You are on page 1of 76

Installation, Operation,

and Maintenance

™ Chillers
HDWA Water-cooled Agility™
With Tracer® AdaptiView™ Control
Model: HDWA
PC 747

X39641347004

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.

October 2019 HDWA-SVX001D-EN


Introduction
Read this manual thoroughly before operating or WARNING
servicing this unit.
Proper Field Wiring and Grounding
Warnings, Cautions, and Notices Required!
Failure to follow code could result in death or
Safety advisories appear throughout this manual as serious injury.
required. Your personal safety and the proper All field wiring MUST be performed by qualified
operation of this machine depend upon the strict personnel. Improperly installed and grounded
observance of these precautions. field wiring poses FIRE and ELECTROCUTION
hazards. To avoid these hazards, you MUST follow
The three types of advisories are defined as follows:
requirements for field wiring installation and
Indicates a potentially hazardous situation grounding as described in NEC and your local/
WARNING which, if not avoided, could result in death or state/national electrical codes.
serious injury.

CAUTION
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
WARNING
moderate injury. It could also be used to alert Personal Protective Equipment (PPE)
against unsafe practices.
Required!
Indicates a situation that could result in
NOTICE Failure to wear proper PPE for the job being
equipment or property-damage only
accidents. undertaken could result in death or serious injury.
Technicians, in order to protect themselves from
potential electrical, mechanical, and chemical
Important Environmental Concerns hazards, MUST follow precautions in this manual
Scientific research has shown that certain man-made and on the tags, stickers, and labels, as well as the
chemicals can affect the earth’s naturally occurring instructions below:
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified • Before installing/servicing this unit,
chemicals that may affect the ozone layer are technicians MUST put on all PPE required for
refrigerants that contain Chlorine, Fluorine and Carbon the work being undertaken (Examples; cut
(CFCs) and those containing Hydrogen, Chlorine, resistant gloves/sleeves, butyl gloves, safety
Fluorine and Carbon (HCFCs). Not all refrigerants glasses, hard hat/bump cap, fall protection,
containing these compounds have the same potential electrical PPE and arc flash clothing).
impact to the environment. Trane advocates the ALWAYS refer to appropriate Material Safety
responsible handling of all refrigerants-including Data Sheets (MSDS)/Safety Data Sheets
industry replacements for CFCs and HCFCs such as (SDS) and OSHA guidelines for proper PPE.
saturated or unsaturated HFCs and HCFCs. • When working with or around hazardous
chemicals, ALWAYS refer to the appropriate
Important Responsible Refrigerant MSDS/SDS and OSHA/GHS (Global
Practices Harmonized System of Classification and
Labelling of Chemicals) guidelines for
Trane believes that responsible refrigerant practices information on allowable personal exposure
are important to the environment, our customers, and levels, proper respiratory protection and
the air conditioning industry. All technicians who handling instructions.
handle refrigerants must be certified according to local
rules. For the USA, the Federal Clean Air Act (Section • If there is a risk of energized electrical
608) sets forth the requirements for handling, contact, arc, or flash, technicians MUST put
reclaiming, recovering and recycling of certain on all PPE in accordance with OSHA, NFPA
refrigerants and the equipment that is used in these 70E, or other country-specific requirements
service procedures. In addition, some states or for arc flash protection, PRIOR to servicing
municipalities may have additional requirements that the unit. NEVER PERFORM ANY SWITCHING,
must also be adhered to for responsible management DISCONNECTING, OR VOLTAGE TESTING
of refrigerants. Know the applicable laws and follow WITHOUT PROPER ELECTRICAL PPE AND
them. ARC FLASH CLOTHING. ENSURE
ELECTRICAL METERS AND EQUIPMENT ARE
PROPERLY RATED FOR INTENDED
VOLTAGE.

©2019 Ingersoll Rand HDWA-SVX001D-EN


Introduction

WARNING assembled unit— compliance with the following is


required to preserve the factory warranty:
Follow EHS Policies!
• Trane, or an agent of Trane specifically authorized
Failure to follow instructions below could result in
to perform start-up and warranty of Trane®
death or serious injury.
products, will perform or have direct on-site
technical supervision of the disassembly and
• All Ingersoll Rand personnel must follow reassembly work.
Ingersoll Rand Environmental, Health and
• The installing contractor must notify Trane—or an
Safety (EHS) policies when performing work
agent of Trane specifically authorized to perform
such as hot work, electrical, fall protection,
startup and warranty of Trane® products—two
lockout/tagout, refrigerant handling, etc. All
weeks in advance of the scheduled disassembly
policies can be found on the BOS site. Where
work to coordinate the disassembly and
local regulations are more stringent than
reassembly work.
these policies, those regulations supersede
these policies. • Start-up must be performed by Trane or an agent of
Trane specifically authorized to perform startup and
• Non-Ingersoll Rand personnel should always
warranty of Trane® products.
follow local regulations.
Trane, or an agent of Trane specifically authorized to
perform start-up and warranty of Trane® products, will
WARNING provide qualified personnel and standard hand tools to
Refrigerant under High Pressure! perform the disassembly and reassembly work at a
location specified by the contractor. The contractor
Failure to follow instructions below could result in
shall provide the rigging equipment such as chain falls,
an explosion which could result in death or
gantries, cranes, forklifts, etc. necessary for the
serious injury or equipment damage.
disassembly and reassembly work and the required
System contains refrigerant under high pressure.
qualified personnel to operate the necessary rigging
Recover refrigerant to relieve pressure before
equipment.
opening the system. See unit nameplate for
refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or refrigerant Copyright
additives.
This document and the information in it are the
property of Trane, and may not be used or reproduced
in whole or in part without written permission. Trane
Factory Warranty Information reserves the right to revise this publication at any time,
Compliance with the following is required to preserve and to make changes to its content without obligation
the factory warranty: to notify any person of such revision or change.
All Unit Installations
Startup MUST be performed by Trane, or an authorized Trademarks
agent of Trane, to VALIDATE this WARRANTY. All trademarks referenced in this document are the
Contractor must provide a two-week startup trademarks of their respective owners.
notification to Trane (or an agent of Trane specifically
authorized to perform startup).
Additional Requirements for Units Requiring
Revision History
Disassembly and Reassembly • Updated Model Number Description, digits 18 and
When a new chiller is shipped and received from our 22 for the 150 PSI marine 2 pass. Updated Updates
Trane manufacturing location and, for any reason, it Reversing Waterboxes and Waterbox Removal to
requires disassembly or partial disassembly, and show match marking.
reassembly— which could include but is not limited to • Added 208 incoming Line/ 460–60 Hz - 3 phase in
the evaporator, condenser, control panel, compressor/ Model Number Description section.
motor, economizer, factory-mounted starter or any • Miscellaneous edits in Operating Principles and
other components originally attached to the fully Maintenance chapter.

HDWA-SVX001D-EN 3
Table of Contents
Unit Nameplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . 23
Compressor Nameplate . . . . . . . . . . . . . . . . . . . 7 Installation: Water Piping . . . . . . . . . . . . . . . . . . 25
Model Number Descriptions. . . . . . . . . . . . . . . . 8 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

General Information . . . . . . . . . . . . . . . . . . . . . . . 10 Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . 25


Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . 10 Water Pressure Gauges . . . . . . . . . . . . . . . . . . 25
Component Locations. . . . . . . . . . . . . . . . . . . . 10 Valves—Drains and Vents . . . . . . . . . . . . . . . . 25
Chiller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Strainers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Adaptive Frequency Drive . . . . . . . . . . . . 12 Required Flow-Sensing Devices. . . . . . . . . . . 26
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . 13 Water Flow Detection Controller and
Dimensions and Weights . . . . . . . . . . . . . . . . . 14 Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 14 Evaporator and Condenser Water
Unit Specifications—Imperial (I-P) Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Water Piping Connections . . . . . . . . . . . . . . . . 29
Unit Specifications—International
System (SI) Units . . . . . . . . . . . . . . . . . . . . 15 Waterbox Locations . . . . . . . . . . . . . . . . . . . . . 29
Reversing Waterboxes . . . . . . . . . . . . . . . 30
Pre-installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Grooved Pipe Coupling . . . . . . . . . . . . . . . . . . 30
ASHRAE Standard 15 Compliance . . . . . . . . 16 Flange-connection Adapters . . . . . . . . . . . . . . 30
Inspection Checklist. . . . . . . . . . . . . . . . . . . . . . 16 Victaulic Gasket Installation . . . . . . . . . . . . . . 31
Loose Parts Inventory . . . . . . . . . . . . . . . . . . . . 16 Screw-Tightening Sequence for Water
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Piping Connections . . . . . . . . . . . . . . . . . . . . . . 31
Installation Requirements and Flanges with 8 Screws . . . . . . . . . . . . . . . . 31
Contractor Responsibilities . . . . . . . . . . . . . . . 16 Pressure Testing Waterside Piping . . . . . . . . 32
Installation: Mechanical . . . . . . . . . . . . . . . . . . . 18 Eddy Current Testing . . . . . . . . . . . . . . . . . . . . 32
Location Requirements . . . . . . . . . . . . . . . . . . 18 Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Sound Considerations . . . . . . . . . . . . . . . . 18 Unit Insulation Requirements . . . . . . . . . . . . . 33
Foundation Requirements . . . . . . . . . . . . 18
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Insulation Thickness Requirements . . . . . . . 33
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Factory-applied Insulation . . . . . . . . . . . . 33
Water Drainage . . . . . . . . . . . . . . . . . . . . . . 18 Electrical Requirements . . . . . . . . . . . . . . . . . . . 35
Access Restrictions. . . . . . . . . . . . . . . . . . . 18
Operating Environment. . . . . . . . . . . . . . . 18 Installation Requirements . . . . . . . . . . . . . . . . 35
Adaptive Frequency Drive Enclosure Electrical Requirements . . . . . . . . . . . . . . . . . . 35
Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Adaptive Frequency Drive . . . . . . . . . . . . . . . . 36
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 System Control Circuit Wiring (Field
Standard Chiller Lift . . . . . . . . . . . . . . . . . . 20 Wiring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Special Lift Requirements. . . . . . . . . . . . . 20 Sensor Circuits . . . . . . . . . . . . . . . . . . . . . . 38
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . 20 Schematic Wiring Drawings . . . . . . . . . . 40
Isolation Pads. . . . . . . . . . . . . . . . . . . . . . . . 20
Leveling the Unit. . . . . . . . . . . . . . . . . . . . . 21 Adaptive Frequency Drive . . . . . . . . . . . . . . . . 40
Refrigerant Pressure Relief Valve Programming. . . . . . . . . . . . . . . . . . . . . . . . 40
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Communications Interface . . . . . . . . . . . . . . . 40

4 HDWA-SVX001D-EN
Table of Contents

LonTalk Interface (LCI-C). . . . . . . . . . . . . . 40 Ice Making (Auto to Ice Making to Ice


BACnet Interface (BCI-C) . . . . . . . . . . . . . . 40 Making Complete) . . . . . . . . . . . . . . . . . . . 59
MODBUS Remote Terminal Unit Limit Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 60
Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Control Panel Devices and Unit-Mounted
Installation: Controls . . . . . . . . . . . . . . . . . . . . . . 41 Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
UC800 Specifications . . . . . . . . . . . . . . . . . . . . 41 Unit Control Panel . . . . . . . . . . . . . . . . . . . 60
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . 41 User-defined Language Support . . . . . . 60
Wiring and Port Descriptions. . . . . . . . . . 41 Unit Start-up and Shut-down
Communication Interfaces . . . . . . . . . . . . 42 Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Rotary Switches . . . . . . . . . . . . . . . . . . . . . 42 Unit Start-up. . . . . . . . . . . . . . . . . . . . . . . . . 61
LED Description and Operation. . . . . . . . 42 Temporary Shut-down and
Installing the Tracer AdaptiView Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Extended Unit Shut-down . . . . . . . . . . . . 61
Seasonal Unit Start-up . . . . . . . . . . . . . . . 61
Adjusting the Tracer AdaptiView Display
Arm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Operating Principles . . . . . . . . . . . . . . . . . . . . . . . 47 Recommended Maintenance . . . . . . . . . . . . . 63
Weekly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
General Requirements . . . . . . . . . . . . . . . . . . . 47 Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Cooling Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Annual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
HDWA Compressor . . . . . . . . . . . . . . . . . . 47 Other . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Compressor Motor . . . . . . . . . . . . . . . . . . . . . . 47 Maintenance Procedures . . . . . . . . . . . . . . . . . 63
Adaptive Frequency Drive . . . . . . . . . . . . . . . . 47 Drive Cooling System . . . . . . . . . . . . . . . . 63
Cleaning the Condenser . . . . . . . . . . . . . . 64
Uninterruptible Power Supply . . . . . . . . . . . . 48 Cleaning the Evaporator . . . . . . . . . . . . . . 66
Evaporator and Condenser . . . . . . . . . . . . . . . 48 Waterbox Hinges . . . . . . . . . . . . . . . . . . . . . . . . 66
Drive Cooling System . . . . . . . . . . . . . . . . . . . . 48 Adaptive Frequency Drive Periodic
Tracer AdaptiView Display . . . . . . . . . . . . . . . 48 Maintenance and Inspection . . . . . . . . . . . . . . 67
Visual Inspection—Power
Start-up and Shut-down . . . . . . . . . . . . . . . . . . . 49 Removed. . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Sequence of Operation. . . . . . . . . . . . . . . . . . . 49 Operational Inspection—Power
Software Operation Overview Applied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Power Up to Starting . . . . . . . . . . . . . . . . . 51 Appendix A: Forms and Check
Stopped to Starting . . . . . . . . . . . . . . . . . . 52
Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Running. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Satisfied Setpoint . . . . . . . . . . . . . . . . . . . . 54 Unit Start-up/Commissioning. . . . . . . . . . . . . 69
Normal Shutdown to Stopped or
Appendix B: Agility™ Chiller Installation
Run Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Completion and Request for Trane
Immediate Shutdown to Stopped or
Run Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
AFD Mains Phase Loss . . . . . . . . . . . . . . . 57 Appendix C: Settings . . . . . . . . . . . . . . . . . . . . . . 72
Ice Making (Running to Ice Making to
Running) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Appendix D: Operator Log . . . . . . . . . . . . . . . . . 74

HDWA-SVX001D-EN 5
Unit Nameplate
The unit nameplate is located on the right side of the Figure 1. Typical unit nameplate
control panel. A typical unit nameplate is illustrated in
the following figure and contains the following
information:
• Unit model and size descriptor
• Unit serial number
• Unit electrical requirements
• Correct operating charge and refrigerant type
• Unit test pressures and maximum operating
pressures
• Unit literature
• Drawing numbers for unit wiring diagrams
S e r i a l N u m b e r . The unit serial number provides the
specific chiller identity. Always provide this serial
number when calling for service or during parts
identification.
S e r v i c e M o d e l N u m b e r . The service model represents
the unit as built for service purposes. It identifies the
selections of variable unit features required when
ordering replacements parts or requesting service.
N o t e : Unit-mounted Adaptive Frequency™ Drives
(AFDs) are identified by a separate number; refer
to “Model Number Descriptions,” p. 8.
P r o d u c t D e s c r i p t i o n B l o c k . The Agility™ chiller
models are defined and built using the Product
Definition and Selection (PDS) system. This system
describes the product offerings using a product coding
block which is made up of feature categories and codes
that identify all characteristics of a unit.

6 HDWA-SVX001D-EN
Unit Nameplate

Compressor Nameplate Figure 2. Compressor nameplate


The compressor assembly has a separate model
number which is required to identify internal and
external compressor parts. The model number begins
with “HDMA” and the nameplate is located on the
interstage pipe; refer to “Model Number
Descriptions,” p. 8.

N o t e : Do NOT cover compressor nameplate with wrap


or insulation (leave a window).

HDWA-SVX001D-EN 7
Model Number Descriptions

Digit 1, 2 — Unit Function Digit 16 — Evaporator Tube Bundle Digit 25 — Control: Generic Building
Automation System (BAS)
HD = Agility™ Centrifugal Water-cooled A = Evaporator Tube Bundle A 0 = None
Chiller B = Evaporator Tube Bundle B G = Generic BAS
C = Evaporator Tube Bundle C
Digit 3 — Drive Digit 26 — Control: Extended
D = Evaporator Tube Bundle D
E = Evaporator Tube Bundle E Operation
W = Direct Drive
S = Special 0 = None
1 = Extended Operation
Digit 4 — Development Sequence Digit 17 — Evaporator Tubes
Digit 27 — Tracer®
® Communication
A C = 0.025 Wall Thickness—0.75 Diameter Interface
Internally Enhanced Copper Evaporator Tube 0 = None
Digit 5, 6, 7 — Nominal Compressor M = 0.025 Wall Thickness—0.75 Diameter 2 = Tracer® Comm 5
High Performance Internal Surface 3 = Tracer® MODBUS®
Tonnage
Evaporator Tube 4 = Tracer® BACnet®
200= 200 nominal tons S = Special
300= 300 nominal tons Digit 28 — Special Options
400 = 400 Nominal Tons Digit 18 — Evaporator Waterbox
SSS = Special 0 = None
B= 150 marine — 2 pass S = Special Option
Digit 8 — Incoming Line Voltage/Unit F = 150 psi Non-marine, 2-Pass Standard
Drive Voltage S = Special Digit 29 — Control: Water Flow
B = 208V Incoming Line/460V-60Hz—3Ph Control
D = 380V Incoming Line/400V-60Hz—3Ph Digit 19 — Condenser Shell Size 0 = None
F = 460V Incoming Line/400V-60Hz—3Ph W = Water Flow Control
G = 480V Incoming Line/400V-60Hz—3Ph A = 020A Condenser Shell
H = 575V Incoming Line/400V-60Hz—3Ph C = 040A Condenser Shell Digit 30 — Control: Chilled Water
J = 600V Incoming Line/400V-60Hz—3Ph S = Special Reset
R = 380V Incoming Line/400V-50Hz—3Ph 0 = None
S = Special Digit 20 — Condenser Tube Bundle 1 = Chilled Water Reset
T = 400V Incoming Line/400V-50Hz—3Ph
A = Condenser Tube Bundle A Digit 31 — Control: Operating Status
U = 415V Incoming Line/400V-50Hz—3Ph
B = Condenser Tube Bundle B
C = Condenser Tube Bundle C 0 = None
Digit 9 — Unit Type
S = Special 1 = Operating Status
A = Cooling Condenser Digit 32 — Industrial Chiller Package
S = Special Digit 21 — Condenser Tubes
(INDP)
Digit 10, 11 — Design Sequence C = 0.025 Condenser Tube Wall— 0.75 0 = Without INDP
Internal Enhanced Copper Tube
AA = Original Design J = 0.028 Condenser Tube Wall—0.75 Digit 33 — Control Power Transformer
Internal Enhanced Copper Tube (CPTR)
S = Special
Digit 12 — Manufacturing Location 0 = Without CPTR
Digit 22 — Condenser Waterbox S = Special
L = La Crosse, Wisconsin
Digit 34 — Thermal Dispersion Water
B = 150 PDI marine — 2 pass
Flow Proving
Digit 13 — Hot Gas Bypass F = 150 psi Non-marine, 2-Pass Standard
S = Special 0 = None, Customer to Provide Device for
Condenser and Evaporator
0 = Without HGB
Digit 23 — Evaporator Expansion A = Thermal Dispersion Water Flow Proving
S = Special
Valve Selected for Condenser and Evaporator
Digit 14 — Control Enclosure A = 400
B = 200
C = Standard Control Enclosure S = Special
D = Standard Control Enclosure with Tracer®
SC Digit 24 — Unit Option
S = Special
B = Insulation Package and Spring Loaded
Digit 15 — Evaporator Shell Size Pressure Relief Valve
D = Spring Loaded Pressure Relief Valve Only
A= 020A Evaporator Shell
C = 040A Evaporator Shell
S = Special

8 HDWA-SVX001D-EN
Model Number Descriptions

HDMA Centrifugal Compressor AFDT Adaptive Frequency Drive


Description Description Digit 13 — Agency Listing

The compressor assembly has a separate The Adaptive Frequency™ Drive (AFD) has a 0 = UL- and CUL-Listed (Standard on All
model number which is required to identify separate model number which is required to Units)
internal and external compressor parts. The identify the drive and its components. The
model number begins with “HDMA” and the model number begins with “AFDT”. Digit 14 — Special Options
nameplate is located on the foot of the volute.
Digit 1, 2, 3 — Adaptive Frequency™
™ 0 = None
Digit 1 — Higher-speed Centrifugal Drive S = Special Options (See Sales Order)
AFD
Digit 15 — VFD Frame Size (SRRL)
Digit 2 — Direct Drive
Digit 4 — Development Sequence D = 362
E = 440
Digit 3 — Medium Pressure T = Unit-mounted, Air-/Liquid-cooled F = 533
Communicating with Tracer® AdaptiView™
G = 676
Controls
Digit 4 — Development Sequence H = 243
Digit 5, 6, 7, 8 — Starter Size
Digit 16 — Connection Type Short
Digit 5, 6, 7 — Nominal Total Compressor Circuit Current Rating (SCCR)
Use Rated Load Amps (RLA) Value
Tonnage 2 = Standard Circuit Breaker
S = Special
Digit 8 — Compressor AFD Input Design Digit 9 — Incoming Line Voltage/Unit
Voltage Drive Voltage Digit 17 — Control Power Option
B = 208V Incoming Line/460V-60Hz—3Ph
Digit 9 — Motor Type D = 380V incoming Line/400V-60Hz-Ph B = Control Power Transformer 3kVA
F = 460V Incoming Line/400V-60Hz-3Ph
Digit 10, 11 — Design Sequence G = 480V Incoming Line/400V-60Hz-3Ph Digit 18 — Panel Option
H = 575V Incoming Line/400V-60Hz-3Ph
J = 600V Incoming Line/400V-60Hz-3Ph 0 = None
Digit 12, 13, 14 — First Stage Impeller R = 380V incoming Line/400V-50Hz-3Ph 1 = Input Harmonic Filter
Designation S = Special 2 = 575V/60 Hz Autotransformer
T = 400V Incoming Line/400V-50Hz-Ph 3 = 208V/60 Hz Autotransformer
Digit 15, 16, 17 — Second Stage Impeller
U = 415V Incoming Line/400V-50Hz-3Ph S = Special Option
Designation
Digit 10, 11 — Design Sequence
Digit 18 — Bearing Type

AA = Original Design of Tracer® AdaptiView™


Digit 19 — Discharge Port Orientation Controls with TR200 Drive
AB

Digit 20 — Motor Cooling Digit 12 — Starter Type

A = Unit-mounted

HDWA-SVX001D-EN 9
General Information
Unit Description chillers and their components. Water inlet and outlet
openings are covered before shipment. The unit ships
Agility™ chillers are centrifugal, water-cooled liquid charged with refrigerant.
chillers designed for indoor installation. Each unit is a
completely assembled, hermetic package that is
factory-piped, wired, leak-tested, dehydrated, charged, Component Locations
and tested for proper control operation before
shipment. The following figures show typical Agility™ Chiller
Figure 3. Typical Agility chiller component location (front view)

10 HDWA-SVX001D-EN
General Information

Figure 4. Typical Agility chiller component location (back view)

HDWA-SVX001D-EN 11
General Information

Adaptive Frequency Drive Figure 6. Assembly harmonic filter options


Figure 5. Assembly transformer options Capacitors
Capacitors
Fans

Contactor

Inductor

Auto-transformer

12 HDWA-SVX001D-EN
General Information

Unit Clearances
Figure 7. Clearance requirements, in. (cm)

HDWA-SVX001D-EN 13
General Information

Dimensions and Weights Table 1. Agility chiller weights (lb)

Dimensions Shipping Weight


Operat-
Refer to unit submittals for specific chiller dimensions Shell With Without ing
Refriger- Refriger- Weight
and water connection locations.
ant ant

Unit Specifications—Imperial (I-P) Units Minimum 10100 9575 14087


020
Maximum 12302 11777 16775
Weights (lb)
I m p o r t a n t : The weight information provided here Minimum 12706 11906 14134
040
should be used for general information Maximum 15058 14258 16830
only. For specific weights for your chiller,
Notes:
refer to your submittal package. 1. All weights ±5 percent.
2. Shipping weights include standard 150 psig waterboxes.
3. Operating weights include refrigerant, glycol, and water
charges.
4. Optional waterbox hinges each weigh 44 lb (19.94 kg).

Center of Gravity (in.)


Table 2. Agility chiller center of gravity (in.)

Shipping Operating

X Y Z X Y Z

Mini- 29.2 31.2 39.7 29.6 29.3 39.8


mum

Maxi- 31.7 32.5 46.9 32.1 30.8 46.4


mum

Notes:
1. All weights ±5 percent.
2. Shipping weights include standard 150 psig waterboxes.
3. Operating weights include refrigerant, glycol, and water
charges.

Figure 8. Zero point location for center of gravity data

Left Rear Right Rear

Left Front Right Front

Right Front Mounting Hole


The bottom of this hole is the (0,0,0) point
for center of gravity dimensions.

Z X

14 HDWA-SVX001D-EN
General Information

Unit Specifications—International Center of Gravity (mm)


System (SI) Units Table 4. Agility chiller center of gravity (mm)
Weights (kg) Shipping Operating
I m p o r t a n t : The weight information provided here
X Y Z X Y Z
should be used for general information
only. For specific weights for your chiller, Mini- 742 793 1007 752 743 1011
refer to your submittal package. mum

Maxi- 804 826 1190 816 781 1178


Table 3. Agility chiller weights (kg) mum

Shipping Weight Notes:


Operat- 1. All weights ±5 percent.
Shell With Without ing 2. Shipping weights include standard 1034.2 kPaG waterboxes.
Refriger- Refriger- Weight 3. Operating weights include refrigerant, glycol, and water
ant ant charges.

Minimum 4591 4352 4980


020
Maximum 5592 5353 5836

Minimum 5775 5412 6425


040
Maximum 6845 6481 7650

Notes:
1. All weights ±5 percent.
2. Shipping weights include standard 1034.2 kPaG waterboxes.
3. Operating weights include refrigerant, glycol, and water
charges.
4. Optional waterbox hinges: each waterbox hinge weights 44 lb
(19.94 kg).

HDWA-SVX001D-EN 15
Pre-installation
ASHRAE Standard 15 Loose Parts Inventory
Compliance Check all items against the shipping list. Display,
display arm and mounting, water vessel drain plugs,
Trane recommends that indoor Agility™ chiller isolation pads, and other optional components are
installations fully meet or exceed the guidelines of the shipped loose in the parts box. Electrical diagrams and
current version of ASHRAE Standard 15, in addition to service literature are located inside the Adaptive
any applicable national, state, or local requirements. Frequency™ Drive (AFD) panel.
This typically includes:
• A refrigerant monitor or detector that is capable of
monitoring and alarming within the acceptable
Storage
exposure level of the refrigerant, and that can N o t e : If the chiller is stored outdoors for any amount of
actuate mechanical ventilation. time, d o N O T r e m o v e A N Y s h i p p i n g
• Audible and visual alarms, activated by the coverings. Protect the chiller from the
refrigerant monitor, inside the equipment room and elements and protect against freezing,
outside of every entrance. especially if any shipping materials have been
removed.
• The equipment room should be properly vented to If the chiller is to be stored more than one month prior
the outdoors, using mechanical ventilation that can to installation, observe the following precautions:
be activated by the refrigerant monitor.
• Do NOT store the chiller in areas in which the
• If required by local or other codes, a self-contained temperature exceeds 122°F (50.0°C) or the
breathing apparatus should be available in close refrigerant will relieve.
proximity to the equipment room.
• Do NOT remove the protective coverings from the
Refer to the latest copy of ASHRAE Standard 15 for electrical panel.
specific guidelines. Trane assumes no responsibility for
any economic, health, or environmental issues that • Store the chiller in a dry, secure area.
may result from an equipment room’s design or • Upon receipt and every three months thereafter,
function. attach a gauge and manually check the pressure in
the refrigerant circuit. Call a qualified service
Inspection Checklist organization and the appropriate Trane sales office
if:
To protect against loss due to damage incurred in – for R-134a, if the refrigerant pressure is below
transit, complete the following checklist upon receipt of 71 psig at 70°F (489.5 kPaG at 21.1°C) or 46 psig
the unit. at 50°F (317.2 kPaG at 10.0°C).
☐ Inspect the individual pieces of the shipment before – for R-513A, if the refrigerant pressure is below
accepting the unit. Check for obvious damage to the 77 psig (530.9 kPaG at 21.1°C) at 70°F or 50 psig
unit or packing material. at 50°F (344.7 kPaG at 10.0°C).
☐ Inspect the unit for concealed damage as soon as N o t e : Pressure will be approximately 5 psig (34.5
possible after delivery and before it is stored. kPaG) if shipped with the optional nitrogen
Concealed damage must be reported within 10 days charge
after receipt.
☐ If concealed damage is discovered, stop unpacking
the shipment. Do not remove damaged material
Installation Requirements and
from the receiving location. Take photos of the Contractor Responsibilities
damage, if possible. The owner must provide
reasonable evidence that the damage did not occur A list of the contractor responsibilities typically
after delivery. associated with the unit installation process is provided
in the following table.
☐ Notify the carrier’s terminal of the damage
immediately, by phone and by mail. Request an WARNING
immediate, joint inspection of the damage with the
carrier and the consignee.
Combustible Material!
Failure to follow instructions below could result in
☐ Notify the Trane sales representative and arrange death or serious injury or equipment damage.
for repair. Do not repair the unit, however, until
Shrink-wrap is a combustible material. Avoid open
damage is inspected by the transportation
flames and hot sparks.
representative.

16 HDWA-SVX001D-EN
Pre-installation

N o t e : The chiller should remain within its protective


shrink-wrap covering during storage.
Trane Supplied Trane Supplied Field Supplied
Type of Requirement
Trane Installed Field Installed Field Installed
Foundation • Meet foundation requirements
• Safety chains
Rigging • Rigging shackles
• Lifting beam
• Trane will perform or have
direct on-site supervision
Disassembly/Reassembly of the disassembly and
(as required) reassembly work (contact
your local Trane office for
pricing)
• Isolation pads
• Optional spring isolators, when required, are
Isolation • Isolation pads installed by others; do NOT overload springs and do
NOT install isolation springs if they block serviceable
parts such as service valves, etc.
• Electrical connections to unit-mounted AFD
• Wiring sizes per submittal and National Electric Code
(NEC)
• Circuit breakers • Temperature sensor • Ground connection(s)
(optional outdoor air)
• Unit-mounted Adaptive • BAS wiring (optional)
Frequency™ Drive (AFD) • Flow switches (may be
Electrical field supplied) • Inter-processor communication (IPC) wiring
• Harmonic filter (optional)
• Tracer® AdaptiView™ • Control voltage wiring
• Autotransformer display and mounting • High condenser pressure interlock wiring
(optional) arm
• Chilled water pump contactor and wiring
• Condenser water pump contactor and wiring
• Option relays and wiring

• Flow switches (may be • Thermometers


field supplied) • Water flow pressure gauges
Water piping • Condenser water • Isolation and balancing valves in water piping
regulating valve
controller (optional; • Vents and drain valves
may be field-supplied) • Pressure relief valves (for waterboxes as required)
Pressure Relief • Relief valves • Vent line and flexible connector
Insulation • Insulation (optional) • Insulation
“Appendix B: Agility™
Chiller Installation
Completion and Request
for Trane Service,” p. 70 • To be completed by installing contractor prior to
(HDWA-ADF001*-EN; contacting Trane for start-up
refer to “Appendix A:
Forms and Check
Sheets,” p. 69)
• Trane, or an agent of
Chiller start-up Trane specifically
commissioning(a) authorized to perform
start-up of Trane®
products
Post-commissioning
transport of empty • Move empty refrigerant containers to an easily
refrigerant containers for accessible point of loading
return or recycling
(a) Start-up must be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products. Contractor shall
provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the
scheduled start-up.

HDWA-SVX001D-EN 17
Installation: Mechanical
Location Requirements Ventilation
The unit produces heat even though the compressor is
Sound Considerations cooled by the refrigerant. Make provisions to remove
• Install rubber vibration isolators in all water piping. heat generated by unit operation from the equipment
• Isolate all pipe hangers and be sure they are not room. Ventilation must be adequate to maintain an
supported by main structure beams that could ambient temperature lower than 104°F (40°C).
introduce vibration into occupied spaces. Vent the evaporator, condenser, and compressor
• Make sure that the piping does not put additional pressure relief valves in accordance with all local and
stress on the unit. national codes. Refer to “Refrigerant Pressure Relief
Valve Venting,” p. 21.
N o t e : Do not use metal braided type eliminators on
the water piping. Metal braided eliminators Make provisions in the equipment room to keep the
are not effective at the frequencies at which chiller from being exposed to freezing temperatures
the unit will operate. (32°F [0°C]).

• Use flexible electrical conduit. Water Drainage


• Seal all wall penetrations. Locate the unit near a large capacity drain for water
N o t e : Consult an acoustical engineer for critical vessel drain-down during shutdown or repair.
applications. Condensers and evaporators are provided with drain
connections. Refer to “Overview,” p. 25. All local and
Foundation Requirements national codes apply.
Chiller mounting surface must be:
Access Restrictions
• rigid non-warping mounting pads or a concrete
foundation, and Door clearances are provided in “Unit Clearances,” p.
13. See unit submittals for specific "per unit"
• able to support the chiller at its full operating dimensional information.
weight (including completed piping and full
operating charges of refrigerant and water). Operating Environment
For proper unit operation, the chiller must be level Important:
within 1/4 in. (6.35 mm) over its length and width when
set into place on the mounting surface. Refer to • The standard chiller is designed for
“Leveling the Unit,” p. 21 for more information. For INDOOR USE ONLY and as such has
minimum and maximum chiller weights/dimensions in NEMA Type 1 enclosures.
pounds/inches and kilograms/millimeters, refer to • The warranty requires an equipment
“Weights (lb),” p. 14 and “Weights (kg),” p. 15, room/chiller environment surrounding
respectively. the NEMA 1 chiller to be maintained in
N o t e : For specific weight information, refer to the unit the temperature range of 34°F to 104°F
submittal package. (1.1°C to 40°C) AND at less than 95%
relative humidity (non-condensing
I m p o r t a n t : Trane will not assume responsibility for conditions). If your equipment room/
equipment problems resulting from an chiller environment does not meet
improperly designed or constructed these conditions, contact your local
foundation. Trane Service Agency immediately.
Clearances
NOTICE
Provide enough space around the unit to allow the
installation and maintenance personnel unrestricted
Equipment Damage!
access to all service points. Refer to submittal drawings Failure to protect the unit from freezing could
for the unit dimensions. result in equipment damage.
If fluid has been added to the piping, the unit must
Refer to “Unit Clearances,” p. 13 for minimum be protected from freezing. Freeze damage from
clearances required for service. In all cases, local codes an unheated equipment room is not the Trane
will take precedence over these recommendations. company's responsibility. These are indoor units.

18 HDWA-SVX001D-EN
Installation: Mechanical

NOTICE Table 5. Environmental conditions

AFD Component Damage! Condition Specification


Ambient Temperature 32°F to 104°F
Operating unit at ambient temperatures below 34° (outside NEMA 1 enclosure) (0°C to 40°C)
F (1.1°C) or in excess of 104°F (40°C), or in excess -20°F to 122°F
Storage Temperature (ambient)
of 95% relative humidity (non-condensing (-28.9°C to 50.0°C)
conditions), could result in AFD component Humidity 5% to 95% (non-condensing)
damage due to the panel’s inability to dissipate
heat adequately.
If any of these adverse operating conditions are Rigging
present, take necessary action to improve the Lifting is the recommended method for moving
equipment room environment. chillers. Suggested lifting arrangements for standard
units are described in “Standard Chiller Lift,” p. 20.
To ensure that electrical components operate properly,
do NOT locate the chiller in an area exposed to dust, N o t e : The lifting beam used for HDWA Agility™ chillers
dirt, corrosive fumes, or excessive heat and humidity. must be at least 12.5 ft (3.8 m) long.
The ambient temperature range for chiller operation is I m p o r t a n t : If unit must be disassembled for
34°F to 104°F (1.1°C to 40°C). installation, refer to Installation
Instructions: Agility Chiller Disassembly/
Adaptive Frequency Drive Enclosure Reassembly Units (HDWA-SVN001*-EN) for
Rating instructions, including weights and rigging
instruction for components.
The Adaptive Frequency™ Drive (AFD) cabinet has a
Agility™ chillers should be moved ONLY by lifting at
NEMA 1 enclosure rating:
designated lift points. Refer to the following
NEMA 1: Vented. Intended for general-purpose indoor instructions in this manual for typical rigging
applications. arrangements.

Environmental Conditions WARNING


I m p o r t a n t : Location of the Adaptive Frequency™ Drive Heavy Object!
(AFD) is important if proper performance Failure to follow instructions below could result in
and normal operating life is to be expected. unit dropping which could result in death or
Therefore, unless designed for special serious injury, and equipment or property-only
environments, the controller should be damage.
installed in an area where the following
Ensure that all the lifting equipment used is
conditions exist
properly rated for the weight of the unit being
• Verify that NEMA 1 enclosure drives can be kept lifted. Each of the cables (chains or slings), hooks,
clean and dry. and shackles used to lift the unit must be capable
• The area chosen should allow the space required of supporting the entire weight of the unit. Lifting
for proper air flow. Adequate clearance for air cables (chains or slings) may not be of the same
circulation around the enclosure is a 6 in. (16 cm) length. Adjust as necessary for even unit lift.
minimum clearance required wherever vents are
located in the cabinet. WARNING
• Be sure that the NEMA 1 enclosure is installed away Improper Unit Lift!
from oil, coolants, or other airborne contaminants. Failure to properly lift unit in a LEVEL position
• Do NOT install the drive above 3300 ft (1005.8 m) could result in unit dropping and possibly
without derating output power. For every 300 ft crushing operator/technician which could result in
(91.4 m) above 3300 ft (1005.8 m), derate the output death or serious injury, and equipment or
current 1 percent. property-only damage.
• Line frequency is 50 or 60 Hz. Test lift unit approximately 24 inches (61 cm) to
verify proper center of gravity lift point. To avoid
• Non-corrosive location. dropping of unit, reposition lifting point if unit is
• Verify that the drive location will meet the not level.
environmental conditions specified in the following
table.

HDWA-SVX001D-EN 19
Installation: Mechanical

NOTICE Special Lift Requirements


Wiring Damage! NOTICE
Damage to unit wiring could result in equipment
failure.
Equipment Damage!
Care must be taken during rigging, assembly and Moving the chiller using a fork lift could result in
disassembly to avoid damaging unit wiring. equipment or property-only damage.
Do not use a fork lift to move the chiller!

Standard Chiller Lift If the chiller cannot be moved using a standard chiller
lift, consider the following:
1. Insert rigging shackles at the points indicated in the
following figure. A 1.25 in. (31.8 mm) diameter • When job site conditions require rigging of the
lifting hole is provided at each of these points. chiller at an angle greater than 45° from horizontal
(end-to-end), the unit may require removal of the
2. Attach the lifting chains or cables. compressor. Contact Trane or an agent of Trane
3. After the lifting cables are in place, attach a safety specifically authorized to perform start-up and
chain or cable between the first-stage of the warranty of Trane® products regarding the
compressor and the lifting beam. disassembly and reassembly work. For more
I m p o r t a n t : There should NOT be tension on this information, refer to “Factory Warranty
safety cable; the cable is used only to Information,” p. 3.
prevent the unit from rolling during the N o t e : Disassembly and reassembly work includes
lift. removing the compressor from the unit.
4. Position isolator pads beneath the chiller feet (refer Contact Trane or an agent of Trane
to “Unit Isolation,” p. 20 for instructions). specifically authorized to perform start-up
and warranty of Trane® products for specific
5. Once the isolators are in place, lower the chiller— rigging instructions. Do NOT attempt to
working from end to end—in small increments to rotate the chiller onto its side.
maintain stability.
• When lifting the chiller is either impractical or
6. When lift is complete, detach the rigging shackles undesirable, machinery dollies should be placed
and safety chain. under the supports; then push or pull the unit
Figure 9. Typical rigging arrangements across a smooth surface. Should the chiller be on
blocks, it is not necessary to remove the blocks
Lifting beam
from the chiller before moving it into place.
• Use care on uneven surfaces. Piping in the center of
10 to 12 ft (3.0 to 3.7 m) the unit is within 1/2 in. (12.7 mm) of the ground.
6 in. (15.2 cm) effective length

Unit Isolation
To minimize sound and vibration transmission through
the building structure and to ensure proper weight
distribution over the mounting surface, Trane
recommends installing isolation padding under the
chiller feet. For seismic installations, refer to the
specific installation details provided by the foundation
designer.
N o t e : Isolation pads are provided with each chiller.
Specific isolator loading data is provided in the unit
submittal package. If necessary, contact your local
Trane sales office for further information.
I m p o r t a n t : When determining placement of isolation
pads, remember that the control panel side
Safety chain
of the unit is always designated as the front
side of the unit.

Isolation Pads
When isolation pads are used, place them under each
of the eight individual mounting points. The pads may

20 HDWA-SVX001D-EN
Installation: Mechanical

be cut to suit the application, but should cover the both the condenser and evaporator; refer to the
entire face of the support. following figures.
2. Use a water level to align the tooling holes across
Leveling the Unit the condenser tube sheet; refer to the following
N o t e : The chiller MUST be set level within 1/4 in. figures.
(6.35 mm) over its length and width. I m p o r t a n t : Do NOT level the tooling holes from the
1. Use a water level to align the tube sheet tooling evaporator to the condenser as they
holes or bottom edge of the tube sheet axially along may be at different heights.

Figure 10. Leveling the chiller (front and left views)

Figure 11. Leveling the chiller (tooling hole) Refrigerant Pressure Relief Valve Venting
WARNING
Confined Space Hazards!
Failure to follow instructions below could result in
death or serious injury.
Do not work in confined spaces where refrigerant
or other hazardous, toxic or flammable gas may be
Tooling hole leaking. Refrigerant or other gases could displace
available oxygen to breathe, causing possible
asphyxiation or other serious health risks. Some
gases may be flammable and or explosive. If a leak
in such spaces is detected, evacuate the area
immediately and contact the proper rescue or
response authority.

N o t e : Vent pipe size must conform to the ANSI/


ASHRAE Standard 15 for vent pipe sizing. All
federal, state, and local codes take precedence
over any suggestions stated in this manual.
All relief valve venting is the responsibility of the
installing contractor.
All HDWA chillers use evaporator and condenser
pressure relief valves (refer to the following figure) that
must be vented to the outside of the building.

HDWA-SVX001D-EN 21
Installation: Mechanical

Figure 12. Location of relief valves NOTICE


Equipment Damage!
Failure to comply with specifications may result in
capacity reduction, unit damage and/or relief valve
Condenser
damage.
Pressure
Relief Valve Do NOT exceed vent piping code specifications!

Relief valve discharge setpoints and capacities rates


are provided in the following table. After the relief
valve has opened, it will re-close when pressure is
reduced to a safe level.
Evaporator
se r N o t e : After they are opened, relief valves may have
den Pressure
Con tendency to leak and must be replaced.
Relief Valve
Pressure relief valve discharge capacities varies with
tor
pora shell diameter and length and also compressor
Eva
displacement. Discharge venting capacity should be
calculated as required by ASHRAE Standard 15-94. Do
NOT adjust relief valve setting in the field.
Relief valve connection sizes and locations are shown
in unit submittals. Refer to local codes for relief valve
vent line sizing information.

Table 6. Pressure relief valve data


Factory Shell Side
Discharge Setpoint Rated Capacity Field Connection Pipe Size
Connection
Valve Location
lb air/ kg air/
psi kPa NPT mm in. mm
min. min.
Evaporator—
Compressor Low Side 200 1379.0 78.8 35.7 1-1/4 31.8 1-5/8 - 12 41.3 – 304.8
Pipe (Suction)
Condenser 300 2068.4 49.2 22.3 3/4 19.1 7/8 - 14 22.2 – 355.6

22 HDWA-SVX001D-EN
Installation: Mechanical

Freeze Protection freezing. Refer to the following tables for adjusted


settings and recommended ethylene glycol and
For unit operation in a low temperature environment, propylene glycol solution strengths.
adequate protection measures must be taken against

Table 7. Agility chiller control settings based on ethylene glycol percentage

Ethylene Glycol Solution Freeze Point Minimum Recommended LRTC Minimum Recommended LWTC
Percentage, % °F °C °F °C °F °C
0 32.0 0.0 28.6 -1.9 34.0 1.1
2 31.0 -0.6 27.6 -2.5 33.0 0.5
4 29.7 -1.3 26.3 -3.2 31.7 -0.2
5 29.0 -1.7 25.6 -3.6 31.0 -0.6
6 28.3 -2.0 24.9 -3.9 30.3 -0.9
8 26.9 -2.8 23.5 -4.7 28.9 -1.7
10 25.5 -3.6 22.1 -5.5 27.5 -2.5
12 23.9 -4.5 20.5 -6.4 25.9 -3.4
14 22.3 -5.4 18.9 -7.3 24.3 -4.3
15 21.5 -5.9 18.1 -7.7 23.5 -4.7
16 20.6 -6.3 17.2 -8.2 22.6 -5.2
18 18.7 -7.4 15.3 -9.3 20.7 -6.3
20 16.8 -8.4 13.4 -10.3 18.8 -7.3
22 14.7 -9.6 11.3 -11.5 16.7 -8.5
24 12.5 -10.8 9.1 -12.7 14.5 -9.7
25 11.4 -11.4 8.0 -13.3 13.4 -10.3
26 10.2 -12.1 6.8 -14.0 12.2 -11.0
28 7.7 -13.5 4.3 -15.4 9.7 -12.4
30 5.1 -15.0 1.7 -16.8 7.1 -13.8
32 2.3 -16.5 -1.1 -18.4 5.0 -15.0
34 -0.7 -18.2 -4.1 -20.1 5.0 -15.0
35 -2.3 -19.0 -5.7 -20.9 5.0 -15.0
36 -3.9 -19.9 -7.3 -21.8 5.0 -15.0
38 -7.3 -21.8 -10.7 -23.7 5.0 -15.0
40 -10.8 -23.8 -14.2 -25.7 5.0 -15.0

Table 8. Agility chiller control settings based on propylene glycol percentage


Propylene Solution Freeze Point Minimum Recommended LRTC Minimum Recommended LWTC
Glycol
Percentage, % °F °C °F °C °F °C
0 32.0 0.0 28.6 -1.9 34.0 1.1
2 31.0 -0.6 27.6 -2.4 33.0 0.6
4 29.9 -1.2 26.5 -3.1 31.9 -0.1
5 29.3 -1.5 25.9 -3.4 31.3 -0.4
6 28.7 -1.8 25.3 -3.7 30.7 -0.7
8 27.6 -2.5 24.2 -4.4 29.6 -1.4
10 26.4 -3.1 23.0 -5.0 28.4 -2.0
12 25.1 -3.8 21.7 -5.7 27.1 -2.7
14 23.8 -4.6 20.4 -6.5 25.8 -3.5
15 23.1 -5.0 19.7 -6.8 25.1 -3.8
16 22.4 -5.4 19.0 -7.2 24.4 -4.2
18 20.9 -6.2 17.5 -8.1 22.9 -5.1
20 19.3 -7.1 15.9 -9.0 21.3 -6.0

HDWA-SVX001D-EN 23
Installation: Mechanical

Table 8. Agility chiller control settings based on propylene glycol percentage (continued)
Propylene Solution Freeze Point Minimum Recommended LRTC Minimum Recommended LWTC
Glycol
Percentage, % °F °C °F °C °F °C
22 17.6 -8.0 14.2 -9.9 19.6 -6.9
24 15.7 -9.0 12.3 -10.9 17.7 -7.9
25 14.8 -9.6 11.4 -11.5 16.8 -8.5
26 13.8 -10.1 10.4 -12.0 15.8 -9.0
28 11.6 -11.3 8.2 -13.2 13.6 -10.2
30 9.3 -12.6 5.9 -14.5 11.3 -11.5
32 6.8 -14.0 3.4 -15.9 8.8 -12.9
34 4.1 -15.5 0.7 -17.4 6.1 -14.4
35 2.7 -16.3 -0.7 -18.1 5.0 -15.0
36 1.3 -17.1 -2.1 -19.0 5.0 -15.0
38 -1.8 -18.8 -5.2 -20.7 5.0 -15.0
40 -5.2 -20.7 -8.6 -22.5 5.0 -15.0

24 HDWA-SVX001D-EN
Installation: Water Piping
Overview Valves—Drains and Vents
The following water piping circuits must be installed NOTICE
and connected to the chiller:
Waterbox Damage!
• Pipe the evaporator into the chilled water circuit.
Failure to follow instructions could result in
• Pipe the condenser into the cooling tower water damage to the waterbox.
circuit. Do not over-tighten or use excessive Teflon® pipe
N o t e : Piping must be arranged and supported to avoid tape when installing valves, drains, plugs and
stress on the equipment. It is strongly vents on waterboxes.
recommended that the piping contractor does
1. Install field-supplied air vents and drain valves on
not run pipe closer than 3 ft (0.9 m) minimum to
the waterboxes. Each waterbox is provided with a
the equipment. This will allow for proper fit upon
National Pipe Thread Female (NPTF) vent and drain
arrival of the unit at the job site. Any adjustment
connection; depending on the waterbox types
that is necessary can be made to the piping at
ordered, the openings may be 1/4 in. (6.35 mm), 1/
that time. Expenses that result from a failure to
2 in. (12.7 mm), or 3/4 in. (19.05 mm).
follow this recommendation will NOT be paid by
Trane.
NOTICE
Piping suggestions for each of the water circuits listed
above are outlined in “Evaporator and Condenser Waterbox Damage!
Water Piping,” p. 28. General recommendations for the Failure to follow instructions could result in
installation of field-supplied piping components (e.g., damage to the waterbox due to hydrostatic
valves, flow switches, etc.) common to most chiller expansion.
water circuits are listed in the following sections. Install pressure-relief valves in the condenser
and evaporator water circuits.
Water Treatment
NOTICE
The use of untreated or improperly treated water in a
Agility™ chiller may result in inefficient operation and Equipment Damage!
possible tube damage. Failure to follow instructions could result in
I m p o r t a n t : Trane strongly recommends using the equipment damage.
services of a qualified water treatment Do NOT allow chiller to freeze! Bundles must
specialist to determine necessary water be drained and air-blown dry if chiller is stored
treatment. A label with a customer in an unheated equipment room.
disclaimer note is affixed to each unit.
2. If necessary for the application, install pressure-
NOTICE relief valves at the drain connections on the
evaporator and condenser waterboxes. To do so,
Proper Water Treatment Required! add a tee with the relief valve attached to the drain
The use of untreated or improperly treated water valve.
could result in scaling, erosion, corrosion, algae or
slime. To determine whether or not pressure relief valves
are needed for a specific application, keep in mind
Use the services of a qualified water treatment
that:
specialist to determine what water treatment, if
any, is required. Trane assumes no responsibility a. Vessels with close-coupled shutoff valves may
for equipment failures which result from untreated cause high potentially damaging hydrostatic
or improperly treated water, or saline or brackish pressures as fluid temperature rises.
water. b. Relief valves are required by American Society
of Mechanical Engineers (ASME) codes when
the shell waterside is ASME. Follow ASME
Water Pressure Gauges guidelines or other applicable codes to ensure
Locate pressure gauge taps in a straight length of pipe. proper relief valve installation.
Place each tap a minimum of one pipe diameter
downstream of any elbow, orifice, etc. For example, for
a 6 in. (16 cm) pipe, the tap would be at least 6 in. (16
cm) from any elbow, orifice, etc.

HDWA-SVX001D-EN 25
Installation: Water Piping

Strainers Figure 13. Installation of ifm efector flow detection


controller and sensor
NOTICE
Water Born Debris! If factory-provided,
To prevent components damage, pipe strainers located in control panel.
must be installed in the water supplies to protect Components:
A. E40174 – 1/2" NPT adapter (for flow probe)
components from water born debris. Trane is not B. SF6200 – Flow probe
C. SN0150 – Flow control monitor
responsible for equipment-only-damage caused D. E70231 – Combicon connectors (quantity 5)
by water born debris.
4
E. E10965 – Micro DC cable, 10m length, PUR jacket
F. F53003 – Din rail, 40mm length

Install a strainer in the entering side of each piping


circuit to avoid possible tube plugging in the chiller 3
with debris.
Installation
1. Install adapter (A) into pipe.
Required Flow-Sensing Devices
2
2. Mount flow probe (B) into adapter (A).
3. Install DIN rail (F) into control cabinet.

The ifm efector® flow detection controller and sensor 4. Install control monitor (C) onto DIN rail (F).
Use a marker to draw a line
5. Connect cable (E) to flow probe (B), (hand tighten only).
(refer to “Water Flow Detection Controller and on the
6. Wire cable in combicon probe
connectors atto 3.5 in. (8.9 cm)
(D) according
wiring diagram.
Sensor,” p. 26) is used to verify evaporator and from the probe end.
1
7. Wire relay outputs for flow, wire-break, and/or
temperature monitoring, according to wiring diagram.
condenser water flows.
If a customer-supplied flow sensing device is used to To wire the flow monitoring L
and wire-break monitoring AC

ensure adequate chiller flow protection, refer to the relay outputs in series, use
the wiring diagram at right.
Jumper N

wiring diagrams that shipped with the unit for specific Flow monitoring
Wire break monitoring
Jumper

Temperature monitoring
electrical connections. Power-on delay time
Selection liquid / gas
Do NOT insert more than
Output to
control cabinet

Be sure to follow the manufacturer’s recommendations Temperature monitoring can


also be incorporated using 3.5 in. (8.9 cm) of the
terminals 10, 11, and 12.
for device selection and installation. probe length into the pipe.
Water Flow Detection Controller and
Sensor Figure 14. Location of ifm efector flow detection
I m p o r t a n t : Before installing the ifm efector® flow controller and sensor
detection controller and sensor, use a
marker to draw a line on the probe at 3.5 in.
(8.9 cm) from the end of the probe. Do NOT
insert more than 3.5 in. (8.9 cm) of the
probe length into the pipe. Refer to the
following figure.

N o t e : In Agility™ chillers, the ifm efector® flow


detection controller and sensor is mounted in the
waterbox nozzle, as shown in the preceding
figure.

26 HDWA-SVX001D-EN
Installation: Water Piping

1. Mount the 1/2-in. NPT adapter in a horizontal or NOTICE


vertical section of pipe. The maximum distance
from the control panel must not exceed 29.5 ft (9 m) Do Not Apply Electrical Power to a
(see item labeled “1” in the preceding figure). Allow Unit in a Vacuum!
at least five pipe diameters straight run of pipe Failure to follow instructions below could
upstream of the sensor location, and three pipe result in motor and compressor damage.
diameters straight run of pipe downstream of the Do not apply electrical power to a motor in a
sensor location. vacuum.
Notes:
5. Apply power to the chiller control panel to verify the
• In Agility™ chillers, the ifm efector® flow Flow Control Monitor has power and the Low Volt
detection controller and sensor is Broken Wire Relay light is NOT lit.
mounted in the waterbox nozzle, as
shown in the preceding figure. 6. Remove all air from the piping circuit prior to
adjusting the low water flow setpoint.
• If the ifm efector® flow detection
controller and sensor is mounted in an 7. Reduce the water flow to the minimum allowable
alternate location on a horizontal pipe, flow and adjust the Flow setting on the Flow
mounting the sensor in the side of the Control Monitor (see item labeled “7” in the
pipe is preferred; in the case of a vertical following figure). Adjusting the “Flow”
pipe, mounting the sensor in a place potentiometer clockwise (+) reduces the flow
where the water flows upwards is setting cutout and adjusting counterclockwise (-)
preferred. increases the flow setting cutout.
N o t e : The “Temp” potentiometer on the ifm
NOTICE efector® control module has no effect in
Trane application. It is NOT necessary to
Overtightening! make adjustments to the “Temp”
Do not exceed torque specifications as it could potentiometer.
result in equipment damage.
8. After the cutout setting is adjusted, the cutout
2. Insert the flow sensor probe (see item labeled “2” setpoint will be indicated with a yellow light on the
in the preceding figure) through the 1/2-in. NPT Flow Control Monitor LED bar graph display. When
adapter so that 3 to 3.5 in. (7.6 to 8.9 cm) of the the water flows are higher than the cutout, a green
probe’s length extends into the pipe. Tighten the 1/ light will indicate proper flow status. If the flows fall
2-in. NPT adapter as needed to prevent leakage and below the cutout setpoint, a red light will indicate
keep the probe from backing out under pressure. low/no flow status.
Do NOT exceed 40 ft·lb (54.2 N·m) of torque on ® flow sensing device terminal
Figure 15. ifm efector®
the fitting. Sensor damage can occur if it is connection
overtightened.
N o t e : When installed, the tip of the ifm efector®
sensor probe must be at least 1 in. (2.54 cm)
away from any pipe wall. Do NOT insert more
than 3.5 in. (8.9 cm) of the probe length into
the pipe.
3. Install the Micro DC Cable by inserting it through
the wire openings on the back side of the control
panel (see item labeled “3” in the preceding figure). 7
Install the supplied Micro DC Cable (29.5 ft [9 m] in
length) to the Flow Probe and hand-tighten the
connector nut.
4. Plug the other end of the Micro DC Cable into the
Flow Control Monitor with the Combicon connector
(see item labeled “4” in the preceding figure). Refer
to the following figure for cable wiring.

HDWA-SVX001D-EN 27
Installation: Water Piping

NOTICE Figure 16. Typical evaporator water piping circuit

Proof of Flow Switch!


Failure to provide flow switches or jumping-out of
Outlet
switches could result in severe equipment
damage. 2 1 7 3 5 4
2
Evaporator and condenser water circuits require
9
proof of flow switches.
• Failure to include the proof of flow devices and/ 2
or jumping out these devices could cause the unit Inlet
to stop on a secondary level of protection. 6 8 2 3 5 4
• Frequent cycling on these higher level
diagnostic devices could cause excessive thermal
and pressure cycling of unit components (O-rings, 1. Balancing valve.
gaskets, sensors, motors, controls, etc.) and/or 2. Gate (Isolation) valve or ball valve.
freeze damage, resulting in premature failure of
3. Thermometer (if field supplied).
the chiller.
4. Waterbox nozzle connection.
Evaporator and condenser proof of flow switches are
required. These switches are used with control logic to 5. Drain, vent, and anode.
confirm flow prior to starting a unit and to stop a 6. Strainer.
running unit if flow is lost. For troubleshooting, a 7. Chilled water flow switch (5S1). Flow switch 5S1
viewable diagnostic is generated if a proof of flow may be installed in either the entering or leaving leg
switch does not close when flow is required. of the chilled water circuit.
8. Pump.
Evaporator and Condenser 9. Pressure gauge. It is recommended to pipe the
Water Piping gauge between entering and leaving pipes. A
shutoff valve on each side of the gauge allows the
The following two figures illustrate the recommended
operator to read either entering or leaving water
(typical) water piping arrangements for the evaporator
pressure.
and condenser.
Figure 17. Typical condenser water piping circuits

Outlet
4 2 5 3 7 1 2 8

10

2
Inlet
4 5 3 2 9 6

1. Balancing valve.
2. Gate (isolation) valve or ball valve.
3. Thermometer (if field supplied).
4. Waterbox nozzle connection.
5. Drain, vent, and anode.
6. Strainer.
7. Condenser water flow switch (5S2). Flow switch
5S2 may be installed in either the entering or
leaving leg of the chilled water circuit.
8. Three-way valve (optional).
9. Condenser water pump.
10. Pressure gauge. It is recommended to pipe a single
gauge between entering and leaving pipes.

28 HDWA-SVX001D-EN
Installation: Water Piping

Piping must be arranged and supported to avoid stress Piping joined using grooved type couplings, like all
on the equipment. It is strongly recommended that the types of piping systems, requires proper support to
piping contractor does not run pipe closer than 3 ft carry the weight of pipes and equipment. The support
(0.9 m) minimum to the equipment. This will allow for methods used must eliminate undue stresses on joints,
proper fit upon arrival of the unit at the job site. Any piping, and other components, allow movement where
adjustment that is necessary can be made to the piping required, and provide for any other special
at that time. Expenses that result from a failure to requirements (i.e., drainage, etc.).
follow this recommendation will NOT be paid by Trane. N o t e : If needed, plug-type sensor extension cables are
Water piping connection sizes and components are available for purchase from Trane Parts Service.
identified in the tables in “Water Piping These sensor extension cables may be necessary
Connections,” p. 29 and “Grooved Pipe Coupling,” p. if the waterboxes are changed or if the
30. Remember that with many waterboxes, the temperature sensors are moved out into the unit
entering and leaving evaporator water can be piped to piping for better mixed temperature readings.
either waterbox connection when the tube bundles are
Table 9. Water connection pipe sizes
split vertically. However, large evaporator waterboxes
with entering and leaving connections not at the same Nominal Pipe Size
level must be connected with the entering water at the EVSZ/CDSZ 2 Pass
bottom and the leaving water at the top.
in. mm
Waterboxes with multiple pass arrangements utilize a 020 6 168.3
baffle to separate the passes. These baffles are
040 8 219.1
designed for a maximum pressure of 20 psid
(137.9 kPaD). If larger pressure drops are expected in
the application, contact your local Trane representative Figure 18. Typical grooved pipe connection
to discuss special waterbox options.
I m p o r t a n t : Water flows must be piped in accordance
with nameplate designation.
Field-provided isolation valves for the evaporator and
condenser water lines should be installed upstream
and downstream of the heat exchangers, and be
installed far enough away from the chiller to also
provide practical service isolation for flow sensing
devices, field thermometers, flexible connectors, and
any removable pipe spools.
Ensure that the evaporator water piping is clear; check
it after the chilled water pump is operated but before
initial chiller start-up. If any partial blockages exist, they
can be detected and removed to prevent possible tube
damage resulting from evaporator freeze-up or
erosion.
For condenser and evaporator connections, arrange
the water piping so that the water supply enters the
shell at the lower connection and exits from the top
connection. Operational problems may result if this
piping is not correct.
For applications that include an “infinite source” or
“multiple-use” cooling condenser water supply, install
a valved bypass “leg” (optional) between the supply
and return pipes. This valved bypass allows the
Waterbox Locations
operator to short-circuit water flow through the cooling N o t e : Do NOT interchange evaporator and condenser
condenser when the supply water temperature is too waterboxes. Supply evaporator waterbox and
low. tubesheet contain match marks to aid in
identifying matching shells and waterboxes.
Water Piping Connections If removal of waterboxes is necessary, refer to
“Waterbox Removal,” p. 65.
All standard units use grooved-pipe connections.
These are grooved-end NSP (Victaulic® style) pipe If the waterboxes on any of the shells are exchanged
connections. Flanged connections are optional. end-for-end, be sure to reinstall them right-side up to

HDWA-SVX001D-EN 29
Installation: Water Piping

maintain the correct baffle arrangements. Use a new Figure 19. Customer piping connection types
gasket with each waterbox cover.
Flanged Victaulic®
Reversing Waterboxes Waterbox Waterbox
All waterboxes can be reversed end-for-end. Refer to
Customer
“Waterbox Removal,” p. 65 for detailed waterbox
removal instructions.
Remove sensors from wells before removing
waterbox.
Do NOT rotate waterboxes.
Flange Adaptor Style 77 Flexible
Complete the waterbox switch and replace sensors. Trane provided Customer provided
Notes:
• If waterboxes are reversed, be sure to Notes:
properly rewire water temperature sensors • Refer to the coupling manufacturer’s
in the control panel. guidelines for specific information
• Be sure to replace waterboxes right-side-up concerning proper piping system design
to maintain proper baffle orientation. Use and construction methods for grooved
new O-rings. water piping systems.
• if the waterbox is revered, be sure to match • Flexible coupling gaskets require proper
mark on the baffle and the waterbox to lubrication before installation to provide a
ensure they are aligned. good seal. Refer to the coupling
manufacturer’s guidelines for proper
lubricant type and application.

Flange-connection Adapters
NOTICE
Never Weld to Cast Boxes!
Welding to cast boxes will result in equipment
damage.
Adapters must be used to convert flanges.

When flat-face flange connections are specified, flange-


to-groove adapters are provided (Victaulic® Style 741 ,
150 psig [1034.2 kPaG]). The adapters are shipped in
spare parts box included with the unit. Adapter
descriptions are given in the tables in “Victaulic Gasket
Installation,” p. 31. The flange adapters provide a
Grooved Pipe Coupling direct, rigid connection of flanged components to the
grooved-pipe chiller waterbox connections.
A customer-supplied, standard flexible grooved pipe
coupling (Victaulic® Style 77 or equivalent) should be In this case, the use of flexible type connectors (i.e.,
used to complete the Victaulic® connection for both braided steel, elastomeric arch, etc.) are recommended
150 psig (1034.2 kPaG) and 300 psig (2068.4 kPaG) to attenuate vibration and prevent stress at the
waterboxes. waterbox connections.
When a flexible coupling such as this is installed at the All flange-to-flange assembly screws must be provided
waterbox connections, other flexible piping connectors by the installer. Hex head screw sizes and number
(i.e., braided-steel, elastomeric arch, etc.) are not required are included in the tables in “Victaulic Gasket
usually required to attenuate vibration and/or prevent Installation,” p. 31. The Style 741 (150 psig
stress on the connections. [1034.2 kPaG]) flange adapter requires a smooth, hard
surface for a good seal.
Connection to other type flange faces (i.e., raised,
serrated, rubber, etc.) requires the use of a flange
washer between the faces. Refer to the flange adapter
manufacturer’s guidelines for specific information.

30 HDWA-SVX001D-EN
Installation: Water Piping

The flange-adapter gasket must be placed with the 4. Open fully and place hinged Victaulic® flange
color-coded lip on the pipe and the other lip facing the around the grooved pipe end with the circular key
mating flange. section locating into the groove.

NOTICE 5. Insert a standard hex head screw through the


mating holes of the Victaulic® flange to secure the
Piping Connection Leaks! flange firmly in the groove.
Failure to provide effective seal could result in 6. Tighten fasteners alternately and equally until
equipment or property-only damage. housing screw pads are firmly together (metal-to-
To provide effective seal, gasket contact surfaces metal); refer to “Screw-Tightening Sequence for
of adapter must be free of gouges, undulations or Water Piping Connections,” p. 31. Do NOT
deformities. excessively tighten fasteners.
N o t e : Uneven tightening may cause the gasket to
Victaulic Gasket Installation pinch.

1. Inspect supplied gasket to be certain it is suited for ® flange gasket


Figure 20. Typical Victaulic®
intended service (code identifies gasket grade). configuration
Apply a thin coat of silicone lubricant to gasket tips
and outside of gasket.
2. Install gasket, placing gasket over pipe end and
making sure gasket lip does not overhang pipe end.
Refer to the following figure for gasket
configuration.
3. Align and bring two pipe ends together and slide
gasket into position centered between the grooves
on each pipe. No portion of the gasket should
extend into the groove on either pipe.

Table 10. Installation data for 150 psig (1034.2 kPaG) flange adapters (Style 741)
Assembly
Nominal Pipe Size Number of Assembly Screw Pattern Diameter Weight
Screw Size(a)
Screws Required
in. mm in. in. mm lb kg
6 168.3 3/4 x 3-1/2 8 9.5 241 10.3 4.7

8 219.1 3/4 x 3-1/2 8 11.75 298 16.6 7.5


(a) Screw size for conventional flange-to-flange connection. Longer screws are required when flange washer must be used. Grade 5 screws are
recommended.

Screw-Tightening Sequence for Figure 21. Flange screw tightening sequence (8


screws)
Water Piping Connections
7 1
This section describes a screw-tightening sequence for
flanges with flat gaskets or O-rings. Remember that 4 5
improperly tightened flanges may leak.
N o t e : Before tightening any of the screws, align the
flanges. 8 3

Flanges with 8 Screws 2 6

Tighten all screws to a snug tightness, following the


numerical sequence for the appropriate pattern as
8 screws
shown in the following figure. Repeat this sequence to
apply the final torque to each screw.

HDWA-SVX001D-EN 31
Installation: Water Piping

Pressure Testing Waterside water-cooled chillers every three years. Eddy current
tests are intended to identify defects on or within the
Piping walls of heat exchanger tubing that could lead to in-
service tube failures. Eddy current tests conducted
NOTICE before a chiller is put into service are considered
Equipment Damage! “baseline” eddy current tests, and are intended to
Failure to follow these instructions could result in establish a reference point to aid in the interpretation of
equipment damage. future eddy current test reports. Many of the anomalies
that can be found through eddy current testing have no
Do not over pressurize the system or exceed
impact on tube life or performance, while others are
design pressure. Always perform a hydro pressure
severe enough to justify removing the affected tube
test with water present in piping and waterboxes.
from service. Ask your sales account manager for a
Waterside design pressure is 150 psig (1034.2 kPaG). copy of the engineering bulletin (CTV-PRB024*-EN) for
clarification of the role of eddy current testing in chiller
maintenance by providing information about eddy
Eddy Current Testing current technology and heat exchanger tubing.
Trane recommends conducting an eddy current
inspection of the condenser and evaporator tubes in

32 HDWA-SVX001D-EN
Insulation
Unit Insulation Requirements Table 11. Agility chiller insulation requirements
Factory-installed insulation is available as an option for 3/4 in. (19.05 mm)
all units. Factory installation does NOT include Insulation,
Location
Square Feet (Square
insulation of the chiller feet. In applications where the
Meters)
chiller is not factory-insulated, install insulation over all
020A Evaporator, suction elbow,
surfaces shown in the figure in “Factory-applied 105 (9.8)
pipe
Insulation,” p. 33 (i.e., compressor, condenser, 040A Evaporator, suction elbow,
120 (11.1)
economizer, and drive [not shown]). pipe

The quantity of insulation required is listed in the


following table. Insulation thickness is determined at
normal design conditions which are:
Insulation Thickness
• Standard comfort-cooling leaving chilled water Requirements
temperature
Factory-applied Insulation
• 85°F (29.4°C) dry bulb ambient temperature
All low-temperature surfaces are covered with 3/4 in.
• 75 percent relative humidity (19.05 mm) Armaflex® II or equal.
Operation outside of normal design conditions as The insulation is Armaflex® or equivalent closed cell
defined in this section may require additional
elastomeric insulation to prevent the formation of
insulation; contact Trane for further review.
condensation . Chillers in high humidity areas or ice
N o t e : If the unit is not factory-insulated, install storage, low leaving water temperature (less than 36°F
insulation around the evaporator bulbwells and [2.2°C] chilled water temperature/glycol) units, may
ensure that the bulbwells and connections for require double thickness to prevent formation of
the waterbox drains and vents are still accessible condensation.
after insulation is applied. The sensor modules
(Low Level Intelligent Devices [LLIDs]) and NOTICE
interconnecting four-wire cable inter-processor Insulation Damage!
communication (IPC) bus must be raised up Failure to follow these instructions could result in
above the field-installed insulation. Secure the insulation damage.
IPC bus to the insulation top/outer surface after To prevent damage to factory installed insulation:
insulation is completed.
• Do not allow the insulation to be exposed to
I m p o r t a n t : Do NOT insulate the compressor, motor excessive sunlight. Store indoors or cover with
housing, unit wiring, or sensor modules. canvas to prevent exposure.
• Do not use thinners and solvents or other types
of paint. Use only water base latex.

HDWA-SVX001D-EN 33
Insulation

Figure 22. Recommended area for unit insulation

Notes:
• Bulbwells, drain, and vent connections must be accessible after insulating.
• All units with evaporator marine waterboxes: wrap waterbox shell insulation with strapping and secure
strapping with seal.
• Evaporators with ASME nameplates must have insulation cut out around the nameplate. Do NOT glue
insulation to the nameplate.
• Apply 2-in. (50.8-mm) wide black tape on overlap joints. Where possible, apply 3-in. (76.2-mm) wide strip of
0.38-in. (9.652-mm) thick insulation over butt joint seams.

34 HDWA-SVX001D-EN
Electrical Requirements
Installation Requirements enclosure. If the AFD enclosure must be cut to provide
electrical access, exercise care to prevent debris from
WARNING falling inside the enclosure. Refer to submittal
drawings.
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or
Electrical Requirements
serious injury. Before wiring begins, observe the following electrical
All field wiring MUST be performed by qualified requirements:
personnel. Improperly installed and grounded • Follow all lockout/tagout procedures prior to
field wiring poses FIRE and ELECTROCUTION performing installation and/or service on the unit.
hazards. To avoid these hazards, you MUST follow
requirements for field wiring installation and • Always wear appropriate personal protective
grounding as described in NEC and your local/ equipment.
state/national electrical codes. • Wait the required time to allow the capacitor(s) to
discharge; this could be up to 30 minutes.
Unit-mounted Adaptive Frequency™ Drives (AFDs) are
• Verify that all capacitors are discharged prior to
standard on all units. While this option eliminates most
service using a properly rated volt meter.
field-installed wiring requirements, the electrical
contractor must still complete the electrical connection • Use appropriate capacitor discharge tool when
for the following: necessary.
• power supply wiring to the AFD • Comply with the safety practices recommended in
PROD-SVB06*-EN.
• other unit control options present
• any field-supplied control devices WARNING
As you review this manual along with the wiring Hazardous Voltage w/Capacitors!
instructions presented in this section, keep in mind Failure to disconnect power and discharge
that: capacitors before servicing could result in death or
• All field-installed wiring must conform to National serious injury.
Electric Code (NEC) guidelines, and any applicable Disconnect all electric power, including remote
local, state, and national codes. Be sure to satisfy disconnects and discharge all motor start/run
proper equipment grounding requirements per capacitors before servicing. Follow proper
NEC. lockout/tagout procedures to ensure the power
cannot be inadvertently energized. For variable
• Compressor motor and unit electrical data frequency drives or other energy storing
(including motor kW, voltage utilization range, components provided by Trane or others, refer to
rated load amps, and locked rotor amps) is listed on the appropriate manufacturer’s literature for
the chiller nameplate. allowable waiting periods for discharge of
• All field-installed wiring must be checked for proper capacitors. Verify with a CAT III or IV voltmeter
terminations, and for possible shorts or grounds. rated per NFPA 70E that all capacitors have
N o t e : Always refer to the actual wiring diagrams discharged.
that shipped with the chiller or the unit For additional information regarding the safe
submittal for specific as-built electrical discharge of capacitors, see PROD-SVB06*-EN.
schematic and connection information.
NOTICE WARNING
Adaptive Frequency Drive (AFD)/ Personal Protective Equipment (PPE)
Starter Component Damage! Required!
Failure to wear PPE and follow proper handling
Failure to remove debris from inside the AFD/
guidelines could result in death or serious injury.
starter panel could result in an electrical short and
could cause serious AFD/starter component Always wear appropriate personal protective
damage. equipment in accordance with applicable
regulations and/or standards to guard against
Do NOT modify or cut enclosure to provide electrical potential electrical shock and flash hazards.
access. Removable panels have been provided, and
any modification should be done away from the

HDWA-SVX001D-EN 35
Electrical Requirements

WARNING Adaptive Frequency Drive


Live Electrical Components! Table 12. Adaptive Frequency Drive (AFD) electrical
Failure to follow all electrical safety precautions data
when exposed to live electrical components could Short Circuit Line
Maximum Breaker AIC
result in death or serious injury. Withstand Connection
RLA Amps
Rating Lugs
When it is necessary to work with live electrical
(2) 3/0 - 250
components, have a qualified licensed electrician 240 65,000 65,500
MCM
or other individual who has been properly trained (2) 3/0 - 250
in handling live electrical components perform 361 65000 65000
MCM
these tasks. 443 65000 65000
(2) 3/0 - 250
MCM
(3) 2/0 - 400
535 65000 65000
MCM
(4) 4/0 - 500
678 65000 65000
MCM

36 HDWA-SVX001D-EN
Electrical Requirements

System Control Circuit Wiring


(Field Wiring)
Figure 23. HDWA Agility chiller field wiring
H N G ND
EXTERNAL J1 120VAC 60HZ
BASE LOADING 1K15
ENABLED/DISABLED DUAL RELAY OUTPUT CUSTOMER PROVIDED
11 J11 MAX OVERCURRENT PROTECTION 15A CUSTOMER GROUND
5S5 -OPTIONAL-
1
2 1 6 1X1-G
-OPTIONAL-
2
5
5S6 J2
3
2 1 4
-OPTIONAL- J2
4
3
EXTERNAL CUSTOMER PROVIDED
HOT WATER 1K9 LINE VOLTAGE
CONTROL -OPTIONAL- 2
5H8 (SEE UNIT NAMEPLATE)
ENABLED/DISABLED DUAL LOW VOLTAGE BINARY INPUT ICE BUILDING
1 INDICATOR

J1
1 2 GND L1 L2 L3 8
J11 -OPTIONAL-

J11 J1

1 OUTPUT 1 1K14
-OPTIONAL-
QUAD RELAY OUTPUT
2-10VDC or 4-20mA 2 INPUT 1 OPERATING STATUS PROGRAMMABLE
EXTERNAL BASE COM 12
LOADING SETPOINT 3 GND
J2 NC 11
4 OUTPUT 2
NO 10
2-10VDC or 4-20mA 5 INPUT 2
GENERIC REFRIGERANT COM 9
MONITOR INPUT L1 L2 L3
6 GND
NC 8
1K8 5H7
-OPTIONAL-
NO 7 CHILLER LIMIT
DUAL ANALOG I/O
J2 1 2 MODE INDICATOR
COM 6 -OPTIONAL- (DEFAULT)
J1

NC 5 2Q1
J11 5H10
NO 4 CHILLER HEAD RELIEF
1 2 REQUEST INDICATOR
COM 3 -OPTIONAL- (DEFAULT)
1 OUTPUT 1
2-10VDC
% RLA COMPRESSOR 2 INPUT 1 NC 2
OUTPUT 5H11
3 GND NO 1 CHILLER MAXIMUM
J2 1 2 CAPACITY INDICATOR
2-10VDC J11 -OPTIONAL- (DEFAULT)
CONDENSER 4 OUTPUT 2
REFRIGERANT
PRESSURE J1
5 INPUT 2
or
EVAPORATOR/CONDENSER 1K13
DIFFERENTIAL PRESSURE 6 GND -OPTIONAL-
OUTPUT QUAD RELAY OUTPUT
OPERATING STATUS PROGRAMMABLE
1K7
-OPTIONAL- COM 12
DUAL ANALOG I/O
NC 11
J1 5H6
NO 10 CHILLER RUNNING
J11 1 2 INDICATOR
-OPTIONAL- (DEFAULT)
CLASS 2 WIRING COM 9 CLASS 1 WIRING

1 OUTPUT 1 NC 8
2-10VDC or 4-20mA 5H1
EXTERNAL CURRENT NOTE: ANY 1K13 OR 1K14 DEFAULT OUTPUT MY BE REPROGRAMED
LIMIT SETPOINT 2 INPUT 1 NO 7 CHILLER LATCHING TO ANY ALTERNATE ALRAM/STATUS OUTPUT SHOWN BELOW.
J2 1 2 ALARM INDICATOR
-OPTIONAL- (DEFAULT) 5H15
3 GND COM 6 CHILLER LIMIT
J2 MODE INDICATOR
NC 5 1 2 (ALTERNATE)
4 OUTPUT 2 -OPTIONAL-
2-10VDC or 4-20mA
EXTERNAL CHILLED
WATER SETPOINT 5 INPUT 2 NO 4

6 GND COM 3

1K6 NC 2
5H2
-OPTIONAL- CHILLER NON-LATCHING
DUAL ANALOG I/O NO 1 ALARM INDICATOR
1 2 (DEFAULT)
J11 -OPTIONAL-
J1
TRACER
J11 J1
COMMUNICATIONS
1

1K12
2
DUAL RELAY OUTPUT
J2
3
COM 6 INSET D
4
5 CUSTOMER SUPPLIED EVAPORATOR
1K5 NC PROOF OF FLOW DEVICES
5K1
-OPTIONAL- EVAPORATOR
NO 4 160A 1
LONTALK LCI-C MODULE 2 1 WATER PUMP
J2 CONTROL 5 5S11 5S17 6 OR J3
4 220V 160A 161A
COM 3 2
REMOVE JUMPERS 1W2 AND 1W3 J1 1 2 1 2 1K11
IF DEVICES ARE PRESENT TO 1X1-2
PRIMARY SECONDARY
NC 2 REQUIRED OPTIONAL
J11 5K2
11 CONDENSER
5S3
1 NO 1 WATER PUMP INSET D
2 1 CONTROL
EXTERNAL AUTO STOP 1W2
J11
2 4
J2 INSET E
5S4 J1
3 CUSTOMER SUPPLIED CONDENSER
EMERGENCY STOP 1W3 PROOF OF FLOW DEVICES
1K11
4
DUAL HIGH VOLTAGE BINARY INPUT 1
CONDENSER & EVAPORATOR 162A
5 5S12 5S18 6 OR J2
WATER FLOW DETECTION
1K4 220U 162A 163A
2 2
DUAL LOW VOLTAGE BINARY INPUT 1 2 1 2 1K11
SEE DETAILS D & E FOR J3 TO 1X1-3
PRIMARY SECONDARY
EVAPORATOR & CONDENSER 1 REQUIRED OPTIONAL
J1 WATER FLOW SWITCH & -SEE INSET D,E,F,G-
WATER PUMP INTERLOCK 5
2 INSET E
5S7 11 J11
J2
2

1 1 INSET F
2 1
21

GRY
-OPTIONAL- J11
1

2 SECONDARY EVAPORATOR WATER


WB12

7 6
20

EXTERNAL ICE BLK PROOF OF FLOW DEVICES


BUILDING J2 Pd
J1
4

3
1K23

COMMAND
19

BRN 5S17
4R18 220G 158A
8

4 J1 1 2
18

BLU TO 1X1-3 TO 1K22-4


CONDENSER
7

1K3 J11 WATER FLOW


17

WHT DETECTOR
DUAL LOW VOLTAGE BINARY INPUT
5

(FIELD INSTALLED)
INSET F
J1 OUTPUT 1 1
2

21

GRY INSET G
J11 INPUT 1 2
1

WB11

SECONDARY CONDENSER WATER


20

J2 BLK Pd 6 7
1 PROOF OF FLOW DEVICES
GND
3
4
1K22
19

J2 BRN
2 5S18
OUTPUT 2 4 4R17 220E 159A
8

1 2
18

3 BLU EVAPORATOR TO 1X1-2 TO 1K23-4


INPUT 2 5
7

WATER FLOW
17

4 WHT DETECTOR
GND 6 (FIELD INSTALLED)
5

1K2 INSET G
HI-TEMP SENSOR 1K10
TRIPLE WINDING INPUT -OPTIONAL-
DUAL ANALOG I/O

J1-2(0V)
FLAG NOTES
J1-1(24VDC) J2-1

1. CAUTION-DO NOT ENERGIZE THE UNIT UNTIL CHECK OUT AND STARTUP PROCEDURES HAVE BEEN COMPLETED.
J3-1(TTL+) J2-2
2. CAUTION-TRANE PUMP CONTROL MUST BE USED TO PROVIDE PUMP CONTROL. EVAPORATOR CHILLED WATER PUMP MUST
1K1 BE CONTROLLED BY THE CHILLER OUTPUT. FAILURE TO COMPLY WITH THIS REQUIREMENT MAY RESULT IN DAMAGE OT THE UNIT.
J3-2(TTL-) TACH BOARD
3. RECOMMENDED FIELD WIRING CONNECTIONS ARE SHOWN BY DASHED LINES

4. UNIT PROVIDED DRY CONTACTS FOR WATER PUMP CONTROL.RELAY RATING AT 120VAC: 7.2 AMPS RESISTIVE, 2.88 AMPS PILOT DUTY,
1/3 HP, 7.2 FLA RELAY RATING AT 240VAC: 5 AMPS GENERAL PURPOSE.

OUTDOOR AIR 5. INSTALLATION OF PRIMARY EVAPORATOR AND CONDENSER WATER PROOF OF FLOW DEVICES ARE REQUIRED. THESE ARE INDICATE
4 TEMPERATURE SENSOR 4 AS 5S11 AND 5S12 CUSTOMER SUPPLIED DEVICES AND MUST BE A FLOW SENSING DEVICE SUCH AS A FLOW SWITCH, WATER FLOW DETECTION
CONTROLLER OR A DIFFERENTIAL PRESSURE SWITCH. SEE INSET D AND E FOR INSTALLATION.
-OPTIONAL-
3 3 6. PRIMARY EVAPORATOR AND CONDENSER WATER PROOF OF FLOW IS ALSO SHOWN USING OPTIONAL TRANE INSTALLED 1K22 AND 1K23 WATER FLOW
DETECTION CONTROLLERS. 4R17 AND 4R18 WATER FLOW DETECTION SENSORS AND WB11 AND WB12 CABLES ARE SUPPLIED BY TRANE FOR FIELD
J1

J11

J1

J11

J3 J3
2 4BT9 2 INSTALLATION BY THE CUSTOMER.
INSTALLATION OF CUSTOMER SUPPLIED SECONDARY EVAPORATOR AND CONDENSER WATER PROOF OF FLOW DEVICES ARE AT THE DISCRETION OF
THE CUSTOMER. THESE ARE INDICATED AS 5S17 AND 5S18 AND MAY BE A WATER PUMP INTERLOCK, VALVE END SWITCH OR ANY OTHER PROOF OF FLOW DEVICE.
1 1 TRANE RECOMMENDS INSTALLATION OF THE 5S17 SECONDARY EVAPORATOR WATER PROOF OF FLOW DEVICE WHEN THE LEAVING WATER TEMPERATURE IS
EXPECTED TO BE 38°F OR LESS AND THAT THE METHOD USED IS INDEPENDENT OF THE PRIMARY WATER PROOF OF FLOW DEVICE TO PROVIDE REDUNDANCY.
GRY
4 4
POWER SUPPLY 1

POWER SUPPLY 1

7. IF OPTIONAL TRANE INSTALLED 1K22 AND/OR 1K23 WATER FLOW DETECTION CONTROLLERS ARE USED AND THE CUSTOMER CHOOSES TO INSTALL 5S17 AND/OR
BLU 5S18 SECONDARY PROOF OF FLOW DEVICES THEN THE CUSTOMER MUST REMOVE TRANE FACTORY WIRE BETWEEN 1X1-2 AND 1K23-4 AND/OR WIRE BETWEEN 1X1-3
3 3 AND 1K22-4. SECONDARY DEVICES WOULD THEN BE INSTALLED AS SHOWN IN INSET G AND/OR F.
1T1

1T2

J4 J4 TRANE RECOMMENDS WIRING THE 5K1 EVAPORATOR AND 5K2 CONDENSER WATER PUMP CONTROL RELAYS AS SHOWN TO ALLOW THE 1K15 MODULE TO CONTROL
BLK PROPER SEQUENCING.
2 2
8. ALL UNIT POWER WIRING MUST BE 600 VOLT COPPER CONDUCTORS ONLY. REFER TO UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM
1 RED 1 OVERCURRENT PROTECTION DEVICE. PROVIDE AN EQUIPMENT GROUND IN ACCORDANCE WITH APPLICABLE ELECTRIC CODES. REFER TO WIRERANGE TABLE FOR LUG SIZES.

9. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND LOCAL REQUIREMENTS.
4 4
CLASS 2 WIRING 10. ALL CUSTOMER CONTROL CIRCUIT WIRING MUST BE COPPER CONDUCTORS ONLY AND HAVE A MINIMUM INSULATION RATING OF 300 VOLTS. EXCEPT AS NOTED, ALL CUSTOMER
3 3 WIRING CONNECTIONS ARE MADE TO CIRCUIT BOARD MOUNTED BOX LUGS WITH A WIRE RANGE OF 14 TO 18 AWG OR DIN RAIL MOUNTED SPRING FORCE TERMINALS.
J5 J5 11. CUSTOMER SUPPLIED CONTACTS FOR ALL LOW VOLTAGE CONNECTIONS MUST BE COMPATABLE WITH DRY CIRCUIT 24 VOLTS DC FOR A 12 mA RESISTIVE
J2 2 J2 2 LOAD. SILVER OR GOLD PLATED CONTACTS RECOMMENDED.
1 2 3 1 2 3
1 1

FUSE REPLACEMENT TABLE


OPTIONAL BACNET DEVICE ID FUSE TYPE FUSE SIZE
OR MODBUS 2F1 CLASS CC 15A
DEVICE PREFIX LOCATION CODES
2F2 CLASS CC 15A
1 CONTROL PANEL 2F3 CLASS CC 10A
2 DRIVE PANEL 2F4 CLASS CC 10A
2F5 CLASS CC 5A
3 NOT USED 2F6 CLASS CC 15A
8

GND A B GND - + GND - +


4 UNIT MOUNTED DEVICE 2F7 CLASS CC 5A
LON LINK 1 LINK 2
+

+
-

+24 VDC
GND

2F8 CLASS CC 20A


MBUS
LINK

5 CUSTOMER PROVIDED DEVICE 2F11 BUSSMANN - 170M3467 315A


1

1 1
IMC-A

IMC-B

IMC-A GND A B GND - + GND - + IMC-B 2F12 BUSSMANN - 170M3467 315A


LON LINK 1 LINK 2
SERVICE TOOL
ETHERNET

1K20 1K21
UC800 UNIT TOOL
CONTROLLER SERVICE

ETHERNET
1 2

HDWA-SVX001D-EN 37
Electrical Requirements

Table 13. Unit control panel wiring 120 Vac


Standard Control Circuits: Unit
Control Panel Control Wiring Unit Control Terminations Input or Output Type Contacts
(120 Vac)
Evaporator Water Flow Switch 1K11-J3-1 to 2 Binary Input Normally Open, Closure with Flow

Condenser Water Flow Switch 1K11-J2-1 to 2 Binary Input Normally Open, Closure with Flow

Evaporator Water Pump Control 1K12-J2-4 to 6 Binary Output Normally Open

Condenser Water Pump Control 1K12-J2-1 to 3 Binary Output Normally Open


Optional Control Circuits (120
Note: Defaults are factory programmed; alternates can be selected at start-up using the service tool.
Vac)
Maximum Capacity Relay Output 1K14-J2-4 Binary Output Normally Open

Head Relief Request Relay Output J11-J2-4 to 6 Binary Output Normally Open

Ice Building Indicator 1K15-J2-1 to 3 Binary Output Normally Open


Standard Low Voltage Circuits
Unit Control Panel Terminations Input or Output Type Contacts
(Less than 30 Vac)(a)
Closure Required for Normal
External Auto Stop Input 1K4-J2-1 to 2 Binary Input
Operation
Closure Required for Normal
Emergency Stop Input 1K4-J2-3 to 4 Binary Input
Operation
Optional Low Voltage Circuits

External Base Loading Enable Input 1k8-J2-2 to 3 Binary Input Normally Open
External Hot Water Control Enable
1k9-J2-3 to 4 Binary Input Normally Open
Input
External Ice Machine Control
1K3-J2-1 to 2 Binary Input Normally Open
Enable Input
Condenser Refrigerant Pressure 1K7-J2-4 to 6 Analog Output 2–10 Vdc
Chiller % Capacity Output 1K7-J2-1 to 3 Analog Output 2–10 Vdc
Evaporator/Condenser Differential
1K7-J2-4 to 6 Analog Output 2–10 Vdc
Pressure Output
External Current Limit Setpoint
1K6-J2-2 to 3 Analog Input 2–10 Vdc, or 4–20 mA
Input
External Chilled Water Setpoint
1K6-J2-5 to 6 Analog Input 2–10 Vdc, or 4–20 mA
Input
External Base Loading Setpoint
1K8-J2-2 to 3 Analog Input 2–10 Vdc, or 4–20 mA
Input
Generic Refrigerant Monitor Input 1K8-J2-5 to 6 Analog Input 2–10 Vdc, or 4–20 mA
Inter-processor Communication
Outdoor Air Temperature Sensor (IPC) Bus Connection and Sensor— Communication and Sensor
4BT9
1K5-J2-1(+) to 2(-) Communication to Tracer
Trace Comm Interface or LonTalk (As Ordered; See Sales Order)
1K5-J2-3(+) to 4(-) or LonTalk
Communication to BACnet or
BACnet or MODBUS 1K20 5(+) to 6(-) (As Ordered; See Sales Order)
MODBUS
Communication to Tracer SC
Tracer SC Module 1K21
Module
Note: All wiring to be in accordance with National Electrical Code (NEC) and any local codes.

(a) Standard low-voltage circuits (less than 30 Vac) must be separated from 120 Vac or higher wiring.

Sensor Circuits Use the following guidelines to locate and mount the
outdoor air temperature sensor. Mount the sensor
All sensors are factory-installed except the optional
probe where needed; however, mount the sensor
outdoor air temperature sensor (refer to the following
module in the control panel.
figure for sensor locations). This sensor is required for
the outdoor air temperature type of chilled water reset.

38 HDWA-SVX001D-EN
Electrical Requirements

Figure 24. Agility chiller sensor locations

1. 4 P 1 , Tracer® AdaptiView™ display


2. 4 B T 3 , Condenser entering water temperature
3. 4 B T 6 , Condenser leaving water temperature
4. 4 B T 2 , Evaporator entering water temperature
5. 4 B T 5 , Evaporator leaving water temperature
6. 4 B P 4 , Condenser leaving water differential pressure (LO)
7. 4 B P 4 , Condenser entering water differential pressure (HI)
8. 4 B P 5 , Evaporator leaving water differential pressure (LO)
9. 4 B P 5 , Evaporator entering water differential pressure (HI)
10. 4 R 1 8 , Condenser water flow detector
11. 4 R 1 7 , Evaporator water flow detector
12. 4 B P 3 , Economizer leaving pressure

HDWA-SVX001D-EN 39
Electrical Requirements

13. 4 B P 2 , Condenser pressure


14. 4 B T 7 , Compressor discharge temperature
15. 4 B T 8 , Economizer leaving refrigerant temperature
16. 4 M 2 , Evaporator EXV
17. 4 M 4 , Economizer EXV
18. 4 M 6 , Drive cooling EXV
19. 4 B T 4 , Drive cooling supply temperature
20. 4 M 5 , Inlet guide vane second stage actuator
21. 4 B 1 , Condenser liquid level
22. 4 M 3 , Motor bearing control cooling EXV
23. 4 M 8 , Motor cooling EXV

Optional Control and Output Circuits Field replacement drives must be programmed via the
Install various optional wiring as required by the keypad interface. Contact your local Trane Service
owner’s specifications (refer to “System Control Circuit Agency for assistance.
Wiring (Field Wiring),” p. 37).
Communications Interface
Schematic Wiring Drawings
Please refer to the submittals and drawings that
LonTalk Interface (LCI-C)
shipped with the unit. Additional wiring drawings for UC800 provides an optional LonTalk® Communication
Agility™ chillers are available from your local Trane Interface (LCI-C) between the chiller and a Building
office. Automation System (BAS). An LCI-C LLID shall be used
to provide “gateway” functionality between a
Adaptive Frequency Drive LonTalk® compatible device and the Chiller. The
inputs/outputs include both mandatory and optional
The Trane TR200 Adaptive Frequency™ Drive (AFD) is network variables as established by the LONMARK®
an electronic motor controller that converts alternating Functional Chiller Profile 8040.
current (AC) mains input into a variable AC waveform
N o t e : For more information, refer to Hardware and
output. The frequency and voltage of the output are
Software Installation Guide: LonTalk
regulated to control the motor speed or torque. The
Communication Interface for Trane Chillers with
TR200 drive includes the following features:
Tracer AdaptiView Control (ACC-SVN100*-EN).
• Soft start to minimize inrush current
• Improved harmonic mitigation with direct current BACnet Interface (BCI-C)
(DC) link reactor Optional BACnet® Communication Interface for
• Integrated power fuse Chillers (BCI-C) is comprised of a Tracer® UC800
controller with interface software. It is a non-
• Graphical liquid-crystal display (LCD) keypad
programmable communications module that allows
• Unit-mounted with factory pre-wiring units to communicate on a BACnet® communications
• “Trane Drive Utility” for configuration and tracking network.

Programming MODBUS Remote Terminal Unit


Interface
NOTICE Modicon Communication Bus (MODBUS®) enables the
Equipment Damage! chiller controller to communicate as a slave device on a
Changing default clockwise phase rotation or MODBUS® network. Chiller setpoints, operating
enabling phase reversal protection could prevent modes, alarms and status can be monitored and
proper chiller operation or cause equipment controlled by a MODBUS® master device.
damage.

• Do NOT change Adaptive Frequency™ drive


(AFD) phase rotation to counterclockwise.
• Do NOT enable phase reversal protection.

40 HDWA-SVX001D-EN
Installation: Controls
This section covers information pertaining to the
UC800 controller hardware. For information about the
Tracer® AdaptiView™ display, which is used to
interface with the internal chiller data and functions
provided by the UC800, refer to Tracer AdaptiView
Display for Water-cooled Agility Chillers Operations
Guide (HDWA-SVU001*-EN).

UC800 Specifications
Power Supply
The UC800 (1K20) receives 24 Vac (210 mA) power
from the 1T2 power supply located in the chiller control
panel.

Wiring and Port Descriptions


The following figure illustrates the UC800 controller
ports, LEDs, rotary switches, and wiring terminals. The
numbered list following the figure corresponds to the
numbered callouts in the illustration.

HDWA-SVX001D-EN 41
Installation: Controls

Figure 25. UC800 wiring locations and connection 5. Power (210 mA at 24 Vdc) and ground terminations
ports (same bus as Item 4). Factory wired.
6. MODBUS® Master.
7. Marquee LED power and UC800 Status indicator
(refer to the table in “LED Description and
+ + + +24
VDC Operation,” p. 42).
LINK MBUS
8. Status LEDs for the BAS link, MBus link, and IMC
Front View link.
2345 9. USB device Type B connection for the service tool
(Tracer® TU).
10. The Ethernet connection can only be used with the
Tracer® AdaptiView™ display.

6 6 11. USB Host (not used).

Communication Interfaces
7 There are four connections on the UC800 that support
the communication interfaces listed. Refer to the figure
8 in “Wiring and Port Descriptions,” p. 41 for the
locations of each of these ports.
• BACnet® MS/TP
1 9
• MODBUS® Slave
• LonTalk® using LCI-C (from the IPC3 bus)

0 Rotary Switches
- There are three rotary switches on the front of the
UC800 controller. Use these switches to define a three-
Bottom View digit address when the UC800 is installed in a BACnet®
or MODBUS® system (e.g., 107, 127, etc.).
N o t e : Valid addresses are 001 to 127 for BACnet® and
001 to 247 for MODBUS®.

LED Description and Operation


There are ten LEDs on the front of the UC800. The
following figure shows the locations of each LED and
the following table describes their behavior in specific
instances.

1. Rotary Switches for setting BACnet® MAC address


or MODBUS® ID.
2. LINK for BACnet® MS/TP, or MODBUS® Slave (two
terminals, ±). Field wired if used.
3. LINK for BACnet® MS/TP, or MODBUS® Slave (two
terminals, ±). Field wired if used.
4. Machine bus for existing machine LLIDs (IPC3
Tracer bus). IPC3 Bus: used for LonTalk® using LCI-
C.

42 HDWA-SVX001D-EN
Installation: Controls

Figure 26. LED locations Table 14. LED behavior


LED UC800 Status
Marquee LED Powered. If the Marquee LED is green solid, the
UC800 is powered and no problems exist.
Low power or malfunction. If the Marquee LED
LINK MBUS IMC Marquee LED is red solid, the UC800 is powered but there are
TX problems present.
Alarm. The Marquee LED blinks red when an alarm
exists.
The TX LED blinks green at the data transfer rate
RX when the UC800 transfers data to other devices on
LINK, MBUS, the link.
IMC The RX LED blinks yellow at the data transfer rate
LINK when the UC800 receives data from other devices
on the link.
SERVICE The LINK LED is solid green if the Ethernet link is
connected and communicating.
ACT Ethernet Link
The ACT LED blinks yellow at the data transfer rate
when data flow is active on the link.
The Service LED is solid green when pressed. For
Service
qualified service technicians only. Do NOT use.

I m p o r t a n t : Maintain at least 6 in. (16 cm) between low-


voltage (less than 30V) and high voltage
circuits. Failure to do so could result in
electrical noise that could distort the
signals carried by the low-voltage wiring,
including inter-processor communication
(IPC).

HDWA-SVX001D-EN 43
Installation: Controls

Figure 27. Control panel: Tracer AdaptiView main unit assembly (showing low voltage and higher voltage areas for
proper routing of field wiring)

1K9

1K15

1K8

1K14

1K7

1K13 1XP5/1XJ5
1K6 Service Power

1K5

1XJ1/1XP1
1K12

1K4

1K11
1K3

1K10 1K22
1K2
1K23
1XJ3/1XP3

1K1 1XJ4
XP4

1XJ2 XP 1P1
A

1K21

1K20

B
C
1P1

30-115 Volt Maximum 30 Volt Maximum

44 HDWA-SVX001D-EN
Installation: Controls

Installing the Tracer AdaptiView I m p o r t a n t : Use care when positioning the Tracer®
AdaptiView™ display on top of the
Display support arm base plate and do NOT
During shipment, the Tracer® AdaptiView™ and drop the display.
support arm are boxed, shrink-wrapped, and shipped 7. Align the four holes in the display with the screw
with unit. The display and support arm must be holes in the display support arm base plate.
installed at the site.
8. Attach the Tracer® AdaptiView™ display to the
I m p o r t a n t : For best results, Trane, or an agent of display support arm base plate (labeled E in the
Trane, must install the Tracer® following figure) using the M4 (metric size 4)
AdaptiView™ display and support arm. screws referenced in step 3.
1. Unwrap the chiller. Locate the box containing the Figure 28. Display arm installation
Tracer® AdaptiView™ display and support arm
strapped to the shear plate between the condenser
and the evaporator (see the following figure).
2. Remove the display and support arm from the box.
N o t e : Display to support arm screws are M4 (metric
size 4), 6 to 8 mm long, and are shipped with
the display. Display arm screws are M6
(metric size 6), 16 mm long, washers, and
nuts used to secure arm to unit bracket are
shipped in the parts box.
3. Using the M6 hardware shipped in the parts box,
attach the display support arm to the mounting
bracket on the side of the control panel (labeled A A
and B in the following figure). B
4. Plug the power cable (labeled C in the following
figure) and the Ethernet cable (labeled D in the
following figure) into the bottom of the display.
Plug other ends of the cables into the ports on the
Figure 29. Power cable and Ethernet cable
side of the control panel. connections
5. Adjust the Tracer® AdaptiView™ display support
arm so the base plate that attaches to the display is
horizontal.

CAUTION
Tension in Display Support Arm! C
Failure to follow instructions below could
result in unexpected movement of the spring-
loaded support arm which could result in minor
to moderate injury.
D
Ensure that the support arm is in the full
upright position when removing the Tracer
AdaptiView display from the support arm.

N o t e : Review “Adjusting the Tracer AdaptiView


Display Arm,” p. 46 before attaching the
display as some adjustments may be
required prior to attaching the display to the
support arm base.
6. Position the Tracer® AdaptiView™ display—with
the LCD screen facing up—on top of the display
support arm base plate.
N o t e : Ensure the Trane logo is positioned so that it
will be at the top when the display is attached
to the display support arm.

HDWA-SVX001D-EN 45
Installation: Controls

Figure 30. Display attachments to the support arm To adjust the tension on the display arm:
base plate
• At each joint in the display arm, there is either a hex
bolt (1
1 and 2 ) or hex screw (3
3). Turn the hex bolt or
screw in the proper direction to increase or
E decrease tension.
N o t e : Each hex bolt or screw is labeled with
l o o s e n /tti g h t e n or + /-- indicators.
• Joint 3 has a 6 mm hex screw controlling the
tension on a gas spring, which allows the Tracer®
AdaptiView™ display to tilt up and down.
• Joints 1 and 2 are covered by a plastic cap. Remove
the plastic cap to access the screw. Adjust using a
13 mm wrench as necessary.
• To adjust the swivel rotation tension of the Tracer®
AdaptiView™ display, adjust the screw located in
the support arm base plate, as described in the final
step in “Installing the Tracer AdaptiView
Display,” p. 45. This adjustment must be done prior
to attaching the display to the support arm base.
Use a 14 mm wrench to adjust the tension.
Adjusting the Tracer AdaptiView • To adjust the left/right swivel of the entire display
arm, use a 13 mm wrench to adjust the screw
Display Arm labeled 4 in the preceding figure.
The Tracer® AdaptiView™ display arm may become
too loose or too tight and may need adjustment. There
are three joints on the display arm that allow the
display to be positioned at a variety of heights and
angles (refer to items labeled 1 , 2 , and 3 in the
following figure).
Figure 31. Joint locations on the display arm

2 3

46 HDWA-SVX001D-EN
Operating Principles
General Requirements heat exchanger economizer, while a significantly
smaller portion of the flow passes through an
Operation and maintenance information for HDWA expansion valve, lowering refrigerant pressure and
Agility™ chillers are covered in this section. By temperature before entering the secondary side of the
carefully reviewing this information and following the BPHE as two-phase refrigerant. The heat transfer
instructions given, the owner or operator can between the primary and secondary channels in the
successfully operate and maintain a Agility™ chiller. If BPHE results in further subcooling of the primary liquid
mechanical problems do occur, however, contact a as it rejects heat to, and consequently superheats, the
Trane service technician to ensure proper diagnosis secondary flow. The additional subcooling of the liquid
and repair of the unit. prior to expansion through the main electronically-
Important: controlled valve effectively increases the overall
• Although Agility™ chillers can operate capacity of the evaporator. In addition, the superheated
through surge, it is NOT recommended vapor bypasses the evaporator and first stage of
to operate them through repeated compression (the secondary BPHE flow is added prior
surges over long durations. If repeated to the second stage of compression).
surges of long durations occur, contact Figure 32. Refrigerant flow
your Trane Service Agency to resolve
the issue.
• Agility™ are selected, designed, and
Primary
built for a particular set of design
conditions. Operation outside of design 4 Condenser 3
conditions may result in improper 5
8
Pressure

operation. Refer to chiller selection for Compressor


Second Stage
minimum unloading.
Secondary
6 7 2
Cooling Cycle
When in the cooling mode, liquid refrigerant is Compressor
First Stage
distributed along the length of the evaporator and Evaporator
sprayed through small holes in a distributor (i.e., 9 1
running the entire length of the shell) to uniformly coat
each evaporator tube. Here, the liquid refrigerant
absorbs enough heat from the system water circulating Enthalpy
through the evaporator tubes to vaporize. The gaseous
refrigerant is then drawn through the suction
connection and the first-stage variable inlet guide Compressor Motor
vanes, and into the first-stage impeller. Two magnetic bearing modules levitate and align the
rotating assembly. The motor is permanent magnet
HDWA Compressor type and is cooled by refrigerant gas sourced from the
The unit is equipped with a semi-hermetic, direct-drive, interstage pipe, metered through an orifice or
two-stage, centrifugal compressor that includes inlet electronic expansion valve, and routed through the
guide vanes for capacity control. The Adaptive bearing modules and motor windings.
Frequency™ Drive (AFD) provides capacity control with
lower speeds. Compressed gas from the first-stage
impeller is discharged through the interstage pipe to
Adaptive Frequency Drive
the second-stage impeller. Here, the refrigerant gas is An Adaptive Frequency™ Drive (AFD) and control
again compressed, and then discharged into the panel is provided on every chiller. Microprocessor-
condenser. Baffles within the condenser shell distribute based unit control modules (Tracer® UC800) provide
the compressed refrigerant gas evenly across the for accurate chilled water control as well as monitoring,
condenser tube bundle. Cooling tower water circulated protection, and adaptive limit functions. The "adaptive"
through the condenser tubes absorbs heat from the nature of the controls intelligently prevents the chiller
refrigerant, causing it to condense. The subcooled from operating outside of its limits, or compensates for
liquid refrigerant then flows out of the bottom of the unusual operating conditions, while keeping the chiller
condenser. running rather than simply tripping due to a safety
concern. When problems do occur, diagnostic
The liquid refrigerant is then split such that the primary
messages assist the operator in troubleshooting.
flow is directed through one side of the brazed plate

HDWA-SVX001D-EN 47
Operating Principles

Uninterruptible Power Supply ASME Code for refrigerant-side/working-side pressure


of 200 psig (1379.0 kPaG). The condenser is designed,
Agility™ chillers contain an on-line double-conversion tested, and stamped in accordance with ASME Code
Uninterruptible Power Supply (UPS) to ensure that the for refrigerant-side/ working-side pressure of 300 psig
compressor’s magnetic bearing system continues to (2068.4 kPaG).
function in the event of an power failure. The UPS (2T5)
provides power to the UC800 controls for 90 seconds All water pass arrangements are available with
while the compressor coasts to a stop. When line grooved connections (150 psig [1034.2 kPaG] waterside
power fails, power is supplied to the UPS with an working pressure). All connections may be either right-
internal battery. or left-handed. Waterside shall be hydrostatically
tested at 1.5X design working pressure.
When power is removed, or if the chiller’s disconnect
switch is turned off, the UPS will supply power to the
UC800 controls for 90 seconds and then the UPS will Drive Cooling System
de-activate. The UPS’s internal battery is not The drive cooling system rejects heat through a hybrid
completely discharged so that when power is restored, air and fluid heat sink. The Adaptive Frequency™ Drive
the battery can provide enough power for additional (AFD) controls the fan speed to reject some of the heat
shutdowns. while the refrigerant expansion valve modulates to
The UPS has a fault indicator that is wired to a UC800 maintain a fluid supply temperature to reject the
controls Low Level Intelligent Device (LLID; 1K3). If the remaining heat.
UPS indicates a fault, an immediate shutdown Drive cooling circuit includes a wet rotor circulation
diagnostic will be announced on the UC800 controls. pump that circulates a secondary heat transfer fluid in a
The following UPS issues could cause this diagnostic: closed system through the AFD heat sinks, output load
• EPO Protection inductor and a brazed plate heat exchanger. The pump
is fed from a thermal expansion tank with a vented-
• Busbar Voltage Fault pressure cap which is also used as the circuit pressure
• IGBT Over-Temperature relief. The circuit also includes a particulate strainer
and a drain valve for servicing.
• Fan Fault
• Battery Fault
• Output Fault
Tracer AdaptiView Display
Information is tailored to operators, service
• Multiple Inverting Fault
technicians, and owners.
When operating a chiller, there is specific information
Evaporator and Condenser you need on a day-to-day basis—setpoints, limits,
Heat exchangers are shell and tube design. Standard diagnostic information, and reports.
tubes are externally finned, internally enhanced Day-to-day operational information is presented at the
seamless copper with lands at all tube sheets. All tube display. Logically organized groups of information—
sheets are made of carbon steel. Tubes are chiller modes of operation, active diagnostics, settings,
mechanically expanded into tube sheets and graphs, and reports put information conveniently at
mechanically fastened to tube supports. Evaporator your fingertips. For more information, refer to Tracer
and condenser tubes are 0.75-in. (19.05-mm) diameter. AdaptiView Display for Water-cooled Agility Chillers
All tubes can be individually replaced. Operations Guide (HDWA-SVU001*-EN).
Shells are carbon steel plate. The evaporator is
designed, tested, and stamped in accordance with

48 HDWA-SVX001D-EN
Start-up and Shut-down
I m p o r t a n t : Initial unit commissioning start-up must be state chart, with the arrows and arrow text, depicting
performed by Trane or an agent of Trane the transitions between states:
specifically authorized to perform start-up • The text in the circles is the internal software
and warranty of Trane products. Contractor designations for each state.
shall provide Trane (or an agent of Trane
specifically authorized to perform start-up) • The first line of text in the circles is the visible top
with notice of the scheduled start-up at level operating modes that can be displayed in
least two weeks prior to the scheduled Tracer® AdaptiView™.
start-up. • The shading of each software state circle
corresponds to the shading on the time lines that
Sequence of Operation show the chiller’s state.
There are five generic states that the software can be
Adaptive control algorithms are used on Agility™
in:
chillers. This section illustrates common control
sequences. • Power Up
• Stopped
Software Operation Overview Diagram
• Starting
The following figure is a diagram of the five possible • Running
software states. This diagram can be thought of as a
• Stopping

Figure 33. Software operation overview

Power
Stopped Up
Stopped
Run Inhibit

Co Star
d mm t
me
n fir an
d
Co Di
ag
wn no
t do Re st
Shu se ic
t
Starting
Stopping Fast Restart or Satisfied Setpoint Auto
Preparing to Shut Down Waiting to Start
Shutting Down Starting Compressor
Stop Command or Diagnostic

St d
op
me
Co
mm nfir
C o
Di an
d t
ag ar
no
sti St
c Running
Running
Running—Limit

HDWA-SVX001D-EN 49
Start-up and Shut-down

Figure 34. Sequence of operation: Tracer AdaptiView power up


Loading UI
Black Screen Grey Screen (User Interface from UC800)

First Trane Logo Second Trane Logo Display Ready

12 seconds 18 seconds 30 seconds 15 seconds 15 seconds


Last Mode
Apply
(i.e., Auto
Control
or Stopped
Power
as Shown)
90 seconds total

Note: The variation in power up time is dependent on the number of installed options.

In the following diagrams: • Smaller cylinders under the main cylinder indicate
• The time line indicates the upper level operating diagnostic checks.
mode, as it would be viewed in the Tracer® • Text outside a box or cylinder indicates time-based
AdaptiView™. functions.
• The shading color of the cylinder indicates the • Solid double arrows indicate fixed timers.
software state. • Dashed double arrows indicate variable timers.
• Text in parentheses indicates sub-mode text as
viewed in the Tracer® AdaptiView™. Power Up
• Text above the time line cylinder is used to illustrate “Software Operation Overview Diagram,” p. 49
inputs to the UC800. This may include user input to includes an illustration of Tracer® AdaptiView™ during
the Tracer® AdaptiView™ touch screen, control a power up of the UC800. This process takes from 30 to
inputs from sensors, or control inputs from a 50 seconds depending on the number of installed
generic BAS. options.
• Boxes indicate control actions such as turning on
relays, or moving the inlet guide vanes.

50 HDWA-SVX001D-EN
Start-up and Shut-down

Power Up to Starting • Evaporator and condenser water flowing


The following figure shows the timing from a power up • Power up start delay setpoint set to 0 minutes
event to energizing the compressor. The shortest • Need to cool
allowable time would be under the following The above conditions would allow for a minimum
conditions: power up to starting compressor time of 45 seconds.
• All temperatures below their starting limits

Figure 35. Sequence of events: power up to starting

Last Chiller Mode


Was Auto Call for Cooling

Power
Applied Starting
Auto Waiting to Start Waiting to Start
to Compresor
Controls
Wait for Evaporator Wait for Condenser Water Flow
Water Flow (6 Second Filter)

UC800 Enforce Power-up Temperature Checks: Send Run


Boot Time Start Delay Timer • Motor Winding Temp <90% Command to
(30 to 50 (0 to 30 Minutes) of the Motor Winding Temp AFD
Seconds) Cutout
• AFD Heatsink Temp <90%
Check MBC of the AFD Heatsink Temp MBC Clearance Check
Parameter Cutout
Table Set • MFC PCB Temp <90% of the
PCB Temp Cutout
• Compressor Bearing Temps
Overdrive All <90% of the Cutout Levitate Bearings
EXVs Closed

Overdrive Energize Condenser


IGV Closed Water Pump Relay

Energize Evaporator Confirm Condenser Water


Water Pump Relay Flow Within 20 Minutes
(6 Second Filter)

Confirm Evaporator Water


Flow Within 20 Minutes Evaporator EXV
(6 Second Filter) Pre-position

HDWA-SVX001D-EN 51
Start-up and Shut-down

Stopped to Starting • Power up start delay timer has expired


The stopped to starting diagram shows the timing from • Adjustable stop to start timer has expired
a stopped mode to energizing the compressor. The • Need to cool
shortest allowable time would be under the following The above conditions would allow the compressor to
conditions: start in 45 seconds.
• All temperatures below their starting limits
• Evaporator and condenser water flowing

Figure 36. Sequence of events: stopped to starting

Chiller Mode Need to Cool


(Satisfied Differential to Start)
Set to Auto
Stopped
or
Auto Waiting to Start Waiting to Start Starting Starting
Run
Inhibit
MBC Clearance Check and
Levitate Bearings (~10 Seconds)

Confirm Evaporator Restart Inhibit Temperature Checks: Confirm Condenser Water Flow AFD Parking
Water Flow • Motor Winding Temp <90% of the (6 Second Filter) (~8 Seconds)
(6 Second Filter) Motor Winding Temp Cutout
• AFD Heatsink Temp <90% of the
AFD Heatsink Temp Cutout MBC Clearance Check MBC Cooling
(if MBC Clearance Check = Valve Closed
• MFC PCB Temp <90% of the PCB Enabled)
Temp Cutout
Energize Evaporator • MBC Bearing Temps <90% of
Water Pump Relay Cutout
Economizer Valve
Levitate Bearings Closed

Confirm Evaporator
Water Flow in 20 Minutes Drive Cooling
Energize Condenser
(6 Second Filter) Valve Closed
Water Pump Relay

Motor Cooling
Confirm Cond Water Valve Closed
Flow in 20 Minutes
(6 Second Filter)
IGV Closed
(Except for Rapid Restart)

Evaporator EXV
Pre-position

52 HDWA-SVX001D-EN
Start-up and Shut-down

Running
The following figure shows a typical running sequence.

Figure 37. Sequence of events: running


AFD Status Limit Mode Exit Limit Mode
is “Running”
Chiller
Starting
Chiller is Running Chiller is Running - Limit Chiller is Running is
Compressor
Running

Capacity and Current


Softloading

Modulate IGV/AFD Modulate IGV/AFD Modulate IGV/AFD


for LWT Control for Limit Control for LWT Control

MBC Cooling Control MBC Cooling Control


MBC Cooling Control

Economizer Superheat Economizer Superheat


Control Control Economizer Superheat
Control

AFD Cooling Control AFD Cooling Control


AFD Cooling Control

Motor Cooling Control


(200 Ton Only) Motor Cooling Control
Motor Cooling Control

Condenser Liquid Condenser Liquid


Level Control Level Control Condenser Liquid
Level Control

HDWA-SVX001D-EN 53
Start-up and Shut-down

Satisfied Setpoint water temperature falling below the differential to stop


setpoint.
The following figure shows the normal transition from
running to shutting down due to the evaporator leaving

Figure 38. Sequence of events: satisfied setpoint

Satisfied Differential to Stop Setpoint

Running Preparing Shutdown Shutting Down Auto Auto

Close IGV (0 to 50 Seconds) MBC Levitation Will Stop When


RPM < 1200 for 60 Seconds

De-levitate
Command IGV Closed
(Check for 24 Hour Overdrive) Compressor

Close Economizer Set Evaporator EXV


Valve to 50%

De-energize Close MBC


Compressor Cooling Valve

De-energize Condenser
Water Pump Relay

Close Drive Cooling


Valve

Close Motor Cooling


Valve

54 HDWA-SVX001D-EN
Start-up and Shut-down

Normal Shutdown to Stopped or Run lines on the top indicate the final mode if the stop is
Inhibit entered via various inputs.

The following figure shows the transition from running


through a normal (friendly) shutdown. The dashed

Figure 39. Sequence of events: normal shutdown to stopped or run inhibit


Local Stop
Normal Latching Diagnostic Stopped
Normal Non-Latching Diagnostic
Tracer Stop
Run Inhibit
External Auto-Stop
Evaporator Pump
Delay &
IGV Closed Compressor Stopped

Stopped
Running Stopped or or
Preparing Shutdown Shutting Down Run Inhibit Run Inhibit

Close IGV (0 to 50 Seconds) MBC Levitation Will Stop When


RPM < 1200 for 60 Seconds
De-levitate Magnetic
Bearings
Command IGV
Closed Evaporator
Pump Off
Delay Time Close MBC Cooling
(0 to 30 Minutes) Valve
De-Energize
Compressor De-Energize Evaporator
Water Pump Relay
Set Evaporator EXV
to 50%
Close Motor Cooling
Valve

Close Drive Cooling


Valve
Every 24 hours, EXV
recalibration is armed.
Close Economizer Recalibration occurs
Valve when it is armed and
control has cycled to
the stop state on every
power up.
De-Energize Condenser
Water Pump Relay

HDWA-SVX001D-EN 55
Start-up and Shut-down

Immediate Shutdown to Stopped or Run the top indicate the final mode if the stop is entered via
Inhibit various inputs.

The following figure shows the transition from running


through an immediate shutdown. The dashed lines on

Figure 40. Sequence of events: immediate shutdown to stopped or run inhibit

Immediate Shut-down Non-Latching Diagnostic Run Inhibit


Immediate Shut-down Latching Diagnostic
Stopped
Immediate Stop

Run Inhibit
Running Shutting Down Stopped or
Stopped
Close IGV (0 to 50 Seconds)

MBC Levitation Will Stop When RPM < 1200 for 60 Seconds De-Levitate Magnetic
Bearings
De-Energize
Compressor

De-Energize Evap Close MBC Valve


Water Pump Relay
No Evap Pump Off Delay
for Immediate Shutdown
Close Evaporator EXV
De-Energize
Cond Water Pump

Close Economizer EXV

Close Motor Cooling


Valve

Close Drive Cooling


Valve

56 HDWA-SVX001D-EN
Start-up and Shut-down

AFD Mains Phase Loss Frequency™ Drive (AFD) diagnoses as a AFD Mains
Phase Loss (MPL) diagnostic.
The following figure shows how the controls act in a
power interruption event that the Adaptive

Figure 41. Sequence of events: AFD mains phase loss

“AFD Mains Phase Loss” From Drive “AFD Mains Phase Loss”
(Controls Remain Powered) Cleared and Need to Cool

Starting
Running Shutting Down Waiting to Start
Compressor

Close IGV (0 to 50 Seconds) Establish Condenser and Evaporator


Water Flow (6 Second Filter)

De-Energize Energize Evaporator


Compressor Water Pump Relay

De-Energize Evaporator
Water Pump Relay Energize Condenser
No Evap Pump Off Delay Water Pump Relay
for Immediate Shutdown

De-Energize
Condenser Water Pump Evaporator
EXV Pre-position

Close Economizer EXV

Close Motor Cooling


Valve (200 and 300 Ton Only)

Close Drive Cooling


Valve

Close IGV

HDWA-SVX001D-EN 57
Start-up and Shut-down

Ice Making (Running to Ice Making to


Running)
The following figure shows the transition from normal
cooling to ice making, and back to normal cooling.

Figure 42. Sequence of events: ice making (running to ice making to running)
Ice Making Command Ice Making Evaporator Leaving
1. Front Panel Command Water Temperature
2. Tracer Withdrawn Rises Above the
3. External Input Differential to Stop

Running Running
Running Running Running
(Ice Building) (Ice to Normal Transition)

Ice to Normal Transition Timer


(0–10 Minutes)
Open IGV at Max Rate/ Modulate IGV/AFD
Softload to CWS
Max AFD Frequency for LWT Control

Ignore Softloading and De-Energize Ice


Set CLS=100% Building Relay

Energize Ice Building De-Energize Head


Relay Relief Request Relay
Head Relief Request Relay Delay
(1–60 Minutes)

Energize Head Relief


Request Relay
Head Relief Request Relay Delay
(1–60 Minutes)

Enforce All Limits and Running Mode Diagnostics

58 HDWA-SVX001D-EN
Start-up and Shut-down

Ice Making (Auto to Ice Making to Ice


Making Complete)
The following figure shows the transition from auto to
ice making, to ice making complete.

Figure 43. Sequence of events: ice making (auto to ice making to ice making complete)
Remove All Ice Making Commands Via
1. Front Panel OD (Auto)
2. Tracer (Auto)
3. External Input (Open)
Evaporator Entering Water
Command Ice Making Via Temperature Falls Below the
1. Front Panel OD (On) Ice Termination Setpoint
2. Tracer (On)
3. External Input (Close/Short) Evaporator Entering Water Temperature Rises
Above the Ice Termination Setpoint

Auto Auto Stopped Stopped


Running Preparing Shutdown Shutting Down
(Waiting to (Starting (Ice Building to
(Ice Building) (Ice Building Complete) (Ice Building Complete)
Start) Compressor) Complete) Starting

MBC Levitation Will Stop When


RPM < 1200 For 60 Secconds

De-Levitate
Load Chiller at
Close IGV Magnetic Bearings
Max Rate De-Energize
Compressor

De-Energize Condenser Close MBC


Ignore Softloading and De-Energize Ice Water Pump Relay EXV
Set Demand Limit=100% Building Relay

Close Motor Cooling


Valve
Energize Ice
Building Relay
Close Drive Cooling
Valve

Energize Head Relief


Request Relay De-Energize Head
Head Relief Request Relay Relief Request Relay
Delay (1 to 60 Minutes) Head Relief Request Relay
Delay (1 to 60 Minutes)

De-Energize Evap
Water Pump Relay
No Evaporator Pump
Off Delay for
Ice Building

Close Economizer Valve

HDWA-SVX001D-EN 59
Start-up and Shut-down

Limit Conditions optimum chiller performance and prevent nuisance


diagnostic trips. These limit conditions are noted in the
The UC800 will automatically limit certain operating following table.
parameters during startup and run modes to maintain

Table 15. Limit conditions


Condition Description
The chiller, circuit, and compressor are currently running, but the operation of the chiller/compressor is being actively
Running - Limit
limited by the controls. Further information is provided by the sub-mode.
Condenser Pressure The circuit is experiencing condenser pressures at or near the condenser limit setting. The compressor will be unloaded to
Limit prevent exceeding the limits.
Evaporator
The circuit is experiencing saturated evaporator temperatures at or near the Low Refrigerant Temperature Cutout setting.
Refrigerant
The compressors will be unloaded to prevent tripping.
Temperature Limit
The compressor is running and its capacity is being limited by high currents. The current limit setting is 100% RLA (to avoid
Current Limit
overcurrent trips).
AFD Heat Sink
This limit will unload the chiller if the communicated heat sink temperature approaches cutout.
Temperature Limit
Demand Limit This limit allows the customer to control the maximum power into the chiller.

Control Panel Devices and Unit- • English


Mounted Devices • French
• French (Canada)
Unit Control Panel • German
Safety and operating controls are housed in the unit • Greek
control paneland the starter panel. The control panel
operator interface is called Tracer® AdaptiView™ and • Hebrew
is located on an adjustable arm connected to the side • Hungarian
of the control panel. For more information about
• Indonesian
operating Tracer® AdaptiView™, refer to Tracer
AdaptiView Display for Water-cooled Agility Chillers • Italian
Operations Guide (HDWA-SVU001*-EN). • Japanese
The control panel houses several other controls • Korean
modules called panel-mounted Low Level Intelligent
• Norwegian
Devices (LLIDs), power supply, terminal block, fuse,
circuit breakers, and transformer. The inter-processor • Polish
communication (IPC) bus allows the communications • Portuguese (Portugal)
between LLIDs and the UC800. Unit-mounted devices
are called frame-mounted LLIDs and can be • Portuguese (Brazil)
temperature sensors or pressure transducers. The • Russian
MODBUS® master connection on the UC800 provides • Romanian
communication to the TR200 AFD and to the Magnetic
Bearing Controller (MBC). These and other functional • Spanish (Europe)
switches provide analog and binary inputs to the • Spanish (Latin America)
control system.
• Swedish
User-defined Language Support • Thai
Tracer® AdaptiView™ is capable of displaying English • Turkish
text or any of 26 other languages (27 total languages).
Switching languages is simply accomplished from a
Language Settings menu. The following languages are
available:
• Arabic (Gulf Regions)
• Chinese—China
• Chinese—Taiwan
• Czech
• Dutch

60 HDWA-SVX001D-EN
Start-up and Shut-down

Unit Start-up and Shut-down procedure:

Procedures 1. Press the STOP key on the Tracer® AdaptiView™.


2. UC800 pump control will turn off the pump (after a
WARNING optional water pump delay time) when the STOP
Live Electrical Components! key is pressed and automatically restart the pump
Failure to follow all electrical safety precautions when the “Auto” key is pressed.
when exposed to live electrical components could 3. The unit will start normally, provided the following
result in death or serious injury. conditions exist:
When it is necessary to work with live electrical a. The UC800 receives a call for cooling and the
components, have a qualified licensed electrician differential-to-start is above the setpoint.
or other individual who has been properly trained
in handling live electrical components perform b. All system operating interlocks and safety
these tasks. circuits are satisfied.

WARNING Extended Unit Shut-down


Asphyxiation Hazard! 1. Perform the normal unit stop sequence using the
STOP key.
A significant release of refrigerant into a confined
space could displace available oxygen to breathe N o t e : Unless the water bundles are valved off and
and cause possible asphyxiation. Failure to follow drained, chiller power should remain ON at
instructions below could result in death or serious all times to allow the magnetic bearings to
injury. levitate the rotor in case water flow-driven
Should a refrigerant release occur, evacuate the rotation should occur. Trane recommends
area immediately and contact the appropriate leaving the power on to maintain the
rescue or response authority. Uninterruptible Power Supply (UPS) battery.
• Do not run evaporator water pump longer than 2. Verify the chilled water and condenser water
30 minutes after the chiller is shut down. pumps are cycled off. If desired, open disconnect
• Ensure that the evaporator is isolated from the switches to the pumps.
hot water loop before changeover to heating 3. Drain the condenser piping and cooling tower.
mode.
4. Remove the drain and vent plugs from the
The relief device is designed to relieve and
condenser headers to drain the condenser.
discharge the refrigerant from the unit if the
pressure in the evaporator exceeds 200 psig 5. After the unit is secured, perform the maintenance
(1379.0 kPaG) on the evaporator or 300 psig identified in the following sections.
(2068.4 kPaG) on the condenser.
Seasonal Unit Start-up
Unit Start-up 1. Close all drain valves and reinstall the drain plugs in
the evaporator and condenser headers.
NOTICE 2. Service the auxiliary equipment according to the
Equipment Damage! start-up and maintenance instructions provided by
Failure to follow instructions could result in the respective equipment manufacturers.
equipment damage. 3. Vent and fill the cooling tower, if used, as well as
Ensure that the Uninterruptible Power Supply the condenser and piping. At this point, all air must
(UPS) has been operating properly for a minimum be removed from the system (including each pass).
of 10 hours before starting. Then, close the vents in the condenser chilled water
circuits.
If required, after the system has been operating for
4. Open all of the valves in the evaporator chilled
approximately 30 minutes and has become stabilized,
water circuit.
complete the remaining start-up procedure, as follows:
5. If the evaporator was previously drained, vent and
1. Check evaporator and condenser refrigerant
fill the evaporator and chilled water circuit. After all
pressures under Condenser and Evaporator Reports
air is removed from the system (including each
on the Tracer® AdaptiView™. The pressures are
pass), install the vent plugs in the evaporator
referenced to sea level (14.6960 psia [101.3254
waterboxes.
kPaA]).

Temporary Shut-down and Restart


To shut down for a short time, use the following

HDWA-SVX001D-EN 61
Start-up and Shut-down

NOTICE 6. Check the adjustment and operation of each safety


and operating control.
Equipment Damage!
7. Close all disconnect switches.
Failure to follow instructions could result in
equipment damage. 8. Perform instructions listed in “Unit Start-up,” p. 61.
Ensure that the Uninterruptible Power Supply
(UPS) has been operating properly for a
minimum of 10 hours before starting.

62 HDWA-SVX001D-EN
Maintenance
WARNING bearing controller and Uninterruptible Power
Supply (UPS).
Hazardous Voltage w/Capacitors!
☐ Inspect all piping components for leakage and/or
Failure to disconnect power and discharge
damage. Clean out any in-line strainers.
capacitors before servicing could result in death or
serious injury. ☐ Clean and repaint any areas that show signs of
Disconnect all electric power, including remote corrosion.
disconnects and discharge all motor start/run ☐ Inspect vent piping of all relief valves for presence
capacitors before servicing. Follow proper of refrigerant to detect improperly sealed relief
lockout/tagout procedures to ensure the power valves.
cannot be inadvertently energized. For variable
☐ Inspect the condenser tubes for fouling. Clean if
frequency drives or other energy storing
necessary; refer to “Cleaning the Condenser,” p.
components provided by Trane or others, refer to
64.
the appropriate manufacturer’s literature for
allowable waiting periods for discharge of ☐ Visually inspect waterbox hinges to ensure that
capacitors. Verify with a CAT III or IV voltmeter hinges have not been damaged or altered.
rated per NFPA 70E that all capacitors have N o t e : If, after 10 years, the battery has not been
discharged. replaced, Trane recommends replacing
For additional information regarding the safe the battery.
discharge of capacitors, see PROD-SVB06*-EN.
Other
☐ Use a nondestructive tube test to inspect the
Recommended Maintenance condenser and evaporator tubes at 3-year intervals.
Weekly N o t e : It may be desirable to perform tube tests on
these components at more frequent intervals,
While the unit is running in stable conditions: depending upon chiller application. This is
☐ Log the chiller. especially true of critical process equipment.
☐ Check evaporator and condenser pressures with Ask your Sales account manager for a copy of
gauges and compare to the reading on the Tracer® engineering bulletin (CTV-PRB024*-EN) for
AdaptiView™ or Tracer® TU service tool. Pressure clarification of the role of eddy current testing in
readings should fall within operating ranges chiller maintenance by providing information
specified in the following tables. If chiller about eddy current technology and heat
measurements vary significantly from values listed exchanger tubing.
in the following tables, problems may exist with ☐ Depending on chiller duty, contact your local Trane
refrigerant charge levels. Contact your local Trane Service Agency to determine when to conduct a
Service Agency. complete examination of the unit to determine the
N o t e : Optimum condenser pressure is dependent condition of the compressor and internal
on condenser water temperature, and should components.
equal saturation pressure of refrigerant at a
temperature 2°F to 5°F (1.1°C to 2.8°C) above
that of leaving condenser water at full load.
Maintenance Procedures
Drive Cooling System
Monthly
☐ Review operating log. NOTICE
☐ Clean all water strainers in both the chilled and Equipment Damage!
condensing water piping systems. Use of unapproved fluids, or dilution of approved
fluid, could result in catastrophic equipment
Annual damage.
Contact your local Trane Service Agency to shut down Use only Trane Heat Transfer Fluid P/N CHM01023.
the chiller once each year and perform the following: This fluid is a direct use concentration and is not
to be diluted. Do not top off with water or any
☐ Perform all weekly and monthly maintenance other fluid.
procedures.
☐ Leak check the chiller, inspect safety controls, and
inspect electrical components, such as magnetic

HDWA-SVX001D-EN 63
Maintenance

Service Intervals Figure 44. Pressure relief cap


NOTICE
Equipment Damage!
Failure to follow instructions could result in
equipment damage.
Drive cooling fluid and strainer must be serviced
every five (5) years.

Interval Task

5 years Drain and replace the drive cooling fluid

5 years Replace the fluid strainer when servicing the fluid

Yearly Perform a fluid pH test.

Unit Diagnostics
An improperly filled drive cooling system (either low
fluid level or entrapped air in the circuit) can result in
the AFD or output filter overheating. This condition
may result in the following diagnostics:
• AFD Fault
Drive Cooling Expansion Tank
• Loss of Drive Cooling Control
Proper fluid level is important to the operation of the
If chiller diagnostics indicate a drive cooling system unit. To verify proper level, inspect the liquid level in
problem, contact your local Trane Service Agency. the fluid reservoir (located on the left side of the
electrical panel); refer to the following figure for fluid
pH Test levels under various temperature conditions. If levels
Obtain a sample of fluid from the drive cooling loop via are low, contact your local Trane Service Agency.
the loop drain located near the discharge of the pump.
Figure 45. Drive cooling expansion tank fill
Test for pH level using litmus paper with a 0.5
resolution.
• pH < 8 indicates fluid to be changed

Pressure Relief Cap Design Fill at


104°F (40.0°C)
The pressure relief cap is an automotive style pressure-
Design Fill at Maximum Fill at
vent radiator cap; refer to the following figure. The 70°F (21.1°C)
70°F (21.1°C)
setting for the relief spring is 16 lb (7.3 kg). The function
of the relief cap can be verified with a standard Maximum Fill at Design Fill at
automotive radiator cap tester. 32°F (0.0°C) 32°F (0.0°C)
Minimum Fill at
70°F (21.1°C)

N o t e : Fill lines are NOT marked on the tank. The top


level is just below the upper fitting and the
bottom level is just above the lower fitting; the
middle level is midway between the two fittings.

Cleaning the Condenser


Condenser tube fouling is suspect when the
“approach” temperature (i.e., the difference between

64 HDWA-SVX001D-EN
Maintenance

the refrigerant condensing temperature and the leaving ensure that they are aligned.
condenser water temperature) is higher than predicted.
Condenser tube fouling is indicated when the approach
temperature (the difference between the condensing
refrigerant temperature and the leaving condenser
water temperature) is higher than predicted. Refer to
sales order selection data for approach temperatures.
N o t e : Glycol in the water system typically doubles the
standard approach.
If the annual condenser tube inspection indicates that
the tubes are fouled, two cleaning methods
(mechanical or chemical) can be used to rid the tubes
of contaminants. The methods are described in the
following sections.

Mechanical Cleaning
Mechanical tube cleaning is used to remove sludge and
loose material from smooth-bore condenser tubes. 6. Remove waterbox bolts.
WARNING WARNING
Heavy Objects! Overhead Hazard!
Failure to properly lift waterbox could result in
Failure to follow instructions could result in
death or serious injury.
death or serious injuries.
Each of the individual cables (chains or slings)
Never stand below or in close proximity to
used to lift the waterbox must be capable of
heavy objects while they are suspended from,
supporting the entire weight of the waterbox. The
or being lifted by, a lifting device in case the
cables (chains or slings) must be rated for
object drops.
overhead lifting applications with an acceptable
working load limit. Refer to the table for waterbox
7. Lift the waterbox away from the shell.
weights.
8. Store the waterbox in a safe and secure location
Waterbox Removal and position.

Review mechanical room limitations and determine the 9. Work a round nylon or brass bristled brush
safest method or methods of rigging and lifting the (attached to a rod) in and out of each of the
waterboxes. condenser water tubes to loosen the sludge.

Important: 10. Thoroughly flush the condenser water tubes with


clean water.
• Do NOT rotate waterboxes.
N o t e : To clean internally enhanced tubes, use a bi-
• Be sure to replace water boxes right- directional brush or consult a qualified
side-up to maintain proper baffle service organization for recommendations.
orientation. Use new O-rings.
• if the waterbox is reversed, be sure to
match mark on the baffle and waterbox
to ensure that they are aligned.
1. Determine the size of chiller being serviced. See
unit nameplate located on chiller control panel.
2. Use a 3/8-in. (9.5-mm) rigging shackle for waterbox
removal as shown in the following figure. The rated
lifting capacity of the selected lift connection device
must meet or exceed the published weight of the
waterbox. Refer to the tables in “Waterbox
Reassembly,” p. 66.
3. Install rigging shackle onto the lifting connection on
the waterbox.
4. Disconnect water pipes, if connected.
5. Match mark on the waterbox and the baffle to

HDWA-SVX001D-EN 65
Maintenance

Figure 46. Waterbox and 3/8-in. (9.5-mm) rigging Obtain the required parts from your local Trane Parts
shackle Center.
Chemical Cleaning
Scale deposits are best removed by chemical means.
Consult a qualified water treatment specialist (i.e., one
that knows the local water supply chemical/mineral
content) for a recommended cleaning solution suitable
for the job. (A standard condenser water circuit is
composed solely of copper, cast iron and steel.)
Improper chemical cleaning can damage tube walls.
All of the materials used in the external circulation
system, the quantity of the solution, the duration of the
cleaning period, and any required safety precautions
should be approved by the company furnishing the
materials or performing the cleaning.
N o t e : Chemical tube cleaning should ALWAYS be
followed by mechanical tube cleaning.

Cleaning the Evaporator


Because the evaporator is typically part of a closed
circuit, it does not accumulate appreciable amounts of
Waterbox Reassembly scale or sludge. However, if cleaning is deemed
After service is complete, the waterbox should be necessary, use the same cleaning methods described
reinstalled on the shell following removal procedures in “Cleaning the Condenser,” p. 64.
in reverse (refer to “Waterbox Removal,” p. 65). After
thoroughly cleaning each joint, use new O-rings on ALL
joints. Torque waterbox bolts in a star pattern to 163
Waterbox Hinges
ft·lb (221.0 N·m) dry. The hinged waterbox option is available for the
evaporator, the condenser, or both. This option can be
Table 16. Waterbox weights ordered with the hinge only on the evaporator and/or
Fabricated Non- only on the condenser; however, the hinges MUST be
Marine Waterbox
Shell Descrip- marine Waterbox ordered for both ends of the evaporator and/or the
Cover
Size tion Welded Dome condenser.
lb kg lb kg
The hinged waterbox option does NOT require annual
Condens-
er Supply,
maintenance or lubrication, although a visual
150 psi 145 65.8 253 115 inspection is recommended to ensure that the hinges
(1034.2 have not been damaged or altered. For assembly and
kPa) disassembly of hinges, please refer to HDWA-
Evapora- SVN001*-EN.
020 tor
Supply,
170 77.1 253 115
150 psi
(1034.2
kPa)
Return 100 45.4 NA NA
Condens-
er Supply,
150 psi 210 95.3 395 179
(1034.2
kPa)
Evapora-
040 tor
Supply,
245 111.1 395 179
150 psi
(1034.2
MARINE NON-MARINE
kPa)
Return 145 65.8 NA NA

Note: Each optional waterbox hinge weighs


44 lb (19.94 kg)

66 HDWA-SVX001D-EN
Maintenance

Adaptive Frequency Drive leaking capacitors, discolored reactors or inductors,


broken pre-charge resistors, smoke or arc trails on
Periodic Maintenance and MOVs and capacitors, etc.).
Inspection 7. Closely inspect the motor terminal board for any
Adaptive Frequency™ Drive (AFD) periodic signs of leakage, arcing, etc..
maintenance and inspections should be performed 8. Check ALL cable/lug/terminal connections inside
every 1–12 months, depending on operating the drive enclosure. Ensure all are clean and tight,
environment. and not rubbing against each other anywhere.
9. Test pH levels annually. Replace fluid as necessary,
Visual Inspection—Power Removed or every 5 years.
WARNING 10. Remove and clean electrical panel air filters.

Hazardous Voltage w/Capacitors! Operational Inspection—Power Applied


Failure to disconnect power and discharge
capacitors before servicing could result in death or WARNING
serious injury.
Live Electrical Components!
Disconnect all electric power, including remote
Failure to follow all electrical safety precautions
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper when exposed to live electrical components could
lockout/tagout procedures to ensure the power result in death or serious injury.
cannot be inadvertently energized. For variable When it is necessary to work with live electrical
frequency drives or other energy storing components, have a qualified licensed electrician
components provided by Trane or others, refer to or other individual who has been properly trained
the appropriate manufacturer’s literature for in handling live electrical components perform
allowable waiting periods for discharge of these tasks.
capacitors. Verify with a CAT III or IV voltmeter
1. Verify the drive cabinet cooling fans are operating.
rated per NFPA 70E that all capacitors have
This should be done from outside the enclosure, by
discharged.
looking into the cabinet at door and cabinet vents,
For additional information regarding the safe to avoid electrical hazards.
discharge of capacitors, see PROD-SVB06*-EN.
N o t e : The power module fan comes on with power.
1. Ensure the door interlocks are present and working. Other fans cycle with drive operation.
2. Verify the safety ground connections to the door 2. Check historic fault codes using Adaptive
panels are securely connected. Frequency™ Drive (AFD) control panel (LCP).
3. Inspect power wire cables and devices to assure no N o t e : The AFD control panel is used ONLY for
abrasion is occurring from vibrations against service and should never be used for
chassis of cabinets, or other edges. machine operation.
4. Ensure the drive interior and exterior is clear of any 3. Check configuration settings and confirm all proper
dust or debris. Fans, vents, etc. must be clean. settings are still present in the controls.
I m p o r t a n t : Only use a vacuum for cleaning. Do 4. Review the diagnostic history.
NOT use compressed air. 5. Make Chiller Service report to document all
5. Inspect the interior of the drive for any signs of setpoints.
moisture entry or leakage. 6. Check the UC800 alarm histories for any indications
6. Visually inspect all drive components and wiring. of operational problems.
Look for signs of heat or failure (look for swelled or

HDWA-SVX001D-EN 67
Wiring
The following tables provide lists of field wiring Table 17. Wiring drawings
diagrams, electrical schematics, and connection
Drawing Description
diagrams for Agility™ chillers. To determine the
specific electrical characteristics of a particular chiller, 2311-4987 Diagram—Schematic Wiring; Standard
refer to the nameplates mounted on the units. 2311-4988 Diagram—Field Wiring: Harmonic Filter
Diagram — Schematic Wiring;
2311–4989
Autotransformer
Diagram — Field Wiring; Unit-mounted Low
2311–4919
Voltage AFD (240~678A Range)

68 HDWA-SVX001D-EN
Appendix A: Forms and Check Sheets
The following forms and check sheets are included for • “Appendix D: Operator Log,” p. 74
use with Trane start-up of HDWA Agility™ chillers.
Forms and check sheets are used, as appropriate, for
installation completion verification before Trane start-
Unit Start-up/Commissioning
up is scheduled, and for reference during the Trane I m p o r t a n t : Start-up must be performed by Trane or an
start-up. agent of Trane specifically authorized to
Where the form or check sheet also exists outside of perform start-up and warranty of Trane®
this publication as standalone literature, the literature products. Contractor shall provide Trane
order number is also listed. (or an agent of Trane specifically
authorized to perform start-up) with notice
• “Appendix B: Agility™ Chiller Installation of the scheduled start-up at least two weeks
Completion and Request for Trane Service,” p. 70 prior to the scheduled start-up.
(HDWA-ADF001*-EN)
• “Appendix C: Settings,” p. 72

HDWA-SVX001D-EN 69
™ Chiller Installation Completion
Appendix B: Agility™
and Request for Trane Service
I m p o r t a n t : A copy of this completed form must be ☐ Flow switch or flow proving device installed (if
submitted to the Trane Service Agency that not factory-provided)
will be responsible for the start-up of the ☐ Cooling tower
chiller. Start-up will NOT proceed unless
applicable items listed in this form have Additional piping:
been satisfactorily completed. ☐ Make-up water connected to cooling tower
TO: ☐ Water supply connected to filling system
TRANE SERVICE OFFICE: ☐ Does unit have freeze inhibitor? If unit has
S.O. NUMBER: freeze inhibitor:
SERIAL NUMBERS: ☐ Verify type and concentration correct per
JOB/PROJECT NAME: unit submittal
ADDRESS:
☐ Calculate and record freeze point of the
solution: ___________ (specify °F or °C)
The following items
are being installed ☐ Systems filled
and will be completed by:
☐ Pumps run, air bled from system
☐ Strainers installed in entering water piping
I m p o r t a n t : Start-up must be performed by Trane or an (evaporator and condenser) and cleaned
agent of Trane specifically authorized to
perform start-up and warranty of Trane® ☐ Relief valve ventilation piping installed (as
products. Contractor shall provide Trane applicable)
(or an agent of Trane specifically 3. F l o w b a l a n c i n g v a l v e s i n s t a l l e d
authorized to perform start-up) with notice
☐ Leaving chilled water
of the scheduled start-up at least two weeks
prior to the scheduled start-up. E q u i p m e n t ☐ Leaving condenser water
not started by Trane is not warranted by ☐ Proper porting to measure flow and balance
Trane.
4. G a u g e s , t h e r m o m e t e r s , a n d a i r v e n t s
Check box if the task is complete or if the answer is
“yes”. ☐ Installed on both sides of evaporator

1. A g i l i t y ™ C h i l l e r ☐ Installed on both sides of condenser

☐ Installation meets foundation requirements. 5. W i r i n g

☐ In place and piped. ☐ Wire size per submittal and NEC 310-16

☐ Isolation pads installed. ☐ Full power available

N o t e : Do not insulate the Agility™ chiller or ☐ External interlocks (flow switch, pumps
adjacent piping prior to the chiller auxiliary, etc.)
commissioning by Trane service personnel. ☐ Chilled water pump (connected and tested)
The contractor is responsible for any foreign ☐ Condenser water pump (connected and tested)
material left in the unit.
☐ Cooling tower fan rotation checked
2. P i p i n g
☐ 115 Vac power available for service tools (as
Chilled water piping connected to: required)
☐ Evaporator ☐ All controls installed and connected
☐ Air handling units ☐ If unit was disassembled for installation, all
☐ Pumps interconnecting wiring reinstalled
☐ Flow switch or flow proving device installed (if ☐ For CVHS and CVHM chillers, indicate type of
not factory-provided) power distribution grounding:
Condenser piping connected to: ☐ Solidly Grounded (Center Ground Wye)
☐ Condenser -or-
☐ Pumps ☐ Non-Solidly Grounded (Any Delta, High

70 HDWA-SVX001D-EN
Appendix B: Agility™ Chiller Installation Completion and Request for Trane Service

Impedance Ground, or Ungrounded Wye) 10. O w n e r a w a r e n e s s


6. T e s t i n g ☐ Has the owner been fully instructed on the
☐ Dry nitrogen available for pressure testing proper use and handling of refrigerant?

☐ Trace gas amounts of R-134a available for leak ☐ Does the owner have a copy of the MSDS for
testing (if necessary) refrigerant?
N o t e : Additional time required to properly complete
the start-up and commissioning, due to any
7. R e f r i g e r a n t incompleteness of the installation, will be
☐ Refrigerant on job site and in close proximity to invoiced at prevailing rates.
chiller (if shipped separately)
Total amount in cylinders/drums: This is to certify that the Trane equipment has been
___________ (specify lb or kg) and fill in properly and completely installed, and that the
specifics below: applicable items listed above have been satisfactorily
completed.
Number of cylinders/drums _____ of size
_____ (specify lb or kg) Checklist Completed by
(Print Name):
Number of cylinders/drums _____ of size
_____ (specify lb or kg) SIGNATURE:
DATE:
N o t e : After commissioning is complete, it is the
installer’s responsibility to transport
empty refrigerant containers to an easily In accordance with your quotation and our purchase
accessible point of loading to facilitate order number ______________, we therefore require the
container return or recycling. presence of Trane service on this site, for the purpose
of start-up and commissioning, by ______________
8. S y s t e m (date).
☐ Systems can be operated under all design N o t e : Minimum of two week advance notification is
selection points to verify proper operation. required to allow for scheduling of the chiller
9. E q u i p m e n t r o o m start-up.
☐ Does the equipment room have a refrigerant ADDITIONAL COMMENTS/INSTRUCTIONS
monitor/sensor capable of monitoring and
alarming within the allowable exposure level of
the refrigerant?
☐ Does the installation have properly placed and
operating audible and visual refrigerant alarms?
☐ Does the equipment room have proper
mechanical ventilation?
☐ If it is required by local code, is a self-contained
breathing apparatus available? N o t e : A copy of this completed form must be
☐ Does the equipment room meet environmental submitted to the Trane Service Agency that will
condition requirements specified in the chiller be responsible for start-up of chiller.
Installation, Operation, and Maintenance
manual?

HDWA-SVX001D-EN 71
Appendix C: Settings
Chiller Settings Value
Setpoint Source
Front Panel Hot Water Command
Front Panel Chilled Water Setpoint
Front Panel Hot Water Setpoint
Front Panel Ice Building Command
Front Panel Ice Termination Setpoint
Ice to Normal Cooling Timer Setpoint
Front Panel Demand Limit Setpoint
Front Panel Base Loading Setpoint
Front Panel Base Loading Command
Differential to Start
Differential to Stop
Condenser Water Pump Off Delay
Evaporator Water Pump Off Delay
Evap Low Water Flow Warning Setpoint
Power-Up Start Delay
Chiller Power Demand Time Period
Service Settings Value
Low Evaporator Water Temp Cutout
Low Refrigerant Temperature Cutout
Local Atmospheric Pressure
Maximum Capacity Limit
Minimum Capacity Limit
BAS Setpoint Power Loss Store Enable
Capacity Control Softload Time
Demand Limit Softload Time
Demand Limit Startup Target
Condenser Pressure Limit Setpoint
Feature Settings Value
Ext Chilled/Hot Water Setpoint Enable
External Demand Limit Setpoint Enable
Ice Building Feature Enable
Minimum Capacity Timer
Security
LCI-C Diagnostic Encoding
External Base Loading Setpoint Enable
Chilled Water Reset Value
Chilled Water Reset Type
Return Water Reset Ratio
Return Water Start Reset
Return Water Maximum Reset
Outdoor Air Reset Ratio
Outdoor Air Start Reset
Outdoor Air Maximum Reset

72 HDWA-SVX001D-EN
Appendix C: Settings

Manual Control Settings Value


Evaporator Water Pump Override
Condenser Water Pump Override
Manual Capacity Control
Clear Energy Consumption
Display Settings Value
Date Format
Date Separator
Time Format
Unit System
Pressure Units
Language
Date
Time
UTC Offset
Summer Time

HDWA-SVX001D-EN 73
Appendix D: Operator Log
N o t e : An Operator Log can be captured by using the AdaptiView™ display; refer to the following
“Logsheet Report” found on the Tracer® figures.

Figure 47. Reports, Log Sheet button highlighted

Figure 48. Sample Agility chiller Log Sheet

74 HDWA-SVX001D-EN
Appendix D: Operator Log

Run Time
Data Name
15 Minutes 30 Minutes 1 Hour
Evaporator
Evaporator Entering Water Temperature
Evaporator Leaving Water Temperature
Evaporator Saturated Rfgt Temp
Evaporator Refrigerant Pressure
Evaporator Approach Temperature
Evaporator Water Flow Status
Approx Evap Water Flow
Evap Differential Wtr Press
Evaporator EXV Percent Open
Condenser
Condenser Entering Water Temperature
Condenser Leaving Water Temperature
Condenser Saturated Rfgt Temp
Condenser Refrigerant Pressure
Condenser Approach Temperature
Condenser Water Flow Status
Approx Cond Water Flow
Cond Differential Wtr Press
Condenser Refrigerant Liquid Level
Compressor
Compressor Starts
Compressor Running Time
Compressor Refrigerant Discharge Temperature
IGV Percent Open
Chiller Load Command
MBC PCB Temperature
MBC Cooling Valve Percent Open
Compressor Bearing Temperature 1
Compressor Bearing Temperature 2
Motor
AFD Average Motor Current % RLA
AFD Motor Current U % RLA
AFD Motor Current V % RLA
AFD Motor Current W % RLA
AFD Motor Current U
AFD Motor Current V
AFD Motor Current W
Motor Winding Temp #1
Motor Winding Temp #2
Motor Winding Temp #3
Motor Temperature
AFD Percent Speed
AFD Heatsink Temperature

HDWA-SVX001D-EN 75
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient
environments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® and
Trane® — work together to enhance the quality and comfort of air in homes and buildings; transport and protect
food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a
world of sustainable progress and enduring results.

ingersollrand.com

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications
without notice.
We are committed to using environmentally conscious print practices.

HDWA-SVX001D-EN 15 Oct 2019


Supersedes HDWA-SVX001C-EN (February 2019) ©2019 Ingersoll Rand