Professional Documents
Culture Documents
DOI 10.1007/s12273-008-8219-4
RESEARCH ARTICLE
Thermodynamics Laboratory, University of Liège, Campus du Sart-Tilman, Bâtiment B49 (P33), B-4000 Liege, Belgium
Abstract The today-availability of powerful engineering equation solvers is opening very new
possibilities in technical component modelling and in system simulation. The simulation models, the
“user guide” and the “reference guide” are all included in a same file. Reliable “reference” and
“simplified” models are currently available for the building zone and for most (heating, ventilation
and air-conditioning) HVAC components. Focus is given here on “simplified” models and on a
simulation tool, called “Benchmark”. This tool should help an auditor to make the best use of the
limited information usually available about actual fuel and electricity consumptions and to get a very
first evaluation of the actual performances of a given HVAC system. An example of such use is
presented. Another simulation tools and more information about the modelling of HVAC components
will be presented in a further paper.
Keywords building modelling, HVAC system modelling, building energy audit, benchmarking
List of symbols
The main parameters described above are entered through means of a first order differential equation. A correction
the control panels. The other parameters of the model, as factor (Fa,in, Eq. (4)) has to be applied to the air capacity in
HVAC system characteristics, nominal performances and order to take into account the effect of the vertical air
capacities are automatically computed through a pre-sizing temperature gradient in the zone (Lebrun 1978; Laret 1980).
calculation, or defined on the basis of default values, given
dU
in European standards prEN 13053 (2003) and PrEN = Q roof,surf,in + Q floor,surf,in + Q opaque,frontages,surf,in
13773 (2007). Other information as weather data and dτ in
occupancy rate are provided in “lookup tables”. + Q windows + H s,vent + H s,inf + Q s,in (1)
τ2 dU
3.2 Building modelling ΔU in = ∫ dτ (2)
τ1 dτ in
3.2.1 Indoor conditions ΔU in = Cin × (ta,in − ta,in,1 ) (3)
The indoor conditions (CO2 contamination, global
temperature, and humidity) are computed by means of Cin = Fa,in × Vin × ρ a × cp,a (4)
three different mass and energy balances. Indoor comfort
b) CO2 balance
indexes (PMV and PPD) are evaluated at each time step
A first mass balance is used to compute the CO2
through classical Fanger’s equations (1970).
concentration in the indoor environment (Eqs. (5) − (11)).
a) Sensible heat balance The CO2 flow rate entering the zone is due to two main
A sensible heat balance is made on the indoor node to contributions (Eq. (5)):
compute the combined convective − radiative indoor CO2 brought by ventilation (Eq. (6)), positive infiltration
temperature. and negative exfiltration air flow rates (Eq. (7));
A mono-zone building model is used here. It’s based on CO2 produced by the occupants (function of the occupant
a simplified equivalent RC network including five thermal metabolic rate, Eq. (8)).
masses (Fig. 2; Masy 2006), corresponding to a large Treated ventilation air CO2 concentration is given as an
occupancy zone, surrounded by external glazed and opaque output of the HVAC system model, while, for infiltration,
walls. This scheme corresponds to a typical office building, it corresponds to outdoor air input data.
mainly composed of lattice structure and slabs. dM
The heat flow emitted by the surfaces of the walls (roof, = M CO2 ,vent + M CO2 ,inf + M CO2 ,in (5)
dτ CO2 ,in
floor, opaque frontages, and windows), the enthalpy flow
rate corresponding to ventilation and infiltration air and MM CO2
the internal sensible gains (including local heating/cooling
M CO2 ,vent = M a,ex,supplyduct × × X CO2 ,ex,supplyduct
MM a
and internal generated gains) are summed (Eq. (1)), in order
MM CO2
to compute the energy storage inside the indoor environment − M a,su,returnduct × × X CO2 ,in (6)
(Eqs. (2) and (3)). This energy storage is computed by the MM a
dM
= M w,vent + M w,inf + M w,in (12)
dτ w,in
τ2 dM
ΔM w,in = ∫ dτ (13)
τ1 dτ w,in
Fig. 3 Massive wall two-port network
ΔM w,in = Cw,in × ( win − win,1 ) (14)
of these projections factors are pre-computed all along the The solar radiation incident to each window is computed
year as function of the incidence angles (for the latitude in the same way as for massive walls.
considered) and are provided as inputs for the model. In the case of an “adiabatic wall” (floor, ceiling or party
So, the massive wall heat balance is governed by the walls; Fig. 2), the two-port network can be reduced to a
following equations: simple branch composed of one resistance and one capacity.
The same method is applied to compute solar heat gains
*
tout − tc,wall reaching these walls.
Qout = (23)
Rout Each light wall (as, for example, a window) is modelled
with only one resistance, connected, on one side, to the
t −t indoor temperature node and, on the other side, to a node
Qin = c,wall surf,in (24) of corrected outdoor temperature, taking into account of
Rin − Rsurf,in
sky radiation effect.
dU
= Q in + Q out (25) 3.2.3 Sensible heat gains
dτ wall
Except for the solar radiation transmitted through the
τ2 dU windows which is “injected” to the indoor surfaces, all
ΔU wall = ∫ dτ (26)
τ1 dτ wall sensible heat gains are injected to the indoor node (Fig. 2)
through the sensible heat balance of Eq. (8). They include
ΔU wall = Cwall × (tc,wall − tc,wall,1 ) (27) three contributions:
sensible heat generated by electrical devices (lighting
The indoor surface temperature is computed by means and appliances);
of a supplemental heat balance, taking into account the sensible heat generated by occupants (function of the
short wave solar radiation entering the zone through windows metabolic rate);
and reaching the indoor surface of the wall (Fig. 5). sensible heat generated or absorbed by heating or cooling
terminal units.
t −t
Qsurf,in = surf,in a,in (28) This give:
Rsurf,in
Q s,in = Q s,occ + Wlight + Wappl + Q s,heating − Q s,cooling (32)
Q in + Q r,wall = Q surf,in (29)
where Q s,heating and Q s,cooling are output variables of the
To calculate this radiant heat flow, a simplified hypothesis terminal units models.
is made: short wave solar heat gains are supposed to be
3.2.4 Ventilation, infiltration, and exfiltration sensible
distributed all over the indoor surfaces proportionally to
enthalpy flow rates
their respective areas (Eq. (30)).
The air leaving the zone (through ventilation exhaust and/or
A
Q r,wall = wall × Q sun,windows (30) through exfiltration) is supposed to be at indoor temperature
Awall,tot (due to a perfect “mixing” inside the zone). Ventilation air
temperature is given as an output of the HVAC system
where Q sun,windows is computed as follow:
model, while infiltrated air is at outdoor temperature.
Qsun,windows = SFwindows × Awindows × I sun,windows (31) Supply and exhaust state variables are used to define the
CO2 (Eq. (2)), sensible enthalpy (Eq. (33)) and water (Eq. (16))
flow rates carried by the ventilation and infiltration/
exfiltration:
3.2.5 Validation
Fig. 5 Injection of short wave radiation at indoor surface node of
the walls The thermal aspects of this simple dynamic building zone
240 Build Simul (2008) 1: 234 – 250
model have been validated (Bertagnolio et al. 2008) through 3.3.1 Air handling unit
analytical tests, empirical tests and through BESTEST
The AHU considered may include a return fan, a return
comparative procedure (Judkoff and Neymark 1995).
filter, a recovery system, a supply filter, a preheating coil,
an adiabatic humidifier, a cooling coil, a post heating coil,
3.3 HVAC system model a main fan, and a steam humidifier (Fig. 6). Of course,
these components are usually not included all together (for
The building zone model presented above can be easily
example, both adiabatic and steam humidifiers don’t have
connected to a complete “typical” HVAC system model,
to be selected at same time).
including, for example, a constant air volume (CAV), air
In Benchmark, the CAV AHU is supposed to provide a
handing unit (AHU), some local heating and/or cooling
constant hygienic flow rate to the zone and to ensure
terminal units (TUs) and a heating and cooling plant.
humidity control (by humidification and/or dehumidification).
The system model actually available includes most of
Temperature control is then ensured by terminal units, as
the classical HVAC components currently used (fans, air-
described hereinafter.
to-air static recovery systems, coils, fan coils, pumps…).
Considering that the building model is a mono-zone a) Fans
model, most of components (AHUs, TUs, pumps…) are The different pressure drops of the components are taken
aggregated into “global” components. The different locations into account to compute the fans consumptions and the
of the terminal units and of the air diffusers are not yet corresponding air heating-up.
considered. The equations related to the return (or extraction) fan
Two different modelling levels are distinguished for the give, for instance:
HVAC system (André et al. 2006b; Lebrun et al. 2006a):
ΔP
so-called “mother” (“first principle”, or “mechanistic”) Wreturnfan = Vreturnfan × returnfan (35)
models, containing all the (present) understanding of ε s,returnfan
the physical phenomena, are used as references; where,
so-called “daughter” (“simplified” and very often
polynomial) model, generated with the help of the ΔPreturnfan = ΔPreturnduct + ΔPreturnfilter
previous ones, are preferred to simulate large system on + ΔPreturneconomizer + ΔPreturnrecovery (36)
long time periods.
and,
“Mother” models are preferred in some other domains of
use, as, for instance, to support experimental work (design Wreturnfan
ta,ex,returnfan = ta,su,returnfan + (37)
of the experiment and analysis of experimental results) or C a,returnfan
to characterize some specific equipment. “Daughter” models
only are used in Benchmark. Similar equations are used to model the main supply fan.
b) Heating coils The coil contact effectiveness is defined by the Eq. (44).
Heating coils are simulated by using a simplified ε – NTU
model. In the classical ε – NTU model, the sim- ultaneous
ε c,coil,wet = 1 − exp(− NTU c,coil,wet ) (44)
calculations of air and water evolutions would consume
with
more computational time. The simplification proposed
here consists in not taking into account what happens on 1
NTU c,coil,wet = (45)
the water side; the heating coil is characterized by its Ra,coil × C a,coil
air-side effectiveness only. When the control valve is fully
open and for a constant air flow rate, the air-side This means that (as Ra and C a ) the contact effectiveness is
effectiveness is expressed as: only depending on the air flow rate. The exhaust air
humidity is determined by Eq. (46).
C min
ε a,heatingcoil = ε heatingcoil × (38) wex,coil = wsu,coil − MAX(0, ε c,coil × ( wsu,coil − wc,coil,wet )) (46)
C a
For a constant air flow rate, the maximal air exhaust Once the exhaust air temperature and humidity are
temperature ta,ex,heatingcoil,max is supposed to be reached when known, the sensible and latent heat outputs of the coil can
the valve is fully open: be calculated.
The minimal value of the contact temperature
ta,ex,heatingcoil,max = ta,su,heatingcoil + ε a,heatingcoil (corresponding to the full opening of the control valve)
× (tw,su,heatingcoil − ta,su,heatingcoil ) (39) must be determined as a function of both supply
temperatures: the temperature of the refrigerant and the
The control variable is then used to compute the required (dry bulb or wet bulb) temperature of the air (according to
exhaust temperature ta,ex,heatingcoil: the regime: dry or wet):
ta,ex,heatingcoil = ta,su,heatingcoil + X heatingcoil ε a,coil,dry
tc,coil,min,dry = ta,su,coil − × (ta,su,coil − tr,su,coil ) (47)
× (ta,ex,heatingcoil,max − ta,su,heatingcoil ) (40) ε c,coil
c) Cooling coil
Lemort et al. (2008) have used the same approach to build C min,coil,wet
ε a,coil,wet = ε coil,wet × (50)
a simplified cooling coil model. They propose to do as if C a,f
The coil is supposed to work in dry regime, if the dew is defined as a percentage of the nominal heating/cooling
point temperature at cooling coil supply is lower than the power. The main outputs of this model are the heating/cooling
minimum contact temperature. If not, it is supposed to be power actually delivered and the related fan consumption.
in wet regime: In heating mode, for example, the heating power delivered
by the fan coil is defined as follow:
If tdp,su,coil < tc,coil,min,wet , tc,coil,min = tc,coil,min,dry
Q heating,FCU = X heating,FCU × K heating,FCU
If tdp,su,coil > tc,coil,min,wet , tc,coil,min = tc,coil,min,wet
× (tw,su,heating,FCU − ta,in ) (58)
Lemort et al. (2008) have shown that the agreement
between results of both reference and simplified models is where Kheating,FCU is the equivalent heat transfer coefficient
very good. A comparative test between the reference of the fan coil unit:
and the simplified models proofs that the simplified model
K heating,FCU = ε × C min (59)
can be used without any significant loss of accuracy on
the cooling load calculation. Moreover the calculation This term is defined for the nominal water flow rate (valve
time dramatically reduced and no numerical instability is
fully open) and for the fan rotation speed considered
encountered.
(usually selected by the occupant). Xheating,FCU is the control
d) Humidifiers variable (this control is supposed to consist in a tuning of
Both adiabatic and steam humidification are modelled in the water flow rate).
the present simulation tool. The cooling power is defined in the same way. Possible
Adiabatic humidification is supposed to be controlled water condensation inside the fan coil is not yet taken into
by means of the preheating coil and is modelled by the account in Benchmark, but it could be easily included by
following equations: using a model similar to the one used for the cooling coil
of the air handling unit.
wex,adiabhum = wsu,adiabhum + ε adiabhum
× ( ws,twb,adiabhum − wsu,adiabhum ) (53) 3.3.3 Hot and cold water distributions
The primary water pump consumption is defined as follows: Applying the same methodology to the same boiler for
different values of water supply temperature (e.g., from
ΔPw,hotwaterdistr 50℃ to 80℃), and using reduced variables, the following
Wsh,hotwaterpump = M w,hotwaterdistr,n × (63)
ρ w × ε s,sh,hotwaterpump correlation is established (Eq. (67)).
Wsh,hotwaterpump Q u
Whotwaterpump = (64) qu,red = (65)
ηhotwaterpump Q u,n,on
Q cd
HLF = (71)
Qcd,max
Wel Of course, it may occur that this set point stay below the
ELF = (73)
minimal temperature achievable, in such case, the chiller
Wel,max
is running in full load.
Simple polynomial laws can also be used to correlate
3.3.6 HVAC system control
electrical and cooling load factors to each other (Fig. 10).
A better, but still very simple, approach consists in using When having to deal with a complex system simulation, a
the evaporation and condensation temperatures (in place good engineer approach consists in starting with idealistic
of the secondary fluid temperatures) in the two first hypotheses and going progressively to more realism,
polynomial laws (which then concern the compressor and according to what is looked for. Ideal control allows using
the refrigeration cycle only). Separate semi-isothermal simpler simulation models, gives easier access to benchmarks
heat exchanger models can then be used to deal with the and indicates clearly the maximal performances that could
evaporator and with the condenser. The definitions of the be reached.
part load factors stay the same as for the first model. This A simple proportional control laws is used for each
is the approach preferred in Benchmark. component, with a non dimensional control variable Xcontrol,
In ideal control conditions, the simulation will determine varying between 0 and 1 in proportion of the difference
the chilled water supply temperatures “required” by both observed between the set point and the controlled variable:
air handling and terminal units. These temperatures will be
X control = MIN (1, MAX ( 0, Ccontrol × (tsetpoint − t )))
generated by the (real or fictitious) proportional controls of
both units. The minimum between these two temperatures The control “gain”, Ccontrol, is arbitrarily fixed as a realistic
will become the set point of the chiller control. compromise between accuracy and robustness.
4 Example of use
Fig. 18 Measured and computed fuel consumptions (first run) Fig. 20 Measured and computed fuel consumptions (after
calibration)
References
Lebrun J (1978). Etudes expérimentales des regimes transitoires en Lebrun J, André P, Hannay J, Aparecida Silva C (2006b). Example
chambres climatiques. Ajustement des méthodes de calcul. of audit of an air conditioning system. In: Proceedings of the
Journées Bilan et Perspectives Génie Civil, INSA Lyon, France. Klimaforum Conference, Godovic, Slovenia.
(in French) Lemort V, Cuevas C, Lebrun J, Teodorese I (2008). Development of
Lebrun J, Liebecq G (1988). International Energy Agency — Energy simple cooling coil models for simulation of HVAC systems.
Conservation in Buildings and Community Systems Annex 10: ASHRAE Transactions, 114(1)
Building HVAC System Simulation. Synthesis Report. Masy G (2006). Dynamic simulation on simplified building models
Lebrun J, Ding X, Eppe J-P, Wasacz M (1990). Cooling coil models and interaction with heating systems. In: Proceedings of the 7th
to be used in transient and/or wet regimes. Theoretical analysis International Conference on System Simulation in Buildings,
and experimental validation. In: Proceedings of the 3rd Liège, Belgium.
International Conference on System Simulation in Buildings, Visier J C, Jandon M (2004). International Energy Agency— Energy
Liège, Belgium. Conservation in Buildings and Community Systems Annex 40:
Lebrun J, Wang S (1993). International Energy Agency — Energy Commissioning of Building HVAC Systems for Improved
Conservation in Buildings and Community Systems Annex 17: Energy Performances. Synthesis Report.
Building Energy Management Systems — Evaluation and Woloszyn M (1999). Moisture — Energy — Airflow modelling of
Emulation Techniques. Synthesis Report. multizone buildings. PhD Dissertation, CETHIL Laboratory,
Lebrun J, André P, Aparecida Silva C, Hannay J, Lemort V, INSA Lyon, France.
Teodorese V (2006a). Simulation of HVAC systems: Development
and validation of simulation models and examples of practical
applications. In: Proceedings of the Mercofrio 2006 Conference,
Porto Alegre, Brazil.