Piloting Boiler Startup


at Lightspeed
Many combined cycle power plants are being operated as peaker plants, rather
than as baseload units. That can pose a problem for economizer safety valves.
Pilot-operated safety valves offer several advantages compared to standard
spring-loaded safety valves in this situation.

Matt Byers and Hari Nair

T
he power industry has witnessed
a series of major technology shifts
over the past few decades, from a
20th-century infrastructure that was dom-
inated by coal-fired and nuclear plants to
the more-efficient and environmentally
friendly supply of power that exists today.
A major reduction in the cost of natural
gas drove the rapid emergence of com-
bined cycle power plants (CCPP) that
yield higher efficiencies coupled with a
smaller carbon footprint. For nearly 20
years, CCPPs have been the dominant
technology with new construction and
surging capacity around the world.
More recently, however, reduced 1. A typical pilot-operated safety valve is shown here with a sensing tube that passes the fluid
generation costs, shorter construction to the pilot valve mounted on top of the main safety valve. Courtesy: Baker Hughes
lead-times, and government subsidies
have given renewable energy sources, system called the economizer before it a vibration effect induced by a continu-
such as wind and solar power, a surge is fed to the HRSG where it fully trans- ous series of rapid opening and closing
in global demand. Rampant growth of re- forms into steam to drive the steam tur- events. If left unaddressed, chatter can
newable power has dramatically reduced bine. The economizer itself is designed quickly lead to damage and leakage across
the demand for new CCPPs. According as a fired pressure vessel, and as such, the valve seat, and if severe enough, can
to the International Energy Agency, 2015 is required by ASME code to have one or even result in damage to adjacent piping.
marked a turning point for renewables. more pressure relief devices in the event In response to this trend of damaged
Led by wind and solar, renewables repre- it becomes isolated from the boiler and spring-loaded economizer valves and
sented more than half of all new power needs to exhaust independently. well-documented HRSG startup issues,
capacity installed around the world that Historically, these pressure relief de- the ASME BPVC Section I committee
year, and the growth has continued. vices have been direct, spring-loaded, prepared and approved Code Case 2446,
The increase in total market supply ca- closed-bonnet-type safety valves. These allowing pilot-operated safety valves
pacity, along with the lower operating cost spring-loaded safety valves are required (POSV) to be used to protect the econo-
of renewables, has led the power industry to be certified to ASME Boiler and Pres- mizer. The POSV has many advantages
to transform many CCPPs into “peaker” sure Vessel Code (BPVC) Section I rules, over a spring-loaded valve in this applica-
units to supply power when renewable which means these valves are required tion, including the following:
sources cannot meet full demand, such to be designed, tested, and certified
as when the sun goes down at night. This with steam as the fluid media. However, ■ POSVs can operate closer to set pres-
change in demand has driven CCPPs to the economizer application fluid is com- sure without seat leakage.
alter their operations for rapid generation monly high-temperature water that has ■ POSVs have shorter blowdown, which
availability, which translates into faster not yet fully undergone a phase change is the difference between the set
startup and shutdown, and heavy cycling into steam. pressure and closing pressure; thus,
load on major equipment, such as heat re- This presents a paradox for code de- reducing the amount of steam lost
covery steam generators (HRSGs). sign versus suitable application engineer- from the system during an excursion.
ing, as code-required steam trims are not ■ POSVs are typically not trim dependent,
Economizer Application designed to relieve in liquid applications. meaning they operate equally with ei-
As a CCPP comes online, feedwater tem- In many installations, these spring-loaded ther a liquid or steam relief condition.
perature is elevated as it absorbs heat steam safety valves result in a common
from the gas turbine exhaust through a relief scenario called “chatter.” Chatter is POSVs operate by sensing upstream

|
June 2019 POWER
www.powermag.com
operations & maintenance
system pressure and passing this pres- recommended, as magnetite can be per-
sure through a smaller pilot valve to manently embedded within the filter and
control the closing force acting on the cannot be removed by cleaning. Another
main-valve disc. Increasing pressure at option is to specify dual filters when pur-
the inlet of the valve results in increased chasing the POSV from the valve manu-
closing force until the pilot valve opens. facturer. This option reduces downtime as
Unlike spring-loaded valves that have a it allows for one filter to be serviced while
spring providing a closing force regard- the valve remains in operation simply by
less of inlet pressure, POSVs require switching over to the backup filter. Under
inlet pressure to load pressure into the any scenario, a preventative maintenance
main-valve dome, which provides a clos- schedule is always recommended, even
ing force on the main-valve piston, which with a dual-filter option.
in turn acts on the main-valve disc. As CCPPs today are transforming to
peaker units and are demanded to re- 2. A pressure snubber can be added to the pi-
Planning Against Failure Modes duce time to full power generation loads, lot sensing line to dampen pressure in systems
During plant commissioning, boilers are operators are pushing ramp rates more susceptible to surges. Courtesy: Baker Hughes
often filled at lower system pressures aggressively than ever before. As the
with the economizer experiencing condi- gas turbine engages, the exhaust tem- pressure snubber in the pilot sensing line
tions of about 1–2 barg (15–30 psig). The perature increase causes water in the (Figure 2) can absorb the effects of water
lack of sufficient operating pressure act- economizer to expand, resulting in a hammer in the piping system and damp-
ing on the main-valve dome from the me- rapid increase in pressure inside the unit. en the pressure before entering the pilot
dium can lead to main-valve seat leakage Ramp rates as high as 20 bar/second valve. This solution allows a smooth and
and/or damage to the disc, seat bush- (300 psi/second) have been experienced stable pressure communication from the
ing, and nozzle. Figure 1 demonstrates in many plants that are transforming and pilot valve to the main valve, eliminating
a typical cross-sectional view of these coming online today. chatter in the pilot and main valve. It’s good
internals to show the flow path from the These ramp rates are hitting the practice to consult the POSV manufacturer
sensing line to the pilot to the main-valve valve with a surge of pressure—a ham- during system design for its pressure ramp
dome above the valve seat and disc. mer—that exceeds the ranges for which rate limits and recommendations for snub-
To ensure seat tightness, operators POSVs were designed. By design, a flow ber installation, if necessary.
should install an auxiliary pressure source, path restriction exists from the POSV in-
such as a nitrogen bottle, to the POSV field let to the pilot-valve dome to manage an Code Changes and the Future of
test connection port to keep the main valve offsetting dome pressure, which inher- Economizer POSVs
pressurized and closed during periods of ently results in micro-seconds of time lag The ASME BPVC Section I committee
low system operating pressure. By attach- between the pressure increase within recognized the need for code changes
ing an auxiliary pressure, regulated be- the pilot valve and the inlet pressure act- on economizers to address these appli-
tween 75% and 97% of set pressure, the ing on the seat. Such rapid pressure rise cation challenges. Recent changes to the
main-valve dome may be pre-loaded with can lead to chatter in the pilot valve it- 2017 ASME BPVC Section I code now al-
enough pressure to ensure sufficient clos- self, which then causes the main valve to low economizers to have liquid-certified
ing force is provided to keep the main valve chatter, resulting in damage to both the valves sized at 10% accumulation for
closed and leak tight. Another possible so- pilot and the main-valve components. over-pressure protection. This change will
lution is to consult with the valve manufac- Similarly, pressure increases instan- allow direct spring-loaded liquid-certified
turer to install an additional low-resistance taneously in the economizer when the safety relief valves to be used and dual-
spring in the main-valve dome designed to feed pump is turned on, causing rapid certified to meet both ASME Section I and
provide a downward closing force on the pressure spikes in the economizer. Section VIII requirements. These changes
main-valve disc, which can work in conjunc- These rapid pressure spikes cause wa- bring valve capacity and performance re-
tion with pressure in the main-valve dome ter hammer, which is a pressure surge quirements in line with what products
during this low-pressure startup condition. caused when the water is in motion and pressure relief manufacturers can offer to
Another common failure mode is clog- is forced to stop or change direction sud- meet this demanding application.
ging of filter elements in the pilot sens- denly. The momentum of the fluid abrupt- However, it’s important to keep in mind
ing line from system debris that wasn’t ly stopping or changing direction creates that spring-loaded valves are often not
completely flushed during commission- a pressure wave that travels through the designed to meet the same pressure lim-
ing. Clogging of a filter in the sensing media within the pipe system, subject- its as pilot-operated valves due to spring
line prevents pressure from reaching the ing everything in that closed system to design limitations. Therefore, based on
pilot, resulting in reduced pressure in the significant and damaging forces. the need for higher-pressure, larger-ori-
main-valve dome. The reduced main-valve The best solution to address the prob- fice valves on today’s designed HRSGs,
dome pressure causes the valve to leak lems from a rapid pressure ramp-up is POSVs may be the only product that can
and/or open, wasting steam, reducing ef- simply to reduce ramp rates as much as be offered by valve manufacturers for the
ficiency, and causing startup interruption. possible. Slowing from 20 bar/second higher-pressure economizer applications. ■
A proactive schedule for preventative down to 10 bar/second can drastically re- —Matt Byers is the Consolidated Valves
maintenance on the pilot-valve filters duce the severity of the impact to the point product management leader with Baker
during the first year of plant operation is where pressure damping features, such as Hughes, a GE company; and Hari Nair
highly recommended. Changing the filter a snubber, can withstand the effects of is director—Power Industry with Baker
element rather than cleaning it is typically the hammer. Manufacturer installation of a Hughes, a GE company.