Professional Documents
Culture Documents
Review Report (FINAL)
Review Report (FINAL)
This report contains the results of the technical review of an application for LEED® certification submitted for the specified
project. LEED certification is an official recognition that a project complies with the requirements prescribed within the LEED
rating systems as created and maintained by the U.S. Green Building Council® (USGBC®). The LEED certification program
is administered by Green Business Certification Inc. (GBCI®).
LIVEN
Project ID 1000148950
Design Preliminary Application
Rating system & version LEED V4 BD+C: CS
CERTIFIED: 40-49, SILVER: 50-59, GOLD: 60-79,
Project registration date 09/07/2021 PLATINUM: 80+
Project Information
Awarded.
Integrative Process
Awarded.
Location And Transportation
Awarded.
Awarded.
Awarded.
Awarded.
Awarded.
The project is pursuing the LEED v4.1 substitution path for this credit.
Awarded.
Awarded.
Awarded.
Awarded.
Awarded.
For full certification review, note that LEED Interpretation 10411 includes a listing of standard nonroof materials in lieu of
project-specific testing data. Manufacturer documentation or an independent testing report showing the tested SR value must
be provided if not listed in LEED Interpretation 10411.
Awarded.
Note that a maximum of two points are available for this credit.
Awarded.
Water Efficiency
Awarded.
Awarded.
Awarded.
Awarded.
Awarded.
Awarded.
Energy And Atmosphere
Awarded.
For the full Certification Review, note the commissioning agent must prepare a current facilities requirements and operations
and maintenance plan that contains the information necessary to operate the building efficiently.
ption 1: Whole-Building Energy Simulation, 15.0% ASHRAE 90.1-2010 Appendix G energy cost savings.
Option 1: Whole-Building Energy Simulation, 15.0% ASHRAE 90.1-2010 Appendix G energy cost savings. However, some of
these savings could not be confirmed due to the following outstanding issues.
included an excerpt of the clarification response to verify that the air conditioning and ventilation fans are not included in the
tenant scope. However, this is inconsistent with the full clarification response which explicitly stated the tenant scope included
complete mechanical installation, heating and cooling units, ventilation fans, and that “items not included, such as cooling units
and lighting fixtures, future tenants will sign a binding lease with the obligation that they must comply”. Due to these
inconsistencies, the savings has been reduced to 2% which accounts for savings from lighting and envelope and meets the
prerequisite requirements.
The total percentage improvement has been revised to 3.0%, which includes the 2% minimum requirement plus the 1%
renewable energy contribution, which meets prerequisite requirements.
For the full certification review, ensure that the fully executed TSLAs specifically states whether the tenants are allowed to install
conditioning HVAC equipment. If the tenants are allowed to install conditioning HVAC equipment, ensure all tenant spaces will be
modeled as conditioned (i.e. heating and cooling provided). The HVAC systems shall be modeled identically per ASRHAE
Appendix G unless a Tenant Sales and Lease Agreement (TSLA) signed by the owner and the tenant is provided for the space.
Additionally, ensure that documentation is provided that verifies that the natural ventilation complies with EQ Minimum Indoor
Air Quality Performance along with a detailed description is provided to document the modeling algorithms and/or methodology
for the natural ventilation portion of the energy model and clearly identifies the areas that are taking credit for natural
ventilation. Further, ensure that all relevant sections of the mechanical plans and supporting documentation are highlighted and
translated into English and that the documentation is legible.
Option 1: Whole-Building Energy Simulation, 15% ASHRAE 90.1-2010 Appendix G energy cost savings.
1. The clarification narrative states that air conditioning systems and ventilation fans are included in the tenant scope. However,
based on the model narrative states that air conditioning system have not been included in the model. The tenant spaces shall
be modeled with heating and cooling unless documentation can be provided to confirm that it is not typical for the spaces to be
conditioned.
Provide an updated narrative to confirm that all spaces will be modeled as conditioned (i.e. heating and cooling provided). The
HVAC systems shall be modeled identically per ASRHAE Appendix G unless a Tenant Sales and Lease Agreement (TSLA) signed
by the owner and the tenant is provided for the space.
For the full Certification Review, ensure a detailed description is provided to document the modeling algorithms and/or
methodology for the natural ventilation portion of the energy model and clearly identifies the areas that are taking credit for
natural ventilation. Additionally, ensure that all relevant sections of the mechanical plans and supporting documentation are
highlighted and translated into English and that the documentation is legible.
However, when Eap Minimum Energy Performance was recalculated based on the issues noted there, the project has
demonstrated an energy cost savings of 3%.
Refer to the comments within the prerequisite and resubmit this credit.
Awarded.
Awarded.
Awarded.
Awarded.
Refer to the comments within the prerequisite and resubmit this credit.
1. Due to inconsistencies between the clarification response for PI Project Information and the narrative response to the
preliminary review comments for Eap Minimum Energy Performance, it remains unclear whether the tenant scope will allow air
conditioning equipment.
For the full certification review, provide documentation to confirm that the cooling loads in naturally ventilated spaces are
designed to be met with passive cooling or that fully executed TSLAs for the tenant-controlled air conditioning systems are
provided.
1. The narrative states that the base building scope does not include any air conditioning systems. However, it is unclear
whether the building is designed to meet cooling loads with passive cooling. For core and shell projects without air conditioning
systems in the base building, compliance can only be achieved by either demonstrating that the cooling loads are designed to
be met with passive cooling or by providing fully executed TSLAs for the tenant-controlled air conditioning systems.
Revise the narrative to confirm that the cooling loads are designed to be met with passive cooling or that fully executed TSLAs
for the tenant-controlled air conditioning systems will be provided.
Awarded.
Awarded.
Awarded.
Indoor Environmental Quality
Based on the provided mechanical drawings, it appears that exhaust fans in the apartment units would have sufficient exhaust
airflow rates and the residential units could meet ASHRAE 62.2-2013.
However, the floor plan drawing A-05 indicates that some interior halls, lobby, etc may not be able to meet ASHRAE 62.1-2013
section 6.4 natural ventilation requirements, and mechanical ventilation may be needed in these spaces. For a full certification
review, ensure that these interior spaces meet ASHRAE 62.1-2013 ventilation requirements.
About installing CO2 sensors with visible alarms to prevent opening from being closed during occupancy, it appears that CO2
sensor settings may not be sufficient to alert a person coming into a space as occupancy sensors do. Further, it is unclear how
CO2 sensors control the openings when a person enters into a space. Therefore, CO2 sensors may not be an appropriate device
to control window operations. The common areas such as gym, etc using this method may not meet ASHRAE 62.1-2013 Section
6.4 Exception b.1. However, since no heating or cooling shall be installed in these spaces, the project may meet section 6.4
Exception b.2.
Since EQp Minimum Indoor Air Quality Performance has been awarded for similar project 1000149753 Edificio Multifamiliar Los
Angeles, one time exception is given to this project. Note that previous projects will not set a precedent for future projects.
When the projects are submitted for a full certification review, ensure that the above issues are addressed.
Option 1: ASHRAE Standard 62.1-2010. However, compliance with ASHRAE62.1-2010 could not be confirmed due to the
following outstanding issues.
1. (Preliminary Review Comment #1) The narrative response stated that the openings are operable windows and that the
naturally ventilation spaces meet ASHRAE 62.1-2010 Exception b.1 since the CO2 sensors will have visible alarms to prevent
openings from being closed during occupied periods. However, CO2 sensors are not an appropriate device to control window
operations. Additionally, the proposed control strategy does not appear to address periods of adverse weather including, but not
limited to, rain.
For the full certification review, ensure that documentation is provided to confirm that the building will contain permanent
openings per ASHRAE 62.1-2010 Section 6.4 or verifies that the method of operable window controls is appropriate and
addresses periods of adverse weather such as rain. Alternatively, state if using LEED Interpretation 10416 and that continuous
exhausting for the residential spaces. Note that if LEED Interpretation 10416 is implemented, all non-residential spaces in the
building must comply with ASHRAE 62.1-2013 with addenda. Additionally, for the mechanically ventilated areas, note that Core
and Shell buildings must make reasonable assumptions about the distribution of spaces and ensure that ventilation systems are
capable of providing sufficient outdoor air for anticipated occupants and space types. Ensure that the VRP calculations have
been based on assumptions of a feasible tenant fit-out that includes spaces such as conference rooms, break rooms, individual
or open plan offices, etc. Ensure that Ventilation Rate Procedure calculations are provided for all areas which are mechanically
ventilated. Further, ensure that the documentation confirms that the parking garage exhaust meets the minimum requirements
of ASHRAE 62.1 Table 6.4.
1. Based on the provided documentation, it does not appear that the building will have permanent openings for natural
ventilation. Note that exhaust induced ventilation is not natural ventilation nor engineered natural ventilation, and outdoor air
intake must be permanently open. Additionally, if a residential space does not include permanent openings, then LEED
Interpretation 10416 and ASHRAE 62.1-2013 with addenda may be used; this allows ASHRAE 62.1-2013 with addenda for non-
unit spaces, and ASHRAE 62.2-2013 with addenda for dwelling units, which allows exhaust-only ventilation without intentional
openings. Note that exhaust induced ventilation is not natural ventilation nor engineered natural ventilation, and outdoor air
intake must be permanently open.
Update the narrative to confirm if the building will contain permanent openings per ASHRAE 62.1-2010 Section 6.4.
Alternatively, state if the LEED Interpretation 10416 and that continuous exhausting will be used in the residential spaces. Note
that if LEED Interpretation 10416 is implemented, all non-residential spaces in the building must comply with ASHRAE 62.1-
2013 with addenda.
2. The parking garage exhaust requirements have not been addressed in the narrative. The parking garage exhaust must meet
the exhaust requirements of ASHRAE 62.1 Table 6-4.
Revise the narrative to confirm that the parking garage exhaust will meet the exhaust requirements of ASHRAE 62.1 Table 6-4.
For the full Certification Review, note that Core and Shell buildings must make reasonable assumptions about the distribution of
spaces and ensure that ventilation systems are capable of providing sufficient outdoor air for anticipated occupants and space
types. Ensure that the VRP calculations have been based on assumptions of a feasible tenant fit-out that includes spaces such
as conference rooms, break rooms, individual or open plan offices, etc. Ensure that Ventilation Rate Procedure calculations are
provided for all areas which are mechanically ventilated.
Awarded.
Awarded.
Innovation Attempted
POSSIBLE POINTS: 5
Awarded.
-------
Awarded.
-------
Awarded.
Awarded.
Regional priority credits
Bicycle Facilities
POSSIBLE POINTS: 1
POINTS:
Credit STATUS TYPE ATTEMPTED DENIED PENDING ANTICIPATED
POINTS:
Credit STATUS TYPE ATTEMPTED DENIED PENDING ANTICIPATED