks typically use
slatted shelving (that are void of vertical alignment guides) on which the materials, trays, or containers rest.
As a result, the rack structure does not inherently divert water away from the flue spaces that surround the
stored product, provided the slats do not result in a blocked transverse flue space. Shuttle-type ASRS rack
structures typically use rack uprights that are about 8 to 10 ft (2.4 to 3.0 m) horizontally apart and are about
3 in. (75 mm) in width. Tier heights are roughly 1 to 2 ft (0.3 to 0.6 m).
Solid-walled open-top container (mini-load, shuttle, or top-loading ASRS): A container that has no
openings on any of its side walls. The protection requirements for these types of containers differ from those
for non-solid-walled containers when maintained in a TL-ASRS storage arrangement. A solid-walled container
is referred to as a “non-adequately vented container” when stored within a mini-load or shuttle-type ASRS
storage arrangement
Top-loading ASRS (TL-ASRS): An automatic storage and retrieval system that consists of a metal grid
structure under which containers, usually open-top and made of unexpanded plastic, are stacked one on
top of another in vertically aligned columns. They are accessed from the top of the grid by service robots that
have been programmed to either retrieve a specific container for commodity picking purposes, or for
replenishing the amount of commodity maintained within the storage container.
Tray: A product material handling unit that has an extension around its perimeter that does not rise more
than 1 in. (25 mm) vertically.
Vertical barrier: A barrier that is installed within the transverse flue space of a storage rack for the purpose
of preventing fire from spreading beyond it. It spans the entire height of the rack as well as its depth, including
across any longitudinal flue spaces, from one face of the rack to the other. It is not intended to span across
a material-handling aisle located between storage racks.
Vertically enclosed ASRS: An ASRS unit that typically works with a vertical lift system or a vertical carousel.
The lift system uses a robotic picker that will store and remove trays that rest on fixed storage supports within
the unit and deliver it to the user. The carousel conveyor system uses a rotating storage arrangement that
brings the storage tray to the user. Typical systems are package units where metal trays supported on a rack.
1. Noted that protection options for open-top, gridded-bottom containers are outside the scope of this
data sheet.
2. Added protection options for open-top, non-solid walled containers to this data sheet.
3. Added protection options for noncombustible open-top, solid-walled containers to this data sheet.
D. Clarified TL-ASRS storage arrangements regarding what is needed for sprinkler protection (suppression
or control) and what is needed for final extinguishment. Added new sections for each ASRS storage
arrangement specific to final extinguishment.
E. Added definitions to Appendix A to clarify guidance for the various types of containers described in
this data sheet.
January 2020. Interim revision. Significant changes include the following:
A. Added loss prevention guidelines for top-loading ASRS arrangements that use solid-walled (open- and
closed-top containers).
B. Reformatted the document so each ASRS storage arrangement now has its own section.
C. Incorporated the results of recent full-scale fire testing of top-loading automatic storage and retrieval
systems using solid-walled plastic containers.
January 2018. Interim revision. Clarifications were made to section 2.2.4.2, Longitudinal Flue Spaces,
corrected reference to the table in sections 2.2.4.1.3 and 2.3.4.1.2. Also corrections were made to Table 11,
IRAS Design Guidelines.
October 2017. Interim revision. Minor editorial changes were made.
July 2017. This data sheet has been completely rewritten. The following major changes were made:
A. This data sheet now addresses protection options for ASRS vertically enclosed, rack-structure,
mini-load, and other storage arrangements in which the horizontal support for product material handling
uses rails, angle irons, or other similar supporting structures. When in-rack automatic sprinkler (IRAS)
protection is needed, the protection now offered in this data sheet is designed to prevent the fire from
growing vertically past the in-rack sprinkler protection that has been installed. With this arrangement, the
ceiling and in-rack sprinkler systems operate independent of each other and thus do not need to be
hydraulically balanced nor designed with both systems operating concurrently.
B. The term “storage sprinkler” has been incorporated into this data sheet to replace “Control Mode Density
Area (CMDA) sprinkler.”
C. Ceiling-level sprinkler designs now use the “number of sprinklers @ minimum pressure” design format
in place of the previously used “density/demand area” design format.
D. Added terms to Appendix A, Glossary of Terms.
January 2003. Clarification regarding the storage clearance was added.
September 2000. This revision of the document has been reorganized to provide a consistent format.