00 18/03/2021 Wiring Diagrams Actuators JVP JFR

Rev Date Description Created By Checked By

AL-KHOBAR SEAWATER REVERSE OSMOSIS 2


DESALINATION PLANT

KR02-WM01-T-1601

Project Code Area Code Document Type Document Nº Rev

KR02 WM01 T 1601 A


LIMIT SWITCH BOX CONNECTION
Actuator Position 0º 45º 90º
Valve position Closed intermediate Open
Limit switch CLOSE 1 SWITCH CLOSE 2 SWITCH + OPEN 2 SWITCH OPEN 1 SWITCH

CLOSE 2 SWITCH
OPEN 2 SWITCH
CLOSE 1 SWITCH OPEN 1 SWITCH

B2 B1
LIMIT SWITCH CAMS REGULATION

B1 Solenoid to OPEN actuator (90º)
B2 Solenoid to CLOSE actuator (0º)
CLOSE 1 SWITCH Closed position limit switch. Valve position 0º
CLOSE 2 + OPEN 2 SWITCH Limit switches intermediate position. Valve position 45º
OPEN 1 SWITCH Open position limit switch. Valve position 90º

To close the valve Signal in B2 ‐ No signal in B1‐ CLOSE 1 SWITCH pressed
To open the valve Signal in B1 ‐ No signal in B2 ‐ OPEN 1 SWITCH presed
Signal in B1 (if CLOSE 1 SWITCH pressed) or B2 (If OPEN 
To move valve to intermediate 
1 SWITCH pressed) up to press CLOSE 2 SWITCH or 
position (45º)
OPEN 2 SWITCH
ONLY DOUBLE ACTING ACTUATORS
To improve precission, we recommend:
‐ Exhaust regulators to decrease speed of the actuator
‐ Two limit switches to intermediate position, in order to have different
stop electric signals clockwise and counterclockwise
Nº Fecha / Date Modificación / Modification Acop./ Coupling ACT. Aplicación / Aplication
‐ In case of only use 1 intermediate switch, connect only "CLOSE 2" switch or "OPEN 2" switch 
Dibujado / Drawn Fecha / Date Tratam. / Treatment REV. Nº Dibujado / Drawn

C.F.F. 30/10/2019 1 C.F.F.


Co mpr. / Checked M aterial Recubrim. / Co vered Fecha / Date Co mpr. / Checked

R.A.G. 30/10/2019 R.A.G.


TOL.GRA L. Escala / Scale CONNECTION OF 90º D.A. ACTUATOR CODIGO:
ISO-2768-mK N/A WITH INTERMEDIATE STOP CODE: