EN0H-0327UK01 R0421

Zone Valves

VC series motorized valves


2-port zone valves and 3-port diverter valves

APPLICATION
VC Series balanced 2-position hydronic valves are used in
domestic and small commercial heating and cooling
applications to control the flow of hot and/or cold water.
They consist of an actuator, valve and a cartridge assembly.
2-way valves are designed for on-off zone control of
domestic systems.
3-way valves can be piped for diverting applications in
domestic central heating and/or cooling systems.
Both versions can be used to control individual fan coil,
radiator, space heater or convector applications.
They can be controlled by a line voltage SPST or SPDT
controller such as a room thermostat, aquastat or flow
switch.
VC Series hydronic valves are designed to take advantage of
sinusoidal valve actuator travel, and therefore operate
silently and reduce water hammer.
Through internal logic the actuator only takes power while
driving the valve to the commanded position.
The actuator head is removable without affecting the
integrity of the water system.
All actuator versions are interchangeable with any valve
body, offering the highest flexibility for installation in the
SPECIAL FEATURES
field or boiler production line assembly, and maintenance. • Rugged design
The valve piston construction allows for port sealing that is • High pressure differential up to 4 bar
independent of the differential pressure across the valve. • Control by a line voltage SPST or SPDT controller
Flow through the 2-way valve can be in either direction, so • Minimal actuator power consumption
the ports are not designated. • Double insulated actuator
3-way valves are suitable for both diverting water from AB to • Quick and easy replacement of moving parts
A or B, and from A or B to AB. • Actuator head installation does not require draining of
the system
• High flow rate capacity

Product Specification Sheet • EN0H-0327UK01 R0421 • Subject to change 1


VC series motorized valves - 2-port zone valves and 3-port diverter valves

TECHNICAL DATA
VALVES ACTUATORS

Media Specifications
Medium: Water or water-glycol mixture Voltage: 200-240 V, 50-60 Hz (red
(max. 50 % glycol content), label)
quality to VDI 2035 or Power consumption: 4 VA (when valve position
BS7593 (2019) changes)
Operating temperatures Auxiliary switch rating: 1.0 A @ 250 V, 50-60 Hz
Operating temperature: 1...95 °C (34...203 °F) (minimum 0.05 A @ 24 Vdc)
120 °C (248 °F) short Nominal timing: Valve opens in 7 seconds
duration peak (20% faster for 60 Hz)
Ambient temperature: max. 65 °C (149 °F) Electrical termination: With integral 1 m leadwire
Pressure values Shipping temperature: -40…65 °C (-40…149 °F)
Operating pressure: max. 20 bar (290 psi) static Humidity rating: 5…95 % RH (non-
Differential pressure: max. 4 bar (58 psi) condensing)
Specifications Atmosphere: non-corrosive, non-explosive
kvs-values: see chapter “Dimensions”
below
Flow: 2-way: flow can be in either
direction. When actuator is
not mounted valve is in
closed position
3-way: bottom port is marked
AB. End ports are marked A
and B. When actuator is not
mounted port A is closed.

CONSTRUCTION
Overview Components Materials
1 Spindle and cartridge Stainless steel
assembly Cartridge made of Ryton™
(polyphenylene sulphide) or
Fortron™ (polyphenylene
sulphide) and Noryl™
(polyphenylene oxide)
2 2-way or 3-way valve Brass
housing available with
various pipe connections
3 Actuator with cable Cover made of Noryl™ (94V-0)
Base made of Ryton™ (94V-0)
or Tedur™ (PPS) (94V-0) or
Fortron™ (94V-0)
Not depicted components:
O-rings and seals EPDM rubber

2 Product Specification Sheet • EN0H-0327UK01 R0421 • Subject to change


VC series motorized valves - 2-port zone valves and 3-port diverter valves

METHOD OF OPERATION
VC Series 2-position hydronic valves are used in domestic 3-way diverter valve
and small commercial applications to control the flow of hot With an SPST (2-wire and common) actuator
and/or cold water.
On a call for heat the controller contacts close, RLY1 is
They consist of an actuator, valve and a cartridge assembly.
energized making the NO contacts in switch SW3, causing
All moving and sealing parts of the valve are constructed in
port B to close and port A to open.
the cartridge assembly.
When port A reaches the fully open position the cam closes
The ports are sealed with O-rings on the outer surface of the
switch SW1 and opens switch SW2.
piston.
When the need for heat is satisfied, the controller contacts
When the valve stem is driven down to open port A the water
open.
will flow through the hollow piston to the other port.
RLY1 is de-energized making the NC contacts in SW3 and
In case of a 3-way valve with the piston driven down port B is
port A is driven closed through SW1 and the NC contacts of
sealed, allowing flow between port AB and port A.
SW3.
With the stem up the flow is between port AB and port B.
When port A is in the fully closed position the cam closes
The valve family offers a variety of versions of pipe SW2 and opens SW1.
connections to suit the different applications.
The valve is ready for the next call for heat.
The valve pressure loss characteristic is dependent on the
A power failure will leave the valve at the position it was when
pipe connections/ dimensions.
interrupted.
For the actual valve rating please refer to the specification
section.
B AB A  AB
2-way valve
With an SPST (2-wire and common) actuator
On a call for heat, the controller contacts close, RLY1 is
energized making the NO contacts in switch SW3 causing
the valve to open. A B A B
When the valve reaches the fully open position the cam
AB AB
closes switch SW1 and opens switch SW2.
When the need for heat is satisfied, the controller contacts Fig. 2 Fluid flow through 3-way VC valve
open, RLY1 is de-energized and the valve motor is driven Wiring
through SW1 and the NC contacts of SW3. Figure 3 shows wiring connections for 2-way and 3-way
When the valve reaches the fully closed position, the cam valves.
closes SW2 and opens SW1. Port A open and closed denotes valve open and closed for 2-
The valve is ready for the next call for heat. way, and AB-A open and AB-B open for 3-way valves
A power failure will leave the valve at the position it was when respectively.
interrupted. A means for disconnection from the supply having a contact
When power is restored, the valve will respond to controller separation of at least 3 mm in all poles must be incorporated
demand. in the fixed wiring.

3
SW1 NC
SW3
6
SW2 NO
CW
L

N RLY1
2
A B A B

Fig. 1 Fluid flow through 2-way VC valve Fig. 3 Logic sequence diagram with 2-wire + common actuator for
SPST controller

Product Specification Sheet • EN0H-0327UK01 R0421 • Subject to change 3


VC series motorized valves - 2-port zone valves and 3-port diverter valves

TRANSPORTATION AND STORAGE Plumbing


Keep parts in their original packaging and unpack them
shortly before use.
The following parameters apply during transportation and
storage:

Parameter Value
Environment: clean, dry and dust free
Min. ambient temperature: -40 °C
Max. ambient temperature: 65 °C
Min. ambient relative 5 % RH
humidity:
Max. ambient relative 95 % RH
humidity:
*non condensing

INSTALLATION GUIDELINES
Installation Fig. 4 Plumbing

WARNING! The valve may be plumbed in any angle but preferably not
Installer must be a trained, experienced service with the actuator head below the horizontal level of the valve
person. body. Make sure there is enough room around the actuator
head for servicing or replacement.
When installing this product:
When used to form part of a central heating system, do not
• Read these instructions carefully. Failure to follow them
locate it where it will block the system vent, cold feed or any
could damage the product or cause a hazardous
bypass when the valve is closed.
condition
Mount the valve directly in the tube or pipe.
• Check the ratings given in the instructions and on the
product to make sure it is suitable for your application. Do not grip actuator while making and tightening up
plumbing connections.
• Always conduct a thorough checkout after installation.
Either hold valve body in your hand or attach adjustable
CAUTION! spanner (38 mm or 1-1/2") across the hexagonal or flat faces
• Disconnect power supply before wire connection to on the valve body.
prevent electrical shock and equipment damage. For trouble free operation follow the recommendations in
• It is advisable to remove the actuator head from the BS7593 (2019) "Code of Practice for the preparation,
valve body for ease of installation. Fit the actuator head commissioning & maintenance of domestic central heating
in the most convenient position for wiring. and cooling water systems" including initial system
flushing, chemical water treatment and the use of
Multifunction Magnetic Dirt Separator Filter.

4 Product Specification Sheet • EN0H-0327UK01 R0421 • Subject to change


VC series motorized valves - 2-port zone valves and 3-port diverter valves

Compression models TECHNICAL CHARACTERISTICS


For compression fitted models, tighten the compression Adjustment and Testing
nuts enough to make a watertight seal. Take care not to
Manual Opener
overtighten.
The manual opener can be manipulated when in the up
To install a replacement actuator head
position.
The motorized valve can be opened by firmly pushing the
manual lever down to midway and in (only possible if the
actuator is in the upper position).
This holds all ports in the open position, and with auxiliary
switch models the NO switch is closed.
Ports A and B of 3-way valves are opened.
This 'manual open' position may be used for filling, venting
or draining the system, or for opening the valve in case of
power failure.
The valve can be restored manually to the closed position by
depressing the manual lever lightly and then pulling it out.
The valve actuator returns to the automatic position when
power is restored.
Checkout
1) Raise the set point of the thermostat above room
Fig. 5 Latch mechanism
temperature to initiate a call for heat. Valve position
Installation of a new actuator head does not require draining indicator should move downward to the open position.
the system providing the valve body and cartridge assembly 2) For all auxiliary switch models, monitor the control
remain in the pipeline. devices. 2-way valve: check that the valve opens, the
1) Disconnect power supply before servicing to avoid auxiliary switch (if present) closes, and at the end of the
electrical shock or equipment damage opening stroke the circuit to the circulator or another
2) The actuator head is automatically latched to valve (see valve is made. 3-way valve: check that port A opens, port
figure 5). To remove, lift up on the latch mechanism B closes, the auxiliary switch (if present) operates, and
located directly below the manual open lever. Press the at the end of the opening stroke the circuit to the
actuator head down towards the body with moderate circulator or another valve is made.
hand force and turn counter-clockwise by 1/8 turn (45 3) Lower the set point of the thermostat below room
degrees) simultaneously. Lift the actuator head off the temperature.
valve body. 4) Observe the control devices. 2-way valve: check that the
Actuator can also be installed at right angles to valve valve closes and all auxiliary equipment stops. 3-way
body but in this position latch mechanism is not valve: check that port A closes and all auxiliary
engaged. equipment stops.
3) Install the new actuator head by reversing process in (2). Service
4) Restore power.
CAUTION!
This valve should be serviced by a trained,
experienced service technician.
1) If the valve is leaking, drain system or isolate valve from
the system.
2) Check to see if cartridge needs to be replaced.
3) If the gear train or the motor is damaged, replace the
actuator assembly.
Note: Honeywell Home hydronic valves are designed and tested for silent
operation in properly designed and installed systems. However,
water noises may occur as a result of excessive water velocity.
Piping noises may occur in high temperature (100°C) systems with
insufficient water pressure.

Product Specification Sheet • EN0H-0327UK01 R0421 • Subject to change 5


VC series motorized valves - 2-port zone valves and 3-port diverter valves

Flow Diagrams

Fig. 6 Valve pressure loss characteristic


100
90
80
70
60 AB-B
Port flow (%) 50 AB-A
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
Travel (%)
Fig. 7 Typical 3-way valve diverting characteristic at constant pressure on port AB

6 Product Specification Sheet • EN0H-0327UK01 R0421 • Subject to change


VC series motorized valves - 2-port zone valves and 3-port diverter valves

DIMENSIONS
Overview

94 68 94 68

90 90
113
D

A B

AB
C/2 C/2
C C

Body: 2-way VC valve 3-way VC valve


C kvs-value C D kvs-value
22mm compression*: 112 5.2 112 140 6.8
28mm compression*: 112 5.7 112 140 8.7
1/ " BSPP (internal): 98 3.2 - - -
2
3/ " BSPP 94 5.0 94 130 6.6
4
1" BSPP 94 5.5 94 136 8.5
Note: All dimensions in mm
* Includes compression nuts and olives

ORDERING INFORMATION
Valve + actuator combinations

Description **kvs-value (m3/h) OS Number


1/ " BSPP Normally closed 2 port valve, female thread 3.2 VC4613AF1000/U
2
3/ " BSPP Normally closed 2 port valve, female thread 5.0 VC4613AJ1000/U
4
22 mm Normally closed 2 port valve 5.2 VC4613AG1000/U
1" BSPP Normally closed 2 port valve, female thread 5.5 VC4613AP1000/U
28 mm Normally closed 2 port valve 5.7 VC4613AN1000/U
3/ " BSPP Diverter valve, female thread 6.6 VC4613MH6000/U
4
22 mm Diverter valve 6.8 VC4613MF6000/U
1" BSPP Diverter valve, female thread 8.5 VC4613MP6000/U
28 mm Diverter valve 8.7 VC4613MM6000/U
** kvs values measured for 2 port valve A > B and for Diverter valve AB > A
Valve body

Description OS Number
3/ " BSPP diverter valve body, female thread VCZMH6000/U
4
22 mm diverter valve body VCZMF6000/U
1" BSPP diverter valve body, female thread VCZMP6000/U
28 mm diverter valve body VCZMM6000/U
1/ " BSPP normally closed, 2 port valve body, female thread VCZAF1000/U
2
3/ " BSPP normally closed, 2 port valve body, female thread VCZAJ1000/U
4
22 mm BSPP normally closed, 2 port valve body VCZAG1000/U
1" BSPP normally closed, 2 port valve body, female thread VCZAP1000/U
28 mm BSPP normally closed, 2 port valve body VCZAN1000/U
Actuator

Description OS Number
Actuator 230V SPST with auxiliary switch, 1m cable VC4613ZZ00/U

Product Specification Sheet • EN0H-0327UK01 R0421 • Subject to change 7


VC series motorized valves - 2-port zone valves and 3-port diverter valves

Spare Parts
VC Series, from 2005 onwards

Overview Description Part No.


1 VC Series replacement cartridge for 2-port zone
valves, on/off
VCZZ1000/U
2 VC Series replacement cartridge for 3-port zone
valves, on/off
1 VCZZ6000/U

Subject to change
© 2021 Pittway Sàrl. All rights reserved.
This document contains proprietary information of
Manufactured for and on behalf of the Pittway Sàrl and its affiliated companies and is
Pittway Sàrl, La Pièce 4, protected by copyright and other international
1180 Rolle, Switzerland laws. Reproduction or improper use without specific
written authorisation of Pittway Sàrl is strictly
forbidden. The Honeywell Home trademark is used
EN0H-0327UK01 R0421 under license from Honeywell International Inc.