You are on page 1of 17

Build Simul (2008) 1: 234 – 250

DOI 10.1007/s12273-008-8219-4
RESEARCH ARTICLE

Simulation of a Building and Its HVAC System with an Equation Solver:


Application to Benchmarking

Stéphane Bertagnolio( ), Jean Lebrun

Thermodynamics Laboratory, University of Liège, Campus du Sart-Tilman, Bâtiment B49 (P33), B-4000 Liege, Belgium

Received: 16 May 2008 / Revised: 7 July 2008 / Accepted: 9 July 2008


© Tsinghua Press and Springer-Verlag 2008

Abstract The today-availability of powerful engineering equation solvers is opening very new
possibilities in technical component modelling and in system simulation. The simulation models, the
“user guide” and the “reference guide” are all included in a same file. Reliable “reference” and
“simplified” models are currently available for the building zone and for most (heating, ventilation
and air-conditioning) HVAC components. Focus is given here on “simplified” models and on a
simulation tool, called “Benchmark”. This tool should help an auditor to make the best use of the
limited information usually available about actual fuel and electricity consumptions and to get a very
first evaluation of the actual performances of a given HVAC system. An example of such use is
presented. Another simulation tools and more information about the modelling of HVAC components
will be presented in a further paper.

Keywords building modelling, HVAC system modelling, building energy audit, benchmarking

List of symbols

albedo albedo SF solar factor


A wall area (m2) t temperature (℃)
C thermal capacity (J/K) U internal energy (J)
CO2 or water capacity (kg) V volume (m3)
CLF cooling load factor V volumetric flow rate (m³/s)
w humidity ratio (kg/kg)
cp specific heat (J/(kg·K))
W electrical power (W)
ELF electrical load factor
X volumetric concentration, or control variable
F correction or increase factor α solar absorbance
h combined convective − radiative heat transfer ε effectiveness
coefficient (W/(m2·K)) η efficiency
HLF heating load factor ρ density (kg/m3)
H enthalpy flow rate (W) τ time (s)
I solar radiation (W/m2)
M mass (kg) Subscripts
MM molar mass (g/mol) 1 initial value
nocc number of occupants a air
ΔP pressure drop (Pa) appl appliance
q heat flux or power (W) c consumed
Q thermal power (W) cd condenser
R thermal resistance (K/W) CO2 carbon dioxide
E-mail: stephane.bertagnolio@ulg.ac.be
dp dew point
Build Simul (2008) 1: 234 – 250 235

el electricity may help a lot in the commissioning process, among others


ev evaporator for functional performance testing (Visier and Jandon
ex exhaust 2004). These detailed models may also help a lot in the daily
exfiltr exfiltration system management, among others for fault detection and
f fictitious diagnosis (Jagpal 2006). More global (and simplified)
FCU fan coil unit simulation can be used in real time to “emulate” building
in indoor energy management systems (Lebrun and Wang 1993). New
inf infiltration simulation capabilities are also appearing today in the
n nominal domain of energy audit (AuditAC 2007; Harmonac 2008).
occ occupant In this paper, special attention is paid to this last use of
out outdoor building energy simulation tools.
r refrigerant
red reduced 2 Use of simulation tools for energy auditing
s sensible
sh shaft Audit is required, among others, to identify the most efficient
su supply and cost-effective Energy Conservation Opportunities (ECOs),
surf surface consisting in more efficient use or in (partial or global)
tot total replacement of the existing components.
twb wet bulb temperature Four audit stages are generally distinguished (André et
TU terminal unit al. 2006a):
u useful (1) The “benchmarking” helps in deciding if it is necessary
vent ventilation to launch a complete audit procedure; it’s based mainly on
w water energy bills and basic calculations. A direct use of such
wb wet bulb global data would not allow the auditor to identify “good”,
“average”, and “bad” energy performances. The experimental
1 Introduction identification of HVAC consumptions is often almost
impossible: these consumptions are, most of the time, not
Early developments of simulation tools were mostly oriented directly measured, but “mixed” with other ones (lighting,
towards supporting system design, i.e., mainly the selection appliances etc.). Simulation is then of great help to define
and sizing of (heating, ventilation and air-conditioning) some, even very provisory, reference performances (or
HVAC components (Lebrun and Liebecq 1988). The “benchmarks”), in view of a first qualification of the
usefulness of simulation tools in further stages of the current building performances.
building life cycle appeared later, among others with the Without simulation, some arbitrary normalization had
apparition of friendly engineering equation solvers and of been required before any comparison of the recorded data
reliable simulation models. Energy simulation may help on the studied installation with reference values deduced
all along the building life cycle, from early design until last from case studies or from statistics.
audit and retrofit actions. Building and HVAC simulation (2) The aim of the “pre-audit” (also called “walk-through
models should therefore be continuously available, but in audit” or “inspection”) is to identify the main defects and
different forms, according to what is expected from the “energy conservation opportunities” (ECOs). Its results are
simulation and according to the information actually supposed to orient the future “detailed” audit. The inspection
available. consists in a visual verification of HVAC equipment, in an
Today, the simulation bottleneck is no more the computer, analysis of operating data records and in a systematic
but the understanding of the user. Simulation models have disaggregation of recorded energy consumptions. Thanks
therefore to be designed in such a way to make easier this to parametric tuning, the building-HVAC simulation model
understanding. can be fitted on the records actually available (very often
Hopefully the equation solvers presently available (Klein no more than monthly fuel and electricity bills) in such a
2008) open the way to the development of fully transparent way to become a “baseline” simulation model, allowing
and fully adaptable simulation models, with all equations the auditor to identify the main energy consumers (lighting,
written as in a text book. This means that a simulation appliances, fans, pumps, chiller …) and to analyse the
program, its user guide, and its reference guide can be actual performance of the building.
combined into only one file, fully readable and directly (3) The “detailed” audit consists in a detailed and
executable. comparative evaluation of the ECOs previously selected.
Reference and detailed models of HVAC components At this step even more, simulation is the key tool.
236 Build Simul (2008) 1: 234 – 250

(4) The “investment grade” audit concerns the detailed


technical and economical engineering studies, justifying
the costs of the retrofits.
This fourth audit stage brings the system (building +
HVAC) to a new life cycle: new design, call for tenders,
submissions, evaluations, installations, commissioning, etc.
Several simulation tools are being developed in the
frame of the HARMONAC project (2008). Focus is given,
in the present paper, to a first one, called “Benchmark”. This
tool is used to compute the “theoretical” (or “reference”)
consumptions of the building, supposed to be equipped
with a “typical” HVAC system, including air quality,
temperature, and humidity control. The building is seen as Fig. 1 Model block diagram
a unique zone, described by a very limited number of
parameters. This first simulation tool should help the auditor
model: transient heat transfer through walls, energy storage
in getting, a very first impression about the performances
in slabs, internal generated gains, solar gains through
of the system considered. Other simulations tools will be
windows, infrared losses and, of course, ventilation and
described in further papers.
heating/cooling devices, are actually taken into account.
3 Modelling
3.1 Inputs, outputs and parameters
For benchmarking, as for further audit actions, the simulation
The outputs, inputs, and parameters must be selected
tool must handle with realism:
according to the specific needs of the user. As in some other
building (static and dynamic) behaviour,
softwares, as TRNSYS for instance (Klein et al. 2004), the
weather and occupancy loads,
parameters are here defined as selected inputs which are
comfort requirements and control strategies (air quality,
air temperature, and humidity), not supposed to vary during the simulation.
full air conditioning process and characteristics of all The main outputs of the tool presented here are
HVAC system components (terminal units, air handling air quality and hygro-thermal comfort achievements:
units, air and water distribution, plants). CO2 contamination, temperature, humidity, predicted
The level of detail required for the calculation of heating/ percentage of dissatisfied (PPD), and predicted mean
cooling demands can vary a lot from case to case: vote (PMV);
For heating calculations, the major issues are a correct global power and energy consumptions: fuel and
description of the building envelope and an accurate electricity consumptions;
evaluation of air renewal. HVAC components specific demands;
For cooling calculations, the fenestration area and
performances of the mechanical equipments: coefficient
orientation, the intensity and distribution of internal
of performance (COP), efficiencies …
gains, the ventilation rates, and the geographical location
appear as critical issues. The main inputs are
At benchmarking stage mainly, the simulation tools have weather data: hourly values of temperature, humidity,
also to be usable with a limited quantity of information global, and diffuse radiations;
only, depending on data actually available. These tools must nominal occupancy loads (in W/m2), occupancy and
be easy-to-use, transparent, reliable, sufficiently accurate, installation functioning rates;
and robust. comfort requirements: air renewal, temperature and
The simulation tool presented hereinafter includes models humidity set points;
of both the building and the HVAC equipment. These models control strategies: feedback on indoor temperature and
are submitted to different loads and interact at each time relative humidity, feedforward on occupancy schedules
step with a control module (Fig. 1). and calendar.
The main phenomena involved in building dynamics are
considered in order to compute realistic heating and cooling The main parameters are
demands. Indeed, the indoor conditions of the zone come dimensions, orientation and general characteristics of the
from the equilibrium established among many different building envelope (e.g., “heavy”, “medium”, or “light”
influences. A compromise is made between the number of thermal mass and walls U values);
influences taken into account and the simplicity of the sizing factors of the main HVAC components.
Build Simul (2008) 1: 234 – 250 237

The main parameters described above are entered through means of a first order differential equation. A correction
the control panels. The other parameters of the model, as factor (Fa,in, Eq. (4)) has to be applied to the air capacity in
HVAC system characteristics, nominal performances and order to take into account the effect of the vertical air
capacities are automatically computed through a pre-sizing temperature gradient in the zone (Lebrun 1978; Laret 1980).
calculation, or defined on the basis of default values, given
dU
in European standards prEN 13053 (2003) and PrEN = Q roof,surf,in + Q floor,surf,in + Q opaque,frontages,surf,in
13773 (2007). Other information as weather data and dτ in
occupancy rate are provided in “lookup tables”. + Q windows + H s,vent + H s,inf + Q s,in (1)

τ2 dU
3.2 Building modelling ΔU in = ∫ dτ (2)
τ1 dτ in
3.2.1 Indoor conditions ΔU in = Cin × (ta,in − ta,in,1 ) (3)
The indoor conditions (CO2 contamination, global
temperature, and humidity) are computed by means of Cin = Fa,in × Vin × ρ a × cp,a (4)
three different mass and energy balances. Indoor comfort
b) CO2 balance
indexes (PMV and PPD) are evaluated at each time step
A first mass balance is used to compute the CO2
through classical Fanger’s equations (1970).
concentration in the indoor environment (Eqs. (5) − (11)).
a) Sensible heat balance The CO2 flow rate entering the zone is due to two main
A sensible heat balance is made on the indoor node to contributions (Eq. (5)):
compute the combined convective − radiative indoor CO2 brought by ventilation (Eq. (6)), positive infiltration
temperature. and negative exfiltration air flow rates (Eq. (7));
A mono-zone building model is used here. It’s based on CO2 produced by the occupants (function of the occupant
a simplified equivalent RC network including five thermal metabolic rate, Eq. (8)).
masses (Fig. 2; Masy 2006), corresponding to a large Treated ventilation air CO2 concentration is given as an
occupancy zone, surrounded by external glazed and opaque output of the HVAC system model, while, for infiltration,
walls. This scheme corresponds to a typical office building, it corresponds to outdoor air input data.
mainly composed of lattice structure and slabs. dM
The heat flow emitted by the surfaces of the walls (roof, = M CO2 ,vent + M CO2 ,inf + M CO2 ,in (5)
dτ CO2 ,in
floor, opaque frontages, and windows), the enthalpy flow
rate corresponding to ventilation and infiltration air and MM CO2
the internal sensible gains (including local heating/cooling
M CO2 ,vent = M a,ex,supplyduct × × X CO2 ,ex,supplyduct
MM a
and internal generated gains) are summed (Eq. (1)), in order
MM CO2
to compute the energy storage inside the indoor environment − M a,su,returnduct × × X CO2 ,in (6)
(Eqs. (2) and (3)). This energy storage is computed by the MM a

Fig. 2 Dynamic building model equivalent RC network


238 Build Simul (2008) 1: 234 – 250

MM CO2 3.2.2 Walls thermal models


M CO2 ,inf = M a,inf × × X CO2 ,out
MM a A 2RC 1st order “two-port networks” model (Fig. 3) is
MM CO2 associated to each massive wall (Laret 1980). The wall
− M a,exfiltr × × X CO2 ,in (7) network (Fig. 2) corresponds either to imposed temperature
MM a
boundary conditions (for “external” massive walls in contact
with outdoor conditions) or to null heat flow boundary
M CO2 ,in = M CO2 ,occ = nocc × M CO2 ,peroccupant (8)
conditions (for ceiling and floor slabs separating two heated
zones characterized by similar temperature profiles). The
τ2 dM
ΔM CO2 ,in = ∫ dτ (9) parameters of each “two-port network” are tuned through
τ1 dτ CO2 ,in a frequency analysis based on the computation of the zone
MM CO2 admittance matrix (Masy 2006).
CCO2 ,in = M a,in × (10) In the case of an “isothermal wall” (massive opaque
MM a frontage or roof slab), the absorbed solar radiation is
injected on the outdoor surface node (Fig. 4).
ΔM CO2 ,in = CCO2 ,in × ( X CO2 ,in − X CO2 ,in,1 ) (11)
A correction heat flow (Bliss 1961) varying from 45 to
100W/m2, is also used to take into account that the sky
The “CO2 capacity” introduced in Eq. (10) is here supposed
temperature is below the outdoor air temperature. These
to correspond to the mass of the air contained in the zone.
two effects (solar and sky radiations) are included in the
A correction factor might be also introduced in order to *
corrected outdoor (“sol-air”) temperature tout (Eq. (19)).
take into account of CO2 absorption in the building
materials (walls and furniture). *
tout = tout + (Q sun − Q sky ) × Rsurf,out (19)
c) Water balance
Solar radiation absorbed by the wall is computed as follow:
A second mass balance is made to compute the water
content of the indoor air. The water flow rate entering the Qsun = α wall × Awall × I sun,wall (20)
zone is due to three main contributions (Eq. (12)):
water brought by ventilation, positive infiltration and 1 1
negative exfiltration air flow rates (Eqs. (16) and (17)); I sun,wall = I beam,wall + × I glob × albedo + × I diff (21)
2 2
water produced by the occupants or local humidification
devices (Eq. (18)); where,
water condensed by local cooling devices (Eq. (18)).
I beam,wall = ( I glob − I diff ) × Fwall (22)
Water exchanges between air and walls or materials are
roughly estimated in the present software. A correction
Fwall is the weighted average of the projection factors of all
factor (Fw,in) is here also applied to the air capacity; it’s
opaque walls facing different orientations. The hourly values
supposed to take into account of the effect of hygroscopic
materials contained in the zone (Woloszyn 1999).

dM
= M w,vent + M w,inf + M w,in (12)
dτ w,in

τ2 dM
ΔM w,in = ∫ dτ (13)
τ1 dτ w,in
Fig. 3 Massive wall two-port network
ΔM w,in = Cw,in × ( win − win,1 ) (14)

Cw,in = Fw,in × Vin × ρa (15)

M w,vent = M a,ex,supplyduct × wex,supplyduct − M a,su,returnduct × win (16)

M w,inf = M a,inf × wout − M a,exfiltr × win (17)

M w,in = M w,occ + M w,heatingTU − M w,coolingTU (18) Fig. 4 Corrected outdoor temperature


Build Simul (2008) 1: 234 – 250 239

of these projections factors are pre-computed all along the The solar radiation incident to each window is computed
year as function of the incidence angles (for the latitude in the same way as for massive walls.
considered) and are provided as inputs for the model. In the case of an “adiabatic wall” (floor, ceiling or party
So, the massive wall heat balance is governed by the walls; Fig. 2), the two-port network can be reduced to a
following equations: simple branch composed of one resistance and one capacity.
The same method is applied to compute solar heat gains

*
tout − tc,wall reaching these walls.
Qout = (23)
Rout Each light wall (as, for example, a window) is modelled
with only one resistance, connected, on one side, to the
t −t indoor temperature node and, on the other side, to a node
Qin = c,wall surf,in (24) of corrected outdoor temperature, taking into account of
Rin − Rsurf,in
sky radiation effect.
dU
= Q in + Q out (25) 3.2.3 Sensible heat gains
dτ wall
Except for the solar radiation transmitted through the
τ2 dU windows which is “injected” to the indoor surfaces, all
ΔU wall = ∫ dτ (26)
τ1 dτ wall sensible heat gains are injected to the indoor node (Fig. 2)
through the sensible heat balance of Eq. (8). They include
ΔU wall = Cwall × (tc,wall − tc,wall,1 ) (27) three contributions:
sensible heat generated by electrical devices (lighting
The indoor surface temperature is computed by means and appliances);
of a supplemental heat balance, taking into account the sensible heat generated by occupants (function of the
short wave solar radiation entering the zone through windows metabolic rate);
and reaching the indoor surface of the wall (Fig. 5). sensible heat generated or absorbed by heating or cooling
terminal units.
t −t
Qsurf,in = surf,in a,in (28) This give:
Rsurf,in
Q s,in = Q s,occ + Wlight + Wappl + Q s,heating − Q s,cooling (32)
Q in + Q r,wall = Q surf,in (29)
where Q s,heating and Q s,cooling are output variables of the
To calculate this radiant heat flow, a simplified hypothesis terminal units models.
is made: short wave solar heat gains are supposed to be
3.2.4 Ventilation, infiltration, and exfiltration sensible
distributed all over the indoor surfaces proportionally to
enthalpy flow rates
their respective areas (Eq. (30)).
The air leaving the zone (through ventilation exhaust and/or
A
Q r,wall = wall × Q sun,windows (30) through exfiltration) is supposed to be at indoor temperature
Awall,tot (due to a perfect “mixing” inside the zone). Ventilation air
temperature is given as an output of the HVAC system
where Q sun,windows is computed as follow:
model, while infiltrated air is at outdoor temperature.
Qsun,windows = SFwindows × Awindows × I sun,windows (31) Supply and exhaust state variables are used to define the
CO2 (Eq. (2)), sensible enthalpy (Eq. (33)) and water (Eq. (16))
flow rates carried by the ventilation and infiltration/
exfiltration:

H s,vent = M a,ex,supplyduct × cp,a × ta,ex,supplyduct


− M a,su,returnduct × cp,a × ta,in (33)

H s,inf = M a,inf × cp,a × tout − M a,exfiltr × cp,a × ta,in (34)

3.2.5 Validation
Fig. 5 Injection of short wave radiation at indoor surface node of
the walls The thermal aspects of this simple dynamic building zone
240 Build Simul (2008) 1: 234 – 250

model have been validated (Bertagnolio et al. 2008) through 3.3.1 Air handling unit
analytical tests, empirical tests and through BESTEST
The AHU considered may include a return fan, a return
comparative procedure (Judkoff and Neymark 1995).
filter, a recovery system, a supply filter, a preheating coil,
an adiabatic humidifier, a cooling coil, a post heating coil,
3.3 HVAC system model a main fan, and a steam humidifier (Fig. 6). Of course,
these components are usually not included all together (for
The building zone model presented above can be easily
example, both adiabatic and steam humidifiers don’t have
connected to a complete “typical” HVAC system model,
to be selected at same time).
including, for example, a constant air volume (CAV), air
In Benchmark, the CAV AHU is supposed to provide a
handing unit (AHU), some local heating and/or cooling
constant hygienic flow rate to the zone and to ensure
terminal units (TUs) and a heating and cooling plant.
humidity control (by humidification and/or dehumidification).
The system model actually available includes most of
Temperature control is then ensured by terminal units, as
the classical HVAC components currently used (fans, air-
described hereinafter.
to-air static recovery systems, coils, fan coils, pumps…).
Considering that the building model is a mono-zone a) Fans
model, most of components (AHUs, TUs, pumps…) are The different pressure drops of the components are taken
aggregated into “global” components. The different locations into account to compute the fans consumptions and the
of the terminal units and of the air diffusers are not yet corresponding air heating-up.
considered. The equations related to the return (or extraction) fan
Two different modelling levels are distinguished for the give, for instance:
HVAC system (André et al. 2006b; Lebrun et al. 2006a):
ΔP
so-called “mother” (“first principle”, or “mechanistic”) Wreturnfan = Vreturnfan × returnfan (35)
models, containing all the (present) understanding of ε s,returnfan
the physical phenomena, are used as references; where,
so-called “daughter” (“simplified” and very often
polynomial) model, generated with the help of the ΔPreturnfan = ΔPreturnduct + ΔPreturnfilter
previous ones, are preferred to simulate large system on + ΔPreturneconomizer + ΔPreturnrecovery (36)
long time periods.
and,
“Mother” models are preferred in some other domains of
use, as, for instance, to support experimental work (design Wreturnfan
ta,ex,returnfan = ta,su,returnfan + (37)
of the experiment and analysis of experimental results) or C a,returnfan
to characterize some specific equipment. “Daughter” models
only are used in Benchmark. Similar equations are used to model the main supply fan.

Fig. 6 Double flux air handling unit


Build Simul (2008) 1: 234 – 250 241

b) Heating coils The coil contact effectiveness is defined by the Eq. (44).
Heating coils are simulated by using a simplified ε – NTU
model. In the classical ε – NTU model, the sim- ultaneous
ε c,coil,wet = 1 − exp(− NTU c,coil,wet ) (44)
calculations of air and water evolutions would consume
with
more computational time. The simplification proposed
here consists in not taking into account what happens on 1
NTU c,coil,wet = (45)
the water side; the heating coil is characterized by its Ra,coil × C a,coil
air-side effectiveness only. When the control valve is fully
open and for a constant air flow rate, the air-side This means that (as Ra and C a ) the contact effectiveness is
effectiveness is expressed as: only depending on the air flow rate. The exhaust air
humidity is determined by Eq. (46).
C min
ε a,heatingcoil = ε heatingcoil × (38) wex,coil = wsu,coil − MAX(0, ε c,coil × ( wsu,coil − wc,coil,wet )) (46)
C a

For a constant air flow rate, the maximal air exhaust Once the exhaust air temperature and humidity are
temperature ta,ex,heatingcoil,max is supposed to be reached when known, the sensible and latent heat outputs of the coil can
the valve is fully open: be calculated.
The minimal value of the contact temperature
ta,ex,heatingcoil,max = ta,su,heatingcoil + ε a,heatingcoil (corresponding to the full opening of the control valve)
× (tw,su,heatingcoil − ta,su,heatingcoil ) (39) must be determined as a function of both supply
temperatures: the temperature of the refrigerant and the
The control variable is then used to compute the required (dry bulb or wet bulb) temperature of the air (according to
exhaust temperature ta,ex,heatingcoil: the regime: dry or wet):
ta,ex,heatingcoil = ta,su,heatingcoil + X heatingcoil ε a,coil,dry
tc,coil,min,dry = ta,su,coil − × (ta,su,coil − tr,su,coil ) (47)
× (ta,ex,heatingcoil,max − ta,su,heatingcoil ) (40) ε c,coil

where X is the control variable (cf. Section 3.3.6). ε a,coil,wet


tc,coil,min,wet = twb,su,coil − × (twb,su,coil − tr,su,coil ) (48)
The heating power actually provided by the coil is then ε c,coil
computed:
In these equations, εa,coil,dry and εa,coil,wet are the “air-side”
Q heatingcoil = C a,heatingcoil × (ta,ex,heatingcoil − ta,su,heatingcoil ) (41) effectiveness’s, defined in dry and wet regimes respectively.
In each regime, the “air side” effectiveness is related to
This simplification allows to avoid the computation of the actual coil effectiveness:
the thermal exchange on water side. Only the characteristics
of the coil in nominal regime are required to compute the C min,coil,dry
air-side effectiveness. ε a,coil,dry = ε coil,dry × (49)
C a,dry

c) Cooling coil
Lemort et al. (2008) have used the same approach to build C min,coil,wet
ε a,coil,wet = ε coil,wet × (50)
a simplified cooling coil model. They propose to do as if C a,f

the cooling coil exhaust air temperature was controlled by


with,
its contact temperature (in place of the refrigerant flow
rate). This control is described by Eq. (42). C a,f = M a,coil × cp,a,f,coil (51)
The exhaust air temperature is first compared to its set
point. The control variable (comprised between 0 and 1) is The fictitious specific heat, cp,a,f is defined by Eq. (52)
then used to adjust the contact temperature (cf. Section 3.3.6). (Lebrun et al. 1990).
tc,coil = ta,su,coil − X coil,control × (ta,su,coil − tc,coil,min ) (42) ha,su,coil − ha,ex,coil,wet
cp,a,f,coil = (52)
twb,su,coil − twb,ex,coil,wet
For given supply air temperature, contact effectiveness
and contact temperature, the exhaust air temperature can
These effectiveness’s are defined with the valve fully
be defined as follows:
open. If the air flow rate is varying, its effect has to be
ta,ex,coil = ta,su,coil − ε c,coil × (ta,su,coil − tc,coil ) (43) pre-identified with the help of the reference model.
242 Build Simul (2008) 1: 234 – 250

The coil is supposed to work in dry regime, if the dew is defined as a percentage of the nominal heating/cooling
point temperature at cooling coil supply is lower than the power. The main outputs of this model are the heating/cooling
minimum contact temperature. If not, it is supposed to be power actually delivered and the related fan consumption.
in wet regime: In heating mode, for example, the heating power delivered
by the fan coil is defined as follow:
If tdp,su,coil < tc,coil,min,wet , tc,coil,min = tc,coil,min,dry
Q heating,FCU = X heating,FCU × K heating,FCU
If tdp,su,coil > tc,coil,min,wet , tc,coil,min = tc,coil,min,wet
× (tw,su,heating,FCU − ta,in ) (58)
Lemort et al. (2008) have shown that the agreement
between results of both reference and simplified models is where Kheating,FCU is the equivalent heat transfer coefficient
very good. A comparative test between the reference of the fan coil unit:
and the simplified models proofs that the simplified model
K heating,FCU = ε × C min (59)
can be used without any significant loss of accuracy on
the cooling load calculation. Moreover the calculation This term is defined for the nominal water flow rate (valve
time dramatically reduced and no numerical instability is
fully open) and for the fan rotation speed considered
encountered.
(usually selected by the occupant). Xheating,FCU is the control
d) Humidifiers variable (this control is supposed to consist in a tuning of
Both adiabatic and steam humidification are modelled in the water flow rate).
the present simulation tool. The cooling power is defined in the same way. Possible
Adiabatic humidification is supposed to be controlled water condensation inside the fan coil is not yet taken into
by means of the preheating coil and is modelled by the account in Benchmark, but it could be easily included by
following equations: using a model similar to the one used for the cooling coil
of the air handling unit.
wex,adiabhum = wsu,adiabhum + ε adiabhum
× ( ws,twb,adiabhum − wsu,adiabhum ) (53) 3.3.3 Hot and cold water distributions

Water networks are modelled in such a way to take both


ta,ex,adiabhum = ta,su,adiabhum + ε adiabhum
pressure drops and heat exchanges into account.
× (twb,su,adiabhum − ta,su,adiabhum ) (54) In Benchmark, a first approximation consists in
characterizing each water distribution network with only
Steam humidification is modelled by means of water
one equivalent thermal efficiency.
and energy balances:
Equivalent nominal water flow rates are defined on the
M steam,su,steamhum basis of nominal heating and cooling powers and of nominal
wex,steamhum = wsu,steamhum + (55) temperature variations. For the hot water distribution, for
M a,steamhum
example,
M steam,su,steamhum
ha,ex,steamhum = wa,su,steamhum + Q heatingplant,n
M a,steamhum M w,hotwaterdistr = (60)
cp,w × Δtw,heatingplant,n
× hsteam,su,steamhum (56)
The so-defined “primary” water flow rate is kept constant
The exhaust air humidity ratio is then calculated by
in the simulation.
using the following control law :
Both heating-up through the pump and heat exchanges
wex,steamhum = wex,steamhum,0 + X steamhum × Δwsteamhum,max (57) along the distribution network are taken into account. For
hot water distribution, for example, this gives
with Xsteamhum as control variable (see hereinafter).
⎛ Wsh,hotwaterpump − Q hotwaterdistr,loss ⎞
3.3.2 Terminal units tw,ex,hotwaterdistr = t w,su,hotwaterdist + ⎜ ⎟
⎜ M w,hotwaterdistr,n × cp,w ⎟
⎝ ⎠
In Benchmark, room sensible heating and cooling are ensured
by a classical fan coil unit. (61)
In first and simple approach, this unit is characterized Q hotwaterdistr,loss = (1 − ηhotwaterdistr ) × Q heatingdemand (62)
by its heat transfer coefficient only. The fan electrical power
Build Simul (2008) 1: 234 – 250 243

The primary water pump consumption is defined as follows: Applying the same methodology to the same boiler for
different values of water supply temperature (e.g., from
ΔPw,hotwaterdistr 50℃ to 80℃), and using reduced variables, the following
Wsh,hotwaterpump = M w,hotwaterdistr,n × (63)
ρ w × ε s,sh,hotwaterpump correlation is established (Eq. (67)).

Wsh,hotwaterpump Q u
Whotwaterpump = (64) qu,red = (65)
ηhotwaterpump Q u,n,on

Similar equations are used to model the chilled water network Q c


qc,red = (66)
and its pump. Q c,n,on
3.3.4 Heat production qc,red = C0 + C1 × qu,red (67)
In the present version of Benchmark, heat is supposed to
The values of C0 and C1 can be correlated with the
be produced by a classical fuel-oil boiler with ON/OFF
water supply temperature as follows:
control.
The “daughter” boiler model used here is derived from C0 = C0,0 + C0,1 × tw,su,boiler (68)
the reference (“mother”) model developed by Bourdouxhe
et al. (1999) in the ASHRAE HVAC1 Toolkit. C1 = C1,0 + C1,1 × tw,su,boiler (69)
In the “mother” model, the boiler is represented by an
assembly of a supposed to be adiabatic combustion chamber If there is no mixing valve or if it’s fully open, the
and two (gas-water and water-environment) heat exchangers boiler water supply temperature corresponds to the heating
plant return water temperature:
(Fig. 7).
At constant water supply temperature, the fuel oil boiler Q heatingdemand
submitted to ON/OFF control has a very linear behaviour tw,return,heatingplant = tw,ex,hotwaterdistr − (70)
M w,hotwaterdistr × cp,w
as shown in Fig. 8. This suggests that a double linear
correlation can be used as simplified model. Consumed In Benchmark, the boiler is only submitted to weather
power is plotted as function of useful power and a linear control: the exhaust water temperature set point is fixed
fit is made on this curve. according to the outdoor temperature.
Of course, it may occur that this set point stay above the
maximal temperature achievable; in such case, the boiler
is running in full load.

3.3.5 Cold production

For the chiller, various simplified “daughter” models are


available (Lebrun et al. 2006a). The simplest one consists
in expressing the chiller “capacity” (full load cooling power)
Fig. 7 Boiler model components and the corresponding electrical consumption as polynomial
functions of two independent variables:
1) the temperature of the secondary fluid supplying (or
leaving) the evaporator,
2) the temperature of the secondary fluid supplying the
condenser (Fig. 9).
The part load regime can be described with the help of
heating, cooling, and electrical load factors (Eqs. (71) − (73)):

Q cd
HLF = (71)

Qcd,max

Fig. 8 Boiler consumption as function of its useful thermal power Q ev


CLF = (72)
at constant water supply temperature (ON/OFF control) 
Qev,max
244 Build Simul (2008) 1: 234 – 250

Wel Of course, it may occur that this set point stay below the
ELF = (73)
minimal temperature achievable, in such case, the chiller

Wel,max
is running in full load.
Simple polynomial laws can also be used to correlate
3.3.6 HVAC system control
electrical and cooling load factors to each other (Fig. 10).
A better, but still very simple, approach consists in using When having to deal with a complex system simulation, a
the evaporation and condensation temperatures (in place good engineer approach consists in starting with idealistic
of the secondary fluid temperatures) in the two first hypotheses and going progressively to more realism,
polynomial laws (which then concern the compressor and according to what is looked for. Ideal control allows using
the refrigeration cycle only). Separate semi-isothermal simpler simulation models, gives easier access to benchmarks
heat exchanger models can then be used to deal with the and indicates clearly the maximal performances that could
evaporator and with the condenser. The definitions of the be reached.
part load factors stay the same as for the first model. This A simple proportional control laws is used for each
is the approach preferred in Benchmark. component, with a non dimensional control variable Xcontrol,
In ideal control conditions, the simulation will determine varying between 0 and 1 in proportion of the difference
the chilled water supply temperatures “required” by both observed between the set point and the controlled variable:
air handling and terminal units. These temperatures will be
X control = MIN (1, MAX ( 0, Ccontrol × (tsetpoint − t )))
generated by the (real or fictitious) proportional controls of
both units. The minimum between these two temperatures The control “gain”, Ccontrol, is arbitrarily fixed as a realistic
will become the set point of the chiller control. compromise between accuracy and robustness.

3.4 Interface and implementation

In Benchmark, all the parameters asked to the user have to


be provided by means of control panels. A main control
panel (Fig. 11) is used to access the other ones. The “Building
description” panel (Fig. 12) is used to fix the geometry of
the building, the characteristics of the envelope, and the
internal gains (occupancy, lighting, and appliances). The
“Air handling unit” panel (Fig. 13) is used to select the
main characteristics of this subsystem (existence of a
mechanical ventilation, hygienic ventilation flow rate, type
of humidification system, water nominal temperature
regimes, and nominal fan efficiencies). The temperature
Fig. 9 Cooling capacity as function of secondary fluid temperatures and humidity set points and the control laws can be
modified in the “HVAC system control” panel (Fig. 14).

Fig. 10 Possible relationship between electrical and thermal load


factors Fig. 11 Main control panel
Build Simul (2008) 1: 234 – 250 245

Fig. 12 “Building description” control panel

Fig. 13 “Air handling unit” control panel


246 Build Simul (2008) 1: 234 – 250

Fig. 14 “HVAC system control” control panel

4 Example of use

4.1 Building description

The model presented here above is applied to an existing


medium-size office building (around 26,700 m2 of air-
conditioned floor area), erected in Brussels at the end of
the sixties (Lebrun et al. 2006b). The building is composed
of three blocks, has a “H” shape (Fig. 15) and is north-
south oriented. Eight storeys of the building include
landscaped offices and meeting rooms and are occupied by
about 1100 people, between 8 a.m. and 18 p.m.. The five
underground levels are dedicated to cars parking. The Fig. 15 Case study building (left) and envelope module (right)
frontages of the lobby are made of single-glazed windows.
The rest of building envelope is made of about 1000 Recorded monthly fuel consumptions are available from
double-glazed modules as shown in Fig. 15. The main 1975 to 2005 and monthly records of electricity consumption
characteristics of the envelope are given in Table 1. About are available from September 2004 to February 2006.
1000 four-pipe heating and cooling induction units are Classical thermal signature based on recorded data (2005)
installed in the offices. The CAV air handling units provide can be built by expressing the monthly average heating
together a total of about 190,000 m3/h of fresh air per hour, powers as function of the average outdoor temperature
75 hours per week, to the conditioned zones (from level (Fig. 16). The slope of this signature (about 42kW/K),
0 to 8). Vitiated air is rejected in the underground storeys should correspond to the global heat transfer coefficient of
to ensure ventilation of the parking. This ventilation flow the building. However, the interpretation of this curve
rate corresponds to about 2.4 air renewals per hour. stays quite difficult because of the very global data used
According to the outdoor weather conditions, the supplied and the poor correlation factor (R2 = 0.6647).
air can be heated, adiabatically humidified, or cooled and Electricity signatures can also be built by expressing the
dehumidified. Heat production is ensured by four fuel-oil monthly electrical power demand (2005) as function of the
boilers, giving together a nominal heating capacity of outdoor temperature. As shown in Fig. 17, no significant
about 4 MW. Chilled water production is ensured by four correlation can be established between the two variables:
water cooled chillers, coupled to two cooling towers, the electricity consumption stays quite constant all along
giving a total cooling capacity of about 2.1MW. the year.
Build Simul (2008) 1: 234 – 250 247

Such information is too limited to be directly used, but


much more can be learned through the use of simulation
model tuned on the available data.

4.2 Use of Benchmark

The software presented above is applied to the nine


conditioned storeys of the building (from level 0 to 8),
simulated as a unique zone. Parking zone is not considered
in the study. The actual characteristics of the building
envelope, the estimated internal generated gains, the actual
occupancy schedules and temperature and humidity setpoints
Fig. 16 Building thermal signature (2005) are entered in the software. The first approach consists in
supposing that the studied building is coupled to the
“typical” HVAC system described above. The performances
of this system (pressure drops and HVAC components
efficiencies) are estimated according to European standards
prEN 13053 (2003) and prEN 13773 (2007) (Table 2). The
constant hygienic ventilation flow rate is fixed to 45 m3/h
of fresh air per hour and per occupant.
This first simulation gives the results plotted in Figs. 18
and 19. To allow a fair comparison between measured and
computed data, monthly fuel consumptions are here averaged
on the 30 years of available data. This method tends to
minimize the error due to the use of a typical set of weather
Fig. 17 Building electrical signature data, based on averages carried out over thirty years of
measurements, realized in Uccle (Belgium). For electricity
Table 1 Main characteristics of the building consumption, the values of 2005 are used as reference.
Case study building It appears that monthly computed and measured
Building conditioned floor area (m2) 26,700 consumptions are very different. Mostly the fuel, but also
Number of storeys 9 the electricity consumptions are largely underestimated by
Building height (m) 30 the software. This suggests the existence of important energy
Main orientation North/south savings potentials.
Geographical location Brussels, Belgium
Table 2 Typical HVAC components characteristics
External walls area (m2) 7090
HVAC components characteristics
Number of occupants 1100
Lighting power (W/m2) 15 Return ducts pressure drop (Pa) 300

Appliances power (W/m2) 20 Supply ducts pressure drop (Pa) 400

Opaque frontages area (m ) 2


2570 Filters pressure drop (Pa) 150
Opaque frontages U value 2
(W/(m ·K)) 1.15 Preheating coil pressure drop (Pa) 80
Opaque frontages thermal mass Light Adiabatic humidifier pressure drop (Pa) 200
Roof deck area (m ) 2
2970 Cooling coil pressure drop (Pa) 140
Roof deck U value (W/(m2·K)) 0.32 Post-heating coil pressure drop (Pa) 80
Roof deck area thermal mass Light Fan efficiency (%) 75
Double-glazed frontages area (m2) 3020 Pump efficiency (%) 50
Double-glazed windows U value (W/(m2·K)) 3.6 Boiler nominal efficiency (%) 90
2
Single-glazed frontages area (m ) 1440 Chiller nominal COP 3
Single-glazed windows U value (W/(m2·K)) 5.8 Heat recovery system effectiveness (%) 80
248 Build Simul (2008) 1: 234 – 250

Fig. 18 Measured and computed fuel consumptions (first run) Fig. 20 Measured and computed fuel consumptions (after
calibration)

Fig. 19 Measured and computed electricity consumptions (first run)

4.3 Calibration Fig. 21 Disaggregation of computed electricity consumption

In this second phase of the study, a more complete tool


using the same bases has to be used. This second tool is 5 Advantages and limitations of equation solvers
very similar to the first one, but includes additional HVAC
components models as induction unit, radiator, cooling The presented model is implemented on an Engineering
ceiling models, etc. These additional components models equation solver (Klein 2008). This implementation ensures
will be described in further papers. also a full transparency for the user and makes easier the
With more realistic hypotheses (much higher ventilation continuous improvement and development of the tools.
flow rate) and a description of the actual HVAC system Indeed, model’s equations are directly readable and easy to
modify by any user (Fig. 22). It is also very easy to
(four-pipe induction units, no heat recovery system...) and
develop additional HVAC components models and to
its performances and operating conditions, the software
connect them to the existing ones. Moreover, the present
gives the results shown in Fig. 20. The computed and
equation solver is very well adapted to solve differential
measured monthly consumptions are now in fair agreement.
equations systems as used to model the thermal behaviour
After this calibration, the tool can be used to disaggregate of the building zone.
the electricity consumption and to identify the main energy Of course, the use of an equation solver to solve complex
consumers (Fig. 21). This indicates that an important part equation systems implies longer computation time than
of the electricity consumption is due to lighting and other simulation softwares, but the continuous increase of
appliances. Fans and pumps are in charge of about 22% of computer performances tends to reduce this inconvenience.
the global electrical consumption, while chiller part is only At present time, about 20 minutes are necessary to simulate
of about 10%. a mono-zone building and its complete HVAC system
Finally, some selected ECOs would be evaluated on (including AHU, terminal units, and heat and cold production
economical and environmental bases. This second part of and distribution) hour by hour on one year with a classical
the work will be described in further papers. computer equipped with a 2.00GHz processor.
Build Simul (2008) 1: 234 – 250 249

References

André P, Lebrun J, Adam C, Aparecida Silva C, Hannay J, Lemort V


(2006a). A contribution to the audit of an air-conditioning system:
Modelling, simulation and benchmarking. In: Proceedings of the
7th International Conference on System Simulation in Buildings,
Liège, Belgium.
André P, Lebrun J, Adam C, Georges B, Lemort V, Teodorese I
(2006b). From model validation to production of reference
simulations: How to increase reliability and applicability of
building and HVAC simulation models. In: Proceedings of the
7th International Conference on System Simulation in Buildings,
Liège, Belgium.
AuditAC (2007). AuditAC project: Field benchmarking and market
development for audit methods in air conditioning. AuditAC
Final report. Intelligent Energy Europe programme.
Bertagnolio S, Masy G, Lebrun J, André P (2008). Building and
HVAC system simulation with the help of an engineering equation
solver. Paper presented at the Simbuild 2008 Conference,
Berkeley, USA.
Fig. 22 Formatted equations as appearing in the software
Bliss R (1961). Atmospheric radiation near the surface of the ground:
A summary for engineers. Solar Energy, 5: 103 − 120.
6 Conclusions Bourdouxhe J-P, Grodent M, Lebrun J, Saavedran C (1999).
ASHRAE HVAC1 Toolkit: A Toolkit for Primary System
Fairly detailed and realistic simulations are possible today Energy Calculation. Atlanta : American Society of Heating,
in the field of buildings and HVAC. The use of an equation Refrigerating and Air-Conditioning Engineers, Inc.
solver makes the models fully transparent and easy to European Standard prEN13053 (2003). Ventilation for buildings—
improve whenever required. Air handling units — Ratings and performance for units,
components and sections.
HVAC equipment modelling can be performed at
European Standard prEN13779 (2007). Ventilation for non-residential
different levels: The most simplified models with very few
buildings — Performance requirements for ventilation and
parameters can be of great help in the first stage of an room-conditioning systems.
energy audit. The “Benchmark” tool presented in this paper Fanger P (1970). Thermal Comfort — Analysis and Applications in
is an example of such simulation model. It allows the auditor Environmental Engineering. Copenhagen: Danish Technical
to get a first impression about energy saving potentials. Press.
Then, a calibrated but still simplified simulation tool is Harmonac (2008). Harmonac project: Harmonizing Air Conditioning
used to disaggregate the electricity consumption and to Inspection and Audit Procedures in the Tertiary Building Sector.
allow a better interpretation of on site records. Intelligent Energy Europe programme.
Finally, more detailed and specific simulation tools Jagpal R (2006). International Energy Agency—Energy Conservation
in Buildings and Community Systems Annex 34: Computer
should be used to allow a safe identification and an
Aided Evaluation of HVAC System Performance. Synthesis
assessment of the most promising retrofit opportunities.
Report.
More detailed and complete simulation tools will be Judkoff R, Neymark J (1995). International Energy Agency—
presented in further papers. Building Energy Simulation Test (BESTEST) and Diagnostic
Method. National Renewable Energy Laboratory, U.S. D.O.E.
Acknowledgments Klein SA (2008). EES: Engineering Equation Solver, User manual.
F-chart software. Madison: University of Wisconsin-Madison,
This work is performed with the support of the Walloon USA.
Region of Belgium and of Intelligent Energy Europe Klein SA, Beckman WA, Mitchell, JW, Duffie JA (2004). TRNSYS
16-a TraNsient System Simulation Program, User Manual. Solar
programme. The sole responsibility for the content of this
Energy Laboratory. Madison: University of Wisconsin-Madison,
document lies with the authors. It does not represent the
USA.
opinion of the Community. The European Commission is Laret L (1980). Use of general models with a small number of
not responsible for any use that may be made of the parameters, Part 1: Theoritical analysis. In: Proceedings of
information contained therein. Conference Clima 2000, Budapest, 263 − 276.
250 Build Simul (2008) 1: 234 – 250

Lebrun J (1978). Etudes expérimentales des regimes transitoires en Lebrun J, André P, Hannay J, Aparecida Silva C (2006b). Example
chambres climatiques. Ajustement des méthodes de calcul. of audit of an air conditioning system. In: Proceedings of the
Journées Bilan et Perspectives Génie Civil, INSA Lyon, France. Klimaforum Conference, Godovic, Slovenia.
(in French) Lemort V, Cuevas C, Lebrun J, Teodorese I (2008). Development of
Lebrun J, Liebecq G (1988). International Energy Agency — Energy simple cooling coil models for simulation of HVAC systems.
Conservation in Buildings and Community Systems Annex 10: ASHRAE Transactions, 114(1)
Building HVAC System Simulation. Synthesis Report. Masy G (2006). Dynamic simulation on simplified building models
Lebrun J, Ding X, Eppe J-P, Wasacz M (1990). Cooling coil models and interaction with heating systems. In: Proceedings of the 7th
to be used in transient and/or wet regimes. Theoretical analysis International Conference on System Simulation in Buildings,
and experimental validation. In: Proceedings of the 3rd Liège, Belgium.
International Conference on System Simulation in Buildings, Visier J C, Jandon M (2004). International Energy Agency— Energy
Liège, Belgium. Conservation in Buildings and Community Systems Annex 40:
Lebrun J, Wang S (1993). International Energy Agency — Energy Commissioning of Building HVAC Systems for Improved
Conservation in Buildings and Community Systems Annex 17: Energy Performances. Synthesis Report.
Building Energy Management Systems — Evaluation and Woloszyn M (1999). Moisture — Energy — Airflow modelling of
Emulation Techniques. Synthesis Report. multizone buildings. PhD Dissertation, CETHIL Laboratory,
Lebrun J, André P, Aparecida Silva C, Hannay J, Lemort V, INSA Lyon, France.
Teodorese V (2006a). Simulation of HVAC systems: Development
and validation of simulation models and examples of practical
applications. In: Proceedings of the Mercofrio 2006 Conference,
Porto Alegre, Brazil.

You might also like