RECORDS OF ANNUAL PROTECTION RELAY TESTING

Installed at 220/132KV
Grid Station NTDC Dera Murad Jamali
S.NO Name of Circuit Name of Relays Make & Type Last Date of Testing
Restricted Fault SEL-587Z 8/2/2021
HV O/Current & Earth Fault SEL-351A 8/2/2021
LV O/Current & Earth Fault SEL-351A 8/2/2021
Differential Protection SEL-787 8/2/2021
160 MVA 220/132 KV Auto Thermal over load SEL-700G 8/2/2021
Transformer T-1 Over Excitation SEL-700G
1 8/2/2021
PTW # 176 Differential Protection SEL-487E 8/2/2021
HV Connection Protection SEL-587Z 8/2/2021
Tertiary Over Current Protection SEL-351A 8/2/2021
LV Connection Protection SEL-587Z 8/2/2021
Neutral Over Current SEL-351A 8/2/2021
Restricted Fault SEL-587Z 9/2/2021
HV O/Current & Earth Fault SEL-351A 9/2/2021
LV O/Current & Earth Fault SEL-351A 9/2/2021
Differential Protection SEL-787 9/2/2021
160 MVA 220/132 KV Auto Thermal over load SEL-700G 9/2/2021
Transformer T-2 Over Excitation SEL-700G
2 9/2/2021
PTW # 174 Differential Protection SEL-487E 9/2/2021
HV Connection Protection SEL-587Z 9/2/2021
Tertiary Over Current Protection SEL-351A 9/2/2021
LV Connection Protection SEL-587Z 9/2/2021
Neutral Over Current SEL-351A 9/2/2021
Distance Protection SEL-481 13-11-2019

220KV Uch Dera Murad Jamali Auto Reclosure SIEMENS-7VK61


13-11-2019
Circuit
3 Distance Protection SIEMENS-SIPROTEC 7SA612
13-11-2019
PTW # 68 Auto Reclosure SIEMENS-7VK61
13-11-2019
Over Current/ Earth Fault SEL-351A 13-11-2019
Distance Protection SEL-481 14-11-2019
220KV Dera Murad Jamali Sibbi
Circuit Auto Reclosure SIEMENS-7VK61 14-11-2019
4 Distance Protection SIEMENS-SIPROTEC 7SA612 14-11-2019
PTW # 72
Auto Reclosure SIEMENS-7VK61
14-11-2019
Over Current/ Earth Fault SEL-351A
14-11-2019
132KV Rojhan Jamali Circuit Distance Protection SEL311C 28-05-2018
5
PTW # N/A Over Current/ Earth Fault SEL-351A 28-05-2018

132KV Dera Murad Jamali Circuit Distance Protection SEL311C


28-05-2018
6
PTW # N/A Over Current/ Earth Fault SEL-351A
28-05-2018

NOTES
1. Tripping of all circuit breakers was confirmed.
2. Functional test of Buchloz's relays,oil &winding thermometers and PRDs was performed, and are working normally.
3. Annunciation and hooters are working properly.
4. All cables, CT & PT terminations were tightened.

All test results are within permissible range, and relays are working normally.

Assistant Manager (P&I)


220 KV G/S NTDC, DMJ