Shell & Coil

R410A(50Hz/60Hz)
0CVW0-01C (Replaces 0CVW0-01B)

P/No. : MFL61741619
Shell & Coil

General Information
Outside Units
Installation of Outside Units
Special Guide
Shell & Coil

General Information

1. Model Names
2. External Appearance
3. Nomenclature
4. Outside Units information
5. Indoor Unit and Outside Unit Capacity Index
6. Outside Unit Function
Shell & Coil
1. Model Names
Power Supply 10HP 20HP 30HP
General Information of

3Ø, 380 - 415V, 50Hz


ARWV100LAL4 ARWV200LAL4 ARWV300LAL4
3Ø, 380V, 60Hz
Outside Units

h If it will be installed 20HP and 30HP, please contact the HQ.

1 _ R410A(50Hz/60Hz)
Shell & Coil
2. External Appearance
n Cooling Only

General Information of
Chassis Model Name External Appearance

Outside Units
UWC ARWV100LAL4

UWC
ARWV200LAL4
UWC

UWC
UWC ARWV300LAL4
UWC

h If it will be installed 20HP and 30HP, please contact the HQ.

R410A(50Hz/60Hz) _ 2
Shell & Coil
3. Nomenclature

ARW V 100 L A L 4
General Information of
Outside Units

Series Number
L : Shell & Coil Heat Exchanger

A: Basic Function

Electrical Ratings
L: 3Ø, 380 - 415V, 50Hz / 3Ø, 380V, 60Hz

Total Cooling Capacity in Horse Power(HP) unit


E X) 10HP → '100'

Model type
V : Cooling Only

Indicates that this is Water System


Outside Unit using the R410A

3 _ R410A(50Hz/60Hz)
Shell & Coil
4. Outside Units information
Power Supply: Outside Unit (3Ø, 380~415V, 50/60HZ)

General Information of
n Cooling Only

Outside Units
System Capacity HP 10 20 30
Combination Unit ARWV100LAL4 ARWV200LAL4 ARWV300LAL4
ARWV100LAL4 ARWV100LAL4 ARWV100LAL4
Model Name
Independent Unit ARWV100LAL4 ARWV100LAL4
ARWV100LAL4
Product Refrigerant Charge kg 2.0 2.0+2.0 2.0+2.0+2.0
Maximum Connection No. of Indoor 16(25) 32(44) 49(60)
kg 120 × 1 120 × 2 120 × 3
Net Weight
lb 265 × 1 265 × 2 265 × 3
mm (755 × 997 × 500) × 1 (755 × 997 × 500) × 2 (755 × 997 × 500) × 3
Dimensions (WxHxD)
inch (29-23/32 × 39-1/4 × 19-11/16) × 1 (29-23/32 × 39-1/4 × 19-11/16) × 2 (29-23/32 × 39-1/4 × 19-11/16) × 3
Refrigerant Liquid mm (inch) 9.52(3/8) 12.7(1/2) 19.05(3/4)
Connecting Pipe Gas mm (inch) 22.2(7/8) 28.58(1-1/8) 34.9(1-3/8)
Inlet mm PT 25 (External Thread) PT 25 + PT 25 (External Thread) PT 25 + PT 25 + PT 25 (External Thread)
Water
Outlet mm PT 25 (External Thread) PT 25 + PT 25 (External Thread) PT 25 + PT 25 + PT 25 (External Thread)
Connecting Pipe
Drain Outlet mm 20 (External Thread) 20 (External Thread) 20 (External Thread)

CAUTION
• Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
• A combination operation over 100% cause to reduce each indoor unit capacity.
n Combination ratio (50~200%)
Outside Number Connection Capacity
Single outside units 200%
Double outside units 160%
Triple outside units 130%
Notes:
* We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and discuss the requirement like below.
1) If the operation of indoor unit is more than 130%, low airflow operation is recommended in all the indoor units.
2) If the operation of indoor unit is more than 130%, additional refrigerant is needed according to the headquar-
ter guidance.
3) Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.
h If it will be installed 20HP and 30HP, please contact the HQ.

R410A(50Hz/60Hz) _ 4
Shell & Coil

5. Indoor Unit and Outside Unit Capacity Index


5.1 Outside Unit Selection
See the indoor unit capacity tables for given Indoor and Outside temperature.
General Information of

Select the unit whose capacity is the nearest to or greater than given load.
Note:
Outside Units

Individual Indoor Unit capacity is subject to change by combination. Actual capacity has to be calculated accord-
ing to the combination by using Outside unit capacity table.

5.2 Outside Unit Selection


Allowable combinations are indicated in INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE. In gener-
al, Outside Unit can be selected depending on the location of the unit, zoning and usage of the rooms.
The Indoor and Outside Unit combination is determined where the sum of Indoor Unit capacity index is the nearest to
and smaller than the capacity index at 100% combination ratio of each Outside Unit.
Indoor Units can be connected to one Outside Unit.

INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE

Indoor Unit Combination Ratio


Outside Unit
Capacity(HP) 50% 60% 70% 80% 90% 100% 110% 120% 130% 160% 200%
ARWV100LAL4 14.0 16.8 19.6 22.4 25.2 28.0 30.8 33.6 36.4 44.8 56.0
ARWV200LAL4 28.0 33.6 39.2 44.8 50.4 56.0 61.6 67.2 72.8 89.6 -
ARWV300LAL4 42.0 50.4 58.8 67.2 75.6 84.0 92.4 100.8 109.2 - -

Indoor unit capacity index


Unit Capacity
5k 7k 9k 12k 15k 18k 24k 28k 36k 42k 48k 54k 76k 96k 98k
(Btu/h)

Capacity 22.4
1.6 2.2 2.8 3.6 4.5 5.6 7.1 8.2 10.6 12.3 14.1 15.8 28.0 32.0*
Index 25.0*

h Capacity Index is same as the capacity(kW).


※ * : Capacity Index only for Hydro Kit. The applicability of Hydro Kit vary by target region.

5 _ R410A(50Hz/60Hz)
Shell & Coil
6. Outside Unit Function
Category Function Single Unit Series Unit
Defrost / Deicing X X

General Information of
High pressure switch O O

Outside Units
Low pressure switch X X
Reliability Phase protection O O
Restart delay (3-minutes) O O
Self diagnosis O O
Soft start O O
Convenience Test function X X
Network function Network solution(LGAP) O O

Note:
O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model
name, supplied with separate package.

Device Multi V Water IV


AC Ez (Simple Controller) PQCSZ250S0
AC Smart ll PQCSW320A1E
AC Smart Premium PQCSW421E0A
128 Unit Expansion Kit for AC Smart PQCSE440U0
Option Kit (SD card type) for AC Smart PQCSE341A0 / PQCSE342A0
Central Controller ACP(Advanced Control Platform) PQCPA11A0E / PQCPB11A0E
AC Manager PQCSS520A0E
ACP(Advanced Control Platform) Standard PQCPC22N0
ACP(Advanced Control Platform) Premium PQCPC22A0
AC Manager Plus PQCSSA21E0
DO(Digital Output) Kit PQNFP00T0
LONWORKS Gateway (DC 12V Adapter) PQNFB16A1 / PLNWKB000
BNU LONWORKS Gateway (AC 24 V) PLNWKB100
(Building Network
Unit) BACnet Gateway (DC 12V Adapter) PQNFB17B0 / PQNFB17C0
BACnet Gateway (AC 24 V) PQNFB17C1
Installation Refrigerant Charging Kit O (Logical operation)
PDI(power distribution indicator) PQNUD1S00
PDI(power distribution indicator) Premium PQNUD1S40

IO Module (ODU Dry Contact) PVDSMN000


Cycle Monitoring LG MV PRCT-FE1
Device Mobile LGMV(Bluetooth) PMVBTQ01

Note:
O : Applied, X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model
name, supplied with separate package.

R410A(50Hz/60Hz) _ 6
Shell & Coil

Outside Units

n Cooling Only (50/60Hz)

1. Specifications
2. Dimensions
3. Piping Diagrams
4. Wiring Diagrams
5. Field Wiring
6. Electric Characteristics
7. Capacity Tables
8. Operation Limits
9. Sound Levels
10. Head loss by Water flow
11. Accessories
Shell & Coil
1. Specifications
n Cooling Only [50Hz/60Hz]
System Capacity HP 10 20 30
Combination Unit ARWV100LAL4 ARWV200LAL4 ARWV300LAL4
ARWV100LAL4 ARWV100LAL4 ARWV100LAL4
Model Name
Independent Unit ARWV100LAL4 ARWV100LAL4
ARWV100LAL4
kW 28.0 56.0 84.0
Cooling kcal/h 24,100 48,200 72,200
Btu/h 95,900 191,100 286,700
Capacity
kW - - -
Heating kcal/h - - -
Btu/h - - -
Cooling kW 5.60 11.20 16.80
Input
Heating kW - - -
Casing Color Warm Gray, Morning Gray Warm Gray, Morning Gray Warm Gray, Morning Gray
Type Hemetically Sealed Scroll Hemetically Sealed Scroll Hemetically Sealed Scroll
Combination (Inverter) × 1 (Inverter) × 2 (Inverter) × 3
Piston Displacement cm3/rev 43.8 43.8 + 43.8 43.8 + 43.8 + 43.8

Outside Units
Number of revolution rev/min Inverter 3,600 at 60Hz Inverter 3,600 at 60Hz Inverter 3,600 at 60Hz
Compressor
Motor Output kW 4.2 4.2 + 4.2 4.2 + 4.2 + 4.2
Starting Method Direct On Line Direct On Line Direct On Line
Oil Type FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)
Oil Charge Amount cc 1,200 1,200 + 1,200 1,200 + 1,200 + 1,200
Type Copper Coil Copper Coil Copper Coil
Maximum Pressure Resistance kgf/cm2 45 45 45
Heat Exchanger
Head Loss kPa 36.5 36.5 + 36.5 36.5 + 36.5 + 36.5
Rated Water Flow LPM 96 96 + 96 96 + 96 + 96
Temp. Range of Cooling ℃(℉) 10 ~ 45(50 ~ 113) 10 ~ 45(50 ~ 113) 10 ~ 45(50 ~ 113)
Circulation Water Heating ℃(℉) - - -
Refrigerant Liquid mm(inch) 9.52(3/8) 12.7(1/2) 19.05(3/4)
Connecting Pipes Gas mm(inch) 22.2(7/8) 28.58(1-1/8) 34.9(1-3/8)
Inlet mm PT 25 (External Thread) PT 25 + PT 25 (External Thread) PT 25 + PT 25 + PT 25 (External Thread)
Water Connecting
Outlet mm PT 25 (External Thread) PT 25 + PT 25 (External Thread) PT 25 + PT 25 + PT 25 (External Thread)
Pipes
Drain Outlet mm 20 (External Thread) 20 (External Thread) 20 (External Thread)
mm (755 × 997 × 500) × 1 (755 × 997 × 500) × 2 (755 × 997 × 500) × 3
Dimensions(W×H×D)
inch (29-23/32 × 39-1/4 × 19-11/16) × 1 (29-23/32 × 39-1/4 × 19-11/16) × 2 (29-23/32 × 39-1/4 × 19-11/16) × 3
kg 126 x 1 126 x 2 126 x 3
Net Weight
lbs 278 x 1 278 x 2 278 x 3
Transmission Cable(CVV-SB) mm2 × No 1.0 ~ 1.5 × 2C 1.0 ~ 1.5 × 2C 1.0 ~ 1.5 × 2C
Name R410A R410A R410A
Refrigerant
Control Device EEV EEV EEV
3, 380 - 415, 50 3, 380 - 415, 50 3, 380 - 415, 50
Power Supply V, Ø, Hz
3, 380, 60 3, 380, 60 3, 380, 60

Notes:
1. Capacities and Inputs are based on the following conditions
Cooling : Indoor temp. 27°C [80.6°F]DB/19°C[66.2°F]WB
Water inlet temp. 30°C[86°F]
Heating : Indoor temp. 20°C[68°F]DB
Water Inlet temp. 20°C[68°F]
* Interconnecting Piping Length 7.5m (25 ft.)
* Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
h If it will be installed 20HP and 30HP, please contact the HQ.

R410A(50Hz/60Hz) _ 1
Shell & Coil
2. Dimensions

ARWV100LAL4
UWC
Outside Units

2 _ R410A(50Hz/60Hz)
Shell & Coil
3. Piping Diagrams
n ARWV100LAL4

Cooling Operation

Flare Flare
IDU HEX EEV Joint IDU HEX EEV Joint

Flare Flare
M Joint M Joint
IDU IDU

High Pressure Gas


High Pressure Liquid

Outside Units
Low Pressure Gas
Water
In

High
Water Pressure
Out Sensor

Ref.
In
Strainer
Gas
Ref.
Out Liquid
Check
valve

Discharge
Temp
[Oil
Separator]
[Accumulator]

High
Pressure
Switch

Check
valve
s

Oil
Low Return
Pressure
[Inv. Comp]

Sensor Suction Temp

SC Out
Temp

Sub-Cooler Strainer Liquid


Temp

Pressure Sensor EEV Service Valve Thermistor


Remarks
S
Pressure Switch Strainer Check Valve Solenoid Valve

R410A(50Hz/60Hz) _ 3
Shell & Coil
4. Wiring Diagrams
n ARWV100LAL4
Outside Units

4 _ R410A(50Hz/60Hz)
Shell & Coil
5. Field Wiring
u Example Connection of Power and Communication Cables
n Single Outside Unit - 3Ø, 380-415V

3 Phase 4 Wires
Power supply
50Hz 380-415V
[Outside Unit]
(Main Switch)
R S T N

Switch

Fuse
Power supply
1 Phase 50Hz
220-240V
L N
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)

Outside Units
Pull Box Pull Box Pull Box Pull Box
(Installer option) (Installer option) (Installer option) (Installer option)

Power Line Power Line Power Line Power Line


(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)

Communication Line
(3 Wires Cable)

[Indoor Units]

WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage.
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install a main electrical protection to interrupt power to all equipment of the system because this system consists of
the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while
the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.

Between Indoor and Master Outside unit

Master The GND terminal at the main PCB is


SODU B SODU A IDU B IDU A INT B INT A
Outside Unit a ‘-’ terminal for day contact, it is not the
point to make ground connection.

3(A) 4(B) 3(A) 4(B) 3(A) 4(B)

R410A(50Hz/60Hz) _ 5
Shell & Coil
5. Field Wiring
n Series Outside Unit - 3Ø, 380-415V
h If it will be installed 20HP and 30HP, please contact the HQ.
n When the power source is connected In series between the units.

3 Phase 4 Wires
Power supply
50Hz 380-415V
[Master] [Slave1] [Slave2]
(Main Switch)
R S T N

Switch

Fuse
Power supply
1 Phase 50Hz
220-240V
L N
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Outside Units

Pull Box Pull Box Pull Box Pull Box


(Installer option) (Installer option) (Installer option) (Installer option)

Power Line Power Line Power Line Power Line


(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)

Communication Line
(3 Wires Cable)

[Indoor Units]

n When the power source is supplied to Each outside unit individually.

3 Phase 4 Wires
Power supply
50Hz 380-415V
[Master] [Slave1] [Slave2]
(Main Switch)
R S T N R S T N R S T N

Switch Switch Switch

Fuse Fuse Fuse


Power supply
1 Phase 50Hz
220-240V
L N

Power Line
(2 Wires Cable)
Communication Line
Power Line
(2 Wires Cable)
(4 Wires Cable)

Pull Box Pull Box Pull Box Pull Box


(Installer option) (Installer option) (Installer option) (Installer option)

Power Line Power Line Power Line Power Line


(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)

Communication Line
(3 Wires Cable)

[Indoor Units]

6 _ R410A(50Hz/60Hz)
Shell & Coil
5. Field Wiring

WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage.
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install a main electrical protection to interrupt power to all equipment of the system because this system consists of
the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while
the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.

Between Indoor and Master Outside unit Master


SODU B SODU A IDU B IDU A INT B INT A
Outside unit
Master
SODU B SODU A IDU B IDU A INT B INT A
Outside Unit

Outside Units
Slave1
SODU B SODU A IDU B IDU A INT B INT A
Outside Unit
3(A) 4(B) 3(A) 4(B) 3(A) 4(B)

Slave2
SODU B SODU A IDU B IDU A INT B INT A
Outside Unit
The GND terminal at the main PCB is a ‘-’
terminal for dry contact.
It is not the point to make ground connec-
tion.
- Make sure that terminal number of master
and slave Outside units are matched.

R410A(50Hz/60Hz) _ 7
Shell & Coil
5. Field Wiring
u Example Connection of Communication Cable
[BUS type] [STAR type]
• Connection of communication cable must be • Abnormal operation can be caused by communica-
installed like below figure between indoor unit to out- tion defect, when connection of communication cable
side unit. is installed like below figure(STAR type).
Outside Units

8 _ R410A(50Hz/60Hz)
Shell & Coil
6. Electric Characteristics
u Wiring of Main Power Supply and Equipment Capacity
1. Use a separate power supply for the Outside Unit and Indoor Unit.
2. The wire size is the minimum value for metal conduit wiring. The electrical cable size should be 1 rank thicker taking into
account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
3. Specific wiring requirements should adhere to the wiring regulations of the region.
4. Electrical cable of parts of appliances for outside use should not be lighter than polychloroprene sheathed flexible cables.
5. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.

WARNING
• Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations and guidance of each electric power company.
• Make sure to use specified wires for connections so that no external force is imparted to terminal connections.
If connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may
include some amount of direct current.

Outside Units
CAUTION
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is
installed, it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire
with too large capacity may cause a malfunction of unit or fire.

R410A(50Hz/60Hz) _ 9
Shell & Coil
6. Electric Characteristics
n 50Hz
Unit Power supply Comp OFM
Model
Hz Volts Voltage-range MCA TOCA MFA MSC RLA kW FLA
ARWV100LAL4 50 380-415 Min.:342,Max.:456 15.4 20 20 - 19.6 - -
ARWV200LAL4 50 380-415 Min.:342,Max.:456 15.4 + 15.4 20 + 20 20 + 20 - 19.6 + 19.6 - -
ARWV300LAL4 50 380-415 Min.:342,Max.:456 15.4 + 15.4 + 15.4 20 + 20 + 20 20 + 20 + 20 - 19.6 + 19.6 + 19.6 - -

n 60Hz
Unit Power supply Comp OFM
Model
Hz Volts Voltage-range MCA TOCA MFA MSC RLA kW FLA
ARWV100LAL4 60 380 Min.:342,Max.:418 15.4 20 20 - 19.6 - -
ARWV200LAL4 60 380 Min.:342,Max.:418 15.4 + 15.4 20 + 20 20 + 20 - 19.6 + 19.6 - -
Outside Units

ARWV300LAL4 60 380 Min.:342,Max.:418 15.4 + 15.4 + 15.4 20 + 20 + 20 20 + 20 + 20 - 19.6 + 19.6 + 19.6 - -

Notes:
1. Voltage range
Voltage supplied to the unit terminals should be within the MCA : Minimum Circuit Amperes (A)
minimum and maximum range MSC : Maximum Starting Current
2. Maximum allowable voltage unbalance between RLA : Rated Load Amperes (A)
phase is 2 % FLA : Full Load Amperes (A)
3. Select wire spec. based on the larger value of MCA or MFA: Maximum Fuse Amperes(A)
TOCA. TOCA: Total Over Current Amperes(A)
4. TOCA means the total over current value of each outside
unit.
5. MSC means the Max. current during the starting of
compressor.
6. Recommended circuit breaker is ELCB
(Earth Leakage Circuit Breaker)
7. MFA is used to select the circuit breaker and ground fault
circuit interrupter (earth leakage circuit breaker)

10 _ R410A(50Hz/60Hz)
Shell & Coil
7. Capacity Tables
7.1 Cooling Only
Cooling Capacity
Cooling Capacity(10HP)
ARWV100LAL4
Inlet Water Indoor Air temperature (°CWB)
Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
48 26.9 4.33 28.9 4.33 31.1 4.39 32.2 4.51 33.3 4.57 35.5 4.57 37.8 4.63
15 96 26.9 4.15 28.9 4.21 31.1 4.33 32.2 4.39 33.3 4.39 35.5 4.45 37.8 4.57
120 26.9 4.09 28.9 4.15 31.1 4.27 32.2 4.33 33.3 4.33 35.5 4.45 37.8 4.51
48 26.9 4.75 28.9 4.75 31.1 4.81 32.2 4.93 33.3 4.93 35.5 4.93 37.8 4.99
20 96 26.9 4.57 28.9 4.63 31.1 4.69 32.2 4.75 33.3 4.75 35.5 4.81 37.8 4.87
120 26.9 4.51 28.9 4.57 31.1 4.63 32.2 4.69 33.3 4.69 35.5 4.75 37.8 4.81
48 26.9 5.29 28.9 5.29 31.1 5.35 32.2 5.47 33.3 5.47 35.5 5.47 37.8 5.47
25 96 26.9 5.17 28.9 5.17 31.1 5.23 32.2 5.23 33.3 5.29 35.5 5.29 37.8 5.35
120 26.9 5.05 28.9 5.05 31.1 5.11 32.2 5.11 33.3 5.17 35.5 5.17 37.8 5.23
130 48 26.9 6.01 28.9 6.01 31.1 6.07 32.2 6.19 33.3 6.19 35.5 6.19 37.8 6.19
30 96 26.9 5.83 28.9 5.83 31.1 5.89 32.2 5.89 33.3 5.89 35.5 5.89 37.8 5.89
120 26.9 5.71 28.9 5.71 31.1 5.77 32.2 5.77 33.3 5.77 35.5 5.77 37.8 5.77
48 26.0 6.55 28.0 6.55 30.0 6.55 31.0 6.79 32.0 6.79 34.2 6.79 36.3 6.79
35 96 26.3 6.37 28.2 6.43 30.1 6.43 31.2 6.43 32.2 6.43 34.3 6.43 36.5 6.49
Outside Units

120 26.3 6.19 28.2 6.25 30.2 6.25 31.2 6.25 32.3 6.31 34.3 6.31 36.6 6.31
48 24.9 7.09 26.6 7.09 28.6 7.15 29.5 7.39 30.5 7.39 32.4 7.39 34.4 7.39
40 96 25.2 6.97 27.0 6.97 28.9 7.03 29.8 7.03 30.8 7.03 32.8 7.03 34.8 7.09
120 25.3 6.79 27.1 6.79 28.9 6.85 29.9 6.85 30.9 6.85 32.9 6.85 34.9 6.91
48 25.7 4.21 27.7 4.27 29.7 4.40 30.8 4.40 31.9 4.46 34.0 4.46 36.2 4.59
15 96 25.7 4.09 27.7 4.15 29.7 4.21 30.8 4.27 31.9 4.34 34.0 4.40 36.2 4.53
120 25.7 3.96 27.7 4.09 29.7 4.15 30.8 4.21 31.9 4.27 34.0 4.34 36.2 4.46
48 25.7 4.71 27.7 4.78 29.7 4.84 30.8 4.84 31.9 4.84 34.0 4.84 36.2 4.90
20 96 25.7 4.46 27.7 4.59 29.7 4.65 30.8 4.65 31.9 4.65 34.0 4.78 36.2 4.84
120 25.7 4.40 27.7 4.46 29.7 4.53 30.8 4.59 31.9 4.59 34.0 4.65 36.2 4.71
48 25.7 5.28 27.7 5.34 29.7 5.41 30.8 5.41 31.9 5.41 34.0 5.34 36.2 5.34
25 96 25.7 5.03 27.7 5.09 29.7 5.15 30.8 5.15 31.9 5.15 34.0 5.22 36.2 5.28
120 120 25.7 4.90 27.7 4.97 29.7 5.03 30.8 5.03 31.9 5.09 34.0 5.09 36.2 5.15
48 25.7 6.03 27.7 6.10 29.7 6.10 30.8 6.10 31.9 6.10 34.0 6.10 36.2 6.10
30 96 25.7 5.72 27.7 5.78 29.7 5.78 30.8 5.78 31.9 5.78 34.0 5.85 36.2 5.85
120 25.7 5.59 27.7 5.59 29.7 5.66 30.8 5.66 31.9 5.66 34.0 5.72 36.2 5.72
48 24.9 6.66 26.8 6.66 28.7 6.66 29.7 6.66 30.6 6.66 32.7 6.66 34.7 6.66
35 96 25.1 6.29 26.9 6.29 28.8 6.35 29.8 6.35 30.8 6.35 32.8 6.35 34.9 6.41
120 25.1 6.10 26.9 6.16 28.9 6.16 29.9 6.16 30.9 6.22 32.8 6.22 35.0 6.22
48 23.8 7.23 25.5 7.29 27.3 7.29 28.2 7.29 29.1 7.29 31.0 7.29 32.9 7.29
40 96 24.1 6.91 25.8 6.91 27.6 6.91 28.5 6.98 29.4 6.98 31.3 6.98 33.3 6.98
120 24.2 6.73 25.9 6.73 27.7 6.79 28.6 6.79 29.6 6.79 31.5 6.79 33.4 6.79
48 24.5 4.15 26.4 4.21 28.4 4.28 29.4 4.35 30.4 4.35 32.4 4.48 34.5 4.54
15 96 24.5 3.95 26.4 4.02 28.4 4.15 29.4 4.21 30.4 4.28 32.4 4.35 34.5 4.41
120 24.5 3.88 26.4 3.95 28.4 4.08 29.4 4.15 30.4 4.21 32.4 4.28 34.5 4.41
48 24.5 4.61 26.4 4.67 28.4 4.74 29.4 4.74 30.4 4.81 32.4 4.81 34.5 4.87
20 96 24.5 4.41 26.4 4.48 28.4 4.54 29.4 4.54 30.4 4.61 32.4 4.67 34.5 4.74
120 24.5 4.28 26.4 4.35 28.4 4.48 29.4 4.48 30.4 4.54 32.4 4.61 34.5 4.67
48 24.5 5.20 26.4 5.27 28.4 5.27 29.4 5.27 30.4 5.33 32.4 5.33 34.5 5.40
25 96 24.5 4.94 26.4 5.00 28.4 5.07 29.4 5.07 30.4 5.07 32.4 5.14 34.5 5.14
120 24.5 4.81 26.4 4.87 28.4 4.94 29.4 4.94 30.4 5.00 32.4 5.00 34.5 5.07
110 48 24.5 5.93 26.4 5.99 28.4 5.99 29.4 5.99 30.4 5.99 32.4 5.99 34.5 6.06
30 96 24.5 5.66 26.4 5.66 28.4 5.73 29.4 5.73 30.4 5.73 32.4 5.73 34.5 5.73
120 24.5 5.47 26.4 5.53 28.4 5.53 29.4 5.53 30.4 5.60 32.4 5.60 34.5 5.60
48 23.8 6.52 25.6 6.58 27.4 6.58 28.3 6.58 29.3 6.58 31.2 6.58 33.2 6.58
35 96 24.0 6.19 25.7 6.26 27.5 6.26 28.5 6.26 29.4 6.26 31.4 6.32 33.3 6.32
120 24.0 6.06 25.7 6.06 27.6 6.06 28.5 6.12 29.5 6.12 31.4 6.12 33.4 6.12
48 22.7 7.18 24.3 7.18 26.1 7.18 26.9 7.24 27.8 7.24 29.6 7.24 31.4 7.24
40 96 23.0 6.78 24.6 6.85 26.4 6.85 27.2 6.85 28.1 6.85 29.9 6.85 31.8 6.91
120 23.1 6.58 24.8 6.65 26.4 6.65 27.3 6.65 28.2 6.65 30.1 6.72 31.9 6.72
48 23.4 4.01 25.2 4.08 27.0 4.22 28.0 4.22 29.0 4.29 30.9 4.36 32.9 4.49
15 96 23.4 3.87 25.2 3.94 27.0 4.08 28.0 4.08 29.0 4.15 30.9 4.29 32.9 4.36
120 23.4 3.80 25.2 3.87 27.0 4.01 28.0 4.01 29.0 4.08 30.9 4.22 32.9 4.29
48 23.4 4.49 25.2 4.56 27.0 4.63 28.0 4.63 29.0 4.70 30.9 4.77 32.9 4.84
100 20 96 23.4 4.29 25.2 4.36 27.0 4.42 28.0 4.49 29.0 4.49 30.9 4.56 32.9 4.63
120 23.4 4.22 25.2 4.29 27.0 4.36 28.0 4.36 29.0 4.42 30.9 4.49 32.9 4.56
48 23.4 5.12 25.2 5.12 27.0 5.19 28.0 5.19 29.0 5.25 30.9 5.25 32.9 5.32
25 96 23.4 4.84 25.2 4.91 27.0 4.98 28.0 4.98 29.0 4.98 30.9 5.05 32.9 5.12
120 23.4 4.70 25.2 4.77 27.0 4.84 28.0 4.84 29.0 4.91 30.9 4.91 32.9 4.98
TC : Total Capacity(kW)
PI : Power Input(kW)

11 _ R410A(50Hz/60Hz)
Shell & Coil
7. Capacity Tables

Cooling Capacity(10HP)

Inlet Water Indoor Air temperature (°CWB)


Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
48 23.4 5.88 25.2 5.88 27.0 5.88 28.0 5.95 29.0 5.95 30.9 5.95 32.9 5.95
30 96 23.4 5.53 25.2 5.60 27.0 5.60 28.0 5.60 29.0 5.60 30.9 5.67 32.9 5.67
120 23.4 5.39 25.2 5.39 27.0 5.46 28.0 5.46 29.0 5.46 30.9 5.53 32.9 5.53
48 22.6 6.43 24.3 6.50 26.1 6.50 27.0 6.50 27.9 6.50 29.7 6.50 31.6 6.50
100 35 96 22.8 6.08 24.5 6.15 26.2 6.15 27.1 6.15 28.0 6.15 29.9 6.22 31.7 6.22
120 22.8 5.95 24.5 5.95 26.3 6.01 27.2 6.01 28.1 6.01 29.9 6.01 31.8 6.08
48 21.7 7.12 23.2 7.12 24.8 7.12 25.7 7.12 26.5 7.12 28.2 7.12 29.9 7.12
40 96 21.9 6.71 23.4 6.71 25.1 6.78 25.9 6.78 26.8 6.78 28.5 6.78 30.3 6.84
120 22.0 6.50 23.6 6.57 25.2 6.57 26.0 6.57 26.9 6.64 28.6 6.64 30.3 6.64
48 21.0 3.11 22.7 3.17 24.3 3.24 25.2 3.30 26.1 3.30 27.8 3.42 29.6 3.48
15 96 21.0 2.99 22.7 3.05 24.3 3.11 25.2 3.17 26.1 3.24 27.8 3.30 29.6 3.42
120 21.0 2.92 22.7 2.99 24.3 3.11 25.2 3.11 26.1 3.17 27.8 3.30 29.6 3.36
48 21.0 3.48 22.7 3.55 24.3 3.61 25.2 3.61 26.1 3.67 27.8 3.73 29.6 3.80
20 96 21.0 3.30 22.7 3.36 24.3 3.42 25.2 3.48 26.1 3.48 27.8 3.61 29.6 3.67

Outside Units
120 21.0 3.24 22.7 3.30 24.3 3.36 25.2 3.42 26.1 3.42 27.8 3.55 29.6 3.61
48 21.0 3.92 22.7 3.98 24.3 4.04 25.2 4.04 26.1 4.11 27.8 4.11 29.6 4.17
25 96 21.0 3.73 22.7 3.80 24.3 3.86 25.2 3.86 26.1 3.92 27.8 3.92 29.6 3.98
120 21.0 3.67 22.7 3.67 24.3 3.73 25.2 3.80 26.1 3.80 27.8 3.86 29.6 3.92
90
48 21.0 4.54 22.7 4.60 24.3 4.60 25.2 4.60 26.1 4.67 27.8 4.67 29.6 4.67
30 96 21.0 4.29 22.7 4.36 24.3 4.36 25.2 4.36 26.1 4.42 27.8 4.42 29.6 4.48
120 21.0 4.17 22.7 4.23 24.3 4.23 25.2 4.29 26.1 4.29 27.8 4.36 29.6 4.36
48 21.0 5.35 22.7 5.35 24.3 5.35 25.2 5.35 26.1 5.35 27.8 5.35 29.6 5.35
35 96 21.0 4.98 22.7 5.04 24.3 5.04 25.2 5.04 26.1 5.04 27.8 5.04 29.6 5.04
120 21.0 4.85 22.7 4.85 24.3 4.92 25.2 4.92 26.1 4.92 27.8 4.92 29.6 4.92
48 21.0 6.28 22.7 6.28 24.3 6.28 25.2 6.28 26.1 6.28 27.8 6.28 29.6 6.28
40 96 21.0 5.85 22.7 5.91 24.3 5.91 25.2 5.91 26.1 5.91 27.8 5.91 29.6 5.91
120 21.0 5.66 22.7 5.72 24.3 5.72 25.2 5.72 26.1 5.72 27.8 5.72 29.6 5.72
48 18.7 2.32 20.1 2.38 21.7 2.43 22.4 2.49 23.2 2.49 24.7 2.60 26.3 2.65
15 96 18.7 2.21 20.1 2.27 21.7 2.38 22.4 2.38 23.2 2.43 24.7 2.49 26.3 2.60
120 18.7 2.16 20.1 2.21 21.7 2.32 22.4 2.38 23.2 2.38 24.7 2.49 26.3 2.60
48 18.7 2.60 20.1 2.65 21.7 2.71 22.4 2.71 23.2 2.77 24.7 2.82 26.3 2.88
20 96 18.7 2.49 20.1 2.54 21.7 2.60 22.4 2.60 23.2 2.65 24.7 2.71 26.3 2.77
120 18.7 2.43 20.1 2.49 21.7 2.54 22.4 2.54 23.2 2.60 24.7 2.65 26.3 2.77
48 18.7 2.99 20.1 3.04 21.7 3.04 22.4 3.10 23.2 3.10 24.7 3.15 26.3 3.15
25 96 18.7 2.82 20.1 2.88 21.7 2.93 22.4 2.93 23.2 2.93 24.7 2.99 26.3 3.04
120 18.7 2.77 20.1 2.77 21.7 2.82 22.4 2.88 23.2 2.88 24.7 2.93 26.3 2.99
80
48 18.7 3.48 20.1 3.48 21.7 3.54 22.4 3.54 23.2 3.54 24.7 3.54 26.3 3.60
30 96 18.7 3.26 20.1 3.26 21.7 3.32 22.4 3.32 23.2 3.37 24.7 3.37 26.3 3.43
120 18.7 3.15 20.1 3.21 21.7 3.21 22.4 3.26 23.2 3.26 24.7 3.32 26.3 3.32
48 18.7 4.09 20.1 4.09 21.7 4.09 22.4 4.09 23.2 4.09 24.7 4.09 26.3 4.09
35 96 18.7 3.82 20.1 3.82 21.7 3.87 22.4 3.87 23.2 3.87 24.7 3.87 26.3 3.87
120 18.7 3.71 20.1 3.71 21.7 3.76 22.4 3.76 23.2 3.76 24.7 3.76 26.3 3.76
48 18.7 4.81 20.1 4.81 21.7 4.87 22.4 4.87 23.2 4.87 24.7 4.87 26.3 4.87
40 96 18.7 4.54 20.1 4.54 21.7 4.54 22.4 4.54 23.2 4.54 24.7 4.54 26.3 4.54
120 18.7 4.37 20.1 4.37 21.7 4.37 22.4 4.37 23.2 4.37 24.7 4.37 26.3 4.37
48 16.3 1.65 17.7 1.69 18.9 1.74 19.6 1.79 20.3 1.84 21.7 1.89 23.0 1.98
15 96 16.3 1.60 17.7 1.65 18.9 1.69 19.6 1.74 20.3 1.79 21.7 1.84 23.0 1.94
120 16.3 1.55 17.7 1.60 18.9 1.69 19.6 1.69 20.3 1.74 21.7 1.84 23.0 1.89
48 16.3 1.89 17.7 1.94 18.9 1.98 19.6 1.98 20.3 2.03 21.7 2.08 23.0 2.13
20 96 16.3 1.79 17.7 1.84 18.9 1.89 19.6 1.89 20.3 1.94 21.7 1.98 23.0 2.03
120 16.3 1.74 17.7 1.79 18.9 1.84 19.6 1.89 20.3 1.89 21.7 1.98 23.0 2.03
48 16.3 2.18 17.7 2.23 18.9 2.23 19.6 2.27 20.3 2.27 21.7 2.32 23.0 2.37
25 96 16.3 2.03 17.7 2.08 18.9 2.13 19.6 2.13 20.3 2.18 21.7 2.23 23.0 2.23
70 120 16.3 1.98 17.7 2.03 18.9 2.08 19.6 2.08 20.3 2.08 21.7 2.18 23.0 2.23
48 16.3 2.56 17.7 2.56 18.9 2.56 19.6 2.61 20.3 2.61 21.7 2.61 23.0 2.66
30 96 16.3 2.37 17.7 2.42 18.9 2.42 19.6 2.47 20.3 2.47 21.7 2.52 23.0 2.52
120 16.3 2.32 17.7 2.32 18.9 2.37 19.6 2.37 20.3 2.37 21.7 2.42 23.0 2.47
48 16.3 3.00 17.7 3.05 18.9 3.05 19.6 3.05 20.3 3.05 21.7 3.05 23.0 3.05
35 96 16.3 2.81 17.7 2.86 18.9 2.86 19.6 2.86 20.3 2.86 21.7 2.86 23.0 2.86
120 16.3 2.71 17.7 2.76 18.9 2.76 19.6 2.76 20.3 2.76 21.7 2.81 23.0 2.81
48 16.3 3.63 17.7 3.63 18.9 3.63 19.6 3.63 20.3 3.63 21.7 3.63 23.0 3.63
40 96 16.3 3.34 17.7 3.39 18.9 3.39 19.6 3.39 20.3 3.39 21.7 3.39 23.0 3.39
120 16.3 3.24 17.7 3.24 18.9 3.24 19.6 3.24 20.3 3.24 21.7 3.24 23.0 3.24
TC : Total Capacity(kW)
PI : Power Input(kW)

R410A(50Hz/60Hz) _ 12
Shell & Coil
7. Capacity Tables

Cooling Capacity(10HP)

Inlet Water Indoor Air temperature (°CWB)


Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
48 14.0 1.29 15.1 1.34 16.2 1.38 16.8 1.43 17.4 1.48 18.6 1.53 19.7 1.62
15 96 14.0 1.24 15.1 1.29 16.2 1.34 16.8 1.38 17.4 1.43 18.6 1.48 19.7 1.57
120 14.0 1.19 15.1 1.29 16.2 1.34 16.8 1.38 17.4 1.38 18.6 1.48 19.7 1.57
48 14.0 1.48 15.1 1.53 16.2 1.57 16.8 1.57 17.4 1.62 18.6 1.67 19.7 1.72
20 96 14.0 1.38 15.1 1.43 16.2 1.48 16.8 1.53 17.4 1.53 18.6 1.62 19.7 1.67
120 14.0 1.34 15.1 1.43 16.2 1.48 16.8 1.48 17.4 1.53 18.6 1.57 19.7 1.67
48 14.0 1.72 15.1 1.77 16.2 1.81 16.8 1.81 17.4 1.81 18.6 1.86 19.7 1.91
25 96 14.0 1.62 15.1 1.67 16.2 1.72 16.8 1.72 17.4 1.72 18.6 1.77 19.7 1.81
120 14.0 1.57 15.1 1.62 16.2 1.67 16.8 1.67 17.4 1.67 18.6 1.77 19.7 1.81
60 48 14.0 2.05 15.1 2.05 16.2 2.10 16.8 2.10 17.4 2.10 18.6 2.15 19.7 2.15
30 96 14.0 1.91 15.1 1.96 16.2 1.96 16.8 2.00 17.4 2.00 18.6 2.00 19.7 2.05
120 14.0 1.86 15.1 1.86 16.2 1.91 16.8 1.91 17.4 1.91 18.6 1.96 19.7 2.00
48 14.0 2.43 15.1 2.48 16.2 2.48 16.8 2.48 17.4 2.48 18.6 2.48 19.7 2.48
35 96 14.0 2.29 15.1 2.29 16.2 2.29 16.8 2.34 17.4 2.34 18.6 2.34 19.7 2.34
Outside Units

120 14.0 2.19 15.1 2.19 16.2 2.24 16.8 2.24 17.4 2.24 18.6 2.29 19.7 2.29
48 14.0 2.96 15.1 2.96 16.2 2.96 16.8 2.96 17.4 2.96 18.6 2.96 19.7 2.96
40 96 14.0 2.72 15.1 2.77 16.2 2.77 16.8 2.77 17.4 2.77 18.6 2.77 19.7 2.77
120 14.0 2.62 15.1 2.67 16.2 2.67 16.8 2.67 17.4 2.67 18.6 2.67 19.7 2.67
48 11.7 0.99 12.6 1.03 13.5 1.08 14.0 1.11 14.5 1.13 15.4 1.22 16.5 1.27
15 96 11.7 0.94 12.6 0.99 13.5 1.03 14.0 1.08 14.5 1.07 15.4 1.18 16.5 1.27
120 11.7 0.89 12.6 0.94 13.5 0.99 14.0 1.03 14.5 1.02 15.4 1.18 16.5 1.27
48 11.7 1.13 12.6 1.18 13.5 1.22 14.0 1.22 14.5 1.27 15.4 1.32 16.5 1.36
20 96 11.7 1.07 12.6 1.12 13.5 1.13 14.0 1.18 14.5 1.18 15.4 1.27 16.5 1.32
120 11.7 1.02 12.6 1.06 13.5 1.10 14.0 1.13 14.5 1.14 15.4 1.22 16.5 1.32
48 11.7 1.32 12.6 1.36 13.5 1.36 14.0 1.41 14.5 1.41 15.4 1.46 16.5 1.50
25 96 11.7 1.22 12.6 1.27 13.5 1.32 14.0 1.32 14.5 1.36 15.4 1.41 16.5 1.46
120 11.7 1.18 12.6 1.22 13.5 1.27 14.0 1.27 14.5 1.32 15.4 1.36 16.5 1.41
50
48 11.7 1.60 12.6 1.60 13.5 1.65 14.0 1.65 14.5 1.65 15.4 1.69 16.5 1.74
30 96 11.7 1.46 12.6 1.50 13.5 1.50 14.0 1.55 14.5 1.55 15.4 1.60 16.5 1.65
120 11.7 1.41 12.6 1.46 13.5 1.46 14.0 1.50 14.5 1.50 15.4 1.55 16.5 1.60
48 11.7 1.93 12.6 1.93 13.5 1.93 14.0 1.97 14.5 1.97 15.4 1.97 16.5 1.97
35 96 11.7 1.79 12.6 1.79 13.5 1.83 14.0 1.83 14.5 1.83 15.4 1.83 16.5 1.88
120 11.7 1.74 12.6 1.74 13.5 1.74 14.0 1.74 14.5 1.79 15.4 1.79 16.5 1.83
48 11.7 2.35 12.6 2.35 13.5 2.35 14.0 2.35 14.5 2.35 15.4 2.35 16.5 2.35
40 96 11.7 2.16 12.6 2.16 13.5 2.16 14.0 2.21 14.5 2.21 15.4 2.21 16.5 2.21
120 11.7 2.12 12.6 2.12 13.5 2.12 14.0 2.12 14.5 2.12 15.4 2.12 16.5 2.12

TC : Total Capacity(kW)
PI : Power Input(kW)

13 _ R410A(50Hz/60Hz)
Shell & Coil
7. Capacity Tables

Cooling Capacity(20HP)
ARWV200LAL4
Inlet Water Indoor Air temperature (°CWB)
Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
96 53.8 8.66 57.9 8.66 62.2 8.78 64.4 9.02 66.6 9.14 71.1 9.14 75.7 9.26
15 192 53.8 8.30 57.9 8.42 62.2 8.66 64.4 8.78 66.6 8.78 71.1 8.90 75.7 9.14
240 53.8 8.18 57.9 8.30 62.2 8.54 64.4 8.66 66.6 8.66 71.1 8.90 75.7 9.02
96 53.8 9.50 57.9 9.50 62.2 9.62 64.4 9.86 66.6 9.86 71.1 9.86 75.7 9.98
20 192 53.8 9.14 57.9 9.26 62.2 9.38 64.4 9.50 66.6 9.50 71.1 9.62 75.7 9.74
240 53.8 9.02 57.9 9.14 62.2 9.26 64.4 9.38 66.6 9.38 71.1 9.50 75.7 9.62
96 53.8 10.58 57.9 10.58 62.2 10.70 64.4 10.94 66.6 10.94 71.1 10.94 75.7 10.94
25 192 53.8 10.34 57.9 10.34 62.2 10.46 64.4 10.46 66.6 10.58 71.1 10.58 75.7 10.70
240 53.8 10.10 57.9 10.10 62.2 10.22 64.4 10.22 66.6 10.34 71.1 10.34 75.7 10.46
130 96 53.8 12.02 57.9 12.02 62.2 12.14 64.4 12.38 66.6 12.38 71.1 12.38 75.7 12.38
30 192 53.8 11.66 57.9 11.66 62.2 11.78 64.4 11.78 66.6 11.78 71.1 11.78 75.7 11.78
240 53.8 11.42 57.9 11.42 62.2 11.54 64.4 11.54 66.6 11.54 71.1 11.54 75.7 11.54
96 52.0 13.11 56.0 13.11 60.0 13.11 62.0 13.59 64.1 13.59 68.4 13.59 72.6 13.59
35 192 52.5 12.75 56.3 12.87 60.3 12.87 62.3 12.87 64.4 12.87 68.7 12.87 73.0 12.99

Outside Units
240 52.5 12.38 56.3 12.50 60.4 12.50 62.5 12.50 64.6 12.62 68.7 12.62 73.1 12.62
96 49.8 14.19 53.3 14.19 57.1 14.31 59.0 14.79 60.9 14.79 64.9 14.79 68.8 14.79
40 192 50.4 13.95 53.9 13.95 57.7 14.07 59.6 14.07 61.5 14.07 65.5 14.07 69.6 14.19
240 50.6 13.59 54.2 13.59 57.9 13.71 59.8 13.71 61.9 13.71 65.8 13.71 69.8 13.83
96 51.4 8.42 55.4 8.55 59.5 8.80 61.6 8.80 63.7 8.92 68.0 8.92 72.4 9.18
15 192 51.4 8.17 55.4 8.30 59.5 8.42 61.6 8.55 63.7 8.67 68.0 8.80 72.4 9.05
240 51.4 7.92 55.4 8.17 59.5 8.30 61.6 8.42 63.7 8.55 68.0 8.67 72.4 8.92
96 51.4 9.43 55.4 9.55 59.5 9.68 61.6 9.68 63.7 9.68 68.0 9.68 72.4 9.80
20 192 51.4 8.92 55.4 9.18 59.5 9.30 61.6 9.30 63.7 9.30 68.0 9.55 72.4 9.68
240 51.4 8.80 55.4 8.92 59.5 9.05 61.6 9.18 63.7 9.18 68.0 9.30 72.4 9.43
96 51.4 10.56 55.4 10.68 59.5 10.81 61.6 10.81 63.7 10.81 68.0 10.68 72.4 10.68
25 192 51.4 10.06 55.4 10.18 59.5 10.31 61.6 10.31 63.7 10.31 68.0 10.43 72.4 10.56
120 240 51.4 9.80 55.4 9.93 59.5 10.06 61.6 10.06 63.7 10.18 68.0 10.18 72.4 10.31
96 51.4 12.07 55.4 12.19 59.5 12.19 61.6 12.19 63.7 12.19 68.0 12.19 72.4 12.19
30 192 51.4 11.44 55.4 11.56 59.5 11.56 61.6 11.56 63.7 11.56 68.0 11.69 72.4 11.69
240 51.4 11.19 55.4 11.19 59.5 11.31 61.6 11.31 63.7 11.31 68.0 11.44 72.4 11.44
96 49.8 13.32 53.6 13.32 57.4 13.32 59.3 13.32 61.3 13.32 65.4 13.32 69.5 13.32
35 192 50.2 12.57 53.9 12.57 57.7 12.70 59.6 12.70 61.6 12.70 65.7 12.70 69.8 12.82
240 50.2 12.19 53.9 12.32 57.8 12.32 59.8 12.32 61.8 12.44 65.7 12.44 69.9 12.44
96 47.6 14.46 51.0 14.58 54.6 14.58 56.4 14.58 58.3 14.58 62.1 14.58 65.8 14.58
40 192 48.2 13.83 51.6 13.83 55.2 13.83 57.0 13.95 58.9 13.95 62.7 13.95 66.6 13.95
240 48.4 13.45 51.9 13.45 55.4 13.58 57.2 13.58 59.2 13.58 63.0 13.58 66.8 13.58
96 49.1 8.30 52.9 8.43 56.8 8.56 58.8 8.69 60.8 8.69 64.9 8.95 69.1 9.09
15 192 49.1 7.90 52.9 8.03 56.8 8.30 58.8 8.43 60.8 8.56 64.9 8.69 69.1 8.82
240 49.1 7.77 52.9 7.90 56.8 8.16 58.8 8.30 60.8 8.43 64.9 8.56 69.1 8.82
96 49.1 9.22 52.9 9.35 56.8 9.48 58.8 9.48 60.8 9.61 64.9 9.61 69.1 9.74
20 192 49.1 8.82 52.9 8.95 56.8 9.09 58.8 9.09 60.8 9.22 64.9 9.35 69.1 9.48
240 49.1 8.56 52.9 8.69 56.8 8.95 58.8 8.95 60.8 9.09 64.9 9.22 69.1 9.35
96 49.1 10.40 52.9 10.53 56.8 10.53 58.8 10.53 60.8 10.67 64.9 10.67 69.1 10.80
25 192 49.1 9.88 52.9 10.01 56.8 10.14 58.8 10.14 60.8 10.14 64.9 10.27 69.1 10.27
240 49.1 9.61 52.9 9.74 56.8 9.88 58.8 9.88 60.8 10.01 64.9 10.01 69.1 10.14
110 96 49.1 11.85 52.9 11.98 56.8 11.98 58.8 11.98 60.8 11.98 64.9 11.98 69.1 12.12
30 192 49.1 11.33 52.9 11.33 56.8 11.46 58.8 11.46 60.8 11.46 64.9 11.46 69.1 11.46
240 49.1 10.93 52.9 11.06 56.8 11.06 58.8 11.06 60.8 11.19 64.9 11.19 69.1 11.19
96 47.5 13.04 51.1 13.17 54.7 13.17 56.6 13.17 58.5 13.17 62.4 13.17 66.3 13.17
35 192 47.9 12.38 51.4 12.51 55.0 12.51 56.9 12.51 58.8 12.51 62.7 12.64 66.6 12.64
240 47.9 12.12 51.4 12.12 55.2 12.12 57.1 12.25 58.9 12.25 62.7 12.25 66.8 12.25
96 45.5 14.35 48.7 14.35 52.1 14.35 53.9 14.49 55.6 14.49 59.2 14.49 62.9 14.49
40 192 46.1 13.56 49.2 13.70 52.7 13.70 54.5 13.70 56.2 13.70 59.8 13.70 63.6 13.83
240 46.2 13.17 49.5 13.30 52.9 13.30 54.6 13.30 56.5 13.30 60.1 13.43 63.7 13.43
96 46.8 8.02 50.3 8.16 54.1 8.43 56.0 8.43 57.9 8.57 61.8 8.71 65.8 8.99
15 192 46.8 7.74 50.3 7.88 54.1 8.16 56.0 8.16 57.9 8.30 61.8 8.57 65.8 8.71
240 46.8 7.60 50.3 7.74 54.1 8.02 56.0 8.02 57.9 8.16 61.8 8.43 65.8 8.57
96 46.8 8.99 50.3 9.13 54.1 9.26 56.0 9.26 57.9 9.40 61.8 9.54 65.8 9.68
100 20 192 46.8 8.57 50.3 8.71 54.1 8.85 56.0 8.99 57.9 8.99 61.8 9.13 65.8 9.26
240 46.8 8.43 50.3 8.57 54.1 8.71 56.0 8.71 57.9 8.85 61.8 8.99 65.8 9.13
96 46.8 10.23 50.3 10.23 54.1 10.37 56.0 10.37 57.9 10.51 61.8 10.51 65.8 10.65
25 192 46.8 9.68 50.3 9.82 54.1 9.96 56.0 9.96 57.9 9.96 61.8 10.09 65.8 10.23
240 46.8 9.40 50.3 9.54 54.1 9.68 56.0 9.68 57.9 9.82 61.8 9.82 65.8 9.96
TC : Total Capacity(kW)
PI : Power Input(kW)

R410A(50Hz/60Hz) _ 14
Shell & Coil
7. Capacity Tables

Cooling Capacity(20HP)

Inlet Water Indoor Air temperature (°CWB)


Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
96 46.8 11.75 50.3 11.75 54.1 11.75 56.0 11.89 57.9 11.89 61.8 11.89 65.8 11.89
30 192 46.8 11.06 50.3 11.20 54.1 11.20 56.0 11.20 57.9 11.20 61.8 11.34 65.8 11.34
240 46.8 10.79 50.3 10.79 54.1 10.92 56.0 10.92 57.9 10.92 61.8 11.06 65.8 11.06
96 45.2 12.86 48.7 13.00 52.1 13.00 53.9 13.00 55.7 13.00 59.4 13.00 63.2 13.00
100 35 192 45.7 12.17 49.0 12.31 52.4 12.31 54.2 12.31 56.0 12.31 59.7 12.44 63.4 12.44
240 45.7 11.89 49.0 11.89 52.6 12.03 54.3 12.03 56.1 12.03 59.7 12.03 63.6 12.17
96 43.3 14.24 46.3 14.24 49.7 14.24 51.3 14.24 53.0 14.24 56.4 14.24 59.9 14.24
40 192 43.9 13.41 46.9 13.41 50.2 13.55 51.9 13.55 53.5 13.55 57.0 13.55 60.6 13.69
240 44.0 13.00 47.2 13.14 50.3 13.14 52.0 13.14 53.8 13.27 57.2 13.27 60.7 13.27
96 42.1 6.22 45.4 6.35 48.7 6.47 50.3 6.60 52.1 6.60 55.6 6.84 59.2 6.97
15 192 42.1 5.97 45.4 6.10 48.7 6.22 50.3 6.35 52.1 6.47 55.6 6.60 59.2 6.84
240 42.1 5.85 45.4 5.97 48.7 6.22 50.3 6.22 52.1 6.35 55.6 6.60 59.2 6.72
96 42.1 6.97 45.4 7.09 48.7 7.22 50.3 7.22 52.1 7.34 55.6 7.47 59.2 7.59
20 192 42.1 6.60 45.4 6.72 48.7 6.84 50.3 6.97 52.1 6.97 55.6 7.22 59.2 7.34
Outside Units

240 42.1 6.47 45.4 6.60 48.7 6.72 50.3 6.84 52.1 6.84 55.6 7.09 59.2 7.22
96 42.1 7.84 45.4 7.96 48.7 8.09 50.3 8.09 52.1 8.21 55.6 8.21 59.2 8.34
25 192 42.1 7.47 45.4 7.59 48.7 7.72 50.3 7.72 52.1 7.84 55.6 7.84 59.2 7.96
240 42.1 7.34 45.4 7.34 48.7 7.47 50.3 7.59 52.1 7.59 55.6 7.72 59.2 7.84
90
96 42.1 9.08 45.4 9.21 48.7 9.21 50.3 9.21 52.1 9.33 55.6 9.33 59.2 9.33
30 192 42.1 8.59 45.4 8.71 48.7 8.71 50.3 8.71 52.1 8.84 55.6 8.84 59.2 8.96
240 42.1 8.34 45.4 8.46 48.7 8.46 50.3 8.59 52.1 8.59 55.6 8.71 59.2 8.71
96 42.1 10.70 45.4 10.70 48.7 10.70 50.3 10.70 52.1 10.70 55.6 10.70 59.2 10.70
35 192 42.1 9.96 45.4 10.08 48.7 10.08 50.3 10.08 52.1 10.08 55.6 10.08 59.2 10.08
240 42.1 9.71 45.4 9.71 48.7 9.83 50.3 9.83 52.1 9.83 55.6 9.83 59.2 9.83
96 42.1 12.57 45.4 12.57 48.7 12.57 50.3 12.57 52.1 12.57 55.6 12.57 59.2 12.57
40 192 42.1 11.70 45.4 11.82 48.7 11.82 50.3 11.82 52.1 11.82 55.6 11.82 59.2 11.82
240 42.1 11.32 45.4 11.45 48.7 11.45 50.3 11.45 52.1 11.45 55.6 11.45 59.2 11.45
96 37.4 4.65 40.3 4.76 43.3 4.87 44.8 4.98 46.3 4.98 49.4 5.20 52.7 5.31
15 192 37.4 4.42 40.3 4.54 43.3 4.76 44.8 4.76 46.3 4.87 49.4 4.98 52.7 5.20
240 37.4 4.31 40.3 4.42 43.3 4.65 44.8 4.76 46.3 4.76 49.4 4.98 52.7 5.20
96 37.4 5.20 40.3 5.31 43.3 5.42 44.8 5.42 46.3 5.53 49.4 5.64 52.7 5.75
20 192 37.4 4.98 40.3 5.09 43.3 5.20 44.8 5.20 46.3 5.31 49.4 5.42 52.7 5.53
240 37.4 4.87 40.3 4.98 43.3 5.09 44.8 5.09 46.3 5.20 49.4 5.31 52.7 5.53
96 37.4 5.97 40.3 6.08 43.3 6.08 44.8 6.19 46.3 6.19 49.4 6.31 52.7 6.31
25 192 37.4 5.64 40.3 5.75 43.3 5.86 44.8 5.86 46.3 5.86 49.4 5.97 52.7 6.08
240 37.4 5.53 40.3 5.53 43.3 5.64 44.8 5.75 46.3 5.75 49.4 5.86 52.7 5.97
80
96 37.4 6.97 40.3 6.97 43.3 7.08 44.8 7.08 46.3 7.08 49.4 7.08 52.7 7.19
30 192 37.4 6.53 40.3 6.53 43.3 6.64 44.8 6.64 46.3 6.75 49.4 6.75 52.7 6.86
240 37.4 6.31 40.3 6.42 43.3 6.42 44.8 6.53 46.3 6.53 49.4 6.64 52.7 6.64
96 37.4 8.19 40.3 8.19 43.3 8.19 44.8 8.19 46.3 8.19 49.4 8.19 52.7 8.19
35 192 37.4 7.63 40.3 7.63 43.3 7.74 44.8 7.74 46.3 7.74 49.4 7.74 52.7 7.74
240 37.4 7.41 40.3 7.41 43.3 7.52 44.8 7.52 46.3 7.52 49.4 7.52 52.7 7.52
96 37.4 9.62 40.3 9.62 43.3 9.73 44.8 9.73 46.3 9.73 49.4 9.73 52.7 9.73
40 192 37.4 9.07 40.3 9.07 43.3 9.07 44.8 9.07 46.3 9.07 49.4 9.07 52.7 9.07
240 37.4 8.74 40.3 8.74 43.3 8.74 44.8 8.74 46.3 8.74 49.4 8.74 52.7 8.74
96 32.7 3.29 35.3 3.39 37.8 3.48 39.2 3.58 40.6 3.68 43.3 3.77 46.1 3.97
15 192 32.7 3.19 35.3 3.29 37.8 3.39 39.2 3.48 40.6 3.58 43.3 3.68 46.1 3.87
240 32.7 3.10 35.3 3.19 37.8 3.39 39.2 3.39 40.6 3.48 43.3 3.68 46.1 3.77
96 32.7 3.77 35.3 3.87 37.8 3.97 39.2 3.97 40.6 4.07 43.3 4.16 46.1 4.26
20 192 32.7 3.58 35.3 3.68 37.8 3.77 39.2 3.77 40.6 3.87 43.3 3.97 46.1 4.07
240 32.7 3.48 35.3 3.58 37.8 3.68 39.2 3.77 40.6 3.77 43.3 3.97 46.1 4.07
96 32.7 4.36 35.3 4.45 37.8 4.45 39.2 4.55 40.6 4.55 43.3 4.65 46.1 4.74
25 192 32.7 4.07 35.3 4.16 37.8 4.26 39.2 4.26 40.6 4.36 43.3 4.45 46.1 4.45
70 240 32.7 3.97 35.3 4.07 37.8 4.16 39.2 4.16 40.6 4.16 43.3 4.36 46.1 4.45
96 32.7 5.13 35.3 5.13 37.8 5.13 39.2 5.23 40.6 5.23 43.3 5.23 46.1 5.32
30 192 32.7 4.74 35.3 4.84 37.8 4.84 39.2 4.94 40.6 4.94 43.3 5.03 46.1 5.03
240 32.7 4.65 35.3 4.65 37.8 4.74 39.2 4.74 40.6 4.74 43.3 4.84 46.1 4.94
96 32.7 6.00 35.3 6.10 37.8 6.10 39.2 6.10 40.6 6.10 43.3 6.10 46.1 6.10
35 192 32.7 5.61 35.3 5.71 37.8 5.71 39.2 5.71 40.6 5.71 43.3 5.71 46.1 5.71
240 32.7 5.42 35.3 5.52 37.8 5.52 39.2 5.52 40.6 5.52 43.3 5.61 46.1 5.61
96 32.7 7.26 35.3 7.26 37.8 7.26 39.2 7.26 40.6 7.26 43.3 7.26 46.1 7.26
40 192 32.7 6.68 35.3 6.78 37.8 6.78 39.2 6.78 40.6 6.78 43.3 6.78 46.1 6.78
240 32.7 6.48 35.3 6.48 37.8 6.48 39.2 6.48 40.6 6.48 43.3 6.48 46.1 6.48
TC : Total Capacity(kW)
PI : Power Input(kW)

15 _ R410A(50Hz/60Hz)
Shell & Coil
7. Capacity Tables

Cooling Capacity(20HP)

Inlet Water Indoor Air temperature (°CWB)


Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
96 28.0 2.58 30.2 2.67 32.4 2.77 33.7 2.86 34.8 2.96 37.1 3.05 39.4 3.24
15 192 28.0 2.48 30.2 2.58 32.4 2.67 33.7 2.77 34.8 2.86 37.1 2.96 39.4 3.15
240 28.0 2.39 30.2 2.58 32.4 2.67 33.7 2.77 34.8 2.77 37.1 2.96 39.4 3.15
96 28.0 2.96 30.2 3.05 32.4 3.15 33.7 3.15 34.8 3.24 37.1 3.34 39.4 3.43
20 192 28.0 2.77 30.2 2.86 32.4 2.96 33.7 3.05 34.8 3.05 37.1 3.24 39.4 3.34
240 28.0 2.67 30.2 2.86 32.4 2.96 33.7 2.96 34.8 3.05 37.1 3.15 39.4 3.34
96 28.0 3.43 30.2 3.53 32.4 3.63 33.7 3.63 34.8 3.63 37.1 3.72 39.4 3.82
25 192 28.0 3.24 30.2 3.34 32.4 3.43 33.7 3.43 34.8 3.43 37.1 3.53 39.4 3.63
240 28.0 3.15 30.2 3.24 32.4 3.34 33.7 3.34 34.8 3.34 37.1 3.53 39.4 3.63
60 96 28.0 4.10 30.2 4.10 32.4 4.20 33.7 4.20 34.8 4.20 37.1 4.29 39.4 4.29
30 192 28.0 3.82 30.2 3.91 32.4 3.91 33.7 4.01 34.8 4.01 37.1 4.01 39.4 4.10
240 28.0 3.72 30.2 3.72 32.4 3.82 33.7 3.82 34.8 3.82 37.1 3.91 39.4 4.01
96 28.0 4.87 30.2 4.96 32.4 4.96 33.7 4.96 34.8 4.96 37.1 4.96 39.4 4.96
35 192 28.0 4.58 30.2 4.58 32.4 4.58 33.7 4.67 34.8 4.67 37.1 4.67 39.4 4.67

Outside Units
240 28.0 4.39 30.2 4.39 32.4 4.48 33.7 4.48 34.8 4.48 37.1 4.58 39.4 4.58
96 28.0 5.92 30.2 5.92 32.4 5.92 33.7 5.92 34.8 5.92 37.1 5.92 39.4 5.92
40 192 28.0 5.44 30.2 5.53 32.4 5.53 33.7 5.53 34.8 5.53 37.1 5.53 39.4 5.53
240 28.0 5.25 30.2 5.34 32.4 5.34 33.7 5.34 34.8 5.34 37.1 5.34 39.4 5.34
96 23.4 1.97 25.2 2.07 27.0 2.16 28.0 2.23 29.0 2.26 30.9 2.44 33.0 2.54
15 192 23.4 1.88 25.2 1.97 27.0 2.07 28.0 2.16 29.0 2.14 30.9 2.35 33.0 2.54
240 23.4 1.79 25.2 1.88 27.0 1.97 28.0 2.07 29.0 2.03 30.9 2.35 33.0 2.54
96 23.4 2.26 25.2 2.35 27.0 2.44 28.0 2.44 29.0 2.54 30.9 2.63 33.0 2.73
20 192 23.4 2.15 25.2 2.23 27.0 2.26 28.0 2.35 29.0 2.35 30.9 2.54 33.0 2.63
240 23.4 2.04 25.2 2.12 27.0 2.20 28.0 2.26 29.0 2.28 30.9 2.44 33.0 2.63
96 23.4 2.63 25.2 2.73 27.0 2.73 28.0 2.82 29.0 2.82 30.9 2.91 33.0 3.01
25 192 23.4 2.44 25.2 2.54 27.0 2.63 28.0 2.63 29.0 2.73 30.9 2.82 33.0 2.91
240 23.4 2.35 25.2 2.44 27.0 2.54 28.0 2.54 29.0 2.63 30.9 2.73 33.0 2.82
50
96 23.4 3.20 25.2 3.20 27.0 3.29 28.0 3.29 29.0 3.29 30.9 3.38 33.0 3.48
30 192 23.4 2.91 25.2 3.01 27.0 3.01 28.0 3.10 29.0 3.10 30.9 3.20 33.0 3.29
240 23.4 2.82 25.2 2.91 27.0 2.91 28.0 3.01 29.0 3.01 30.9 3.10 33.0 3.20
96 23.4 3.86 25.2 3.86 27.0 3.86 28.0 3.95 29.0 3.95 30.9 3.95 33.0 3.95
35 192 23.4 3.57 25.2 3.57 27.0 3.67 28.0 3.67 29.0 3.67 30.9 3.67 33.0 3.76
240 23.4 3.48 25.2 3.48 27.0 3.48 28.0 3.48 29.0 3.57 30.9 3.57 33.0 3.67
96 23.4 4.70 25.2 4.70 27.0 4.70 28.0 4.70 29.0 4.70 30.9 4.70 33.0 4.70
40 192 23.4 4.33 25.2 4.33 27.0 4.33 28.0 4.42 29.0 4.42 30.9 4.42 33.0 4.42
240 23.4 4.23 25.2 4.23 27.0 4.23 28.0 4.23 29.0 4.23 30.9 4.23 33.0 4.23

TC : Total Capacity(kW)
PI : Power Input(kW)

R410A(50Hz/60Hz) _ 16
Shell & Coil
7. Capacity Tables

Cooling Capacity(30HP)
ARWV300LAL4
Inlet Water Indoor Air temperature (°CWB)
Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
144 80.7 12.99 86.8 12.99 93.3 13.17 96.6 13.53 99.9 13.71 106.6 13.71 113.5 13.89
15 288 80.7 12.44 86.8 12.62 93.3 12.99 96.6 13.17 99.9 13.17 106.6 13.35 113.5 13.71
360 80.7 12.26 86.8 12.44 93.3 12.81 96.6 12.99 99.9 12.99 106.6 13.35 113.5 13.53
144 80.7 14.25 86.8 14.25 93.3 14.43 96.6 14.79 99.9 14.79 106.6 14.79 113.5 14.97
20 288 80.7 13.71 86.8 13.89 93.3 14.07 96.6 14.25 99.9 14.25 106.6 14.43 113.5 14.61
360 80.7 13.53 86.8 13.71 93.3 13.89 96.6 14.07 99.9 14.07 106.6 14.25 113.5 14.43
144 80.7 15.87 86.8 15.87 93.3 16.05 96.6 16.41 99.9 16.41 106.6 16.41 113.5 16.41
25 288 80.7 15.51 86.8 15.51 93.3 15.69 96.6 15.69 99.9 15.87 106.6 15.87 113.5 16.05
360 80.7 15.15 86.8 15.15 93.3 15.33 96.6 15.33 99.9 15.51 106.6 15.51 113.5 15.69
130 144 80.7 18.04 86.8 18.04 93.3 18.22 96.6 18.58 99.9 18.58 106.6 18.58 113.5 18.58
30 288 80.7 17.49 86.8 17.49 93.3 17.67 96.6 17.67 99.9 17.67 106.6 17.67 113.5 17.67
360 80.7 17.13 86.8 17.13 93.3 17.31 96.6 17.31 99.9 17.31 106.6 17.31 113.5 17.31
144 78.0 19.66 84.0 19.66 89.9 19.66 93.0 20.38 96.1 20.38 102.5 20.38 109.0 20.38
35 288 78.8 19.12 84.5 19.30 90.4 19.30 93.5 19.30 96.6 19.30 103.0 19.30 109.4 19.48
360 78.8 18.58 84.5 18.76 90.7 18.76 93.7 18.76 96.8 18.94 103.0 18.94 109.7 18.94
Outside Units

144 74.7 21.28 79.9 21.28 85.7 21.46 88.5 22.18 91.4 22.18 97.3 22.18 103.3 22.18
40 288 75.7 20.92 80.9 20.92 86.6 21.10 89.5 21.10 92.3 21.10 98.3 21.10 104.5 21.28
360 75.9 20.38 81.4 20.38 86.8 20.56 89.7 20.56 92.8 20.56 98.7 20.56 104.7 20.74
144 77.2 12.63 83.1 12.82 89.2 13.20 92.4 13.20 95.6 13.39 102.0 13.39 108.6 13.76
15 288 77.2 12.26 83.1 12.44 89.2 12.63 92.4 12.82 95.6 13.01 102.0 13.20 108.6 13.58
360 77.2 11.88 83.1 12.26 89.2 12.44 92.4 12.63 95.6 12.82 102.0 13.01 108.6 13.39
144 77.2 14.14 83.1 14.33 89.2 14.52 92.4 14.52 95.6 14.52 102.0 14.52 108.6 14.71
20 288 77.2 13.39 83.1 13.76 89.2 13.95 92.4 13.95 95.6 13.95 102.0 14.33 108.6 14.52
360 77.2 13.20 83.1 13.39 89.2 13.58 92.4 13.76 95.6 13.76 102.0 13.95 108.6 14.14
144 77.2 15.84 83.1 16.03 89.2 16.22 92.4 16.22 95.6 16.22 102.0 16.03 108.6 16.03
25 288 77.2 15.08 83.1 15.27 89.2 15.46 92.4 15.46 95.6 15.46 102.0 15.65 108.6 15.84
120 360 77.2 14.71 83.1 14.90 89.2 15.08 92.4 15.08 95.6 15.27 102.0 15.27 108.6 15.46
144 77.2 18.10 83.1 18.29 89.2 18.29 92.4 18.29 95.6 18.29 102.0 18.29 108.6 18.29
30 288 77.2 17.16 83.1 17.35 89.2 17.35 92.4 17.35 95.6 17.35 102.0 17.54 108.6 17.54
360 77.2 16.78 83.1 16.78 89.2 16.97 92.4 16.97 95.6 16.97 102.0 17.16 108.6 17.16
144 74.6 19.99 80.3 19.99 86.0 19.99 89.0 19.99 91.9 19.99 98.1 19.99 104.2 19.99
35 288 75.3 18.86 80.8 18.86 86.5 19.04 89.4 19.04 92.4 19.04 98.5 19.04 104.7 19.23
360 75.3 18.29 80.8 18.48 86.7 18.48 89.7 18.48 92.6 18.67 98.5 18.67 104.9 18.67
144 71.5 21.68 76.5 21.87 81.9 21.87 84.7 21.87 87.4 21.87 93.1 21.87 98.8 21.87
40 288 72.4 20.74 77.4 20.74 82.8 20.74 85.6 20.93 88.3 20.93 94.0 20.93 99.9 20.93
360 72.6 20.18 77.8 20.18 83.1 20.36 85.8 20.36 88.8 20.36 94.4 20.36 100.1 20.36
144 73.6 12.44 79.3 12.64 85.2 12.84 88.2 13.04 91.2 13.04 97.3 13.43 103.6 13.63
15 288 73.6 11.85 79.3 12.05 85.2 12.44 88.2 12.64 91.2 12.84 97.3 13.04 103.6 13.23
360 73.6 11.65 79.3 11.85 85.2 12.25 88.2 12.44 91.2 12.64 97.3 12.84 103.6 13.23
144 73.6 13.83 79.3 14.02 85.2 14.22 88.2 14.22 91.2 14.42 97.3 14.42 103.6 14.62
20 288 73.6 13.23 79.3 13.43 85.2 13.63 88.2 13.63 91.2 13.83 97.3 14.02 103.6 14.22
360 73.6 12.84 79.3 13.04 85.2 13.43 88.2 13.43 91.2 13.63 97.3 13.83 103.6 14.02
144 73.6 15.60 79.3 15.80 85.2 15.80 88.2 15.80 91.2 16.00 97.3 16.00 103.6 16.20
25 288 73.6 14.81 79.3 15.01 85.2 15.21 88.2 15.21 91.2 15.21 97.3 15.41 103.6 15.41
360 73.6 14.42 79.3 14.62 85.2 14.81 88.2 14.81 91.2 15.01 97.3 15.01 103.6 15.21
110 144 73.6 17.78 79.3 17.98 85.2 17.98 88.2 17.98 91.2 17.98 97.3 17.98 103.6 18.17
30 288 73.6 16.99 79.3 16.99 85.2 17.19 88.2 17.19 91.2 17.19 97.3 17.19 103.6 17.19
360 73.6 16.40 79.3 16.59 85.2 16.59 88.2 16.59 91.2 16.79 97.3 16.79 103.6 16.79
144 71.3 19.56 76.7 19.75 82.1 19.75 84.9 19.75 87.8 19.75 93.6 19.75 99.5 19.75
35 288 71.9 18.57 77.1 18.77 82.6 18.77 85.4 18.77 88.2 18.77 94.1 18.96 99.9 18.96
360 71.9 18.17 77.1 18.17 82.8 18.17 85.6 18.37 88.4 18.37 94.1 18.37 100.1 18.37
144 68.2 21.53 73.0 21.53 78.2 21.53 80.8 21.73 83.4 21.73 88.9 21.73 94.3 21.73
40 288 69.1 20.35 73.9 20.54 79.1 20.54 81.7 20.54 84.3 20.54 89.7 20.54 95.4 20.74
360 69.3 19.75 74.3 19.95 79.3 19.95 81.9 19.95 84.7 19.95 90.2 20.15 95.6 20.15
144 70.1 12.03 75.5 12.24 81.1 12.65 84.0 12.65 86.9 12.86 92.7 13.07 98.7 13.48
15 288 70.1 11.61 75.5 11.82 81.1 12.24 84.0 12.24 86.9 12.44 92.7 12.86 98.7 13.07
360 70.1 11.41 75.5 11.61 81.1 12.03 84.0 12.03 86.9 12.24 92.7 12.65 98.7 12.86
144 70.1 13.48 75.5 13.69 81.1 13.90 84.0 13.90 86.9 14.10 92.7 14.31 98.7 14.52
100 20 288 70.1 12.86 75.5 13.07 81.1 13.27 84.0 13.48 86.9 13.48 92.7 13.69 98.7 13.90
360 70.1 12.65 75.5 12.86 81.1 13.07 84.0 13.07 86.9 13.27 92.7 13.48 98.7 13.69
144 70.1 15.35 75.5 15.35 81.1 15.56 84.0 15.56 86.9 15.76 92.7 15.76 98.7 15.97
25 288 70.1 14.52 75.5 14.73 81.1 14.93 84.0 14.93 86.9 14.93 92.7 15.14 98.7 15.35
360 70.1 14.10 75.5 14.31 81.1 14.52 84.0 14.52 86.9 14.73 92.7 14.73 98.7 14.93
TC : Total Capacity(kW)
PI : Power Input(kW)

17 _ R410A(50Hz/60Hz)
Shell & Coil
7. Capacity Tables

Cooling Capacity(30HP)

Inlet Water Indoor Air temperature (°CWB)


Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
144 70.1 17.63 75.5 17.63 81.1 17.63 84.0 17.84 86.9 17.84 92.7 17.84 98.7 17.84
30 288 70.1 16.59 75.5 16.80 81.1 16.80 84.0 16.80 86.9 16.80 92.7 17.01 98.7 17.01
360 70.1 16.18 75.5 16.18 81.1 16.39 84.0 16.39 86.9 16.39 92.7 16.59 98.7 16.59
144 67.9 19.29 73.0 19.50 78.2 19.50 80.9 19.50 83.6 19.50 89.2 19.50 94.8 19.50
100 35 288 68.5 18.25 73.4 18.46 78.6 18.46 81.3 18.46 84.0 18.46 89.6 18.67 95.2 18.67
360 68.5 17.84 73.4 17.84 78.8 18.04 81.5 18.04 84.2 18.04 89.6 18.04 95.4 18.25
144 65.0 21.36 69.5 21.36 74.5 21.36 77.0 21.36 79.4 21.36 84.6 21.36 89.8 21.36
40 288 65.8 20.12 70.3 20.12 75.3 20.33 77.8 20.33 80.3 20.33 85.4 20.33 90.8 20.53
360 66.0 19.50 70.8 19.70 75.5 19.70 78.0 19.70 80.7 19.91 85.9 19.91 91.0 19.91
144 63.1 9.33 68.1 9.52 73.0 9.71 75.5 9.89 78.2 9.89 83.4 10.27 88.8 10.45
15 288 63.1 8.96 68.1 9.15 73.0 9.33 75.5 9.52 78.2 9.71 83.4 9.89 88.8 10.27
360 63.1 8.77 68.1 8.96 73.0 9.33 75.5 9.33 78.2 9.52 83.4 9.89 88.8 10.08
144 63.1 10.45 68.1 10.64 73.0 10.83 75.5 10.83 78.2 11.01 83.4 11.20 88.8 11.39
20 288 63.1 9.89 68.1 10.08 73.0 10.27 75.5 10.45 78.2 10.45 83.4 10.83 88.8 11.01

Outside Units
360 63.1 9.71 68.1 9.89 73.0 10.08 75.5 10.27 78.2 10.27 83.4 10.64 88.8 10.83
144 63.1 11.76 68.1 11.95 73.0 12.13 75.5 12.13 78.2 12.32 83.4 12.32 88.8 12.51
25 288 63.1 11.20 68.1 11.39 73.0 11.57 75.5 11.57 78.2 11.76 83.4 11.76 88.8 11.95
360 63.1 11.01 68.1 11.01 73.0 11.20 75.5 11.39 78.2 11.39 83.4 11.57 88.8 11.76
90
144 63.1 13.63 68.1 13.81 73.0 13.81 75.5 13.81 78.2 14.00 83.4 14.00 88.8 14.00
30 288 63.1 12.88 68.1 13.07 73.0 13.07 75.5 13.07 78.2 13.25 83.4 13.25 88.8 13.44
360 63.1 12.51 68.1 12.69 73.0 12.69 75.5 12.88 78.2 12.88 83.4 13.07 88.8 13.07
144 63.1 16.05 68.1 16.05 73.0 16.05 75.5 16.05 78.2 16.05 83.4 16.05 88.8 16.05
35 288 63.1 14.93 68.1 15.12 73.0 15.12 75.5 15.12 78.2 15.12 83.4 15.12 88.8 15.12
360 63.1 14.56 68.1 14.56 73.0 14.75 75.5 14.75 78.2 14.75 83.4 14.75 88.8 14.75
144 63.1 18.85 68.1 18.85 73.0 18.85 75.5 18.85 78.2 18.85 83.4 18.85 88.8 18.85
40 288 63.1 17.55 68.1 17.73 73.0 17.73 75.5 17.73 78.2 17.73 83.4 17.73 88.8 17.73
360 63.1 16.99 68.1 17.17 73.0 17.17 75.5 17.17 78.2 17.17 83.4 17.17 88.8 17.17
144 56.1 6.97 60.4 7.13 65.0 7.30 67.2 7.47 69.5 7.47 74.1 7.80 79.0 7.96
15 288 56.1 6.64 60.4 6.80 65.0 7.13 67.2 7.13 69.5 7.30 74.1 7.47 79.0 7.80
360 56.1 6.47 60.4 6.64 65.0 6.97 67.2 7.13 69.5 7.13 74.1 7.47 79.0 7.80
144 56.1 7.80 60.4 7.96 65.0 8.13 67.2 8.13 69.5 8.30 74.1 8.46 79.0 8.63
20 288 56.1 7.47 60.4 7.63 65.0 7.80 67.2 7.80 69.5 7.96 74.1 8.13 79.0 8.30
360 56.1 7.30 60.4 7.47 65.0 7.63 67.2 7.63 69.5 7.80 74.1 7.96 79.0 8.30
144 56.1 8.96 60.4 9.13 65.0 9.13 67.2 9.29 69.5 9.29 74.1 9.46 79.0 9.46
25 288 56.1 8.46 60.4 8.63 65.0 8.79 67.2 8.79 69.5 8.79 74.1 8.96 79.0 9.13
360 56.1 8.30 60.4 8.30 65.0 8.46 67.2 8.63 69.5 8.63 74.1 8.79 79.0 8.96
80
144 56.1 10.45 60.4 10.45 65.0 10.62 67.2 10.62 69.5 10.62 74.1 10.62 79.0 10.79
30 288 56.1 9.79 60.4 9.79 65.0 9.96 67.2 9.96 69.5 10.12 74.1 10.12 79.0 10.29
360 56.1 9.46 60.4 9.62 65.0 9.62 67.2 9.79 69.5 9.79 74.1 9.96 79.0 9.96
144 56.1 12.28 60.4 12.28 65.0 12.28 67.2 12.28 69.5 12.28 74.1 12.28 79.0 12.28
35 288 56.1 11.45 60.4 11.45 65.0 11.61 67.2 11.61 69.5 11.61 74.1 11.61 79.0 11.61
360 56.1 11.12 60.4 11.12 65.0 11.28 67.2 11.28 69.5 11.28 74.1 11.28 79.0 11.28
144 56.1 14.44 60.4 14.44 65.0 14.60 67.2 14.60 69.5 14.60 74.1 14.60 79.0 14.60
40 288 56.1 13.61 60.4 13.61 65.0 13.61 67.2 13.61 69.5 13.61 74.1 13.61 79.0 13.61
360 56.1 13.11 60.4 13.11 65.0 13.11 67.2 13.11 69.5 13.11 74.1 13.11 79.0 13.11
144 49.0 4.94 53.0 5.08 56.7 5.23 58.8 5.37 60.8 5.52 65.0 5.66 69.1 5.95
15 288 49.0 4.79 53.0 4.94 56.7 5.08 58.8 5.23 60.8 5.37 65.0 5.52 69.1 5.81
360 49.0 4.65 53.0 4.79 56.7 5.08 58.8 5.08 60.8 5.23 65.0 5.52 69.1 5.66
144 49.0 5.66 53.0 5.81 56.7 5.95 58.8 5.95 60.8 6.10 65.0 6.24 69.1 6.39
20 288 49.0 5.37 53.0 5.52 56.7 5.66 58.8 5.66 60.8 5.81 65.0 5.95 69.1 6.10
360 49.0 5.23 53.0 5.37 56.7 5.52 58.8 5.66 60.8 5.66 65.0 5.95 69.1 6.10
144 49.0 6.53 53.0 6.68 56.7 6.68 58.8 6.82 60.8 6.82 65.0 6.97 69.1 7.11
25 288 49.0 6.10 53.0 6.24 56.7 6.39 58.8 6.39 60.8 6.53 65.0 6.68 69.1 6.68
70 360 49.0 5.95 53.0 6.10 56.7 6.24 58.8 6.24 60.8 6.24 65.0 6.53 69.1 6.68
144 49.0 7.69 53.0 7.69 56.7 7.69 58.8 7.84 60.8 7.84 65.0 7.84 69.1 7.99
30 288 49.0 7.11 53.0 7.26 56.7 7.26 58.8 7.40 60.8 7.40 65.0 7.55 69.1 7.55
360 49.0 6.97 53.0 6.97 56.7 7.11 58.8 7.11 60.8 7.11 65.0 7.26 69.1 7.40
144 49.0 9.00 53.0 9.15 56.7 9.15 58.8 9.15 60.8 9.15 65.0 9.15 69.1 9.15
35 288 49.0 8.42 53.0 8.57 56.7 8.57 58.8 8.57 60.8 8.57 65.0 8.57 69.1 8.57
360 49.0 8.13 53.0 8.28 56.7 8.28 58.8 8.28 60.8 8.28 65.0 8.42 69.1 8.42
144 49.0 10.89 53.0 10.89 56.7 10.89 58.8 10.89 60.8 10.89 65.0 10.89 69.1 10.89
40 288 49.0 10.02 53.0 10.16 56.7 10.16 58.8 10.16 60.8 10.16 65.0 10.16 69.1 10.16
360 49.0 9.73 53.0 9.73 56.7 9.73 58.8 9.73 60.8 9.73 65.0 9.73 69.1 9.73
TC : Total Capacity(kW)
PI : Power Input(kW)

R410A(50Hz/60Hz) _ 18
Shell & Coil
7. Capacity Tables

Cooling Capacity(30HP)

Inlet Water Indoor Air temperature (°CWB)


Combination
water Flow Rate 14 16 18 19 20 22 24
(%)
Temp.(°C) (L/min) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
144 42.0 3.86 45.3 4.01 48.6 4.15 50.5 4.29 52.1 4.44 55.7 4.58 59.2 4.87
15 288 42.0 3.72 45.3 3.86 48.6 4.01 50.5 4.15 52.1 4.29 55.7 4.44 59.2 4.72
360 42.0 3.58 45.3 3.86 48.6 4.01 50.5 4.15 52.1 4.15 55.7 4.44 59.2 4.72
144 42.0 4.44 45.3 4.58 48.6 4.72 50.5 4.72 52.1 4.87 55.7 5.01 59.2 5.15
20 288 42.0 4.15 45.3 4.29 48.6 4.44 50.5 4.58 52.1 4.58 55.7 4.87 59.2 5.01
360 42.0 4.01 45.3 4.29 48.6 4.44 50.5 4.44 52.1 4.58 55.7 4.72 59.2 5.01
144 42.0 5.15 45.3 5.30 48.6 5.44 50.5 5.44 52.1 5.44 55.7 5.58 59.2 5.72
25 288 42.0 4.87 45.3 5.01 48.6 5.15 50.5 5.15 52.1 5.15 55.7 5.30 59.2 5.44
360 42.0 4.72 45.3 4.87 48.6 5.01 50.5 5.01 52.1 5.01 55.7 5.30 59.2 5.44
60 144 42.0 6.15 45.3 6.15 48.6 6.30 50.5 6.30 52.1 6.30 55.7 6.44 59.2 6.44
30 288 42.0 5.72 45.3 5.87 48.6 5.87 50.5 6.01 52.1 6.01 55.7 6.01 59.2 6.15
360 42.0 5.58 45.3 5.58 48.6 5.72 50.5 5.72 52.1 5.72 55.7 5.87 59.2 6.01
144 42.0 7.30 45.3 7.44 48.6 7.44 50.5 7.44 52.1 7.44 55.7 7.44 59.2 7.44
35 288 42.0 6.87 45.3 6.87 48.6 6.87 50.5 7.01 52.1 7.01 55.7 7.01 59.2 7.01
Outside Units

360 42.0 6.58 45.3 6.58 48.6 6.73 50.5 6.73 52.1 6.73 55.7 6.87 59.2 6.87
144 42.0 8.87 45.3 8.87 48.6 8.87 50.5 8.87 52.1 8.87 55.7 8.87 59.2 8.87
40 288 42.0 8.16 45.3 8.30 48.6 8.30 50.5 8.30 52.1 8.30 55.7 8.30 59.2 8.30
360 42.0 7.87 45.3 8.01 48.6 8.01 50.5 8.01 52.1 8.01 55.7 8.01 59.2 8.01
144 35.2 2.96 37.9 3.10 40.6 3.24 42.0 3.34 43.4 3.38 46.3 3.67 49.4 3.81
15 288 35.2 2.82 37.9 2.96 40.6 3.10 42.0 3.24 43.4 3.22 46.3 3.53 49.4 3.81
360 35.2 2.68 37.9 2.82 40.6 2.96 42.0 3.10 43.4 3.05 46.3 3.53 49.4 3.81
144 35.2 3.38 37.9 3.53 40.6 3.67 42.0 3.67 43.4 3.81 46.3 3.95 49.4 4.09
20 288 35.2 3.22 37.9 3.35 40.6 3.38 42.0 3.53 43.4 3.53 46.3 3.81 49.4 3.95
360 35.2 3.06 37.9 3.17 40.6 3.30 42.0 3.38 43.4 3.43 46.3 3.67 49.4 3.95
144 35.2 3.95 37.9 4.09 40.6 4.09 42.0 4.23 43.4 4.23 46.3 4.37 49.4 4.51
25 288 35.2 3.67 37.9 3.81 40.6 3.95 42.0 3.95 43.4 4.09 46.3 4.23 49.4 4.37
360 35.2 3.53 37.9 3.67 40.6 3.81 42.0 3.81 43.4 3.95 46.3 4.09 49.4 4.23
50
144 35.2 4.80 37.9 4.80 40.6 4.94 42.0 4.94 43.4 4.94 46.3 5.08 49.4 5.22
30 288 35.2 4.37 37.9 4.51 40.6 4.51 42.0 4.65 43.4 4.65 46.3 4.80 49.4 4.94
360 35.2 4.23 37.9 4.37 40.6 4.37 42.0 4.51 43.4 4.51 46.3 4.65 49.4 4.80
144 35.2 5.78 37.9 5.78 40.6 5.78 42.0 5.92 43.4 5.92 46.3 5.92 49.4 5.92
35 288 35.2 5.36 37.9 5.36 40.6 5.50 42.0 5.50 43.4 5.50 46.3 5.50 49.4 5.64
360 35.2 5.22 37.9 5.22 40.6 5.22 42.0 5.22 43.4 5.36 46.3 5.36 49.4 5.50
144 35.2 7.05 37.9 7.05 40.6 7.05 42.0 7.05 43.4 7.05 46.3 7.05 49.4 7.05
40 288 35.2 6.49 37.9 6.49 40.6 6.49 42.0 6.63 43.4 6.63 46.3 6.63 49.4 6.63
360 35.2 6.35 37.9 6.35 40.6 6.35 42.0 6.35 43.4 6.35 46.3 6.35 49.4 6.35

TC : Total Capacity(kW)
PI : Power Input(kW)

19 _ R410A(50Hz/60Hz)
Shell & Coil
7. Capacity Tables
7.2 Capacity Correction Factor
n ARWV100LAL4 , ARWV200LAL4 , ARWV300LAL4
Rate of change in cooling capacity

α
50 - - - - - - 0.92 0.90 0.89 0.88 0.86 0.85 0.84 0.83
40 - - - - - 0.93 0.92 0.90 0.89 0.88 0.87 0.85 0.84 0.83
30 - - - - 0.95 0.93 0.92 0.91 0.89 0.88 0.87 0.85 0.84 0.83
HU 20 - - - 0.97 0.95 0.94 0.92 0.91 0.89 0.88 0.87 0.86 0.84 0.83
(m) 10 - - 0.99 0.97 0.95 0.94 0.92 0.91 0.89 0.88 0.87 0.86 0.85 0.84
7.5 - 1.0 0.99 0.97 0.95 0.94 0.92 0.91 0.89 0.88 0.87 0.86 0.85 0.84
0 1.0 0.99 0.97 0.96 0.94 0.92 0.91 0.90 0.88 0.87 0.86 0.85 0.84
0 7.5 10 20 30 40 50 60 70 80 90 100 110 120 L(m)
0 1.0 0.99 0.97 0.96 0.94 0.92 0.91 0.90 0.88 0.87 0.86 0.85 0.84
7.5 - 1.0 0.99 0.97 0.96 0.94 0.92 0.91 0.90 0.88 0.87 0.86 0.85 0.84
10 - - 0.99 0.98 0.96 0.94 0.93 0.91 0.90 0.88 0.87 0.86 0.85 0.84
HL 20 - - - 0.98 0.96 0.94 0.93 0.91 0.90 0.88 0.87 0.86 0.85 0.84
(m) 30 - - - - 0.96 0.94 0.93 0.91 0.90 0.89 0.87 0.86 0.85 0.84
40 - - - - - 0.95 0.93 0.91 0.90 0.89 0.87 0.86 0.85 0.84
50 - - - - - - 0.93 0.91 0.90 0.89 0.87 0.86 0.85 0.84 α

Outside Units
[Symbols]
HU : Level difference between indoor and outside units where indoor unit in inferior position (m)
HL : Level difference between indoor and outside units where indoor unit in superior position (m)
L : Equivalent pipe length (m)
α : Capacity correction factor

R410A(50Hz/60Hz) _ 20
Shell & Coil
7. Capacity Tables

Notes
1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under standard
conditions.
(Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the
above figures.)
2. With this outside unit, evaporating pressure constant control when cooling.
3. If heat insulation of piping is insufficient, heat loss will become larger and capacity will decrease
4. Method of calculating cooling capacity : maximum cooling capacity of outside units
= cooling capacity of outside units obtained from capacity table X capacity correction factor due to piping length to the far-
thest indoor unit
5. Equivalent piping length for Y branch and other pipes can be calculated with following table.

Ø6.35 Ø9.52 Ø12.7 Ø15.88 Ø19.05 Ø22.2 Ø25.4 Ø28.58 Ø31.8 Ø34.9 Ø38.1 Ø41.3 Ø44.5 Ø53.98
(1/4) (3/8) (1/2) (5/8) (3/4) (7/8) (1) (1-1/8) (1-1/4) (1-3/8) (1-1/2) (1-5/8) (1-3/4) (2-1/8)
Outside Units

Elbow 0.16 0.18 0.2 0.25 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.85

Y Branch 0.5

Header 1

6. When overall equivalent pipe length is 90 m or more, the diameter of the main gas and liquid pipes.

Upward Outside Increased Pipe Diameter


unit Standard Pipe Diameter When pipe length is 90m or more from
total capacity ODU to 1st branch
kW Liquid pipe[mm(inch)] Gas pipe[mm(inch)] Liquid pipe[mm(inch)] Gas pipe[mm(inch)]
28 Ø 9.52(3/8) Ø 22.2(7/8) Ø 12.7(1/2) Ø 25.4(1)
56 Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) Ø 31.8(1-1/4)
84 Ø 19.05(3/4) Ø 34.9(1-3/8) Ø 22.2(7/8) Ø 38.1(1-1/2)

* If available on site, it use this size. Otherwise it can't be increased.


7. Read cooling capacity rate of change in the above figures based on the following equivalent length.
: overall equivalent length = (equivalent length of main pipe) X correction factor + (equivalent length after first branching)

Overall equivalent pipe length


Correction factor
< 90 m ≥ 90 m
Cooling 1.0 0.5

Ex)
• (Cooling) Overall equivalent length
Equivalent pipe
Indoor unit
= 70 m x 0.5 + 40 m = 75 m
length 70 m The correction factor in cooling capacity when HU
Indoor unit
= 10 m is thus approximately 0.887
HU=10m
Outside
Equivalent pipe
length 40 m

21 _ R410A(50Hz/60Hz)
Shell & Coil
8. Operation Limits

Cooling

45
40

Inlet water temperature (°C)


35

Range for continuous operation

Range for pull down operation


30

25

20

Outside Units
15
Range for
operation
10
10 15 20 25 30

Indoor temperature (°CWB)

Notes:
These figures assume the following operating conditions:
Equivalent piping length:7.5m
Level difference:0m

R410A(50Hz/60Hz) _ 22
Shell & Coil
9. Sound Levels
Notes:
• Data is valid at free field condition
• Data is valid at nominal operating condition
• Sound level will vary depending on a range of factors such
as the construction (acoustic absorption coefficient) of par-
ticular room in which the equipment is installed
1m • The operating conditions are assumed to be standard
(ISO conditions)

1m

Unit:dB(A)
Model Cooling
10 HP 50
20HP 54
Outside Units

30HP 59

Sound Pressure Level


n Cooling
ARWV100LAL4 ARWV200LAL4 ARWV300LAL4
80 80 80

70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

23 _ R410A(50Hz/60Hz)
Shell & Coil
10. Head loss by Water flow
n ARWV100LAL4

70 .0

60 .0

50 .0
Pressure drop [kPa]

40 .0

30 .0

20 .0

10 .0

Outside Units
0.0
0 50 100 150 200
Water flow rate (l/min)

R410A(50Hz/60Hz) _ 24
Shell & Coil
11. Accessories
Optional Accessories
No. Name Model

ARBLN01621

ARBLN03321

1 Y branch pipe ARBLN07121

ARBLN14521

ARBL054

ARBL057

ARBL104
2 Header
ARBL107
Outside Units

ARBL1010

ARBL2010

25 _ R410A(50Hz/60Hz)
Shell & Coil

Installation of Outside Units

1. Alternative Refrigerant R410A


2.Select the Best Location and the Installation space
3. Water Control
4. Lifting Method
5. Installation
6. Device protection unit
7. Refrigerant Piping System
8. Y Branch and Header Branch Pipe type
9. Electrical Wiring
10. Cooling tower applied method
11. Water Solenoid Valve Control
12. Test Run
Shell & Coil
1. Alternative Refrigerant R410A
• The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteris-
tic should be also considered during the installation.
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0.

CAUTION
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed
pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.

2.Select the Best Location and the Installation space


2.1 Select the Best Location
• Select space for installation outside unit, which will meet the following conditions.
• With strength which bears weight of unit
• With space for air passage and service work
Don't install the unit at the space where generation, inflow, stagnation, and leak of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Location with no leakage of combustible gas

Installation of Outside Units


• Recommend the outside unit to be installed within 0~40°C.
• Location with installation or service work space (Refer to required space)
• Do not use the outside unit under any special environment where oil, steam and sulfuric gas exist.
• Install in a separate machine room not exposed to external air
- Install the product so that the noise from the machine room is not transferred outsides
• The floor of the machine room must be water proof.
• Drainage must be installed in the machine room to process the water drainage.
• Install a floor slope to make the drainage smooth.
• Avoid installing the outside unit in the location with following conditions.
• Location where corrosive gas such as acidic gas is generated. (It may cause the refrigerant leakage by corrosion of
the pipe.)
• Location where electromagnetic waves happen. (It may cause the abnormal operation by control parts disorder.)
• Location to be able to leak the combustible gas
• Location with carbon fiber or combustible dust.
• Location with the combustible material like thinner or gasoline. (It may cause a fire by leaking the gas near the product.)

CAUTION
1. Do not install Multi V water outside. Always install indoor like machine room.
2. Inverter product may generate electric noise. Keep the body from computer, stereo etc. at enough dis-
tance. Specially leave space from indoor remote controller to shoes electric devices at the above 3m in
weak electric wave area. Insert the power cable and other wire into separate conduit.

R410A(50Hz/60Hz) _ 1
Shell & Coil
2.Select the Best Location and the Installation space
2.2 Individual Installation
Required the minimum space as shown below for installation and check.
If the space is not fit on this drawing, consult with LG.

: Service area

300
(unit : mm)

100
Product

500
(Outside unit)
Water pipe
installation
space

997
Service
Էҿ֢@ĚÅ area
H‫۾‬ϻI
(Front) 600

350

100
300 755 100 H-Beam Support

<Top View> <Front View>

2.3 Collective / Continuous Installation


Space required for collective installation and continuous installation as shown below considering passage for air and
Installation of Outside Units

people.
: Service area
(Unit : mm)
300

Product Product Product


500

(Outside unit) (Outside unit) (Outside unit)


600

Service area Service area Service area


(Front) (Front) (Front)

350 350 350

300 755 755 755


200 200 100
<Top view>
* In case of the water pipe passing side product, please make sufficient service place to avoid occurring between
water pipe and product side.

2 _ R410A(50Hz/60Hz)
Shell & Coil
3. Water control
3.1 Water control
• Keep the water temperature between 10~45°C. Other it may cause the breakdown.
- Standard water supply temperature is 30°C for Cooling.
• Properly control the water velocity. Otherwise it may cause the noise, pipe vibration or pipe contraction, expansion
according to the temperature. Use the same water pipe size connected with the product or more.
• Refer to the water source pipe diameter and water velocity table below. As the water velocity is fast, air bubble will
increase.

Diameter (mm) Velocity range (m/s)


< 50 0.6 ~ 1.2
50 ~ 100 1.2 ~ 2.1
100 < 2.1 ~ 2.7

• Be careful of the water purity control. Otherwise it may cause the breakdown due to water pipe corrosion.
(Refer to 'Standard Table for Water Purity Control')
• In case the water temperature is above 40°C, it is good to prevent the corrosion by adding The anticorrosive agent.
• Install the pipe, valve and gauge sensor in the space where it is easy to maintain. Install the water valve in the low
position for drain, if required.
• Be careful not to let air in. If so, the water velocity will be unstable in the circulation, pump efficiency will also
decrease and may cause the piping vibration. Therefore, install the air purge where it may generate the air.

Installation of Outside Units

R410A(50Hz/60Hz) _ 3
Shell & Coil
3. Water control
3.2 Standard table for water purity control
The water may contain many foreign substances and hence may influence the performance and lifetime of the prod-
uct due to the corrosion of the condenser and water pipe. (Use water source that complies with the below standard
table for water purity control.)
If you control the water quality in accordance with the following standard water quality table, it can maintain good per-
formance and does not need to cleaning the heat exchanger frequently.

Closed type Effect


Items
Circulating water Supplemented water Corrosion Scale
Basic Item
pH [25C] 7.0~8.0 7.0~8.0 O O
Conductivity [25C] (mS/m) Below 30 Below 30 O O
Chlorine ions (mg Cl- / ) Below 50 Below 50 O -
Sulfate ions (mg SO4 / ) 2 Below 50 Below 50 O O
Acid consumption (pH4.8) (mg CaCO3 / ) Below 50 Below 50 - O
Total hardness (mg CaCO3 / ) Below 70 Below 70 - O
Calcium hardness (mg CaCO3 / ) Below 50 Below 50 - O
Ionic-static silica (mg SiO2 / ) Below 30 Below 30 - O
Reference Item
Iron (mg Fe / ) Below 1.0 Below 0.3 O O
Copper (mg Cu / ) Below 1.0 Below 0.1 O -
2
Sulfate ion (mg SO4 / ) Must not be detected Must not be detected O -
Ammonium ion (mg NH4 / ) +
Below 0.3 Below 0.1 O -
Installation of Outside Units

Residual chlorine (mg CI / ) Below 0.25 Below 0.3 O -


Free carbon dioxide (mg CO2 / ) Below 0.4 Below 4.0 O -
Stability index - - O O

[Reference]
(1) The "O" mark for corrosion and scale means that there is possibility of occurrence.
(2) When the water temperature is 40°C or above or when uncoated iron is exposed to the water, it can result in corro-
sion. Therefore adding anti-corrosion agent or removing the air can be very effective.
(3) In case of using the closed type cooling tower, the cooling water and supplementing water must satisfy the water qual-
ity criteria of closed type system in the table.
(4) Supplementing water and supplied water must be supplied with tap water, industrial water and underground water
excluding filtered water, neutral water, soft water etc.
(5) 15 items in the table are general causes of corrosion and scale.

4 _ R410A(50Hz/60Hz)
Shell & Coil
4. Lifting method
• When carrying the unit suspended, pass the ropes under the unit and use the two suspension points each at the
front and rear.
• Always lift the unit with ropes attached at fours points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less

Sub line

A 40° or less
B Rope supporter WARNING

Installation of Outside Units


CAUTION
• Do not have only one person carry product if it is more than 20kg.
• PP bands are used to pack some products. Do not use them as a means for transportation because they are
dangerous.
• Tear the plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging
bag may suffocate children.
• When carrying in outside unit, be sure to support it at four points. Carrying in and lifting with 3-point support
may make outside unit unstable, resulting in a fall of it.
• When carrying with the forklift, be careful not to drop the product.

R410A(50Hz/60Hz) _ 5
Shell & Coil
5. Installation
5.1 Location of anchor bolt

756
62 632 62
496
465

The location of
anchor bolt

WARNING
• Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
• Have installation work in order to protect against a strong wind and earthquake. Any installation
deficiency may cause unit to fall down, resulting in a personal injury.
Installation of Outside Units

• Especially take care for support strength of the floor surface, water drain processing (processing of
water flown out from the outside unit during operation) and paths of the pipe and wiring when making a
base support.

6 _ R410A(50Hz/60Hz)
Shell & Coil
5. Installation
5.2 Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.

1) Cut the pipes and the cable.


• Use the accessory piping kit or the pipes purchased Copper
locally. tube 90° Slanted Uneven Rough
• Measure the distance between the indoor and the
outside unit.
• Cut the pipes a little longer than measured distance.
• Cut the cable 1.5m longer than the pipe length.

Pipe
Reamer
2) Burrs removal
• Completely remove all burrs from the cut cross sec-
tion of pipe/tube. Point down
• Put the end of the copper tube/pipe to downward
direction as you remove burrs in order to avoid to let
burrs drop in the tubing.

3) Flaring work
• Carry out flaring work using flaring tool as shown Handle
below. Bar Bar
[Unit:mm] "A" Yoke
Indoor unit Pipe " A " Cone
[kW(Btu/h] Gas Liquid Gas Liquid

Installation of Outside Units


≤5.6(19,100) Ø12.7 Ø6.35 1.6~1.8 1.1~1.3 Copper pipe
<16.0(54,600) Ø15.88 Ø9.52 1.6~1.8 1.5~1.7
≤22.4(76,400) Ø19.05 Ø9.52 1.9~2.1 1.5~1.7 Clamp handle
Red arrow mark
Firmly hold copper tube in a bar(or die) as indicated
dimension in the table above.
Smooth all round
Inside is shining without scratches.
4) Check
• Compare the flared work with figure below. = Improper flaring =
• If flare is noted to be defective, cut off the flared
section and do flaring work again

Inclined Surface Cracked Uneven


damaged thickness
Even length
all round

R410A(50Hz/60Hz) _ 7
Shell & Coil
5. Installation
5) Pipe connection
1. Follow the pipe path. Bend the pipe more than 3 times in 1 location and do not bend in the opposite direction.
(This will strengthen the pipe.)
2. After deforming the pipe, align the union fitting and center of the pipe, and tighten it with the wrench.
3. Connect the pipe to the service valve of the outside unit.
4. After finishing the piping work, check if there is any gas leakage
5. For the flare nut, always use the material that complies with Standard or better.
6. After completing the connection of the pipe, vacuum dry the indoor unit and the connecting pipe.
For the vacuum drying, you must use service ports of both the gas and liquid pipes.

Pipe Size Tightening Torque


(mm) (N·m) (kgf·cm)
Ø6.35 18~25 180~250
Ø9.52 34~42 340~420
Ø12.7 55~66 550~660
Ø15.88 63~82 630~820
Ø19.05 99~121 990~1,210

CAUTION
When using two wrenches, tighten at regulated torque
* For the pipe connection, use the method of connecting the end of the pipe to the branch pipe. The refrigerant pipe
coming out from the outside unit is branched out at the end and is individually connected to the indoor unit.

WARNING
Installation of Outside Units

• Always be careful not to leak the refrigerant during the welding.


• When the refrigerant is combusted, it generates a toxic poisonous gas.
• Do not execute the welding work in a closed location.
• Always do a leakage test after welding the pipes.

Cut both the pipe and the valve with a


cutter to suit the length
(Don't cut the length of less than 70mm)

Open status when both the pipe and


the valve are in a straight line.
CLOSE OPEN

WARNING
After completing work, securely tighten both service ports and caps so that gas does not leak.

8 _ R410A(50Hz/60Hz)
Shell & Coil
5. Installation
* High/low pressure side is the ball valve that is opened and
closed by 1/4 rotation
① Pipe joint (auxiliary parts): Securely perform brazing with a
nitrogen blow into the service valve port.(Releasing pressure :
0.02 MPa or less)
② Flare nut: Loose or tighten flare nut by using the wrench with
both ends. Coat the flare connection part with oil for the com-
pressor.
③ Cap: Remove caps and operate valve, etc. After operation,
always reattach caps (tightening torque of valve cap: 25Nm
(250kg-cm) or more).
(Don't remove the internal part of the port)
④ Service port: Make the refrigerant pipe vacuum and charge it
using the service port. Always reattach caps after completing
Ball Valve(Liquid Pipe)
work (tightening torque of service cap: 14Nm (140kg-cm) or
more).
Elbow
⑤ Liquid pipe
⑥ Gas pipe
Ball Valve(Gas Pipe)
⑦ Elbow joint (field supply)

CAUTION
After installing the pipe, block the pipe escape of front and side panel. (It can cause mouse or other animals to
enter and cause damage to the wire.)

Installation of Outside Units


6) Heat Insulation Fastening band
(accessory)
1. Use the heat insulation material for the refrigerant piping
which has an excellent heat-resistance (Over 120°C)
2. When installing in a humid environment, use thicker heat
insulation material.
* Consult with LG on detailed technical specification. Refrigerant piping

Indoor unit
Thermal insulator
(accessory)

R410A(50Hz/60Hz) _ 9
Shell & Coil
5. Installation
7) Standard refrigerant pipe EPDM heat insulation material thickness
[Unit:mm]
Air conditioned location Non-air conditioned location
Classification Note1) Note2) Special location Note3) Note4) Negative condition
General location General location
Ø6.35
Liquid Above t9 Above t9 Above t9 Above t9
Ø9.52
pipe
Above Ø12.7 Above t13 Above t13 Above t13 Above t13
Ø9.52
Ø12.7
Ø15.88
Above t13 Above t19 Above t19
Ø19.05
Gas Ø22.22
pipe Above t25
Ø25.4
Ø28.58
Ø31.75
Ø34.9 Above t19
Above t25 Above t25
Ø38.1
Ø44.45

Note 1) General location: When the pipe passes through indoors in which the indoor unit is operated
- Apartment, classroom, office, mall, hospital, office-tel etc.
Note 2) Special location
1. When the location is air conditioned but has severe temperature/humidity difference due to high ceiling
- Church, auditorium, theater, lobby etc.
2. When the location is air conditioned but the internal temperature/humidity of the ceiling finishing is high
- Bathroom/swimming pool locker room etc. (Building with roof ceiling of sandwich assembly type)
Installation of Outside Units

Note 3) General location: When the pipe passes indoors where the indoor unit is not operated
- Hall way etc. (Dormitory, school, office-tel)
Note 4) Negative condition: When below conditions 1 and 2 are met.
1. When the pipe passes indoors where the indoor unit is not operated
2. When the humidity is high, regionally, and there is no air flow in the pipe passing area
- If you are not sure with the selection of heat insulation material, coordinate with the supervision or HQ.
- The thickness of the above heat insulation material is based on the heat conductivity of 0.088W/m°C.

10 _ R410A(50Hz/60Hz)
Shell & Coil
5. Installation
8) Connecting branch pipe between outside units
[Unit:mm]

Outside units Model Gas Pipe Liquid Pipe

416(16-3/8) 331(13-1/32)
408(16-1/16) 314(12-3/8)
I.D.28.58(1-1/8) I.D.28.58(1-1/8) I.D.15.88(5/8) I.D.15.88(5/8)
A B

83(3-9/32)
111(4-3/8)
(Master) (Slave1) I.D.19.05(3/4) I.D.12.7(1/2) I.D.9.52(3/8)
I.D.22.2(7/8)
I.D.31.8(1-1/4) I.D.34.9(1-3/8)

2 Unit A ARCNN21 I.D.28.58(1-1/8) I.D.12.7(1/2) I.D.15.88(5/8)

I.D.38.1(1-1/2) I.D12.7(1/2)
I.D.41.3(1-5/8) O.D.34.9(1-3/8) I.D.22.2(7/8) O.D.19.05(3/4)
O.D28.58(1-1/8) I.D22.2(7/8) O.D15.88(5/8) I.D9.52(3/8)

I.D19.05(3/4)
130(5-1/8) 70(2-3/4)
120(4-23/32)
110(4-11/32)

406(15-31/32) 334(13-5/32)
353(13-29/32) 281(11-1/16)
I.D38.1(1-1/2)

83(3-9/32)
A B C

111(4-3/8)
(Master) (Slave1) (Slave2) I.D.41.3(1-5/8) I.D34.9(1-3/8) I.D.34.9(1-3/8) I.D.22.2(7/8) I.D.19.05(3/4) I.D.19.05(3/4)

3 Unit ARCNN31 I.D.15.88(5/8) I.D.12.7(1/2)


I.D.28.58(1-1/8)

I.D. 15.88(5/8) I.D.9.52(3/8)


I.D.41.3(1-5/8) O.D.34.9(1-3/8) I.D22.2(7/8) O.D. 19.05(3/4) I.D. 12.7(1/2)
O.D. 12.7(1/2)
O.D28.58(1-1/8) I.D. 6.35(1/4)
X2
I.D19.05(3/4)
125(4-29/32) 120(4-23/32) 110(4-11/32) 110(4-11/32)

* Install the branch pipe between outside units so that the outlet pipe is parallel to the surface.

Installation of Outside Units


Execute the
Within +/- 10 welding while
pouring nitrogen
Viewed from point A Do not cut for
in direction of arrow 70mm or less

CAUTION
When installing the branch pipe vertically between the outside units, the refrigerant can be uneven
between the outside units, leading to compressor burn and reduced capacity

R410A(50Hz/60Hz) _ 11
Shell & Coil
5. Installation
9) Installation of water pipe
1. Water pipe system diagram
• The water pressure resistance of the water pipe system of this product is 1.98MPa
• When the water pipe passes indoors, make sure to execute heat insulation on the pipe so that water drops do not
form on the outer side of the water pipe.
• The size of the drain pipe must be equal to or larger than the diameter of the connecting product.
- Always install a trap so that the drained water does not back flush.
• Always install a strainer (20 Mesh or above) at the entrance of the water pipe. (When sand, trash, rusted pieces
get mixed into the water supply, it can cause problems to the product due to blocking)
- If On/Off valve is applied, by interlocking with outside unit, it can save the energy consumption of pump by
blocking the water supply to the outside unit not operating.
Select appropriate valve and install on site if necessary.
• Install a pressure gauge and temperature gauge at the inlet and outlet of the water pipe.
• Flexible joints must be installed not to cause any leakage from the vibration of pipes.
• Install a service port to clean the heat exchanger at the each end of the water inlet and outlet.
• For the components of the water pipe system, always use components above the designed water pressure.

Pressure gauge Temperature gauge


Water pipe
outlet Gate valve Service port

Water pipe
Inlet Strainer

Gate valve Service port


Installation of Outside Units

Drain line Condensed


water drain

CAUTION
Do not directly connect the drain outlet to the water pipe outlet.
(It can cause problems to the product.)

12 _ R410A(50Hz/60Hz)
Shell & Coil
5. Installation
2. Water pipe connection
• The water pipe should be the same size of the connection on the product or more.
• If necessary install the insulation material in the water pipe inlet/outlet to prevent water drop and to save energy.
(Use the above 20mm thickness Pe insulation material.)
• Tightly connect the socket to the water pipe refer to below table for recommended specification.
(Too much torque may cause the damage of the facility.)

Pipe thickness Shear stress Tensile stress Bending moment Torque

mm inch (kN) (kgf) (kN) (kgf) (N.m) (kgf.m) (N.m) (kgf.m)


12.7 1/2 3.5 350 2.5 250 20 2 35 3.5
19.05 3/4 12 1,200 2.5 250 20 2 115 11.5
25.4 1 11.2 1,120 4 400 45 4.5 155 15.5
31.8 1 1/4 14.5 1,450 6.5 650 87.5 8.75 265 26.5
38.1 1 1/2 16.5 1,700 9.5 950 155 16 350 35.5
50.8 2 21.5 2,200 13.5 1,400 255 26 600 61

Installation of Outside Units


Water pipe outlet
Water pipe connection
Water pipe inlet

R410A(50Hz/60Hz) _ 13
Shell & Coil
6. Device protection unit
6.1 Strainer on water pipe
To protect the water cooling type product, you must install a strainer with 20 mesh or more on the water supply pipe.
If not installed, alien particles can block the heat exchanger and decrease capacity.

Head loss of strainer on water pipe


: Suggestion range
: Allowed range

50
kpa

96
I/min
Base on ARWV100

Upper graph is a theoretical value for selection and it may be different according to specification of strainer.
Installation of Outside Units

14 _ R410A(50Hz/60Hz)
Shell & Coil
6. Device protection unit
6.2 Flow switch work
Cover
• It is recommended to install the flow switch to the water collection pipe
system connecting to the outside unit.
Micro-switch
(Flow switch acts as the 1st protection device when the heat water is not Adjustment screw
supplied. If a certain level of water does not flow after installing the flow Vibration plate
switch, an error sign of CH24 error will be displayed on the product and Bellows
the product will stop operating.)
1 inch or
• When setting the flow switch, it is recommended to use the product with 3/4 inch
default set value to satisfy the minimum flow rate of this product. socket
(The minimum flow rate range of this product is 50%. Reference flow rate
: 10HP - 96LPM, 20HP - 192LPM
• Select the flow switch with the permitted pressure specification consider-
ing the pressure specification of the heat water supply system. Pad
(Control signal from outside unit is AC 220V.)

6.3 Installation of flow switch


• The flow switch must be installed at the horizontal pipe of the heat water supply outlet of the product and check the direc-
tion of the heat water flow before the installation. (Picture 1)
• When connecting the flow switch to the product, remove the jump wire to connect to the communication terminal (5(A) and
5(B)) of the outside unit control box. (Picture 2, 3) (Open the cover of the flow switch and check the wiring diagram before
connecting the wires. The wiring method can differ by the manufacturer of the flow switch.)
• If necessary, adjust the flow rate detection screw after consulting with an expert and adjust to the minimum flow rate
range. (Picture 4) (Minimum flow rate range of this product is 50%. Adjust the flow switch to touch the contact point when
the flow rate reaches 50% of the flow rate.)
- Reference flow rate : 10HP - 96LPM, 20HP - 192LPM)

Installation of Outside Units


Picture 1 Picture 2 Picture 3 Picture 4

CAUTION
• If the set value does not satisfy the minimum flow rate or if the set value is changed by the user arbitrarily, it can result
in product performance deterioration or serious product problem.
• If the product is operated with the heat water supply not flowing smoothly, it can damage the heat exchanger or cause
serious product problems.
• When the product operates while the flow switch touches the contact point at the flow rate range out of the permitted
range, it can cause product performance deterioration or serious product problem.
• Must use the normal closed type flow switch
- Circuit of outside unit is normal closed type

R410A(50Hz/60Hz) _ 15
Shell & Coil
7. Refrigerant piping system
7.1 Refrigerant piping system

Y branch method

Single outside unit system


Example : 5 Indoor Units connected
Ⓐ : Outside Unit IDU
Ⓑ : 1st branch direction
Ⓒ : Y branch
Ⓓ : Indoor Unit
Ⓔ : Header branch
Ⓕ : Pinch off L150m (200 m : Conditional application)
l 40m (90 m : Conditional application)

H 50m

h 40m

* If it is conditionally installed, refer to (table 1).

Series outside unit system


Installation of Outside Units

Example : 5 Indoor Units connected Slave2


Slave1 IDU
Ⓐ : Outside Unit direction
10m or Master
Ⓑ : 1st branch less
Ⓒ : Y branch ODU Capacity
H
Ⓓ : Indoor Unit Master ≥ Slave1 ≥ Slave2
G
Ⓔ : Header branch
Ⓕ : Pinch off L150m (200 m : Conditional application)
Ⓖ : Outside branch(1st) l 40m (90 m : Conditional application)
Ⓗ : Outside branch(2nd)

h If it will be installed 20HP and 30HP,


please contact the HQ.
h 40m

* If it is conditionally installed, refer to (table 1).

16 _ R410A(50Hz/60Hz)
Shell & Coil
7. Refrigerant piping system
Header Method

Single outside unit system


Example : 6 Indoor Units connected
Ⓐ : Outside Unit
Ⓑ : 1st branch
Ⓒ : Y branch
Ⓓ : Indoor Unit
Ⓔ : Header branch L 150m
Ⓕ : Pinch off

H 50 m
40m
E

D D
D D D
40m D

Series outside unit system


Example : 6 Indoor Units connected Slave2
Ⓐ : Outside Unit Slave1
Master
Ⓑ : 1st branch
10m or
Ⓒ : Y branch less
Ⓓ : Indoor Unit

Installation of Outside Units


H
ODU Capacity
Ⓔ : Header branch G
Master ≥ Slave1 ≥ Slave2
Ⓕ : Pinch off
L 150m
Ⓖ : Outside branch(1st)
Ⓗ : Outside branch(2nd) 40m
H 50m

40m

R410A(50Hz/60Hz) _ 17
Shell & Coil
7. Refrigerant piping system
Combination of Y branch/header method

Single outside unit system


Example : 5 Indoor Units connected
Ⓐ : Outside Unit
Ⓑ : 1st branch
Ⓒ : Y branch
Ⓓ : Indoor Unit
Ⓔ : Header branch
Ⓕ : Pinch off

H 50m
L 150m(200m : Conditional application)

40m
40m(90m : Conditional application)

* If it is conditionally installed, refer to (table 1).

Series outside unit system


Example : 5 Indoor Units connected
Slave2
Ⓐ : Outside Unit
Slave1
Ⓑ : 1st branch Master
10m or
Installation of Outside Units

Ⓒ : Y branch less ODU Capacity


Ⓓ : Indoor Unit Master ≥ Slave1 ≥ Slave2
H
Ⓔ : Header branch G
Ⓕ : Pinch off
Ⓖ : Outside branch(1st)
H 50m

Ⓗ : Outside branch(2nd) L 150m(200m : Conditional application)


40m(90m : Conditional application)
40m

* If it is conditionally installed, refer to (table 1).

18 _ R410A(50Hz/60Hz)
Shell & Coil
7. Refrigerant piping system
➲ Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor Unit
Liquid pipe(mm) Gas pipe(mm)
total capacity(kW)
≤ 5.6 Ø 6.35 Ø 12.7
< 16.0 Ø 9.52 Ø 15.88
≤ 23.0 Ø 9.52 Ø 19.05
< 33.0 Ø 9.52 Ø 22.2
< 47.0 Ø 12.7 Ø 28.58
< 71.0 Ø 15.88 Ø 28.58
< 104.0 Ø 19.05 Ø 34.9
< 174.0 Ø 19.05 Ø 41.3

➲ Total pipe length limited

Classification Section Type Y branch Y/header branch Header branch


A+B+C+D+e A+B+b ≤ 150 m
Maximum pipe
≤ 150 m A+C+e ≤ 150 m A+f ≤ 150 m
length(L)
(Conditionally 200 m)* (Conditionally 200m)*
Maximum
Outside unit Corresponding 175 m 175 m
permitted 175 m
↔ indoor unit pipe length (Conditionally 225 m)* (Conditionally 225 m)*
length
Total pipe length
300 m 300 m 300 m
(Outside unit ↔
(Conditionally 500 m)* (Conditionally 500 m)* (Conditionally 500 m)*
total indoor unit)
Outside unit height

Installation of Outside Units


50 m 50 m 50 m
Permitted ↔ indoor unit difference(H)
height Indoor unit height
40 m 40 m 40 m
↔ indoor unit difference(h)
Maximum pipe
Actual pipe 40 m 40 m
length after 40 m
length(ℓ) (Conditionally 90m)* (Conditionally 90m)*
1st branch

WARNING
• It is recommended that difference of piping length for pipes connected to the Indoor Unit is minimized.
Performance difference between Indoor Units may occur.
• When the any one (or both ) of below conditions are satisfied, the diameter of main pipe (A) must be
increased according to below table.
- The equivalent length between outside unit and the farthest indoor unit is 90m or more (Liquid and Gas
pipes are increased)
- The level difference (Outside unit Indoor unit) is 50m or more (Only liquid pipe is increased)

R410A(50Hz/60Hz) _ 19
Shell & Coil
7. Refrigerant piping system
➲ Refrigerant pipe diameter from outside unit to first branch. (A, E, F)

Upward Outside Increased Pipe Diameter


unit Standard Pipe Diameter When pipe length is 90m or more from
total capacity ODU to 1st branch
kW Liquid pipe[mm(inch)] Gas pipe[mm(inch)] Liquid pipe[mm(inch)] Gas pipe[mm(inch)]
28 Ø 9.52(3/8) Ø 22.2(7/8) Ø 12.7(1/2) Ø 25.4(1)
56 Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) Ø 31.8(1-1/4)
84 Ø 19.05(3/4) Ø 34.9(1-3/8) Ø 22.2(7/8) Ø 38.1(1-1/2)

* If the step up size is not available, you can not select the next higher size available.
Installation of Outside Units

20 _ R410A(50Hz/60Hz)
Shell & Coil
7. Refrigerant piping system
◆ (Table 1) Cautions during the installation of Maximum pipe length 90m after the 1st branch

WARNING
To install maximum pipe length after the 1st branch exceeding 40 m and 90 m or less, the following condi-
tions must be satisfied.

Required Example

Select the diameter of the pipe Ø6.35 Ø9.52, Ø9.52 Ø12.7,


between the 1st branch and the last 40 m < B+C+D+e ≤ 90 m
Ø12.7 Ø15.88, Ø15.88 Ø19.05,
branch to be 1 level larger. →
1 Ø19.05 Ø22.2, Ø22.2 Ø25.4,
Provided that, it is not necessary if Change B, C, and D pipe
the pipe diameter is the same as the diameter. Ø25.4 Ø28.58, Ø28.58 Ø31.8,
main pipe. Ø31.8 Ø34.9, Ø34.9 Ø38.1

During the calculation of the total


A+Bx2+Cx2+
2 refrigerant pipe length, the above pipe
Dx2+a+b+c+d+e ≤ 500 m IDU
length shall be calculated as twice. Direction

The length from each indoor unit to


3 a,b,c,d,e ≤ 40 m
the nearest branch pipe ≤ 40 m L

H 50 m

[Length from outside unit to the far-


thest indoor unit] – [Length from out- (A+B+C+D+e)-(A+a)
4
side unit to the nearest indoor unit] ≤ ≤ 40 m h 40m

40 m

Installation of Outside Units


◆ Cautions for Y branch pipe

WARNING
If the pipe diameter(B, C) connected after the 1st branch is larger than the main pipe diameter(A), install the
pipe diameter(B, C) connected after the 1st branch to be the same as the main pipe diameter(A).
Example) If indoor units are connected 120 % to 29 kW
• Outside unit main pipe diameter(A): (Gas pipe) (Fluid pipe)
• Pipe diameter(B, C) after the 1st branch according to 120% indoor unit combination(34.8kW):
(Gas pipe) (Fluid pipe)
Therefore, select the pipe diameter(B, C) after the 1st branch to be main pipe diameter(A) (Gas pipe) (Fluid pipe)

◆ Cautions for header branch pipe

WARNING
• It is recommended to install the difference between the length of the pipe after header branch(a~f) and the
length of the pipe connected to indoor unit to be the minimum.
• As the pipe length difference increases, there may be performance differences between indoor units.
• Y branch and header branch cannot be used after header branch.

R410A(50Hz/60Hz) _ 21
Shell & Coil
7. Refrigerant piping system
7.2 Indoor unit connection
➔ Indoor unit connecting pipe from branch (a~f)
Liquid pipe Gas pipe
Indoor unit capacity [kW(Btu/h)]
[mm(inch)] [mm(inch)]
≤ 5.6(19,100) Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
≤ 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
< 33(112,600) Ø9.52(3/8) Ø22.2(7/8)

7.3 Oil trap application method between outside units


• Because of the possibility of oil being accumulated in the outside unit that has stopped, when there is a height difference
between outside unit pipes or if the pipe distance between the outside units is over 2m, you must always apply an oil trap. (But,
the oil trap between outside units is limited to 1 time and is only applied to the gas pipe.)
• If the pipe distance between the outside units is 2m or below, and if the location of the main pipe is lower than that of the out-
side unit and if the location of the main pipe is lower than that of the outside unit, the oil trap does not have to be applied.
• If the location of the main pipe is higher than the location of the outside unit, be careful since the oil can be accumulated in the
stopped outside unit.
• If there is high/low difference between the outside unit pipes, oil can be accumulated to the outside unit on the lower location
until the unit stops.

Examples of Wrong Pipe Connections


Installation of Outside Units

If the main pipe is higher


than the outdoor units,
oil is accumulated in the Oil Trap
outdoor unit.

If there are differences in the height between


the outdoor units, oil is accumulated in the
lower outdoor unit.

22 _ R410A(50Hz/60Hz)
Shell & Coil
7. Refrigerant piping system
- The pipes between the outside units must maintain horizontal levelness or give an inclination to prevent a back
flow toward the slave outside unit. Otherwise, the unit may not operate properly.

(Example 1)

Toward indoor unit


Toward indoor unit
(Example 2)

Toward indoor unit Pipe inclination (2 or more)


Toward indoor unit
(Example 3)

Toward indoor unit

Toward indoor unit

Installation of Outside Units


- Apply Oil Trap as shown below when the length of the pipe between the outside units is more than 2m. Otherwise,
the unit may not operate properly.

(Example 1)

Toward indoor unit 2m

(Example 2)
0.2m

Oil Trap

Toward indoor unit 2m


2m

R410A(50Hz/60Hz) _ 23
Shell & Coil
7. Refrigerant piping system
- When connecting the pipes between the outside units, the accumulation of oil in the slave outside unit should be
avoided. Otherwise, the unit may not operate properly.

(Example 1)

Toward indoor unit Toward indoor unit

(Example 2)

Toward indoor unit


Installation of Outside Units

(Example 3)

Oil Trap

h h
0.2m

Toward indoor unit Toward indoor unit

24 _ R410A(50Hz/60Hz)
Shell & Coil
7. Refrigerant piping system
7.4 Calculation of amount of refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correction Factor) value of
indoor unit.

= Total liquid pipe


Additional charge(kg) :Ø25.4 mm

Total liquid pipe


+ :Ø22.2 mm

Total liquid pipe


+
:Ø19.05 mm

Total liquid pipe


+
:Ø15.88 mm

Total liquid pipe


+
:Ø12.7 mm

Total liquid pipe


+
:Ø9.52 mm

Total liquid pipe


+
:Ø6.35 mm

+ CF value of indoor unit

Note:
Please refer to the additional refrigerant table for indoor units of installation manual.

Installation of Outside Units

R410A(50Hz/60Hz) _ 25
Shell & Coil
7. Refrigerant piping system

Note:
Fill in the f-gas Label attached on outside about the quantity of the fluorinated greenhouse gases
① Manufacturing site (See Model Name label)
② Installation site (If possible being placed adjacent to the service points for the addition or removal of
refrigerant)
③ The total Charge (①+②)

WARNING
▶Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.

Total amount of refrigerant in the system


≤ 0.44 ( kg / m3)
Volume of the room at which indoor unit of the least capacity is installed

If the above equation cannot be satisfied, the following steps must be followed.
- Selection of air conditioning system: Select one of the following
1. Installation of effective opening part: At the top and bottom of the door connecting the room to the outside, create an opening
with or without the door of with 0.15% of floor space or above.
2. Recheck of outside unit capacity and piping length
3. Reduction of the amount of refrigerant
4. Installation of 2 or more security devices (Alarm for gas leakage)
- Change indoor unit type
: Installation position should be over 2m from the floor (Wall mounted type → cassette type)
- Adoption of ventilation system
Installation of Outside Units

Ventilation system prevents the refrigerant density from increasing when the refrigerant is leaked by the installation.
Ventilation system comes in two types; external air inflow type or exhaust type. External air inflow type is recommended due to
the characteristics of the refrigerant.
Always operate the ventilation system irrelevant from whether the air conditioner is used or not and whether the indoor or not.
When it is impossible to operate this and in case of a refrigerant leakage by the sensor, the ventilation system is automatically
operated.
- Limitation in piping work
: Prepare for earthquake and thermal stress
- Reduction of all refrigerant charge amount of the refrigerant facility (When calculated value exceeds 0.44kg/m3)
1. Shorten the refrigerant pipe length.
Change the location of the outside unit and shorten the length of the refrigerant pipe to reduce all refrigerant charge amount.
2. Distribute the outside unit to several units to reduce the refrigerant charge amount per outside unit. (Ex. 20 HP 1 unit →
10 HP 2 units)

26 _ R410A(50Hz/60Hz)
Shell & Coil
8. Y branch pipe and header branch pipe type
8.1 Y branch pipe [unit:mm]

Models Gas pipe Liquid pipe

I.D12.7 I.D12.7 I.D6.35


I.D15.88 I.D15.88 I.D.6.35 I.D9.52 I.D9.52
1

I.D15.88 74 I.D.6.35 74
ARBLN01621 I.D12.7 I.D.9.52

281 281
292 292
1 O.D9.52
I.D19.05 O.D15.88
I.D12.7 70
70

70

I.D22.2 I.D19.05 I.D15.88 I.D19.05 I.D12.7


2
1 I.D12.7
I.D19.05 I.D9.52 I.D9.52 I.D6.35
I.D25.4 83
I.D15.88 I.D12.7

ARBLN03321 390
413
3 I.D12.7
I.D9.52
I.D12.7
I.D6.35
74

O.D19.05 I.D22.2 I.D28.58 O.D25.4


O.D19.05
I.D22.2
321
I.D25.4
3 1 2 332

70 80 110

I.D19.05 I.D19.05
I.D28.58 I.D22.2 I.D15.88 I.D12.7 I.D15.88 I.D15.88 I.D12.7
2 2
1
I.D12.7
I.D31.8 I.D15.88 I.D19.05 I.D15.88 I.D19.05 83
I.D19.05 I.D12.7 96

ARBLN07121 376
3 371 3
404 394

I.D28.58 I.D31.8 I.D34.9 O.D31.8 O.D19.05 I.D22.2 O.D12.7 I.D9.52 I.D6.35 O.D12.7 I.D9.52
I.D28.58
2 1 3 3 2
O.D22.2

Installation of Outside Units


120 90 120 110 70

I.D34.9
I.D41.3 I.D38.1 I.D28.58 I.D19.05
2 I.D15.88 I.D19.05 I.D22.2 I.D15.88
I.D34.9 2
1
I.D38.1 I.D28.58 I.D15.88
125 I.D22.2
I.D34.9 I.D22.2 I.D19.05 I.D12.7 96

471 3
ARBLN14521 517 416 3
444
I.D19.05 I.D15.88 O.D38.1 I.D41.3 O.D34.9 I.D38.1
3
2 3 I.D41.3
O.D22.2 I.D12.7 O.D19.05 I.D9.52
120 90 130 O.D15.88 I.D9.52 I.D22.2 O.D12.7 I.D6.35
I.D12.7 O.D28.58 I.D22.2 2 3 3
3
2 I.D19.05
O.D15.88 110 80 110

R410A(50Hz/60Hz) _ 27
Shell & Coil
8. Y branch pipe and header branch pipe type
8.2 Header [unit:mm]

Models Gas pipe Liquid pipe


360 360
120 120
ID12.7 ID6.35
ID12.7 ID6.35
4 branch
ID9.52 150
ID15.88 150 ID9.52
120 120
ARBL054 ID15.88

ID19.05 ID15.88 ID12.7 ID9.52

540 540
120 120
ID12.7 ID6.35
7 branch ID12.7
ID15.88 ID9.52
ID15.88
150 120 150
ARBL057 120

ID19.05 ID15.88 ID12.7 ID9.52

400 360
160 120
ID15.88 ID6.35
ID12.7 ID6.35
4 branch
ID19.05 ID9.52 150
150 ID9.52 120
ARBL104 ID15.88 120

ID28.58 ID25.4 ID22.2 ID12.7 ID9.52

580 700
160 120
ID15.88 ID6.35
Installation of Outside Units

ID12.7 ID6.35
7 branch
ID19.05 150 ID9.52 150
ID15.88 120 ID9.52 120
ARBL107
ID28.58 ID25.4 ID22.2 ID12.7 ID9.52

760 720
160 120
ID15.88
10 branch ID12.7 ID6.35
ID6.35

150 150
ARBL1010 ID15.88
ID19.05 120 ID9.52 120

ID9.52
ID12.7 ID9.52
ID28.58 ID25.4 ID22.2

700
775
182 60*9=540 107
ID15.88 ID6.35
10 branch ID12.7 ID6.35
ID19.05 150 ID9.52 150
ID15.88
ARBL2010 120 120

ID9.52 ID15.88 ID19.05


ID31.8 ID34.9 ID28.58

28 _ R410A(50Hz/60Hz)
Shell & Coil
9. Electrical Wiring
9.1 Areas of Caution
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations and guidance of each electric power company.

WARNING
Be sure to have authorized Electrical engineers do electric work using special circuits in accor-
dance with regulations and this installation manual. If power supply circuit has a lack of capacity
or electric work deficiency, it may cause an electric shock or fire.

2. Install the outside unit transmission line away from the power source wiring so that it may not affected by
electric noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to outside unit.

CAUTION
Be sure to correct the outside unit to earth. Do not connect earth line to any gas pipe, water pipe,
lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.

4. Give some allowance to wiring for electrical part box of indoor and outside units, because the box is some-
times removed at the time of service work.
5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts will
be burnt out.
6. Use 2-core shield cable for transmission line.( mark in the figure below) If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor transmission and receiving will cause

Installation of Outside Units


erroneous operations. ( mark in the figure below)
7. Only the transmission line specified should be connected to the terminal block for outside unit transmission.

Outside Unit Outside Unit

Indoor Indoor Indoor Indoor


Unit Unit Unit Unit

Remote Remote Remote Remote


control control control control

Outside Unit

Indoor Indoor Indoor Indoor


Unit Unit Unit Unit

Remote Remote Remote Remote


control control control control

2-core shield cable Multi-core cable

R410A(50Hz/60Hz) _ 29
Shell & Coil
9. Electrical Wiring

Outside Unit Outside Unit


Master Slave1 Slave2 Master Slave1 Slave2

Indoor Indoor Indoor Indoor


Unit Unit Unit Unit

Remote Remote Remote Remote


controller controller controller controller

Outside Unit Outside Unit


Master Slave1 Slave2 Master Slave1 Slave2

Indoor Indoor Indoor Indoor


Unit Unit Unit Unit

Remote Remote Remote Remote


controller controller controller controller

2-Core Shield Cable Multi-Core Cable

WARNING
• Use the 2-core shield cables for transmission lines. Never use them together with power cables.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate
power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never
install a phase leading capacitor.
• Keep power imbalance within 2% of the supply rating. Large imbalance will shorten the life of the
smoothing capacitor.
• Introducing with a missing N-phase or with a mistaken N-phase will break the equipment.
Installation of Outside Units

9.2 Control Box and Wiring Location


- Unscrew all the screw, pull out the panel.
- Connect the transmission wire between outside unit and indoor
unit, the connection between outside unit and central controller
system pass through the sub PCB for central control.
- When connecting indoor unit with the shield cable, ground at
the grounding screw.
When connecting central controller with the shield cable,
ground at the grounding screw.
Front
- Refer to next page about the distance between main power
Panel
cable and communication cable.
- Refer to 106 page about Auto-Addressing and Test Run.

30 _ R410A(50Hz/60Hz)
Shell & Coil
9. Electrical Wiring
9.3 Transmission and Power Lines
1) Transmission cable
• Types : Shielded cable CVVS or CPEVS
• Use wires of size : 1.0 ~ 1.5 mm2
• Insulation material : PVC
• Maximum allowable temperature: 60°C
• Maximum allowable line length: under 300m
2) Remote control cable
• Types : 3-core cable
3) Simple central control cable
• Types : 4-core cable (Shielding wire)
• Use wires of size : 1.0 ~ 1.5 mm2
• Insulation material : PVC
4) Separation of transmission and power lines
• If transmission and power lines are run alongside each other then here is a strong likelihood of operational
faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic cou-
pling.

Current capacity of power line Spacing


10A 300mm
50A 500mm
100V or more
100A 1,000mm

Installation of Outside Units


Exceed 100A 1,500mm

Note:
1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m the
figures will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the table
should be increased.
• If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits.
• Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
conduit.
• In the same way, when grouping the power lines and signal lines should not be bunched together.

CAUTION
• If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the
apparatus must be carried out by a qualified person.
• Use a power wire pipe for the power wiring.

R410A(50Hz/60Hz) _ 31
Shell & Coil
9. Electrical Wiring
◆ Example for mistake of wiring
• Do not separately connect the power of the indoor unit.
3phase 4lines power cable
Transmission cable(3lines): wired remote controller
Single phase 60Hz 220V
Transmission cable(2lines Shield cable) : Indoor~ Outside unit

Single phase 60Hz 220V

3 phase 4 wires
power supply Breaker
50Hz 380~415V
60Hz 380V
Installation of Outside Units

CAUTION
Never install individual switch or individual outlet to cut the power connecting the indoor unit.

32 _ R410A(50Hz/60Hz)
Shell & Coil
9. Electrical Wiring
9.4 Dip switch setting
9.4.1 Setting the function
Select the mode/function/option/value using ‘▶’, ‘◀’ Button and confirm that using the ‘ ’ button after dip
switch No.5 is turned on.

CAUTION
• It is only executed when all indoor units are off.

DIP-SW01 7 - Segment

SW04C ( : cancel)

SW03C ( ඖ: forward)
SW02C (ඔ: backward)
SW01C (̻: confirm)
SW01D (reset)

Mode Function Option Value Action


Remarks
Content Display1 Content Display2 Content Display3 Content Display4 Implement Display5
Cool & Heat Selected the Change the Save in
OFF op1~op2 - - Blank

Installation of Outside Units


Selector option set value EEPROM
Geothermal mode Selected the Change the Save in
ON OFF - - Blank
setting option set value EEPROM
Sol. Valve Selected the Change the Save in
ON OFF - - Blank
200 V output option set value EEPROM
Oil amount change Selected the Change the Save in
Installation ON OFF - - Blank
control option set value EEPROM
Set the Change the Save in
ODU address - - 0~255 Blank
value set value EEPROM
Target pressure Selected the Change the Save in
ON op1~op3 - - Blank
adjusting option set value EEPROM
Selected the Change the Save in
Use Sump Heater ON OFF - - Blank
option set value EEPROM

* Functions save in EEPROM will be kept continuously, though the system power was reset.
To cancel the function you need to set OFF.

R410A(50Hz/60Hz) _ 33
Shell & Coil
9. Electrical Wiring
9.4.2 Dip switch setting
1. Set the dip switch and turn on the power of the outside unit to check whether the set value is correctly
entered in the 7 segment.
2. This function is shown for only 2 seconds after the power is connected.

■ Checking according to dip switch setting


• You can check the setting values of the Master outside unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
• It checks whether the input is properly performed without the bad contact of the dip switch or not

■ Checking the initial display


The number is sequentially appeared at the 7 segment in 5 seconds after applying the power.
This number represents the setting condition.
Master model capacity → Slave1 model capacity → Slave2 model capacity → Slave3 model capacity
→ Total capacity → System type → Power type → Product type

Example) 178 kW(62HP) 4Unit R410A combination (Cooling/heating switching type, 380V general type)
16 → 16 → 16 → 14 → 62 → 2 → 38 → 1

CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.

EX) Details of each symbol Model capacity


Installation of Outside Units

Symbol Number Contents Capacity(kW) Capacity(HP) Remark Refrigerant


① 8~20 Master model capacity 23 8
② 10~20 Slave 1 capacity 29 10
③ 10~20 Slave 2 capacity 35 12 Same
④ 10~20 Slave 3 capacity 41 14 for master R410A
⑤ 8~80 Total capacity 46 16 /slave
1 Cooling only 52 18
Cooling/Heating 57 20
2
⑥ switching type
Simultaneous
3
Cooling/Heating type
38 380 V
⑦ 46 460 V
22 220 V
1 General type
⑧ 2 Tropical type
3 Factory type

34 _ R410A(50Hz/60Hz)
Shell & Coil
9. Electrical Wiring
9.5 Indoor unit auto addressing
• The address of the indoor units would be set by auto addressing.
1) Wait for 3 minutes after applying power supply (master and slave outside unit, indoor unit)
2) Press the switch of the outside unit (SW02V) for 5 seconds.
3) A "88" is indicated on 7-segment LED of the outside unit PCB.
4) For completing addressing, 2~7 minutes are required depending on numbers of indoor unit connection set.
5) Numbers of indoor unit connection set whose addressing is completed are indicated for 30 seconds on 7-segment LED
of the outside unit PCB.
6) After completing addressing, address of each indoor unit is indicated on the wired remote controller display window.
(CH01, CH02, CH03, .... CH06 : Indicated as number of indoor unit connection set.)

[Main PCB]
DIP-SWITCH 7 - Segment

SW04C ( : cancel)

SW03C ( ඖ: forward)

SW02C (ඔ: backward)


SW01C (̻: confirm)

Installation of Outside Units


SW01D (reset)

WARNING
• When replacing the indoor unit PCB, you must execute the auto addressing again. Always execute
this with all the power of indoor units and outside units connected. If the power is not connected to
the indoor unit, it can generate an operation error.
• When power is connected to the Multi V Water II for the first time, it will standby for more than 3 min-
utes to improve the indoor unit communication, and then the address must be set.

R410A(50Hz/60Hz) _ 35
Shell & Coil
9. Electrical Wiring
◆ The Procedure of Automatic Addressing

Power On Turn OFF all DIP switches of the


master main board before
automatic address setting.
Waiting 3 minutes

Press RED Button for 5 sec.


(SW01C)

Automatic addressing start


7-segment LED = 88

Don’t press RED Button


(SW01C)
• Automatic addressing setting end
Numbers of indoor unit connection set whose addressing is
Waiting about 2~7 minutes completed are indicated for 30seconds on 7-segment LED
after completing setting

7-segment LED NO Check the connections


of communication cable
= 88
Installation of Outside Units

YES
Indoor address number is displayed on wired remote control or indoor unit
display window. It is not an error message, will disappeared when on/off
button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units and
Automatic addressing is completed normally.
OK

36 _ R410A(50Hz/60Hz)
Shell & Coil
10. Cooling tower applied method

Open type
cooling tower Closed type
cooling tower

[Open type cooling tower] [Closed type cooling tower]

Heat source water of the cooling tower is supplied directly to the outside unit system.
Because this product is equipped with the shell and coil heat exchanger, it is not necessary for the open
type cooling tower to install the middle heat exchanger.

Installation of Outside Units

R410A(50Hz/60Hz) _ 37
Shell & Coil
11. Water Solenoid Valve Control
11.1 Central Control (Use DDC Port)

Water Water
In Out C_Box CN_24 MAIN PCB

CN_22

CN_18
Flow Switch
INTERNET

1(L) 2(N) 3(L ) 4(N) 5(A) 5(B)


Solenoid
Valve

DDC BMS

11.2 Individual Control (Use 220V Out Port)

Water Water
In Out C_Box CN_24 MAIN PCB
Installation of Outside Units

CN_22

CN_18
Flow Switch

1(L) 2(N) 3(L ) 4(N) 5(A) 5(B)


Solenoid
Valve

Set the dip switch refer to Dip switch setting on Electrical Wiring page.

38 _ R410A(50Hz/60Hz)
Shell & Coil
12. Test Run
12.1 Water supply system test run
• Before executing the test run for the product, you must first test the heat source water system.
The test run for the product must be executed after checking the flow rate and temperature of the heat source
water supplied.

Equipment design Design the system including cooling tower, boiler, pump etc.
- Check the equipment capacity (Water volume, temperature control range).

Water pipe system installation Install the water pipe

Water supply pipe and product Connect the water pipe to the inlet/outlet of the product so that the water
connection can be supplied to the product.

Water supply system test run Execute water supply system test run
- The product does not operate but the pump and water supply equipment
will operate to flow the Heat source water to the heat exchanger on the
product side.
- Flow the water to all water piping system to clean any alien particles inside
the pipes and execute an air purge to remove an air within the pipes to
make the water supply smoother.
- Clean all the strainers of water pipe including around outside units.
Judging whether there is any
Execute the test of water supply system without operating the product.
problem with the water supply
- Check whether outside unit inlet/outlet flow rate complies to the product

Installation of Outside Units


specification.
- Check the water supply temperature. whether is OK

Execute the product test run After checking the normal condition of the water supply, execute the test run
of the product.

R410A(50Hz/60Hz) _ 39
Shell & Coil
12. Test Run
12.2 Precaution before test run
1 Check whether the air is completely removed and the water supply is flowing smoothly.

Check whether there is any refrigerant leakage of any disconnected or loose communication or power wire, or use
2 the electric wiring diagram to check the wiring connection condition.
Check whether the power and communication wire are connected.

Check whether the power cable R, S and T are correctly connected.


Check the insulation resistance with the DB mega tester device (DC 500V) between the power terminal block and
grounding, and check whether it is 2.0MΩ or above when measured.
If the resistance is 2.0MΩ or less, do not operate the product.
Precaution
3 - Never check the insulation resistance for the terminal control board.
(The control board can be damaged.)
- If you leave the system turned off right after the installation or for a long period of time, the refrigerant gets accu-
mulated within the compressor and the insulation resistance reduces to less than 2 MΩ. When the insulation
resistance is 2 MΩ or less, turn on the power and let the electricity be supplied to the crank case heater of the
compressor and let the refrigerant including the oil inside the compressor to evaporate.
Then the insulation resistance value will increase to more than 2.0 MΩ.

4 Check whether the liquid and gas pipes are open.

Precaution when blocking the water cooling type Multi V main power
- While using the product (Air conditioning season/Heating season), always connect the main power of the outside
unit.
- During the test run operation after installing the product or during the operation after blocking the outside unit
main power (Power outage etc.), you must always connect the power 6 hours prior to heating the crank case
5 heater. If the crank case is not preheated for more than 6 hours with the electric heater, it can cause a burn on
Installation of Outside Units

the compressor.
(Heating the bottom part of the compressor with the crank case heater is to evaporate the refrigerant included in
the oil inside the compressor.)

WARNING
• Always check whether the water supply is flowing smoothly before the test run. (If sufficient amount
of water is not flowing, it can burn the product.)
• During the initial test run after installing the product, leaving the product for more than 3 days or
after replacing the compressor, power must be connected 6 hours prior to the operation to heat the
compressor heater. (If the product is not heated sufficiently, it can burn the product.)

40 _ R410A(50Hz/60Hz)
Shell & Coil
12. Test Run
12.3 How to Cope with Abnormal Test Run
Item Phenomenon Cause Checkpoint and resolution
When connecting the flow switch, Check whether the heat source water supply pump is operating.
heat-sourced water doesnʼt flow Check whether the heat source water supply pipe is clogged.
CH24 or the amount of its flow lacks due (Clean strainer, valve locked, valve issue, air trapped etc.)
to the checked error related to Check whether the flow switch is normal condition.
Whether heat-sourced water. (Flow switch problem, arbitrary control, disconnection etc.)
heat
Check whether heat source water supply pump is operating.
water is Heat water not supplied or flow
supplied CH32 Check whether the heat source water supply pipe is clogged.
rate is insufficient
(Clean strainer, valve locked, valve issue, air trapped etc.)
Heat water not supplied or flow Check whether heat source water supply pump is operating.
CH34 rate is insufficient(During Check whether the heat source water supply pipe is clogged.
Cooling) (Clean strainer, valve locked, valve issue, air trapped etc.)

12.4 Maintenance of Shell & coil type heat exchanger


1. Chemical Washing
1) Connect water piping in sizes 25A to 32A expansion pipe fitting.
2) Connect the SCHEX and circulation pump through the 32A water piping.
3) Install the drain pipe to the other pipe line.
4) After open upper plate of SCHEX, put 5% Phosphoric acid aqueous solution in the case. And close the upper plate.
5) Circulation washing for 30 minutes, using a circulation pump. After repeat 3 or 4 times this operation, discharge the

Installation of Outside Units


solution through the drain pipe.
6) 4),5) in the same way, circulation cleaning 3~4 times with clean water once every 30 minutes. And discharge the
water through the drain pipe.
7) Finally, In order to neutralize the acidic conditions of the coil, after circulates the water intermixed with NaOH, dis-
charge the water through the drain pipe.

5 % Phosphoric acid / Water / NaOH

Drain pipe

Circulation
pump

R410A(50Hz/60Hz) _ 41
Shell & Coil
12. Test Run
2. Mechanical Washing
1) Using the Socket Wrench, divide the case and bolt fixed on the lower plate of SCHEX.
2) Spray the Water to the horizontal direction for washing of the entire coil.
3) Brush the coil to the rotating direction and with spraying water.
4) Remove the scale divide from coil with spraying.
5) Assemble the case of SCHEX with Socket Wrench.
6) Operate the system after assembly.

3. Chemical / Mechanical Washing


5 % Phosphoric acid NaOH
Installation of Outside Units

Water

1) After open upper plate of SCHEX, put 5% Phosphoric acid aqueous solution in the case. And close the upper plate.
2) After about 1 hour, discharge 5% Phosphoric acid aqueous solution through the drain pipe.
3) Using the Socket Wrench, divide the case and bolt fixed on the lower plate of SCHEX.
4) Scrub the Coil to the direction from row 4 to row 1 with size Ø 6~8 mm brush.
5) Spray the Water to the horizontal direction for washing of the entire coil.
6) Assemble the case of SCHEX with Socket Wrench.
7) Open the upper plate then circulates the water intermixed with NaOH, discharge the water through the drain pipe.
8) Operate the system after assembly.

42 _ R410A(50Hz/60Hz)
Shell & Coil
12. Test Run
12.5 Daily check/management
1. Water quality control
The shell & coil heat exchanger is not structured to be disassembled, cleaned or replaced with parts.
To prevent corrosion or scaling on the shell & coil heat exchanger, special care must be taken to control the water quali-
ty.
Water quality must satisfy the minimum criteria of the reference water quality items.
When anti-corrosion agent or corrosion inhibitor is added, the substance must not have any corrosive effect on stainless
steel and copper. Even if the circulating water is not contaminated by the external air, it is recommended to empty the
water flowing in the pipe and to resupply the water.
2. Flow rate control
Check whether the strainer is clogged or whether the pipe is filled with air and then check the temperature and pressure
difference of the inlet and outlet pipe to check whether the flow rate is insufficient.
If the temperature and pressure difference is above the appropriate level, it means that the flow rate is reduced. In this
case, the operation must immediately be stopped and re-operated when the root cause is resolved. (*If air is trapped in
the pipe, the air must be purged. Air inside the water pipe interferes with the circulation of the heat water supply and can
cause insufficient flow rate.)

12.6 Maintenance/Repair checklist


Period (Year) 1 2 3 4 5 6 7 8 9 10
Checkpoint
Product operating condition ● ● ● ● ● ● ● ● ● ●
Heat exchanger cleaning (Wash) ● ● ● ● ●
Strainer cleaning ● ● ● ● ● ● ● ● ● ●
Water quality check ● ● ● ● ● ● ● ● ● ●

Installation of Outside Units


Refrigerant leakage check ●
Indoor unit filter cleaning ● ● ● ● ● ● ● ● ● ●

(●: Check mark)

CAUTION
• The above checklist is set based on the minimum period and more frequent checking can be required depending on the
operating condition/water quality condition.
• When cleaning the heat exchanger, make sure to take parts out or lock the value so that chemical detergent does not
penetrate into the pressure gauge etc.
• When cleaning the heat exchanger, check the connecting part of the water pipes prior to cleaning so that the chemical
detergent does not leak.
• After sufficiently mixing the chemical detergent with water, start cleaning.
• Cleaning the heat exchanger is easier at the initial stage and becomes difficult after the scaling has accumulated.
• In areas where the water quality is poor, cleaning is required periodically.
Because chemical detergent has strong acidity, it must be washed off thoroughly with water.
• To check whether it is cleaned well inside, remove the hose and check the inside.
• Purge the air to remove any air inside the water pipe.
• After checking, always check whether the heat water supply is flowing normally flowing before operating the product.

R410A(50Hz/60Hz) _ 43
Shell & Coil

Special Guide

1. Cautions for Refrigerant Leaks


1.1 Introduction
1.2 Checking procedure of limiting concentration
Shell & Coil

1. Caution For Refrigerant Leaks


The installer and system specialist shall secure safety against leakage according to local regulations or standards.
The following standards may be applicable if local regulations are not available.

1.1 Introduction
Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should be large to
such an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room.

n Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting
human body when refrigerant leaks in the air. The limiting concentration shall be described in the unit of kg/m3 (Freon gas
weight per unit air volume) for facilitating calculation.
Limiting concentration: 0.44kg/m3(R410A)

Outside unit

Flow of
(No.1 system) refrigerant

Indoor unit Room where refrigerant leaks


(Refrigerant of the whole No.1
system flows out.)

1.2 Checking procedure of limiting concentration


Check limiting concentration along following steps and take appropriate measure depending on the situation.
n Calculate amount of all the replenished refrigerant (kg) per each refrigerant system.
Amount of replenished Amount of additional Total amount of replenished
=
refrigerant per one outside + replenished refrigerant refrigerant in refrigerant
unit system facility (kg)

Amount of replenished Amount of additionally Note : In case one refrigerant facility is


refrigerant at factory shipment replenished refrigerant divided into 2 or more refrigerant
depending on piping systems and each system is
length or piping independent, amount of replenished
diameter at customer refrigerant of each system shall be
adopted.

n Calculate minimum room capacity


Calculate room capacity by regarding a portion as one room or the smaller room.
(1) Without partition (2) With partition and with opening which serve as passage of
Outside unit
air to adjoining room
Outside unit
Special Guide

In the case of opening


Indoor unit Indoor unit
without door , or 0.15
Opening
% or more openings
(to floor space) both
Partition above and below door)

R410A(50Hz/60Hz) _ 1
Shell & Coil

1. Caution For Refrigerant Leaks


(3) With partition and without opening which serve as passage of air to adjoining room

Outside unit

Indoor unit

Smallest
room

n Calculate refrigerant concentration


Total amount of replenished
refrigerant in refrigerant facility (kg) In case the result of calculation exceeds
= Refrigerant concentration the limiting concentration, perform the
Capacity of smallest room where (kg/m3)
indoor unit is installed (m3) same calculations by shifting to the
(R410A) second smallest, and the third smallest
rooms until at last the result is below the
limiting concentration.

n In case the concentration exceeds the limit


When the concentration exceeds the limit, change original plan or take one of the counter measure shown below:
• Counter measure 1
Provide opening for ventilation.
Provide 0.15% or more opening to floor space both above and below door, or provide opening without door.
• Counter measure 2
Provide gas leak alarm linked with mechanical ventilator.
Reducing the outside refrigerant qty.

Gas leak alarm


Countermeasure 2
Mechanical ventilator

Indoor unit
Special Guide

Countermeasure 1 Opening effective to ventilation

Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is
heavier than air.

2 _ R410A(50Hz/60Hz)
P/No.: MFL61741619

Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com

All rights reserved


Printed in Korea March / 2015 The air conditioners manufactured by LG have received ISO9001 certificate for
The specifications, designs, and quality assurance and ISO14001 certificate for environmental management system.
information in this brochure are subject to
change without notice.