MICROCONTROLLER
AIR MONITOR ASC
OPERATION SUPPLEMENT
CompAir LeROI
P.O. Box 927
211 E. Russell Road
Sidney, OH 45365-0927
URL www.compairusa.com
O/M SS2 SERIES
6/09
2
AIR MONITOR ASC
Table of Contents
Page
General Information................................................................................................................... 5
Analog Inputs............................................................................................................................. 6
Starting ...................................................................................................................................... 7
Stopping..................................................................................................................................... 7
Pressure Control........................................................................................................................ 8
3
4
GENERAL INFORMATION
• Keyboard on controller
• Digital input
• RS485 communication line
• Keyboard on controller
• Digital input contact
• RS485 communication port
CONTROL MODES
STATUS / READOUT
5
ANALOG INPUTS producing a too high pressure. If a too
high pressure is detected, the
The AIR MONITOR ASC controller analog compressor will immediately shut down.
inputs are as follows: The standard set point is set above the
HP rating.
1. DELIVERY AIR PRESSURE - This
input is to monitor the delivery air 7. START/STOP SWITCH - This input is
pressure and prevent dangerous for remote starting and stopping by use
overpressure. of a single pole, single throw switch.
Close to start, open to stop.
2. COMPRESSOR DISCHARGE TEMP-
ERATURE - This input is used to SAFETY FUNCTIONS
monitor the outlet air / oil mixture
temperature, which will protect the SHUTDOWN CONDITIONS - Protects unit
compressor element from overheating. and operator. From dangerous conditions.
6
ERROR 7: COMPRESSOR & FAN MOTOR • The motor starter is activated
OVERLOAD; Shutdown
• After the compressor is running, the
ERROR 8: SEPARATOR ELEMENT start procedure is terminated and control
OUTLET TEMPERATURE TOO HIGH; is passed to the pressure control system
Shutdown
ERROR 12: AIR FILTER LIFETIME • Unload the compressor and initiate a
EXPIRED: REPLACE; Maintenance programmable unload run on timer.
Condition (Timer = 0 in case of shutdown)
ERROR 13: OIL LIFETIME EXPIRED: • Allow the run on timer to count down to
REPLACE; Maintenance Condition 0 while keeping the compressor running.
ERROR 14: OIL FILTER LIFETIME • Stop the compressor. (Starter OFF)
EXPIRED: REPLACE; Maintenance
Condition • Initiate a blow down timer to allow the
motor to stop and completely blow down
ERROR 15: OIL SEPARATOR LIFETIME the internal pressure.
EXPIRED: REPLACE; Maintenance
Condition
EMERGENCY STOP
COMPRESSOR MOTOR START
In case of an emergency, press the
The compressor will start by means of the emergency stop button and the unit will stop
keyboard, digital control input or the RS-485 immediately and the system will blow down.
communication line. Before the unit will start
a check procedure is done to see that: NOTE:
THE EMERGENCY STOP BUTTON
• There is no start inhibit condition SHOULD ONLY BE USED IN A GENUINE
EMERGENCY AND MUST NOT BE USED
• There is no shutdown condition AS THE NORMAL METHOD OF
STOPPING THE COMPRESSOR.
• The unit has blown down properly
7
PRESSURE CONTROL
AUTOMATIC CONTROL -
This mode is essentially the same as
continuous control with one additional
feature: if the compressor remains unloaded
for a (programmable) number of minutes the
compressor motor is stopped. After stopping
the motor the controller keeps monitoring
the system pressure, if it goes below the
load pressure the compressor is
automatically restarted.
8
FAULT FINDING
Below is a list of shutdown and warning fault should occur use the list below to as a
messages along with the possible causes guideline to resolve the problem.
and the action required for servicing. If a
1. SHUTDOWN MESSAGES
“Emergency Stop” (1) Emergency Stop (1) Check cause of fault and rectify.
Switch operated. Turn Emergency Stop Switch to
release latch. Press RESET.
(2) Starter circuit fuse blown. (2) Check cause and rectify.
“Motor fault” (1) High ambient temperature. (1) Check room ventilation.
(Motor Overload
Amperage) (2) Insufficient cooling air flow. (2) Inspect/clean: enclosure filter,
ducting; motor cooling air intake.
(3) Fan operation/rotation incorrect. (3) Check and rectify electrical circuit.
“Air Temp Fault” (1) High ambient temperature (1) Check room ventilation
(Air Temperature
Fault) (2) Insufficient cooling water flow (2) Check water supply. Check
adjustment of water valve
Inspect/clean water strainer
Inspect/clean oil cooler
“High press fault” (1) Compressor is failing to unload. (1) Check/renew solenoid. Operated
(High Receiver unloader valve. Check that suction
Pressure) regulator inlet valve is closing
fully. Rectify if necessary.
“Motor rot fault” (1) Supply wiring configuration (1) Check supply wiring
(Motor Reverse Incorrect, motor rotation connections. Reverse 2
Rotation) Will be incorrect. Incoming power lines.
9
2. WARNING MESSAGES
“Air filt P warn” (1) Intake air filter blocked. (1) Check/renew element.
(High Air Filter
Differential (2) Filter pressure switch fault. (2) Check operation. Renew
Pressure) if necessary.
“Comp temp warn” (1) High ambient temperature. (1) Check room ventilation.
(High Discharge
Temperature) (2) Insufficient cooling water flow. (2) Check water supply. Check
adjustment of water valve.
Inspect/clean water strainer.
Inspect/clean oil cooler.
“Oil sep P warn” (1) Oil separator element blocked. (1) Renew separator filter
(Separator
Differential (2) Differential pressure switch (2) Check operation. Renew if
Pressure) fault necessary
10
11
12
13
MENU KEY FUNCTIONS
The following explains the function of each “Fault log nr. 1” Press “PLUS” key
key as marked by symbols on the control one (1) time to
panel. The functions are as follows: display. This menu
shows and stores
“PLUS” key + – This allows you to go to the latest fault in
the next menu. the unit.
“DOWN” key ∇ - This allows you to go to 1. This function stores the last ten (10)
the next menu item. faults. Which can be seen by pressing
the “DOWN” key one time for each fault.
“MINUS” key - - This allows you to go
back to the previous 2. Press “RESET” key to return to start.
menu.
“Timers” Press “PLUS” key two (2)
“UP” key Δ - This allows you to go times to display. This menu
back to the previous shows the run hours on the
menu item. unit.
“ENTER” key - This allows you to modify 1. Press “DOWN” key to show the load
a menu or menu item. hours on the unit.
“RESET” key - This allows you to return 2. Press “DOWN” key to show the
to the beginning of the remaining life of the air filter (Air fl tm)
menu tree or the “Ready
to Start” menu. 3. Press “DOWN” key to show the
remaining life of the oil filter (Oil fl tm)
For example following the menu tree a
“Programmable Service Timer” can be set 4. Press “DOWN” key to show the
as follows: remaining life of the oil separator (Oil
sep tm).
Start from the “Ready to Start” menu and
press the “PLUS” key two (2) times. Then 5. Press “DOWN” key to show the
press the “DOWN” key five (5) times to get remaining life of the oil (Oil chg tm).
to the “Oil chg tm” menu item. To modify this The air filter time through the oil change
item, press the “ENTER” key. The display time can be modified. These menu
will start to flash and the “PLUS” or “MINUS” items show the remaining life on a filter,
key will allow you to change the time that separator or the oil itself.
you prefer. Press the “ENTER” key to store
your modifications. FOR EXAMPLE:
A new unit may show the oil filter time to be
MENU DISPLAY FUNCTIONS 2000 hours. Each hour the machine runs the
remaining life is less. When the time
reaches zero the filter is ready to be
“Ready To Start” This menu shows the
changed.
date and time set at
the factory before
6. Press “RESET” key to return to start.
shipping.
14
“Operate settings” Press “PLUS” key load for new pressure schedule entry.
three (3) times to See note on diagram.
display. This menu
shows pressure 3. Press “RESET” to return to start.
controls.
“SETTING SERVICE TIMERS”
The default for the Econotrol unit is (RCN)
Regulated Continuous Pressure. The “SERVICE TIMERS” are programmable
to aid in preventative maintenance. These
The default for the Standard unit is (CNT) timers must be reset when service is
Continuous Pressure. performed. The timers can be set as follows:
1. Press “DOWN” key to show unload 1. From the “Ready to Start” prompt press
pressure (P. unload psi). See chart at “+” four times to obtain “Main
bottom of menu tree for defaults with selection/Mach config”.
and without Econotrol.
2. Press the down arrow three times to
2. Press “DOWN” key to show the load obtain “Main selection/Service settings.
pressure (P. load psi).
3. Press “+” one time to obtain “Service
3. Press “DOWN” key to show run on time settings/Air fl tm”. The time remaining
(Run on tm). This default is set for 10 will be displayed. A negative number will
minutes. display if the time had expired before
service.
4. Press “DOWN” key to show P. schedule
which the default is set for “OFF”. If this 4. The down key can be used to select any
is turned “ON” it can be programmed to of the four timer settings.
start target pressure on any day at any
time. 5. To reset a given timer press enter. The
“Air Monitor” will request a code. Use
5. Press “DOWN” key to show the PRESS. the “+” & “-“ to enter 012. Then press
Schedule. enter.
6. Press “DOWN” key to show the drain 6. The value will flash. The “+” & “-“ keys
spit time (Drain sp tm). This default is are used to select a new value. Press
set for 5 seconds. enter to accept the new value.
7. Press “DOWN” key to show the drain 7. The arrow keys can be used to make
dwell time (Drain dw tm). This default is another selection or press enter to
set for 30 seconds. return to “Ready to Start”.