You are on page 1of 4

LV RACEWAY

A B A/B
50% Area of
Dia of Cat- Maximum
Total Area Available Cat-6
Raceways 6 Cable No of Cat-6
Sqmm Space Cable
mm Cable
Sqmm sqmm
300 X 75 22500 11250 10 100 112.5
200 X 75 15000 7500 10 100 75
100 X 50 7500 3750 10 100 37.5
50 X 50 2500 1250 10 100 13

40%
CONDUIT Available
Space Sqmm

32 804 322 10 100 3


25 491 196 10 100 2

POWER RACEWAY

40%
DIA of 4 Area of 4
Total Area Available Maximum No of ckt in
Raceways Wires Wires
Sqmm Space No of Wires trunking
sqmm sqmm
Sqmm
300 X 40 12000 4800 4.8 18 267 89
200 X 40 8000 3200 4.8 18 178 59
100 X 50 5000 2000 4.8 18 111 37
50 X 40 2000 800 4.8 18 44 15
75 X 50 3750 1500 4.8 18 83 28

AS PER NBC 2016 (WITH BUFFER)


Nominal Overall
Conduit diameter (mm)
Cross sec. dia
Area 20 25 32 40
(mm2) (mm) Number of wires
1 3.4 3 9 12 -
1.5 3.4 3 9 12 -
2.5 4.2 3 6 12 -
4 4.8 3 6 9 -
6 5.6 - 3 6 -
10 7 - 3 3 5

75 x 50 3750 3750 4.8 60 62 21


100 X 75 7500 7500 8 167 45 45

100 X 75 7500 3375 8 100 34 34

100 X 75 7500 7500 7 128 58 58


45

18.0864
cat 6 cable