Delta Power Meter


DPM Series

w w w. d e l t a w w. c o m
Product Introduction
Delta's Power Meter DPM Series offers precise measurement of various electrical energy values and
power quality parameters, including power factor, harmonics, and current / voltage unbalance with
functions such as off-limit alarms and history logs. It provides exceptional communication quality and
monitoring functions that are especially suitable for sectors where power quality is critical.

Specifications
Model Name DPM-C530A DPM-C520 DPM-D520I

Product Appearance

Accuracy Class
Active Energy (IEC 62053-22) Class 0.5S Class 0.5S Class 0.5S
Measurement Accuracy
Current 1A/ 5A 1A/ 5A 63 A
Voltage ● ● ●

Frequency ● ● ●

Active, Reactive, and Apparent Power ● ● ●

Power Factor ● ● ●

Active, Reactive, and Apparent Energy ● ● ●

Interval Energy ● - ●

Demand Values
Current ● - ●

Power ● - ●

Calculation Mode Block - Block


Multiple Rate
Interval Numbers 8 groups - 8 groups
Power Quality Measurement
Current / Voltage Unbalance ● ● ●

Total Voltage Harmonic Distortion ● ● ●

Total Current Harmonic Distortion ● ● ●

Individual Current / Voltage Harmonic Distortion 2 ~ 31 - -


Data Recording
Max. / Min. of Instantaneous Values With Timestamp ● ● ●

Selectable 17 Selectable 17
Data Logs Type -
measurement values measurement values
Data Logs Recording Duration Up to 2 months - Up to 2 months
Alarms History 500 - 500
Alarms
Alarm Types 29 10 29
Communication
RS-485 Interface ● ● ●

Parameter Grouping ● ● ●

MODBUS MODBUS RTU/ASCII MODBUS RTU MODBUS RTU/ASCII


* Min. / max. of instantaneous : Phase voltage, line voltage, current, frequency, total 3 - phase active power, total 3 - phase reactive power, total 3 - phase apparent power, total power factor, total voltage
harmonic distortion, total phase voltage harmonic distortion, total current harmonic distortion, phase voltage unbalance, 3 - phase voltage unbalance, 3 - phase current unbalance
* Alarm types: Over-current, under-current, over natural current, over line voltage, under line voltage, over phase voltage, under phase voltage, over voltage unbalance, over current unbalance, over active
power, over reactive power, over apparent power, power factor (lead), power factor (lag), over current demand, over active power demand, over reactive power demand, over apparent power demand,
over frequency, under frequency, over total voltage harmonic distortion, over total current harmonic distortion, phase lose, meter restore factory, phase sequence reversal, over DUI, over EU
* Data log: Phase voltage, line voltage, current, natural current, power factor, displacement power factor, total active power, total reactive power, total apparent power, positive active energy, reversed active
energy, positive reactive energy, reversed reactive energy, positive apparent energy, reversed apparent energy, total voltage harmonic distortion, total current harmonic distortion

1
Features
High Precision Power Measurement
►► Highly
precise measurement of bidirectional electrical energy and power parameters, meeting Class 0.5S of
IEC 62053 and CNS14607 standards.
►► Supports
power quality measurement, including total and individual harmonic distortion, voltage and current
unbalance, and more.

Large Screen LCD


DPM-C530A
►► White-light widescreen LCD with resolution of 198x160 dots.

■■ Visibility better than segment-type LCD

Ptot 123456.78 kW

Etot 123456.78 kVARh

Easy Operation and Installation


►► Easy installation and disassembling with two fixing mounts, no screws or extra tools required.
►► Built-in RS-485 communication port supports MODBUS communication.
►► Transmission of all measurement values to the PLCs via communication.

HMI SCADA Server

Ethernet

PLC

MODBUS RTU

DPM-C530A DPM-D520I

2
Features
Event Alarms and History Logs
DPM-C530A & DPM-D520I
►► Keeps max. 2 months of power and electricity energy measurement values for history analysis.
Up to 17 power parameters selectable for recording different time intervals (ex. recording
17 electricity parameters every 5 minutes, for up to 2 months). 29 types of built-in event alarms for
up to 500 event records.

DPM-C520
►► 10 types of built-in event alarms.
500
►► Front LED indicators for real-time alarms. Alarm messages
with time stamps can be transmitted to PLCs via communication.

Auto Meter Reading


DPM-C530A & DPM-D520I
►► Two built-in individual data registers record active / reactive energy in a certain given time lapse when triggered
through communication.

Two individual
time lapse settings

START START

END

END

Parameter Grouping
►► Groupingthe measurands for faster data transmission and reading by the PLCs improves the efficiency and
performance of data transmission.
SCADA Server

Current
Voltage
Energy
RS-485

Demand

Power
System
DPM

3
PC-based Configuration Software
►► Utilizing
DPMSoft software through MODBUS communication for power meter setup and data acquisition
provides easy power management and analysis.

PC Notebook

IFD6500

RS - 485

DPM

4
Applications
►► Power Monitoring and Control, Energy Management Systems, Medium / Low Voltage Power Distribution
Panels, Building Energy Management Systems, Factory Energy Management Systems, Factory Automation
and Intelligent Buildings.

Energy Management Systems Ethernet


Programmable Logic
Controller
Human
Machine MODBUS
Interface
Power Meter

Active Front End


Integrated Programmable
Elevator Logic
Programmable Drive Controller
AC Motor Drive
Logic
Controller AC Reactor

Chiller
Permanent Cooling Tower
7F Magnetic
6F Synchronous
Motor
5F
Light
4F
AC Motor Drive
3F
AC Motor
Drive
2F HJGH
K
HJGH
HJGH
HJGH
HJGH

NVH FDH
K
K
K NVH FDH
NVH FDH
NVH FDH
NVH FDH
22 SDF
02 SDF
18 SDF
13 SDF
HJGHF
HJGUTYRK
HDRWSJGK
HJGK
GFY
457FY
GJDFGDHFY
GHG45FY

Light
13 SDF
HJGK
GHG45FY

Air Handling
1F
Unit
Pump
Lighting System Elevator HVAC System

Human Machine
Factory Automation Interface

Programmable
Logic Controller

MODBUS

Temperature Pressure Timer  /  Counter  /   AC Servo Power Meter AC Motor


Controller Sensor Tachometer Drive Drive

Wave Soldering Semi-finished Conformal


Product Testing Coating
Fluxing
Drying
Hand Insertion

5
Common Technical Data
Model Name DPM-C530A DPM-C520 DPM-D520I
Electrical Characteristics
Current ± 0.5%
Voltage ± 0.2% ± 0.5%
Power ±0.5%
Measurement
Active Energy IEC 62053-22 Class 0.5S
Accuracy
Reactive Energy ±0.5%
Power Factor ±0.5%
Frequency ±0.5%
Wiring Method 1P2W, 1P3W, 3P3W, 3P4W 3P3W, 3P4W
Wire voltage: 35 ~ 690 VAC (L-L)
Voltage
Phase voltage: 20 ~ 400 VAC (L-N)
Input Current 1A/ 5A 63 A
Frequency Range 45 ~ 70 Hz
80 ~ 265 VAC (Max. power consumption 4.6 W)
Power Supply
100 ~ 300 VDC
Communication
RS-485 Interface Baud rate 9600 / 19200 / 38400 bps, MODBUS
Mechanical Characteristics
IP Degree of Front Display IP54 -
Protection Meter Body IP20 IP20
Dimensions ( W x H x D ) 96 x 96 x 95.4 mm 126 x 90 x 67.4 mm
Environmental Conditions
Operating Temperature -20 ℃ ~ +70 ℃ -20 ℃ ~ +60 ℃
Storage Temperature -30 ℃ ~ +80 ℃ -30 ℃ ~ +70 ℃
Relative Humidity ~ 95% RH
Altitude Below 2000 m
Electromagnetic Compatibility
Electrostatic Discharge IEC 61000-4-2
Immunity to Radiated Fields IEC 61000-4-3
Immunity to Fast Transients IEC 61000-4-4
Immunity to Impulse Waves IEC 61000-4-5
Conducted Immunity IEC 61000-4-6
Immunity to Magnetic Fields IEC 61000-4-8
Immunity to Voltage Dips IEC 61000-4-11
Radiated Emissions FCC part 15 EN 55011 Class A
Conducted Emissions FCC part 15 EN 55011 Class A
Harmonics Emissions IEC 61000-3-2
Flicker Emissions IEC 61000-3-3
Safety
Europe CE, IEC 61010 -

6
Dimensions (Units: mm)

Panel Type

90
90
71.0
71
22.1
22.1

96
96 93.1
93.1 Spec. Label
96.0

90.0
96
96

DIN Rail Type


126
126.0 64
64.0
45.3
90.0

93.3
93.3
90

67.4
67.4

7
Wiring Diagrams
Panel Type
• 3-Phase 3-Wire, Δ-Connection • 3-Phase 4-Wire, Y-Connection
• 1-Phase 2-Wire (1CT)
(3CT, no PT) (3CT, no PT)

A B C N

A B C N

A N

I1+ V1 V2 V3 Vn
I1+ V1 V2 V3 Vn
I1+ V1 V2 V3 Vn
I1-
I1-
I1-
I2+
I2+
I2+
I2-
I2-
I2- I3+
I3+
I3+ I3-
I3-
I3-
Load
Load Load

• 3-Phase 3-Wire, Δ-Connection • 3-Phase 4-Wire, Y-Connection


• 1-Phase 3-Wire (2CT)
(2CT, no PT) (2CT, 3 PT)

A B C N
A B C N

A B N

I1+ V1 V2 V3 Vn

I1+ V1 V2 V3 Vn I1- I1+ V1 V2 V3 Vn

I1- I2+ I1-

I2- I2+
I2+

I3+ I2-
I2-

I3- I3+
I3+

I3-
I3-
Load Load

Load

• 3-Phase 3-Wire, Δ-Connection • 3-Phase 4-Wire , Y-Connection


(3CT, 2PT) (3CT, 3 PT)
A B C N
A B C N

I1+ V1 V2 V3 Vn I1+ V1 V2 V3 Vn

I1- I1-

I2+ I2+

I2- I2-

I3+ I3+

I3- I3-

Load Load

8
Wiring Diagrams
DIN Rail Type
• 3-Phase 3-Wire, CT Connection • 3-Phase 4-Wire, CT Connection
C B A N C B A

IA+ V1 V2 V3 Vn
+ V1 V2 V3 Vn

IA-
IA-

IB+
IB+

IB-
IB-

IC+ IC+

IC- IC-

Load Load

• 3-Phase 3-Wire, Direct Connection • 3-Phase 4-Wire, Direct Connection

C B A A
N C B

IA+ V1 V2 V3 Vn
IA+ V1 V2 V3 Vn
IA-
IA-

IB+
IB+

IB-
IB-

IC+ IC+

IC- IC-

Load Load

How to Connect DPMSoft PC Notebook

PIN Definition
4 D+
5 D-

DPM 8←1
USB

IFD6500
RJ - 45
PIN 5

PIN 4

9
Optional Accessories
Primary Secondary Max. Measurement
Model Sizes (Units: mm)
Current Current Load Accuracy
Outer
115 x 89 x 51 40
Frame
DCT - S301C 100A 5A 1.5VA 1.0% 34

Inner
32 x 21 x 32 P1
Frame
Outer

115
32
115 x 89 x 51
Frame
DCT - S211C 200A 5A 1.0VA 0.5% P1
Inner
32 x 21 x 32 21 32
Frame 89 50
67
Outer
115 x 89 x 51
Frame
DCT - S221C 300A 5A 1.5VA 0.5%
Inner
32 x 21 x 32
Frame
Outer
115 x 89 x 51 51

Frame 50 34

DCT - S231C 400A 5A 2.5VA 0.5%


Inner
32 x 21 x 32
Frame

145
80
Outer
145 x 116 x 51
Frame
DCT - S241C 500A 5A 2.5VA 0.5% P1

Inner
80 x 50 x 32 79.5 32

Frame 116 50
67
Outer
145 x 116 x 51
Frame
DCT - S251C 600A 5A 2.5VA 0.5%
Inner
80 x 50 x 32
Frame
Outer
145 x 116 x 51
Frame 51.6

DCT - S261C 750A 5A 3.0VA 0.5% 80 35

Inner
80 x 50 x 32
Frame
Outer

196
122

145 x 116 x 51
Frame
DCT - S271C 1000A 5A 5VA 0.5%
Inner P1

80 x 50 x 32
Frame 109.2 32
146 50
Outer 67
196 x 146 x 51
Frame
DCT - S281C 1500A 5A 7.5VA 0.5%
Inner
122 x 80 x 32
Frame
Outer
250 x 186 x 1.4 51.4

Frame 81 35

DCT - S291C 2000A 5A 10VA 0.5%


Inner P1

160.5 x 81 x 32
Frame
Outer
250
160.5

250 x 186 x 51.4


Frame
DCT - S2A1C 2500A 5A 15VA 0.5%
Inner P1

160.5 x 81 x 32
Frame 121 32
186 50

Outer 67

250 x 186 x 51.4


Frame
DCT - S2B1C 3000A 5A 20VA 0.5%
Inner
160.5 x 81 x 32
Frame

* All models are CE-certified but not UL-certified.

10
Industrial Automation Headquarters
Delta Electronics, Inc.
Taoyuan Technology Center
No.18, Xinglong Rd., Taoyuan Dist.
Taoyuan City 33068, Taiwan
TEL: 886-3-362-6301 / FAX: 886-3-371-6301

Asia
Delta Electronics (Jiangsu) Ltd.
Wujiang Plant 3
1688 Jiangxing East Road,
Wujiang Economic Development Zone
Wujiang City, Jiang Su Province,
People's Republic of China (Post code: 215200)
TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290

Delta Greentech (China) Co., Ltd.


238 Min-Xia Road, Pudong District,
ShangHai, P.R.C.
Post code : 201209
TEL: 86-21-58635678 / FAX: 86-21-58630003

Delta Electronics (Japan), Inc.


Tokyo Office
2-1-14 Minato-ku Shibadaimon,
Tokyo 105-0012, Japan
TEL: 81-3-5733-1111 / FAX: 81-3-5733-1211

Delta Electronics (Korea), Inc.


1511, Byucksan Digital Valley 6-cha, Gasan-dong,
Geumcheon-gu, Seoul, Korea, 153-704
TEL: 82-2-515-5303 / FAX: 82-2-515-5302

Delta Electronics Int’l (S) Pte Ltd


4 Kaki Bukit Ave 1, #05-05, Singapore 417939
TEL: 65-6747-5155 / FAX: 65-6744-9228

Delta Electronics (India) Pvt. Ltd.


Plot No 43 Sector 35, HSIIDC
Gurgaon, PIN 122001, Haryana, India
TEL : 91-124-4874900 / FAX : 91-124-4874945

Americas
Delta Products Corporation (USA)
Raleigh Office
P.O. Box 12173,5101 Davis Drive,
Research Triangle Park, NC 27709, U.S.A.
TEL: 1-919-767-3800 / FAX: 1-919-767-8080

Delta Greentech (Brasil) S.A


Sao Paulo Office
Rua Itapeva, 26 - 3° andar Edificio Itapeva One-Bela Vista
01332-000-São Paulo-SP-Brazil
TEL: +55 11 3568-3855 / FAX: +55 11 3568-3865

Europe
Delta Electronics (Netherlands) B.V.
Eindhoven Office
De Witbogt 20, 5652 AG Eindhoven, The Netherlands
TEL: +31 (0)40-8003800 / FAX: +31 (0)40-8003898

*We reserve the right to change the information in this catalogue without prior notice.

DELTA_IA-SI_DPM_C_EN_20161117

You might also like