Professional Documents
Culture Documents
Use this manual if you are responsible for designing, installing, programming, or troubleshooting
the Allen-Bradley 1394 family of products.
If you do not have a basic understanding of the 1394, contact your local Allen-Bradley
representative for information on available training courses before using this product.
The purpose of this manual is to enable the customer to successfully replace select 1394 models
that have been designated as Silver Series, with recommended alternative products (series C 1394
product family).
Section
I. Replace / upgrade System Module
II. Replace / upgrade Axis Module
III. Appendix
1
I. Replace / Upgrade System Module
Overview
Follow the steps in this document to replace a 1394 GMC / 1394 GMC Turbo series A or series B
System module.
These steps, which are described in detail in the succeeding sections of this document, include:
A. Tools required.
B. Note controller switch settings.
C. Connect Serial Comms.
D. Upload script.
E. Remove all power.
F. Disconnect system module – Replacement is a series A or B ONLY
G. Disconnect system module – Replacement is a series C ONLY
H. Remove system module.
I. Insert new system module.
J. Reconnect the system series A or B ONLY
K. Reconnect the system – series C ONLY
L. Download.
A. Tools required
PC running GML Commander 4.03.
Serial cable to interface with 1394 system.
Controlled GML diagram (Required if controller is not responding).
Terminal screwdriver.
Terminal tools (supplied with system module).
Philips No1 screwdriver.
4mm Hex driver or other device for fixing module to panel.
Pen.
5mm Ring Crimp and tool (Series C only).
Label and remove the 380/460VAC input power from the system module.
Secure any mechanical loads that may be connected to the motor.
Switch off 24V control power to the system.
Open the system module door.
You will identify the positions of the system module configuration switches in the spaces provided
below. These will be used to set the switches on the replacement unit.
Fig 1 (Positions of switches)
System module Jumper Fitted series A and B only Fitted ( ! ) Not Fitted ( ! )
2
Serial Port Config. Dipswitch
Bitswitch No Left ( ! ) Right ( ! )
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
ATTENTION. This product contains stored energy devices. Only qualified personnel familiar with solid state
control equipment and safety procedures in publication NFPA 70E or applicable local codes should
attempt this procedure.
Ensure that mechanical loads are secured.
Ensure that 380/460V AC input power is disconnected.
Disconnect 24V control power.
3
F. Disconnect system module (Ref.A-03)– Replacement is a Series A or
B ONLY
Ensure that all cables connected to the front and bottom of the system module motion board are
identified and removed.
Ensure that all cables connected to the front and bottom of the system module are identified and
removed.
The 1394 5 and 10KW System Module (Series “C”) uses connectors instead of IEC terminals for
connecting power. You will wire the system using power connectors (J1, J10 and J11) that mate
with plugs (P1, P10 and P11) conveniently located on the bottom of the System Module. See below
for details of location.
• Remove wire from COL and fit to 3 way connector (J11) pin 1.
• Remove wire from DC+ and fit to 3 way connector (J11) pin 3.
• Go to 7.
External Shunt not Used.
4
Remove U, V, W and incoming PE then fit to 4 way connector (J10) pins 1-4.
Remove the 24V control and fit to 2 way connector (J1) pins 1&2
Fit a 5mm ring crimp to the end of the Protective Earth returning to the Earth bar.
5
In the case of scheduled maintenance see appendix (Ref.A-05)
Connect PC serial cable to CHAN A / J3
Verify switch settings:
• Axis Link and RS-422 Multidrop Address rotary switch is set to value noted on previous
module.
• Serial Port Config. Bitswitch all to left
• Application Lock Keyswitch is Unlocked
L. Download
Initialise the controller. This involves setting essential drive data parameters to their default values.
• Apply 24V control power to the system module.
• Press in and Hold the INIT button. (This is the right most pushbutton switch revealed when
the front panel of the controller is open.)
• While still pressing the INIT button, press and release the RESET button on the front of the
controller.
• Continue pressing the INIT button until the system module status LED flashes red / green.
• Release the INIT button.
Clear the controller’s Application and parameter memory:
• Ensure that the controller is on line.
• Select the Terminal window (Lower right), within Diagram view with the left button of
the mouse, type the command .I and press the Enter key on the keyboard.
• Press and release the Reset button on the front of the controller.
Or
If a controlled diagram is to be downloaded
6
I. Replace / Upgrade Axis Module
Overview
Follow the steps in this Section to replace / upgrade an axis. Installing the new system module
requires the following steps described in detail in the succeeding sections of this document,
include:
A. Tools required
B. Remove all power.
C. Disconnect the axis module.
D. Install a replacement axis module.
A. Tools required
Terminal screwdriver
4mm Hex driver or other device for fixing module to panel.
Pen
7
In the case of scheduled maintenance Series C axis only see appendix (Ref.A-
06)
8
Appendix to Changing System / Axis Module on 1394 GMC and
1394 GMC Turbo Controllers
5. Click the Configure Interface button. The Serial Interface Configuration dialog will open.
9
• Ensure that the Baud rate is set to 9600 and the appropriate port is set for your PC.
• Click OK twice to close the dialog boxes.
6. Select Configure, Control Options from the menu bar.
7. Ensure that the control type is IMC S Class 1394/1394 Turbo, and the iCODE version
represents the controller Firmware Version or lower (Located on System module left hand
side). Also select the multi-drop checkbox if multi-drop addressing was previously used. And
set the control address to match the system module. Then click OK.
10
8. Select Diagram, Online Connection. The controller should come Online.
If the controller came online go to 11. (This may take some seconds for the controller to
respond)
OR
If the controller did not come online:
9. Repeat part 5 with increasing baud rates selected from the dropdown choice.
10. Press F8 (Online connection) Twice. If the controller does not come on line after 30 seconds.
• Repeat 9 until all available baudrates have been tried.
• Ensure that the controlled copy of the diagram is available to download to the replacement
controller.
• Go to 6. Remove all power
11. In GML Commander, select Upload Options in the dialog menu. The Upload Options dialog
box opens.
12. In the Upload Options dialog box:
• Select All as an Upload Option,
• Accept a Lower Variable Address,
• Set the Upper Variable Address to 1999,
• Accept a Lower Cam Point,
• Set the Upper Cam Point to 12999,
11
13. Select OK. GML Commander uploads the program, then displays the uploaded code in the
Script Editor Window.
14. Select Save in the Script Editor Window File Menu. The Save As Dialog box opens.
• Save the uploaded diagram script.
• Be sure to note the saved name and location of the new text file.
• Return to Upload script.
12
Ref.A-04 Disconnect system module (Series C)
Picture…Fig B2, Fig B1
1 2 3 4
5
Return to scheduled maintenance.
14
Ref.A-06 Replace / Upgrade Axis Module
1. Series ‘A’ non-flex cables produced before 1998 have a foil shield instead of braid. In order to
bond these shields to ground it is necessary to affect the following procedure.
• Remove approximately 25mm of insulation. Care must be taken not to cut the foil or inner
insulation.
• Fold back the foil to reveal its conductive side. Note that the outer of the foil is non-conductive.
• Insert copper tape, ensuring that a good connection is made with the drain wire.
• Go to 3
2. Braided shield type motor power cable.
• Remove approximately 25mm of insulation to exposes the braid underneath.
3. Place the exposed cable shield into the cable shield clamp and tighten the clamp. Then screw the clamp
to the bottom of the axis module.
4. Return to scheduled maintenance Series C axis.
15