CONTROL VALVE POSITIONER 3730-2, 3730-3 CALIBRATION

1. Overview.

Item Code: 09.51.03.103.0

When signal loss: The positioner will supply air to Output port 2.

UP button
CAL button

Output port
DOWN 2
button
2. Mounting Positioner on a Rotary Actuator
3. Parameter configuration
a. Flow config.
- Press “CAL” button to enter menu.

- Use “UP” ,”DOWN’, and press “CAL” buttons to choose config


function.
- Use “UP” ,”DOWN’ buttons to choose flow function.
- Press “CAL” button to enter Config Flow menu.
- Use “UP” ,”DOWN’ and press “CAL” buttons to choose “Linear
flow”.

b. Type config.

Rotary valve
c. Flop config.

Fail close

d. OPSP config.

OPSP 5
e. CLSP config.

CLSP 5
f. Note:
 With option Direct Control Mode: CRev=OFF
4-20 mA = 0-100%
 With option Direct Control Mode: CRev=ON
4-20 mA = 100-0%
4. Calibration.
- Connect with loop current
And adjust at 12mA.

12mA

Source

Press “CAL”
button to
- Press and Hold CAL Button in a several seconds, Tyco Positioner
will calibrate automatically.
- When Positioner completed calibration. Open valve and monitor
actual feedback on LCD.
4 mA 0%
8 mA 25%
12 mA 50%
16 mA 75%
20 mA 100%