You are on page 1of 4

T4800 Load Sharer

» • Automatic load sharing with relay o


speed control
­ utputs for

• 2-wire communication with other T4800 Load


Sharers
• System frequency control
• Unload facility
• Reverse power and unloaded trip
• Visual indication of voltage, increase, decrease and
unload signals
• Cost effective and highly reliable compact design
• 50 hours burn-in before final test
• Vibration test up to 4g RMS
• Certified by major marine classification societies
• Flame retardant enclosure

Application Function The speed governor must operate with


The T4800 Load Sharer provides ­automatic The input to the T4800 is the voltage droop (frequency decrease with load in-
and current, from which the active load crease) in order to obtain fast load balance
load sharing and system f­ requency control
and frequency are determined. with load changes.
for parallel running generators. The load
The T4800 calculates I x cos φ, represen­ An unload function is also provided. When
sharing is ­proportional, meaning that
ting the active load. The load on each activated, the T4800 will reduce the
the ­generators will be loaded equally generator load to zero. A built-in relay can
generator is compared with the load on
­compared to their individual capacity. automatically trip the circuit breaker when
the other generators. Contact signals for
increase and decrease with proportional the unload procedure is completed.
The load on each generator is compared pulses are obtained as output. These pulses
with the load on the other generators and regulate the frequency and load via the The T4800 has a built-in reverse power
corrected until balance is obtained. electric servomotor on a conven­­­tio­nal protection with selectable limits and time
Load sharing is necessary after synchro­ speed gover- delays.
nization in order to re-establish load nor, or by controlling an electronic speed
balance and to obtain long term stability of controller via an inter­mediate E7800 Supply voltage / current
Motorized Potentiometer. The supply voltage from L1 and L2 is
load and system frequency.
connected to terminals 1 and 3 or 2 and 3,
depending on the system voltage.
When applied with the B9300 Power
Reference Unit, one or several genera­tors
can be operated in parallel with the grid
(utility).

Together with the T4500 Auto Synchro­


nizer, the T4800 provides the optimal solu-
tion for generator control, both in marine
and land-based applications.
The T4800 is type approved by major
marine classification societies. The T4900
VAr-Load Sharer can also be used as a
supplement. The combination of the T4800
and the T4900 will provide ­complete load
sharing of both active load and reactive
load.

Fig. 1. Application Diagram.

» Control. Monitor. Protect


essary to connect terminal 8 to t­ erminal open (NO) contact on termi­nals 23-24 and
The measuring current from L3 is 12 for disabling the frequency control. normally closed (NC) contact on terminals
­connected to terminals 5 and 6 with 5 re- 24-25. The reverse power trip signal is
ferring to the generator (see the ­diagram Frequency in / sync. control continuous, and the unload trip signal has
figure 1). An external voltage injected between a duration of 0.5 sec.
The current measure­ment must be taken terminals 9 (FREQ. IN) and 12 can control
from the same phase on all ­generators. the frequen­cy. The same signal can be Auto mode
The current is measu­red in the phase that connected between terminals 29 (FREQ. Terminals 31 and 32 (AUTO) must be
is not supplying the unit. It is important to IN) and 12. The synchronizing control on bridged for automatic load sharing
ensure that the phase sequence is correct. terminal 28 (SYNC.) will switch this signal ­function. If only reverse power protec­
on and at the same time disable the inter- tion is wanted, the terminals should be
This relation between the connections nal frequency control. disconnected.
of voltage and current must be correct in
order to achieve a correct load measure­ This feature can be used for simulta- Adjustments
ment. It can be checked on terminal 11 neous synchronization of already parallel LOAD DEV. can be used for fine
(TEST OUT), where an input of nominal ­running generators to another busbar ­adjustments of the load balance. It should
current (1A or 5A) and power factor 1.0 section, a shaft generator or the grid. An also be used to obtain balance with gener-
gives -2.0V for correct connection. output from terminals 12 (COM) and 13 ators of different size and with different
(FREQ. OUT) on the T4500 connected to types of CTs. For generators of the same
Common reference terminals 12 (COM) and 29 (FREQ. IN) on size and with the same type of CT the set-
Terminal 12 (COM.) is common reference all the T4800 Load Sharers will allow the ting 0 should be used on all load sharers.
for all terminals 7 to 13 and 28 to 29. frequency to be aligned for synchro-nizing.
SYS. FREQ. is used for adjustment of
Power and frequency balance Terminals 28 (SYNC.) on all load sharers the system frequency. It can be adjusted
Two normally de-energized relays (INCR. are interconnected and with a contact between 48Hz and 62Hz.
and DECR.) with LED indica­tions on termi- between terminals 28 and 12, the exter­nal
nals 14, 15 and 16, are for ­increase and de- frequency signal from T4500 Synchro­ni­- STABILITY is used for adjusting the reg-
crease pulses to the gover­­nor servo motor zer on terminal 29 will be active and all ulation time. A high setting of S­ TABILITY
or to an interme­diate E7800 Motorized internal frequency controls are disabled will give a slow, but accurate regulation.
Potentiometer (control­ling the speed trim (see application diagram figure 3). A low setting will give a fast regulation.
input of an electronic speed controller). However, too low a setting may cause
The width of the pulses is proportional to Watt in instability.
the frequency / load difference. Between terminals 10 (WATT IN) and
12 a negative voltage –1.0V from a volt With the STABILITY adjustment the pro-
Communication between load sharers free watt converter can be connected to portional band (pulsing band) is adjustable
For communication between the load substitute the internal load measuring cir- between ±50 - 250% load and ±5 - 25%
sharers all terminals 12 (COM.) are inter­ cuit. In this case no current trans-former frequency, and the dead band zone (in
connected, as well as all terminals 13 (+). (CT) needs to be connected to terminals balance - no pulsing) is a
­ djustable between
5 and 6. Most standard mea-surement ±2 -10% load and ±0.2 - 1.0% frequency.
Unload sig­nals can be adapted with external
Connecting terminals 7 (UNLOAD) and 12 resistors.
will reduce the power on the ­generator to 0 - 10V : Series resistor 820kΩ
Trouble Shooting
If load balance is not obtainable
zero load, and maintain zero load. When 0 - 5mA : Parallel resistor 200Ω
If load balance is not obtainable and the
the load passes below 5% load, a trip
load goes to maximum or reverse
signal is provided as a normally open (NO) Reverse power trip / unload trip
power, one of the signals is inverted
contact on t­ erminals 23-24 and a normally The reverse power trip operates at 10%
due to wrong polarity or interchanged
closed (NC) contact on terminals 24-25. with a delay of 10 sec., but it can be
wires. If this is the case, the following
This trip signal can be used to trip the ­reduced to 5% by bridging terminals 17
should be checked:
circuit breaker. and 18 and to 5 sec. delay by bridging
terminals 18 and 19. A resistor of 510kΩ
1. The polarity of the power measuring
Frequency out between terminals 17 and 18 gives 7.5%,
signals on terminal 11 (TEST OUT) must
Connecting terminal 8 (FREQ. OUT) to a resistor of 2.7MΩ between terminals 18
be positive with the generator on load.
terminal 12 will disable the frequency and 19 gives 7.5 sec. delay.
If the polarity is positive, change the vol­
control and can be used when running in
tage connections 1 and 3 or 2 and 3 or the
parallel with the grid where the ­frequency If the generator is unloading (contact
current connections 5 and 6.
is fixed by the grid. between terminals 7 and 12) a trip
2. Increase and decrease outputs should
signal is obtained when the load passes
be obtained as indicated by the LEDs on
Note: When using the B9300 Power below +5% load.
the front.
Reference Unit, connected to the paral­lel
3. The parallel lines connected to 12
lines (terminals 12 and 13) of the T4800, Both tripping signals are available on the
(COM.) and 13 (+) between load sharers
the frequency control will automa­tically same potential free contact set, normally
must not be interchanged.

»
be disabled. In such situations it is not nec-

Control. Monitor. Protect


BUS

Fig. 2. Application Diagram. Synchronization and load sharing with T4500 and T4800. Unload trip and reverse power trip.

If the load balance is incorrect.


If there is a balance point, but the load
GRID
balance is incorrect, the following should
be checked:
SYNCHRONIZER
T4500

1. Load deviation shall be set to 0 for same


size of generators and same type of CTs.
2. If the deviation from other genera-tors
is approximately two times, it is likely
that the current on terminals 5 and 6 is
BUS
measured in one of the phases supplying
the T4800. The current must be measured
in the phase that is not supplying the unit
(see the application in fig. 1).

LOAD SHARER LOAD SHARER


Check the voltage on terminal 11 (TEST T4800 T4800

OUT) to be -2.0V DC for nominal current


input (IN=1A or IN=5A) and power factor
= 1.0. A current measurement in a wrong
phase will give
+1V DC.

Example:
If the current in terminals
5 and 6 is 2.0A, the nominal current IN is
5A, and the power factor is 0.8, then
the voltage for correct ­connection is:
2
-2 x —x 0.8 = -0.64V.
5
If the load is fluctuating up and down
If there is a correct balance point, but
the load is ­fluctuating up and down, the
STABILITY should be turned clockwise
in order to obtain stability, but not more

» Control. Monitor. Protect


» Specifications
T4800 Load Sharer
Max. voltage
Voltage range
660V
70 - 110% 150
Consumption Voltage 4VA at UN
Current 0.4VA at IN
Continuous current 2 x IN Fixing holes

50
2 x ø 4.5 mm.
Frequency range 35 - 70Hz
Frequency adjustment 48 - 62Hz

10
Proportional band ±50 - 250% load 7.5 135
±5 - 25% frequency
115
Dead band zone ±2 - 10% load
±0.2 - 1.0% frequency
Contact rating AC: 400V, 2A, 250VA
DC: 110V, 2A, 100W
Dimensions in mm.

70
Operating temperature -20°C to +70°C
Vibration test 4g RMS according to IEC 60068-2-64
EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2, EN61000-6-2:1999
Fig. 4 Dimensions
Approvals Certified by major marine classification societies
Burn-in 50 hours before final test
Enclosure material Polycarbonate, flame retardant
Weight 0.7kg
Dimensions 70 x 150 x 115mm (H x W x D)
Installation 35 DIN rail or two 4mm (3/16”) screws

The specifications are subject to change without notice.

Approvals &
Certificates
Type Selection Table
Standard types: IN =5A The T4800 has been approved by major
Type Terminals IN marine classification societies.
1-3 2-3
For more information about the indivi-
T4800.0010 450V 400V 5A
dual certificates, please visit selco.com
T4800.0020 230V 5A
T4800.0030 480V 415V 5A
T4800.0040 110V 100V 1A
T4800.0050 450V 400V 1A
T4800.0060 127V 120V 5A
T4800.0070 110V 100V 5A

Other supply voltages, nominal currents and combinations are available on request.

SELCO
Betonvej 11 Tel.: + 45 - 70 26 11 22
01-2017

DK- 4000 Roskilde Fax: + 45 - 70 26 25 22


Denmark e-mail: selco@selco.com selco.com

You might also like