1. Overview.
When signal loss: The positioner will supply air to Output port 2.
UP button
CAL button
Output port
DOWN 2
button
2. Mounting Positioner on a Rotary Actuator
3. Parameter configuration
a. Flow config.
- Press “CAL” button to enter menu.
b. Type config.
Rotary valve
c. Flop config.
Fail close
d. OPSP config.
OPSP 5
e. CLSP config.
CLSP 5
f. Note:
With option Direct Control Mode: CRev=OFF
4-20 mA = 0-100%
With option Direct Control Mode: CRev=ON
4-20 mA = 100-0%
4. Calibration.
- Connect with loop current
And adjust at 12mA.
12mA
Source
Press “CAL”
button to
- Press and Hold CAL Button in a several seconds, Tyco Positioner
will calibrate automatically.
- When Positioner completed calibration. Open valve and monitor
actual feedback on LCD.
4 mA 0%
8 mA 25%
12 mA 50%
16 mA 75%
20 mA 100%