ADDENDUM
This addendum is intended to be used in conjunction Arc rejection level – If arc rejection is
with form number 95-8479 “Configuring Eagle Systems selected
Using EagleVision-NT Software” and contains the Latching/non-latching – With “latching”
procedure for configuring UV/IR flame detectors used selected, fire alarm
with Eagle Quantum systems. signal is present until
cleared by a reset
Refer to the Eagle Quantum hardware instruction command from the
manual (form number 95-8470) for a complete OIS.
description of the UV/IR flame detector’s features and
Automatic oi – Selecting “manual”
options. Note that the “Specifications” section of this
disables the automatic
manual provides suggested settings for detecting
oi test.
various fires at specified distances using the Eagle
Quantum UV/IR detector. These settings are oi sensitivity – IR only
recommended as a “starting point,” with the final Time delay – 0 to 7 seconds
settings determined and verified through field tests. oi test frequency – IR only (UV fixed at
once per minute)
1. Highlight the desired address on the Point
Configuration screen. Click on the Modify Point 7. Enter the desired update rate value in the box
button. labeled “Now” under Update Rate.
2. Click on the Define button. 8. Enter the Destination Address(es). (Refer to form
number 95-8479, step 8 under “IDC Configuration”
3. Click on the UV/IR Detector button, then click on for instructions regarding selection of destination
OK. The UV/IR Configuration screen will be addresses.)
displayed. See Figure 1.
9. Click on Accept. Click on Close to exit and return
4. Type a tag name for the point in the space to the Point Configuration screen, or use the scroll
provided. arrows to select the next point for configuration.